| 2007-03-31 14:50:38 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| | FBC2004 |
| | FACFLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | ***WINDOW OR DOOR PERMIT APPLICATION, ONLY CHECKED |
| | ITEMS APPLY*** |
| | |
| | ____1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH |
| | THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13. |
| | |
| | _XX_2. DESIGN PRESSURES FOR BUILDINGS OVER 60FEET ARE |
| | REQUIRED TO BE DESIGNED USING ASCE7, FBC1609.1.1. |
| | DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| | PUBLIC RECORD ARE TO BE SIGNED SEALED ORIGINALS |
| | FAC61G15-23.002. |
| | |
| | _XX_3.PROVIDE A COPY OF THE CONDO ASSOCIATION |
| | APPROVAL. |
| | |
| | ____4.IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R |
| | 301.2.1.2.IF LESS THAN 25% OF THE TOTAL GLAZED AREA |
| | IS BEING REPLACED, PROVIDE CALCULATIONS FBC EB507.3. |
| | |
| | ____5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG. |
| | |
| | ____6.PROVIDE A FLOOR PLAN SHOWING: WINDOW |
| | LOCATIONS, SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE |
| | EXISTING CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE |
| | FOR BEDROOMS, FBC R310, FBC EB 505.1. |
| | |
| | _XX_ 7.CIRCLE (USING INK, NOT HIGHLIGHTER) WHICH |
| | MULLION PRODUCT YOU ARE USING.NOTE ON YOUR UNSEALED |
| | WIND PRESSURE ENGINEERING YOU HAVE A DESIGN PRESSURE OF |
| | -83, BUT HAVE HIGHLIGHTED A MULLION PRODUCT WHICH IS |
| | LIMITED TO -67PSF. |
| | |
| | |