Plan Review Details - Permit 07030991
Plan Review Stops For Permit 07030991
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-09-27 Cont ID  
Sent By jjohnsto Date 2007-09-27 Time 15:18 Rev Time 1.00
Received By jjohnsto Date 2007-09-27 Time 15:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-26 Cont ID  
Sent By jjohnsto Date 2007-09-26 Time 11:38 Rev Time 2.00
Received By jjohnsto Date 2007-09-26 Time 08:00 Sent To  
Notes
2007-09-26 11:38:22CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON, PERMIT NO 07030991
 BUILDING PLAN EXAMINERII
 PROJECT IBIS GOLF & COUNTRY CLUB
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS
 8225 IBIS BOULEVARD
  DATE SEPTEMBER 26, 2007
  
 STRUCTURALPLANREVIEW
  
  
 F.S.713.13NOTICE OF COMMENCEMENT
 FILE NOTICE WITH THE CLERK OF COURT RECORDING DIVISION.
 IF THE WORK DESCRIBED IN THE NOTICE IS NOT COMMENCED
 WITHIN 90 DAYS OF FILING THE NOTICE WILL BECOME NULL
 AND VOID. SUBMIT THE NOTICE AT THE TIME OF PERMIT
 ISSUANCE AND POST A COPY AT THE JOB SITE BEFORE THE
 FIRST INSPECTION.
 COMMENT-FOR YOUR INFORMATION
  
 DOCUMENTS SIGNED AND SEALED
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL
 AND BEING FILED FOR PUBLIC RECORD SHALL HAVE THE
 SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT WITH THE DATE.
 COMMENT-DESIGNEROF RECORD MUST SIGN PRODUCT
 APPROVALS FOR ACCEPTANCE OF USE ON THIS PROJECT
  
  
  
 1 CORRECT ADDRESS ON PLANS AND PERMIT
 PROPERTY I.D. NO.74-41-42-13-02-013-0130IDENTIFIES
 THIS ADDRESSAS8850IBIS BLVD.
 (SEE ATTACHEDGIS INFORMATION)
 PLANS AND HOOD FAN MASTERPERMITSTATE ADDRESS IS
 8225
  
  
 2. 2307.1 LOAD AND RESISTANCE FACTOR DESIGN (LRFD).
 THE STRUCTURAL ANALYSIS AND CONSTRUCTION OF WOOD
 ELEMENTS AND STRUCTURES USING LOAD AND RESISTANCE
 FACTOR DESIGN (LRFD) METHODS SHALL BE IN ACCORDANCE
 WITH ASCE 16.
 VERIFY TRUSS CHORDCAN SUSTAIN LOAD FROM HOOD
 ATTACHMENT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-07 Cont ID  
Sent By jwitmer Date 2007-08-07 Time 16:50 Rev Time 0.77
Received By jwitmer Date 2007-08-07 Time 16:50 Sent To PC
Notes
2007-08-07 17:01:06BUILDING PLAN REVIEW
 PERMIT: 07030991
 ADD: 8225 IBIS BLVD.
 CONT: PLAN REVIEW
 TEL: (561)719-8645
 RICHARD HOBSON PROJECT MAN.
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
  
 3) 2ND REQUEST , COMMENT 4C FROM THE PREVIOUS REVIEW,
 WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE PRODUCT
 WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-05 Cont ID  
Sent By jwitmer Date 2007-06-05 Time 14:24 Rev Time 1.11
Received By jwitmer Date 2007-06-05 Time 14:24 Sent To PC
Notes
2007-06-05 14:46:40BUILDING PLAN REVIEW
 PERMIT: 07030991
 ADD: 8225 IBIS BLVD.
 CONT: PLAN REVIEW
 TEL: (561)719-8645
 RICHARD HOBSON PROJECT MAN.
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET M-1 NOTE 14 INDICATES THAT LOUVERS ARE TO BE
 TESTED FOR LARGE MISSLE IMPACT RESISTANCE. PLEASE TAKE
 NOT THAT THE LARGE MISSLE IMPACT TESTING IS FOR GLAZED
 UNITSSEE 2006 FBC BUILDING 1609.1.4 PROTECTION OF
 OPENINGS.
  
 4) MAKE UP AIR LOUVERS ARE PART OF THE COMPONENTS AND
 CLADDING THAT DO REQUIRE PRODUCT APPROVALS LISTED UNDER
 THE FLORIDA ADMINISTRATIVE CODE,
 RULE 9B-72 .031(C) WALL LOUVERS.
  
 4A) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS FOLLOWS: WALL
 LOUVERS.
  
 4B) PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 4C)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-09-23 Cont ID  
Sent By dpalmer Date 2007-09-23 Time 10:47 Rev Time 0.00
Received By dpalmer Date 2007-09-23 Time 10:47 Sent To I
Notes
2007-09-23 10:47:59** PLANS REMOVED FROM INCOMING FOR REVIEW.
  
 ELECTRICAL REVIEW OK, PLANS ROUTED BACK TO INCOMING
 WAITING FOR COMM BOARD.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-07-13 Cont ID  
Sent By dpalmer Date 2007-07-13 Time 07:52 Rev Time 0.00
Received By dpalmer Date 2007-07-13 Time 07:34 Sent To  
Notes
2007-07-13 07:52:47** UNSAT 2ND REVIEW**
  
 1) NOTE: AS STATED ON THE PREVIOUS REVIEWS.
 PLEASE KNOW THAT PLANS HAVE ONLY BEEN SUBMITTED FOR *
 PLAN REVIEW* ONLY AND HAVE NOT BEEN SUBMITTED FOR
 PERMIT. UNDER *PLAN REVIEW* PLANS ARE TO BE 100% AS
 PERMIT APPLICATION HAS NOT BEEN MADE. PLEASE ALSO KNOW
 EVEN ONCE PLANS ARE 100% CODE COMPLIANT, THE REVIEW
 STATUS WILL STILL BE *FAILED* UNTIL PERMIT APPLICATION
 HAD BEEN MADE.
 PLEASE KNOW ONCE PERMIT IS APPLIED FOR, THE VALUE FOR
 THE COMPLETE SCOPE OF WORK SHALL INCLUDE ALL LABOR AND
 MATERIALS INCLUDING EQUIPMENT. EVEN IF ANY EQUIPMENT IS
 OWNER SUPPLIED.
 PLANS INDICATE MUCH GREATER WORK AND EQUIPMENT THAN THE
 VALUE AS INDICATED.
 FBC 108.3
  
 2) NOTE: PLEASE SEE THE CODE SECTIONS BELOW AS STATED
 ON PREVIOUS REVIEW.
 PLEASE SEE A COUPLE OF THE CODES SEEM TO BE
 MISPRINTED.
 PLEASE SEE THE PLANS STATE A 2003 NEC/NFPA-70 SHOWS A
 2002 NFPA-101.
 ** PREVIOUS REVIEW NOTE**
 PLEASE KNOW THAT ANY PERMITS APPLIED FOR AFTER
 DECEMBER 8TH, 2006 PLACES THE PROJECT UNDER NEW CODES.
 PLEASE BE SURE PLANS REFLECT THE FOLLOWING AT A MINIMUM
 AND SEE NOTES FROM OTHER TRADES FOR ANY OTHER CODES
 NEEDED.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 PLEASE SEE COMMENTS WITH RESPECT TO TRADES FOR NFPA-96
  
 3) NOTE: PLEASE CLARIFY THE SHUT DOWN OF EQUIPMENT.
 PLEASE SEE RESPONSE MENTIONS TO SEE 1.2 ON SHEET E3,
 HOWEVER COULD NOT LOCATE THE INFORMATION FOR THIS.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE CLARIFY DETAIL FOR SHUT DOWN OF ANY ELECTRICAL
 APPARATUS UNDER HOODS SUCH AS LIGHTING WHICH WILL BE
 PART OF THE FIRE SUPPRESSION.
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION.
  
 ** PLANS HAVE NOT BEEN SUBMITTED FOR PERMIT.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-08 Cont ID  
Sent By dpalmer Date 2007-04-08 Time 11:59 Rev Time 0.00
Received By dpalmer Date 2007-04-08 Time 11:42 Sent To  
Notes
2007-04-08 11:59:57 
 ** UNSAT **
  
 1) NOTE: PLEASE KNOW THAT PLANS HAVE ONLY BEEN
 SUBMITTED FOR * PLAN REVIEW* ONLY AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT.
 PLEASE KNOW ONCE PERMIT IS APPLIED FOR, THE VALUE FOR
 THE COMPLETE SCOPE OF WORK SHALL INCLUDE ALL LABOR AND
 MATERIALS INCLUDING EQUIPMENT. EVEN IF ANY EQUIPMENT IS
 OWNER SUPPLIED.
 PLANS INDICATE MUCH GREATER WORK AND EQUIPMENT THAN THE
 VALUE AS INDICATED.
 FBC 108.3
  
 2) NOTE: PLEASE KNOW THAT ANY PERMITS APPLIED FOR AFTER
 DECEMBER 8TH, 2006 PLACES THE PROJECT UNDER NEW CODES.
 PLEASE BE SURE PLANS REFLECT THE FOLLOWING AT A MINIMUM
 AND SEE NOTES FROM OTHER TRADES FOR ANY OTHER CODES
 NEEDED.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 PLEASE SEE COMMENTS WITH RESPECT TO TRADES FOR NFPA-96
  
 3) NOTE: PLEASE CLARIFY DETAIL FOR SHUT DOWN OF ANY
 ELECTRICAL APPARATUS UNDER HOODS SUCH AS LIGHTING WHICH
 WILL BE PART OF THE FIRE SUPPRESSION.
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION.
  
 4) NOTE: PLEASE CLARIFY THE CONTINUOUS LOADS AND
 LARGEST MOTOR LOADS AT 125%.
 215.3, 230.42 ETC.
 FBC 106.1.2
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-10-01 Cont ID  
Sent By mawillia Date 2007-10-01 Time 11:41 Rev Time 0.00
Received By mawillia Date 2007-10-01 Time 11:39 Sent To  
Notes
2007-10-01 11:41:05*****APPROVED*****
  
  
 MECHANICAL HOOD DRAWING SHEETS 1 AND 2 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 15:54 Rev Time 0.00
Received By mawillia Date 2007-07-26 Time 15:47 Sent To  
Notes
2007-07-26 15:54:49*****PROVISO*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEET(S)
 TO BE FIRE-STAMPED WHEN ALL OTHER REVIEWS HAVE BEE
 SATISFIED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-05-08 Cont ID  
Sent By mawillia Date 2007-05-08 Time 16:34 Rev Time 0.00
Received By mawillia Date 2007-05-08 Time 16:03 Sent To  
Notes
2007-05-08 16:27:06*****DENIED*****
  
  
 1.THE NUMERICAL ADDRESS OF WHERE THE SCOPE OF WORK IS
 TO BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2.ON SHEET M-1, IN ADDITION TO GENERAL MECHANICAL
 NOTE #8, INCLUDE THAT COMBUSTIBLE WASTE MATERIALS,
 DUST, AND DEBRIS SHALL BE REMOVED FROM THE SITE DAILY
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.ALL EXIT COMPONENTS ARE TO BE MAINTAINED AT ALL
 TIMES DURING THE SCOPE OF WORK.
  
 4.IN ADDITION TO PLANS AND PERMIT NEEDED FOR THE
 INSTALLATION OF THE HOOD SYSTEM, SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED FOR THE HOOD SUPPRESSION
 SYSTEM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-31 Cont ID  
Sent By adarroug Date 2007-08-31 Time 15:03 Rev Time 0.00
Received By adarroug Date 2007-08-31 Time 15:03 Sent To  
Notes
2007-09-24 15:59:12TO "COMM" BD#8
2007-08-31 15:04:07WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-25 Cont ID  
Sent By adarroug Date 2007-06-25 Time 15:28 Rev Time 0.00
Received By adarroug Date 2007-06-25 Time 15:28 Sent To  
Notes
2007-07-12 14:47:40TO "COMM" BD#10
2007-06-25 15:28:24WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-29 Cont ID  
Sent By dpalmer Date 2007-03-29 Time 09:06 Rev Time 0.00
Received By dpalmer Date 2007-03-29 Time 09:06 Sent To  
Notes
2007-03-30 18:03:20TO COMM BOARD # 32
2007-03-29 09:06:36WAITING FOR COMM BOARD.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-09-27 Cont ID  
Sent By tgordon Date 2007-09-27 Time 16:19 Rev Time 2.00
Received By tgordon Date 2007-09-27 Time 16:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-07-17 Cont ID  
Sent By tgordon Date 2007-07-17 Time 14:41 Rev Time 0.30
Received By tgordon Date 2007-07-17 Time 14:41 Sent To  
Notes
2007-07-17 14:50:44* FOR PLAN REVIEW ONLY NOT FOR PERMIT *
 *** DENIED ***
 1) THE NOA FOR THE LOUVERS NEED TO BE REVIEWED, STAMPED
 (SHOP STAMP), AND SIGNED BY THE ENGINEER OF RECORD.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-27 Cont ID  
Sent By tgordon Date 2007-04-27 Time 10:27 Rev Time 1.30
Received By tgordon Date 2007-04-27 Time 10:26 Sent To  
Notes
2007-04-27 10:55:59** FOR PLAN REVIEW ONLY NOT FOR PERMIT **
 *** DENIED ***
 1) INFORMATION MISSING FROM TITLE BLOCK, ENGINEER'S
 PRINTED NAME AND LICENSE NUMBER.
 SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 2) JOB ADDRESS NEEDS TO BE IN TITLE BLOCK, SEE 2004 FBC
 WPB AMEND. 106.1.3.
  
 3) PLEASE SUBMIT PRODUCT APPROVAL FOR MAKE UP AIR
 LOUVERS, SEE FS 553.842(1) AND FAC 9B-72.010(31)(G).
 THE USE OF HURRICANE SHUTTERS ARE NOT DESIGNED FOR THIS
 APPLICATION.
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 4) PAGE M-4 AND M-5 OF THE PLANS SHOW A/C DUCT WORK,
 UNABLE TO DETERMINE WHAT A/C DUCT WORK IS TO BE DONE .
 PLEASE PROVIDE MORE INFORMATION. (BE ADVISED A SEPARATE
 PERMIT WILL BE NEEDED FOR THE A/C DUCT WORK).
  
 5) PAGE M-6 DETAIL #4 SHOWS THE USE OF NEOPRENE GASKET,
 PLEASE ADD FOR EXHAUST FANS USE GASKET LISTED FOR THIS
 APPLICATION.
  
 6) PLEASE PROVIDE A DETAIN ON HOW THE ROOF CURBS ARE TO
 BE ANCHORED TO THE ROOF, AND HOW THE FANS ARE TO BE
 ANCHORED TO THE CURBS TO WITHSTAND 140 MPH WINDS (AND
 CALCULATIONS), SEE 2004 FBC 1609.
  
 7) PLEASE PROVIDE DETAIL ON HOW THE HOODS ARE TO BE
 HUNG FROM THE ROOF.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 3 Status P Date 2007-10-01 Cont ID  
Sent By lmartine Date 2007-10-01 Time 11:27 Rev Time 0.00
Received By lmartine Date 2007-10-01 Time 11:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2007-07-19 Cont ID  
Sent By lfranco Date 2007-07-19 Time 19:34 Rev Time 0.00
Received By lfranco Date 2007-07-19 Time 19:34 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-04-05 Cont ID  
Sent By lfranco Date 2007-04-05 Time 18:48 Rev Time 0.00
Received By lfranco Date 2007-04-05 Time 18:48 Sent To I
Notes
2007-04-05 19:04:49PLANNING AND ZONING:***** FAILED *****
  
 1.PROVIDE COMMENTS IN WRITING.
  
 2.THE PERMIT INDICATES, "NEW EXHAUST FANS ON ROOF,
 NEW ROOF-MOUNTED MAKE-UP FAN FOR 2ND FLOOR HOOD."THE
 PHOTOGRAPHS SHOWN IN MECHANICAL SHEET M-9, SHOW
 EXISTING HVAC AND EXHAUST FANS.ARE THEY PART OF THIS
 PERMIT? OR ARE THEY GOING TO BE REPLACED.PROVIDE A
 CROSS SECTION AND ELEVATION OF THE EQUIPMENT WITH
 RESPECT TO THE BUILDING, IN ORDER TO SHOW THAT THE
 MECHANICAL EQUIPMENT IS COVERED BY THE EXISTING
 PARAPET.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME AT THE
 NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443