Plan Review Details - Permit 07030943
Plan Review Stops For Permit 07030943
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-05-08 Cont ID  
Sent By rmcdouga Date 2007-05-08 Time 09:50 Rev Time 0.00
Received By rmcdouga Date 2007-05-08 Time 09:50 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-18 Cont ID  
Sent By rmcdouga Date 2007-04-18 Time 13:14 Rev Time 0.00
Received By rmcdouga Date 2007-04-18 Time 13:13 Sent To  
Notes
2007-04-18 11:59:10DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) EACH SHEET OF THE DRAWINGS IS REQUIRED TO HAVE A
 TITLE BLOCK IDENTIFYING THE PROJECT, AS WELL AS, THE
 PRINTED NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. FBC* 106.1.2.
  
 3) FBC * 106.1.2 QUALITY OF PLANS
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT. SUBMIT PLANS
 THAT ARE CLEAR AND DRAWN TO SCALE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-05-03 Cont ID  
Sent By btrobaug Date 2007-05-03 Time 12:10 Rev Time 1.00
Received By btrobaug Date 2007-05-03 Time 07:58 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-02 Cont ID  
Sent By btrobaug Date 2007-04-02 Time 15:44 Rev Time 0.25
Received By btrobaug Date 2007-04-02 Time 15:32 Sent To P
Notes
2007-04-02 15:44:38 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH
 210.52(A), 210.52(C), AND 210.8(A)(6) GFI.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
  
 3} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE
 PLANS FOR RECORD RETENTION.106.1.3.FBC AS AMENDED.
  
 4} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW PER 106.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-11 Cont ID  
Sent By adarroug Date 2007-05-11 Time 09:05 Rev Time 0.00
Received By adarroug Date 2007-05-11 Time 09:05 Sent To Z
Notes
2007-05-11 09:06:11TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-25 Cont ID  
Sent By adarroug Date 2007-04-25 Time 16:07 Rev Time 0.00
Received By adarroug Date 2007-04-25 Time 16:07 Sent To E
Notes
2007-04-25 16:07:46TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-18 Cont ID  
Sent By rmcdouga Date 2007-04-18 Time 13:25 Rev Time 0.00
Received By rmcdouga Date 2007-03-27 Time 18:34 Sent To  
Notes
2007-03-27 18:34:18TO SFR "ELEC"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-05-04 Cont ID  
Sent By tgordon Date 2007-05-04 Time 09:26 Rev Time 0.25
Received By tgordon Date 2007-05-04 Time 09:26 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-30 Cont ID  
Sent By tgordon Date 2007-03-30 Time 08:49 Rev Time 0.25
Received By tgordon Date 2007-03-30 Time 08:49 Sent To E
Notes
2007-03-30 08:53:35*** DENIED ***
 1) MECHANICAL PERMIT # 07030946 HAS BEEN APPLIED FOR
 BUT NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW.
 PLEASE SUBMIT MECHANICAL PLANS FOR REVIEW, SEE 2004 FBC
 CITY WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-05-03 Cont ID  
Sent By mperson Date 2007-05-03 Time 14:34 Rev Time 0.33
Received By mperson Date 2007-05-03 Time 14:34 Sent To M
Notes
2007-05-03 14:37:11****************PROVISO****************
 (A) 604.9 WATER HAMMER. A WATER-HAMMER
 ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED.
 NOTE: WATER HAMMER ARRESTOR REQUIRED ON ICE MAKER AND
 DISHWASHER.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-10 Cont ID  
Sent By btrobaug Date 2007-04-02 Time 15:58 Rev Time 0.33
Received By mperson Date 2007-04-10 Time 08:14 Sent To B
Notes
2007-04-10 09:21:42DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLUMBING PERMIT APPLICATION IS INCOMPLETE PER STATE
 STATUTE 713.135 (6) CONTRACTOR SIGNATURE REQUIRED ON
 PLUMBING PERMIT APPLICATION.
  
 2. NOTE: VALUE OF $250.00 SEEMS LOW ON THE PLUMBING
 PERMIT APPLICATION. PLEASE PROVIDE PROOF OF COST
 (CONTRACT) IN THE RESUBMITTAL REFLECTING THE
 FOLLOWING.
 PER FBC-2004, CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
  
 3.MORE INFORMATION IS REQUIRED.
 A} IF PLUMBING LAYOUT IS THE SAME
 WITH NO CHANGES, PLEASE INDICATE THIS ON
 THE DRAWING.
 B} IF PLUMBING LAYOUT IS THE
 SAME AND THE PLUMBING FIXTURES ARE TO BE
 CHANGED, PLEASE INDCATE ON THE DRAWING.
 "EXACT FIXTURE CHANGE OUT ONLY."
 C} IF THE NEW PROPOSED PLUMBING LAYOUT IS DIFFERENT
 FROM THE EXISTING PLEASE FOLLOW WHAT IS REQUIRED IN
 COMMENT #4
  
 4. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 1 Status P Date 2007-05-08 Cont ID  
Sent By choops Date 2007-05-08 Time 10:27 Rev Time 0.00
Received By choops Date 2007-05-08 Time 10:27 Sent To PC
Notes
***NONE***