Plan Review Details - Permit 07030967
Plan Review Stops For Permit 07030967
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-06 Cont ID  
Sent By jgomez Date 2007-12-06 Time 14:51 Rev Time 0.00
Received By jgomez Date 2007-12-06 Time 14:46 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-10-16 Cont ID  
Sent By jgomez Date 2007-10-16 Time 10:02 Rev Time 0.00
Received By jgomez Date 2007-10-16 Time 07:47 Sent To PC
Notes
2007-10-16 10:29:08RESIDENTIAL ALTERATION BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW DONE UNDER EXISTING BUILDING CODE 2004,FLORIDA
 RESIDENTIAL CODE 2004 AND FBC 2004 WITH 2007
 REVISIONS.
  
 ***NOTE: SCOPE OF WORK WAS CHANGED.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13FLORIDA STATUTE.
  
 2- DESIGNER OF RECORD NEED TO SPECIFYROOF SHEATHING
 NAILTYPEAND SPACING INCLUDING NAILING AT ZONE 3 AS
 REQUIRED BY SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 3- SPECIFY WALL SHEATHING NAIL TYPE AND SPACING.SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 ***NOTE: SEE HARDIPLANK PRODUCT APPROVAL FOR SHEATHING
 REQUIREMENTS.
  
 4- HARDIPLANKDRAWINGS ON SHEET A2 ARE NOT LEGIBLE.
 NEED CLEAR AND LEGIBLE DRAWINGS AS REQUIRED BY SEC.
 106.1.3 CITY AMENDMENTS TO FBC 2004.
 ***ALSO,COORDINATE INFORMATION WITH PRODUCT APPROVAL
 TO AVOID DISCREPANCIES AND EXPEDITE THE REVIEW PROCESS.
 SEE REQUIRED STUD SPACING,SHEATHING THICKNESSS, ETC.
  
  
 5- TYPICAL WINDOW/DOOR OPENING FRAMING DETAIL ON SHEET
 A1:REVISE SPECIFIED CONNECTORS. HUGHES IS OUT OF
 BUSINESS.
  
 6- BASE PLATE DETAIL ON SHEET A1: SPECIFY HOW LONG ARE
 THE 1/2" J BOLTS.SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 7- TYPICAL WALL SECTION ON SHEET A1:
 A) REVISE CS-18CONNECTOR SPECIFIED TO ATTACH WALL
 TO STEM WALL.NEED TO SPECIFY WOOD TO MASONRY
 CONNECTOR. SEE CATALOG FOR PROPER CONNECTOR TYPE AND
 TYPE AND NUMBER OF FASTENERS.OTHERWISE PROVIDE
 COMPLETE ENGINEERING ANALYSIS FOR NAIL TYPE AND NUMBER
 THAT DIFFER FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 B) REVISE NUMBER AND TYPE OF FASTENERS SPECIFIED FOR
 CS-18 AT CONNECTION TO ROOF TRUSS. SEE CATALOG.
 OTHERWISE PROVIDE COMPLETE ENGINEERING ANALYSIS FOR
 FASTENER TYPE AND NUMBER OF FASTENERS THAT DON'T MATCH
 THOSE TESTED AND PUBLISHED BY THE MANUFACTURER. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 8- THE DESIGN PROFESSIONAL MUST ELECT THE ALTERATION
 LEVEL AS REQUIRED BY SEC. 301.5 OF EXISTING BUILDING
 CODE 2004.
  
 9- IDENTIFY WINDOWS IN BEDROOMS THAT ARE GOING TO BE
 REPLACEDTO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. 505 OF EXISTING BUILDING 2004.
  
 10 PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) HARDIPLANK.NOA 02-0729.02 SUBMITTED EXPIRED ON
 MAY 01/2007.
  
 B) ALLSIMPSON OR USP STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS.
 ***NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL PAGE
 AND PAGE SHOWING THE CONNECTOR TO EXPEDITE REVIEW AND
 SAVE PAPER.
  
 C) ROOF SHINGLES.
  
 11- DESIGNER OF RECORD NEEDS TO REVIEW AND APPROVE IN
 WRITING (NOT SIGNING AND SEALING)ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS
 TO FBC 2004
  
 12- ARCHITECT TO REVIEW PRODUCT APPROVAL FOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-24 Cont ID  
Sent By jgomez Date 2007-04-24 Time 16:46 Rev Time 0.00
Received By jgomez Date 2007-04-24 Time 16:46 Sent To PC
Notes
2007-04-24 16:53:40BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713. 13 FLORIDA STATUTE.
  
 2- AFTER DRAWINGS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY TO PAY IMPACT FEES. BRING BACK STAMPED PLANS AND
 COPY OF PAID RECEIPT.
  
 3- ARCHITECT TO PROVIDE THE FIRM'S NUMBER IN THE TITLE
 BLOCK AS REQUIRED BY SEC. 61G1-16.004OF FLORIDA
 ADMINISTRATIVE CODE.
  
 4- SURVEY, SITE PLAN AND FLOOR PLAN DON'T MATCH. REVISE
 AS REQUIRED.
  
 5- AREA CALCULATIONS DON'T ADD UP. REVISE AS REQUIRED.
  
 6- REVISE INFORMATION IN SURVEY REGARDING THE FLOOD
 ZONE ELEVATION.FLOOD ZONE IN THE CITY OF WEST PALM
 BEACH IS DETERMINED BY REFERRING TO MAP DATED MARCH
 1ST, 1979.SEE MAP AND REVISE AS REQUIRED.
  
 7- SHEET A-1:
 A) SPECIFYALL DESIGN LOADS INCLUDING ALL DEAD,
 LIVE AND WIND LOADS AS REQUIRED BY SEC. R301 AND TABLE
 R301.5OF 2004 FLORIDA RESIDENTIAL CODE.
  
 B) REVISE DESIGN WIND LOADS FOR ROOF FOR CORNER
 AREAS. SEE REVISED TABLE 1609.6.2.1(2) FBC 2004.
  
 C) SPECIFY ATTIC ACCESS SIZE. SEC. R807 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 D) THICKNESS OF ROOF SHEATHING TO MATCH. SEE DETAIL
 2 AND ROOF FRAMING PLAN. REVISE AS REQUIRED.
  
 E) POST & BEARING WALL CONNECTION DETAIL AND
 CONNECTION SCHEDULE TO MATCH.ALSO, SEE CURRENT
 SIMPSON CATALOG AND REVISE TYPE,NUMBER OF FASTENERS
 AND SPECIFIC LOADS. OTHERWISE, PROVIDE COMPLETE
 ENGINEERING ANALYSIS FOR INFORMATION THAT DIFFER FROM
 THAT TESTED AND PUBLISHED BY THE MANUFACTURER. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 F) PROVIDE COMPLETE DETAIL AND SPECS FOR GABLE END
 AT ENTRY PORCH. SPECIFY ALL FASTENERS, ETC. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 G) POST & BEARING WALL CONNECTION DETAILAND WALL
 SECTION -1 DON'T MATCH. REVISE AS REQUIRED.
  
 H) ROOF FRAMING PLAN:
 * SPECIFY SIZE AND NUMBER OF HEADERS. SEC. 106.1.2 CITY
 AMENDMENT STO FBC 2004.
 ** CLARIFY HOW ARE WINDOWS AT MEDIA ROOM INSTALLED.
 ROOF FRAMING PLAN SHOWS 3 SEPARATEHEADERS?. PROVIDE
 COMPLETE DETAILS AND SPECS. SEC. 106.1.2 CITY
 AEMNDMENTS TO FBC 2004.
  
 I) STRUCTURAL BUCK DETAIL FOR DOORS AND WINDOWS
 DON'T APPLY TO THIS TYPE OF CONSTRUCTION. PROVIDE
 DETAILS THAT APPLY TO THIS PROJECT.SEE SEC. R613.6.2
 TO SEE PROPER WAY OF INSTALLING STRUCTURAL BUCKS AND
 PROVIDE INFORMATION AS REQUIRED.
  
 J) SEE SECTION R803.2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODE AND REVISE ROOF SHEATHING FASTENING AS
 REQUIRED.
  
 K) 2X4 EXTERIOR FRAMED WALLS REQUIRE R11 MIN. WHILE,
 2X6 EXTERIOR WALLS REQUIRE R-19 MIN. SEE SEC.
 13-602.1.C.1.1 OF 2004 FBC AND REVISE PLANS/DETAILS AS
 REQUIRED.
  
  
 8- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) GABLE END ALUMINUM VENT.
 ***NOTE: ARCHITECT TO SPECIFY IN PLANS SIZE OF VENT AND
 CONSIDER THIS VENTS IN THE ATTIC VENTILATION
 CALCUALTIONS.
  
 9- ARCHITECT TO REVIEW AN APPROVE IN WRITING (NOT
 SIGNING AND SEALING)ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 10- TYPICAL WALL SECTION TO PROVIDE COMPLETE
 SPECIFICATIONS FOR WALL SHEATHING THICKNESS AND
 FASTENING. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 11- PROVIDE COMPLETE FRAMING DETAILS FOR EXTERIOR DOORS
 AND WINDOWS. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 12- ENERGY CALCULATIONS:
 A) PROVIDE REVISED FORM 600A-2004 R.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM.
  
 13- ENERGY CALCULATIONS ARE TAKEN THE CEILING FAN
 CREDIT. THEREFORE, NEED TO SPECIFY ON PLANS SPECIFIC
 SIZE OF FAN TO BE INSTALLED AS REQUIRED BY TABLE
 13-607.1.A.1 OF 2004 FBC.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-02-25 Cont ID  
Sent By btrobaug Date 2008-02-25 Time 08:34 Rev Time 0.00
Received By btrobaug Date 2008-02-25 Time 08:20 Sent To PC
Notes
2008-02-25 08:33:57 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} INCREASE THE VALUE OF THE JOB TO INCLUDE THE
 ADDITIONAL WORK, LABOR AND MATERIAL ADJUST THE VALUE AT
 THE PERMIT CLERK?S DESK, AND PAY THE DIFFERENCE IN FEES
 PRIOR TO RESUBMITTING.
  
 2} THE ARCHITECT?S SIGNATURE IS A PHOTOCOPY. WHEN
 SUBMITTING FOR PERMITTING THE SIGNATURE MUST BE WET PER
 481.221(1)(A) FLORIDA STATUTES.PLEASE NOTE THAT HAND
 DRAWN CHANGES TO THE PLAN ARE NOT ACCEPTABLE AS THEY
 CANNOT BE VERIFIED AS BEING MADE BY THE DESIGNER OF
 RECORD AS REQUIRED BY FS 481.
  
 3} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS, LOAD CALCULATIONS,
 PANEL SCHEDULES, SERVICE EQUIPMENT AND PANEL LOCATIONS
 PER 106.3.5.4 FBC. 215.5NEC.
  
 4} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-12-05 Cont ID  
Sent By btrobaug Date 2007-12-05 Time 08:57 Rev Time 0.00
Received By btrobaug Date 2007-12-05 Time 07:32 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-10-05 Cont ID  
Sent By btrobaug Date 2007-10-05 Time 07:36 Rev Time 0.00
Received By btrobaug Date 2007-10-05 Time 06:47 Sent To M
Notes
2007-10-05 07:07:26 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.
  
 THE PLANS SUBMITTED FOR THIS REVIEW ARE NOT THE SAME AS
 THE SET SUBMITTED ON 3/27/07, THE SCOPE HAS CHANGED TO
 ALL EXTERIOR WORK. AN ELECTRICAL PERMIT IS REQUIRED TO
 INSTALL THE RECESSED LIGHT IN THE COVERED ENTRY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-11 Cont ID  
Sent By btrobaug Date 2007-04-11 Time 17:10 Rev Time 1.00
Received By btrobaug Date 2007-04-11 Time 12:02 Sent To M
Notes
2007-04-11 16:16:53 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE #2 CU GROUNDING ELECTRODE CONDUCTOR WHILE NOT A
 VIOLATION, MUST BE INSTALLED IF IT IS ON THE PLAN. THE
 REQUIRED SIZE IS #4 CU PER 250.66.
  
 2} PLEASE INDICATE THE CONDUCTOR SIZE FROM THE METER TO
 THE DISCONNECT. PER 310.15 (B)(6), OR 310.16.
  
 3} 230.70 GENERAL.
 MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN
 A BUILDING OR OTHER STRUCTURE FROM THE SERVICE-ENTRANCE
 CONDUCTORS. THE PANEL IS LISTED AS MAIN LUG ONLY. IF IT
 DOES NOT HAVE A MAIN BREAKER THEN A DISCONNECT MUST BE
 INSTALLED AFTER THE METER.
  
 4} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 5} ALSO VERIFY FROM FPL THAT THE SERVICE IS 3 PHASE
 120/208 VOLT. THAT AREA IS ONLY KNOWN TO HAVE SINGLE
 PHASE 120/240 VOLT TRANSFORMERS. THE VOLTAGE RATING OF
 THE PANEL ON THE PLAN IS NOT RATED FOR A 120/240
 VOLTAGE.
  
 6} THE AIR HANDLER OVERCURRENT PROTECTION, CIRCUIT
 #20,22, IS NOT COMPLIANT PER 424.3(B) NEC.-
 BRANCH-CIRCUIT SIZING FIXED ELECTRIC SPACE HEATING
 EQUIPMENT SHALL BE CONSIDERED CONTINUOUS LOAD.(125%)
 10000/240=41.66X125%=52 AMPS= 60 AMP BREAKER(240.4) AND
 #6 CONDUCTORS (310.16).
  
 7} PLEASE INDICATE THE CODE THE PLAN WAS DESIGNED AND
 APPLICATION WAS MADE UNDER. 2004 FBC AND 2005 NEC.
  
 8} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (2),
 SEE MASTER BEDROOM WALL BETWEEN ENTRY AND THE
 BATHROOM.
  
 9} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.1
 RESIDENTIAL FLORIDA BUILDING CODE. THIS IS IN ALL
 BEDROOMS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-02-13 Cont ID  
Sent By adarroug Date 2008-02-13 Time 14:00 Rev Time 0.00
Received By adarroug Date 2008-02-13 Time 14:00 Sent To E
Notes
2008-02-13 14:00:54TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-11-30 Cont ID  
Sent By adarroug Date 2007-11-30 Time 08:56 Rev Time 0.00
Received By adarroug Date 2007-11-30 Time 08:56 Sent To Z
Notes
2007-11-30 08:56:49TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-10-01 Cont ID  
Sent By adarroug Date 2007-10-01 Time 11:28 Rev Time 0.00
Received By adarroug Date 2007-10-01 Time 11:28 Sent To Z
Notes
2007-10-01 11:28:54TO "Z" BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-10 Cont ID  
Sent By adarroug Date 2007-04-10 Time 11:36 Rev Time 0.00
Received By adarroug Date 2007-04-10 Time 11:36 Sent To E
Notes
2007-04-10 11:37:17TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-24 Cont ID  
Sent By adavila Date 2007-04-09 Time 19:48 Rev Time 0.00
Received By jgomez Date 2007-03-28 Time 17:45 Sent To Z
Notes
2007-03-28 17:45:44TO ZONING BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2007-10-10 Cont ID  
Sent By tgordon Date 2007-10-10 Time 16:30 Rev Time 0.20
Received By tgordon Date 2007-10-10 Time 16:30 Sent To P
Notes
2007-10-10 16:33:07NEW SCOPE OF WORK DOES NOT INCLUDE ANY MECHANICAL WORK
 OR THE ADDITION.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-12 Cont ID  
Sent By tgordon Date 2007-04-12 Time 08:56 Rev Time 1.00
Received By tgordon Date 2007-04-12 Time 08:55 Sent To P
Notes
2007-04-12 09:56:05*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM600A-04R,
 SEE 2004 FBC 13-600.3.A (12-8-06 REVISION).
  
 2) PLANS SHOW THE SOUTH EXTERIOR WALL OF THE NEW
 ADDITION TO BE 6" WHICH WILL REQUIRE AN R-19 MINIMUM
 INSULATION, SEE 2004 FBC 13-602.1C.1, PLEASE SHOW ON
 PLANS.
  
 3) ENERGY CALCULATIONS AND THE MECHANICAL PLANS ARE
 CALLING FOR A FIVE TON A/C SYSTEM 48,000 SENSIBLE BTU'S
 WHICH IS TO LARGE, SEE THE COOLING LOAD CALCULATIONS
 ARE CALLING FOR 29,044 SENSIBLE BTU'S, THE PLANS CAL
 ONLY CALL FOR 15% MORE THAN THE COOLING LOAD CAL'S, SEE
 2004 FBC 13-607.1.ABC.1.1, PLEASE CORRECT.
  
 4) SEE THE MECHANICAL PLANS "WALL CAP DETAIL" IS
 CALLING FOR AN INSECT/BIRD SCREEN, A SCREEN MAY NOT BE
 IN THE CLOTHS DRYER VENT BUT WILL NEED A BACKDRAFT
 DAMPER, SEE 2004 FBC/R M1501.1, PLEASE CORRECT.
  
 5) CLOTHES DRYER VENT TERMINATION MAY NOT DISCHARGE
 NEAR THE A/C CONDENSER UNIT, SEE2004 FBC/M 501.2,
 PLEASE CORRECT .
  
 6) SEE MECHANICAL PLANS SHOWING A 10" SUPPLY AIR DUCT
 TO THE MASTER BATHROOM, BELIEVED TO BE A TYPE-O, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status N Date 2007-10-12 Cont ID  
Sent By jleech Date 2007-10-12 Time 07:25 Rev Time 0.00
Received By jleech Date 2007-10-12 Time 07:25 Sent To B
Notes
2007-10-12 07:26:23NO PLUMBING SHOWN ON PLANS

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-04-24 Cont ID  
Sent By jleech Date 2007-04-24 Time 10:22 Rev Time 0.00
Received By jleech Date 2007-04-24 Time 10:12 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2007-12-03 Cont ID  
Sent By adavila Date 2007-12-03 Time 15:27 Rev Time 0.00
Received By adavila Date 2007-12-03 Time 15:27 Sent To E
Notes
2007-12-03 15:27:57PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-10-04 Cont ID  
Sent By adavila Date 2007-10-04 Time 14:11 Rev Time 0.00
Received By adavila Date 2007-10-04 Time 14:11 Sent To E
Notes
2007-10-04 14:42:14PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. SITE PLAN DOES NOT MATCH SURVEY.
 A. SETBACK DIMENSIONS, LOT WIDTH AND LOT DEPTH SHALL BE
 CORRECTED TO REFLECT ACTUAL CONDITIONS.
 B. ACCORDING TO THE SURVEY, THE PROPOSED ENTRY IS 25.2
 FROM THE NORTH PROPERTY LINE.HOWEVER, ACCORDING TO
 THE SITE PLAN, THE PROPOSED ENTRY ENCROACHES INTO THE
 REQUIRED FRONT SETBACK OF 25 FEET.PLEASE REVISE.
  
 2. PROVIDE ROOF OVERHANG DIMENSION.PLEASE NOTE THAT
 PER SECTION 94-305(B)(2), STRUCTURAL OVERHANGS
 INCLUDING EAVES AND ROOF OVERHANG PROJECTIONS SHALL NOT
 EXTEND FARTHER THAN 3 FEET INTO ANY SETBACK.
  
 3. PROVIDE BUILDING HEIGHT DIMENSION OF THE PROPOSED
 ENTRY FROM GRADE.
  
 COMMENTS/QUESTIONS CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-04-09 Cont ID  
Sent By jgomez Date 2007-04-24 Time 16:54 Rev Time 0.00
Received By adavila Date 2007-04-09 Time 15:23 Sent To I
Notes
2007-04-09 19:48:16PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. SITE PLAN DOES NOT MATCH SURVEY.
 A. SETBACK DIMENSIONS, LOT WIDTH AND LOT DEPTH SHALL BE
 CORRECTED TO REFLECT CORRECT CIRCUMSTANCES.
 B. PLEASE NOTE THAT PER SECTION 94-72(A)(2)(C),
 REQUIRED REAR SETBACK IS 15 FEET OR 10 PERCENT OF THE
 DEPTH OF THE LOT, WHICHEVER IS LESS.
  
 2. PROVIDE DIMENSIONS FROM WALL TO END OF ROOF EVE.
 ACCORDING TO SHEET A1 OF 3, PROJECTION OF PROPOSED ROOF
 EAVE WILL MATCH EXISTING; HOWEVER, EXISTING DIMENSION
 IS NOT STATED.
  
 3. PROVIDE BUILDING HEIGHT DIMENSION OF PROPOSED
 ADDITION FROM GRADE.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.