Plan Review Details - Permit 07030932
Plan Review Stops For Permit 07030932
Review Stop AD ADDRESSING
Rev No 4 Status P Date 2008-02-26 Cont ID  
Sent By lursu Date 2008-02-26 Time 08:19 Rev Time 0.00
Received By lursu Date 2008-02-26 Time 08:19 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 3 Status P Date 2008-02-20 Cont ID  
Sent By jwitmer Date 2008-02-20 Time 07:57 Rev Time 0.00
Received By jwitmer Date 2008-02-20 Time 07:57 Sent To  
Notes
2008-02-20 07:57:46UNIT NUMBER IS TO BE 1800 FOR PENTHOUSE

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2007-09-19 Cont ID  
Sent By jwitmer Date 2007-09-19 Time 21:19 Rev Time 4.00
Received By jwitmer Date 2007-09-19 Time 21:19 Sent To  
Notes
2007-09-19 21:34:55BUILDING PLAN REVIEW
 PERMIT: 07030932
 ADD: 525 OKEECHOBEE BLVD PENTHOUSE A & B
 CONT: CENTEX/ BALFOUR BEATTY
 TEL: (954)214-9415
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) NOTE IN SOME TITLE BLOCKS THERE IS YCJ DESIGN AND
 OTHER TITLE BLOCKS YJ ARCHITECTURAL DESIGNS ( YOUSEF
 JALALI) , PLEASE SEE THE FOLLOWING FLORIDA STATUTES FOR
 ARCHITECTS AND INTERIOR DESIGNERS:
  
 3A)Y J ARCHITECTURAL DESIGN WILL REQUIRE A
 CERTIFICATE OF AUTHORIZATION, FLORIDA STATE STATUTE
 481.219(2) (ARCHITECT),THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT PRACTICING UNDER
 A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ARCHITECTURAL SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER.
  
 3B) YCJ DESIGN, FLORIDA S. S. 481.219(3)(INTERIOR
 DECORATORS)FOR THE PURPOSES OF THIS SECTION, A
 CERTIFICATE OF AUTHORIZATION SHALL BE REQUIRED FOR A
 CORPORATION, LIMITED LIABILITY COMPANY, PARTNERSHIP, OR
 PERSON OPERATING UNDER A FICTITIOUS NAME, OFFERING
 INTERIOR DESIGN SERVICES TO THE PUBLIC JOINTLY OR
 SEPARATELY. HOWEVER, WHEN AN INDIVIDUAL IS PRACTICING
 INTERIOR DESIGN IN HER OR HIS OWN NAME, SHE OR HE SHALL
 NOT BE REQUIRED TO BE CERTIFIED UNDER THIS SECTION.
  
 3C) PLEASE SEE FLORIDA STATE STATUTE 481.2131 (INTERIOR
 DESIGNERS) PRACTICE REQUIREMENTS; DISCLOSURE OF
 COMPENSATION FOR PROFESSIONAL SERVICES.
  
 3D) THE CONSULTING STRUCTURAL ENGINEER NAIM& ASSOCIATES
 ARE THE ONLY STRUCTURAL ENGINEERING FIRM LISTED ON THE
 SHEET, NO INDIVIDUAL ENGINEER HAS SIGNED AND SEALED THE
 PLANS.FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002(2)
  
 3E) ) 61G15-23.002(2)FL. ADMIN. CODE. PLANS SIGNED &
 SEALED BY A PROFESSIONAL ENGINEER
 SHALL INCLUDE EITHER:
 - THE NAME,ADDRESS AND LICENSE NUMBER OF THE ENGINEER
 OR,
 - THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING
 (471.025 F.S. AND471.023 F.S.).
  
 4)SECOND REQUEST, SHEET S-1 DOES NOT APPEAR IN THE
 INDEX SHEET. STRUCTURAL SHEET S-1 WILL REQUIRE A RAISED
 IMPRESSION TYPE SEAL NOT A STAMPED SEAL. FLORIDA
 ADMINISTRATIVE CODE 61G15-23.001, THE DESIGN
 PROFESSIONAL MUST BE A LICENSED ENGINEER IN THE STATE
 OF FLORIDA. FL S. S.471.025. THE RESPONSE INDICATES
 THAT THE STRUCTURAL SHEETS WILL HAVE A RAISED
 IMPRESSION SEAL BY A LICENSED ENGINEER IN FLORIDA BUT
 THIS SET OF PLANS THE CONSULTING STRUCTURAL ENGINEER
 NAIM& ASSOCIATES ARE THE ONLY STRUCTURAL ENGINEERING
 FIRM LISTED ON THE SHEET, NO INDIVIDUAL ENGINEER HAS
 SIGNED AND SEALED THE PLANS.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.002(2).PLANS
 SIGNED & SEALED BY A PROFESSIONAL ENGINEER SHALL
 INCLUDE EITHER THE NAME, ADDRESS AND LICENSE NUMBER OF
 THE ENGINEER OR, THE NAME AND LICENSE NUMBER OF THE
 ENGINEER AND THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS
 THROUGH WHICH THE ENGINEER IS PRACTICING
  
 5) SECOND REQUEST, THE SAME HOLDS TRUE FOR THE
 CALCULATIONS SUBMITTED FOR THE STAIRS BETWEEN THE 15TH
 & 16TH FLOOR. MUST BE A LICENSED ENGINEER FOR THE STATE
 OF FLORIDA AND IF THE ENGINEER OF RECORD DOES NOT SEAL
 EACH SHEET THEN A SEALED COVER SHEET LISTING HOW MANY
 PAGES ARE COVERED UNDER THIS SEAL. 61G15-23.002.
  
 6) COMPLIED.
  
 7A) LS-01 THERE IS A DISCREPANCY IN FLOOR AREA FROM THE
 LIFE SAFETY PLAN & THE ENERGY CALCS PLEASE CORRECT.
  
 7B) LIFE SAFETY PLANS HAVE THE WRONG WIND CRITERIA
 PLEASE CORRECT THE REFERENCE TO ASCE 7-98.
 8)COMPLIED.
  
 9) COMPLIED.
  
 10) SECOND REQUEST, SHEET 1-16C INDICATE TWO TYPE OF
 DOORS THAT WILL BE PENETRATING THE 1 HR RATED WALL DOOR
 TYPED-6 WHICH DOES HAVE 45 MINUTE RATING AND DOOR TYPE
 D-3 WHICH DOES NOT PLEASE CORRECT. TABLE 715.3.
  
 11) SECOND REQUEST, RESPONSE INDICATES THE NOTE IS
 ADDED TO THE GENERAL NOTES NOT NUMBER 58, SHEET I-G.1
 THE GENERAL NOTES ONLY GO UP TO 44.PLEASE TAKE NOTE
 OF : 404.7 INTERIOR FINISH. THE INTERIOR FINISH OF
 WALLS AND CEILINGS OF THE ATRIUM SHALL NOT BE LESS THAN
 CLASS B WITH NO REDUCTION IN CLASS FOR SPRINKLER
 PROTECTION.
  
 12) COMPLIED.
  
 13-15) COMPLIED.
  
 16) 2ND REQUEST, A FLORIDA REGISTERED ENGINEER,
 PLEASE PROVIDE ADDITIONAL INFORMATION ON THE GLASS
 HANDRAILS AND GUARDS SEE 2407.
 2407.1.1 LOADS.
 THE PANELS AND THEIR SUPPORT SYSTEM SHALL BE DESIGNED
 TO WITHSTAND THE LOADS SPECIFIED IN SECTION 1607.7 . A
 SAFETY FACTOR OF FOUR SHALL BE USED.
  
 2407.1.2 SUPPORT.
 EACH HANDRAIL OR GUARD SECTION SHALL BE SUPPORTED BY A
 MINIMUM OF THREE GLASS BALUSTERS OR SHALL BE OTHERWISE
 SUPPORTED TO REMAIN IN PLACE SHOULD ONE BALUSTER PANEL
 FAIL. GLASS BALUSTERS SHALL NOT BE INSTALLED WITHOUT AN
 ATTACHED HANDRAIL OR GUARD.
  
 17)COMPLIED.
  
 18) SECOND REQUEST, THE RESPONSE SHEET INDICATES A NOTE
 59 WAS ADDED TO THE GENERAL COMMENTS? THE GLASS WALL IS
 ALSO CONSIDERED A HAZARDOUS LOCATION 15TH AND 16TH
 FLOORS. SEE 2406.3(7)
 7.GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE
 PANEL, OTHER THAN IN THOSE LOCATIONS DESCRIBED IN
 PRECEDING ITEMS 5 AND 6, WHICH MEETS ALL OF THE
 FOLLOWING CONDITIONS:
 7.1.EXPOSED AREA OF AN INDIVIDUAL PANE GREATER
 THAN 9 SQUARE FEET (0.84 M 2 );
 7.2.EXPOSED BOTTOM EDGE LESS THAN 18 INCHES (457
 MM) ABOVE THE FLOOR;
 7.3.EXPOSED TOP EDGE GREATER THAN 36 INCHES (914
 MM) ABOVE THE FLOOR; AND
 7.4.ONE OR MORE WALKING SURFACE(S) WITHIN 36
 INCHES (914 MM) HORIZONTALLY OF THE PLANE OF THE
 GLAZING.
 EXCEPTION: SAFETY GLAZING FOR ITEM 7 IS NOT REQUIRED
 FOR THE FOLLOWING INSTALLATIONS:
 1.A PROTECTIVE BAR 1? INCHES (38 MM) OR MORE IN
 HEIGHT, CAPABLE OF WITHSTANDING A HORIZONTAL LOAD OF 50
 POUNDS PLF (730 N/M) WITHOUT CONTACTING THE GLASS, IS
 INSTALLED ON THE ACCESSIBLE SIDES OF THE GLAZING 34
 INCHES TO 38 INCHES (864 MM TO 965 MM) ABOVE THE
 FLOOR.
  
 19-23B) COMPLIED.
  
 24) A NEW COMMENT, E2.1 INDICATES WORK BEING COMPLETED
 ON THE 17TH FLOOR AND E2.2 INDICATES THE 16TH FLOOR,
 PLEASE CORRECT THIS DISCREPANCY.
  
 25) A NEW COMMENT,I-15.C ROOMS 1543& 1544 BOTH ARE
 INDICATED AS COMPUTER EQUIPMENT ROOMS SEE ELECTRICAL
 COMMENTS AS TO THE 1 HR FIRE RATING REQUIREMENTS.
  
 26) ENERGY CALCULATIONS PLEASE PROVIDE THE INFORMATION
 FOR THE SKYLIGHTS TO BE INSTALLED ON THE
 ROOF OF THE 16TH FLOOR. ADDITIONAL INFORMATION REQUIRED
 106.1.2*
 27) SHEET I-15.R PLEASE CORRECT THIS SHEET TITLE BLOCK
 IT APPEARS WHITE OUT WAS USED IN THE TITLE BLOCK AND
 THEN HAND DRAWN NUMERALS.
  
 28) SHEETS S-1 AND S-2 INDICATE NEW STAIRS AND FLOOR
 BEAMS COMMUNICATING BETWEEN THE FLOORS, AS PART OF A
 THRESHOLD BUILDING THE FOLLOWING ITEMS WILL NEED TO BE
 ADDRESSED:
  
 28A)105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A "STRUCTURAL
 INSPECTION PLAN"
 PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 28B) THE SHELL BUILDING HAS NOT ACHIEVED A CERTIFICATE
 OF COMPLETION, THE STRUCTURAL PLANS FOR THIS TENANT
 SPACE SHALL BE REVIEWED BY THE ENGINEER OF RECORD FOR
 THE " BASE BUILDING"
 AND BE STAMPED WITH THEIR SHOP DRAWING STAMP THEY ARE
 APPROVING THE PLANS AND WORK TO BE COMPLETED UNDER THIS
 PERMIT BEFORE THEIR CERTIFICATE OF COMPLETION HAS BEEN
 ISSUED.
  
 28C) THE SAME HOLDS TRUE FOR THE ARCHITECTURAL SHEETS,
 THE DESIGNER OF RECORD FOR THE BUILDING SHALL REVIEW
 AND AFFIX THEIR SHOP DRAWING STAMP TO THESE PLANS WITH
 THEIR APPROVAL.
  
 28D) SINCE THERE WILL NEED TO BE A THRESHOLD INSPECTOR
 ON SITE, A THIRD SET OF PLANS, SUBMITTALS AND OR OTHER
 DOCUMENTS WILL NEED TO BE SUBMITTED BEFORE ISSUANCE OF
 THIS PERMIT.
  
 28E) SINCE THE STEEL BEAMS ARE NEW ELEMENTS AND NEED TO
 INDICATE FIRE PROOFING AS TO TABLE 601 FLOOR AND BEAM 3
 HR RATING SEE FOOTNOTE "G" 1 HR REDUCTION FOR FIRE
 SPRINKLED BUILDINGS.
 PLEASE SHOW COMPLIANCE.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-06-13 Cont ID  
Sent By lursu Date 2007-06-13 Time 13:36 Rev Time 0.00
Received By lursu Date 2007-06-13 Time 13:36 Sent To  
Notes
2007-06-13 13:40:30THE SITE ADDRESS ON THE APPLICATION HAS UNITS A & B
 .ARE THESE TWO UNITS COMBINED INTO ONE? ARE THESE UNITS
 OWNED INDIVIDUALLY ?
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2008-11-07 Cont ID  
Sent By jwitmer Date 2008-11-07 Time 16:46 Rev Time 0.77
Received By jwitmer Date 2008-11-07 Time 16:46 Sent To PC
Notes
2008-11-07 16:49:38 
 BUILDING PLAN REVIEW
 PERMIT: 07030932
 ADD: 525 OKEECHOBEE BLVD SUITE# 1700/ 1800
 CONT: BALFOUR BEATTY CONSTRUCTION
 TEL: (561)531-1456
 HEIDI
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: REVIEWED
  
 REVISION:# 18 SHEET I-D.4
 GARDEN AREA & SAND BOX DETAILS

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2008-10-17 Cont ID  
Sent By jwitmer Date 2008-10-17 Time 14:28 Rev Time 0.77
Received By jwitmer Date 2008-10-17 Time 14:28 Sent To PC
Notes
2008-10-17 14:29:30REVISION# 16 FRAMING DETAILS I-D.3

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2008-07-14 Cont ID  
Sent By jwitmer Date 2008-07-14 Time 13:45 Rev Time 0.77
Received By jwitmer Date 2008-07-14 Time 13:45 Sent To  
Notes
2008-07-14 13:57:25 
 BUILDING PLAN REVIEW
 PERMIT: 07030932
 ADD: 525 OKEECHOBEE BLVD 1700/1800
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)531-1456
 HEIDI DANIELSEN
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW
 ACTION: REVIEWED/ PROVISO
  
 RAMPAGE COMPLIES WITH 11-4.8 1-5
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2008-07-03 Cont ID  
Sent By jwitmer Date 2008-07-03 Time 16:12 Rev Time 0.77
Received By jwitmer Date 2008-07-03 Time 16:12 Sent To  
Notes
2008-07-03 16:14:34 
 BUILDING PLAN REVIEW
 PERMIT: 07030932
 ADD: 525 OKEECHOBEE BLVD # 1700/1800
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)348-2222
 TOM REEDER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: REVIEWED
 SUBMITTAL: GFRG SHOP DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2008-06-30 Cont ID  
Sent By jwitmer Date 2008-06-30 Time 13:29 Rev Time 1.11
Received By jwitmer Date 2008-06-30 Time 13:29 Sent To PC
Notes
2008-06-30 13:30:03SHOP DRAWINGS FOR STCKWALL GLASS SYSTEMS

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-06-03 Cont ID  
Sent By jwitmer Date 2008-06-03 Time 13:07 Rev Time 0.77
Received By jwitmer Date 2008-06-03 Time 13:07 Sent To PC
Notes
2008-06-03 13:09:32INTECH SUBMITTALS:
 FIRESTOPPING MATERIALS
 REV# 10 I-15.C
 I-E.!A
 I-E.1C
 I-E.1C
 I-D.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-05-10 Cont ID  
Sent By jwitmer Date 2008-05-10 Time 12:51 Rev Time 1.33
Received By jwitmer Date 2008-05-10 Time 12:51 Sent To PC
Notes
2008-05-10 12:56:59 
 BUILDING PLAN REVIEW
 PERMIT: 07030932
 ADD: 525 OKEECHOBEE BLVD SUITE 1700/1800
 CONT:BALFOUR BEATTY CONSTRUCTION
 TEL: (561)718-0935
 SEAN STICHTER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: REVIEWED
 SUBMITTAL:
 SUBMITTAL# 05510-005R-1SOUTH STAIR SHOP DRAWING
 SUBMITTAL# 055-006 NORTH STAIR SHOP DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-05-06 Cont ID  
Sent By jwitmer Date 2008-05-06 Time 10:32 Rev Time 1.22
Received By jwitmer Date 2008-05-06 Time 10:32 Sent To  
Notes
2008-05-06 10:44:38BUILDING PLAN REVIEW
 PERMIT: 070300932
 ADD: 525 OKEECHOBEE SUITE 1700/ 1800
 CONT: BALFOUR BEATTY CONSTRUCTION
 TEL: (561)248-2222 TOM REEDER
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SHOP DRAWINGREVIEW
 ACTION: DENIED
  
 THE ENGINEER OF RECORD MICHAEL ROBINSON IS MISSING
 THEIR TITLE BLOCK, INFORMATION RQUIRED IS:
 61G15-23.002(2)FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.)

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-02-20 Cont ID  
Sent By jwitmer Date 2008-02-20 Time 07:52 Rev Time 2.22
Received By jwitmer Date 2008-02-20 Time 07:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-12-12 Cont ID  
Sent By jwitmer Date 2007-12-12 Time 10:36 Rev Time 4.44
Received By jwitmer Date 2007-12-12 Time 10:36 Sent To  
Notes
2007-12-12 10:44:32525 OKEECHOBEE BLVD
 INTECH
 DEC.11, 2007
  
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07030932
 ADD: 525 OKEECHOBEE BLVD PENTHOUSE A & B
 CONT: CENTEX/ BALFOUR BEATTY
 TEL: (954)214-9415
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SECOND REQUEST, YC J DESIGN WILL REQUIRE A
 CERTIFICATE OF AUTHORIZATION,481.219 F.S.
 CERTIFICATE OF AUTHORIZATION,THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT PRACTICING UNDER
 A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ARCHITECTURAL SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER.
 481.219CERTIFICATION OF PARTNERSHIPS, LIMITED
 LIABILITY COMPANIES, AND CORPORATIONS.--
 (1)THE PRACTICE OF OR THE OFFER TO PRACTICE
 ARCHITECTURE OR INTERIOR DESIGN BY LICENSEES THROUGH A
 CORPORATION, LIMITED LIABILITY COMPANY, OR PARTNERSHIP
 OFFERING ARCHITECTURAL OR INTERIOR DESIGN SERVICES TO
 THE PUBLIC, OR BY A CORPORATION, LIMITED LIABILITY
 COMPANY, OR PARTNERSHIP OFFERING ARCHITECTURAL OR
 INTERIOR DESIGN SERVICES TO THE PUBLIC THROUGH
 LICENSEES UNDER THIS PART AS AGENTS, EMPLOYEES,
 OFFICERS, OR PARTNERS, IS PERMITTED, SUBJECT TO THE
 PROVISIONS OF THIS SECTION.
 3A-C) COMPLIED
  
 3D) THE STRUCTURAL ENGINEER NAIM & ASSOCIATES STILL
 INDICATES THEY ARE THE DESIGNERS FOR THE STAIRS. THEIR
 NAME DOES NOT APPEAR ON THE STRUCTURAL SHEETS BUT DOES
 APPEAR ON THE STAIR 1 & STAIR 2 STRUCTURAL CALCULATIONS
 AS WELL AS THE HANDRAIL CALCULATION. FLORIDA
 ADMINISTRATIVE CODE
 61G15-23.002(2)
 . ENGINEERING REPORTS MUST BE SIGNED, SEALED AND DATED
 ON A SIGNATURE PAGE OR COVER LETTER BY EACH
 PROFESSIONAL ENGINEER WHO IS IN RESPONSIBLE CHARGE OF
 ANY PORTION OF THE REPORT. A PROFESSIONAL ENGINEER MAY
 ONLY SEAL AN ENGINEERING REPORT, PLAN, PRINT OR
 SPECIFICATION IF THAT PROFESSIONAL ENGINEER WAS IN
 RESPONSIBLE CHARGE OF THE PREPARATION AND PRODUCTION OF
 THE ENGINEERING DOCUMENT AND THE PROFESSIONAL ENGINEER
 HAS THE EXPERTISE IN THE ENGINEERING DISCIPLINE USED IN
 PRODUCING THE ENGINEERING DOCUMENT IN QUESTION.
  
  
 4) COMPLIED.
  
 5) THE SAME HOLDS TRUE FOR THECALCULATIONS SUBMITTED
 FOR THE STAIRS BETWEEN THE 15TH & 16TH FLOOR. MUST BE A
 LICENSED ENGINEER FOR THE STATE OF FLORIDA AND IF THE
 ENGINEER OF RECORD DOES NOT SEAL EACH SHEET THEN A
 SEALED COVER SHEET LISTING HOW MANY PAGES ARE COVERED
 UNDER THIS SEAL. 61G15-23.002.THE ENGINEER SIE H WONG
 WILL ASSUME THE WORK AS HIS OWN WITH THE
 CALCULATIONS COMPLETED AND UNDER THAT PERSONS SEAL.
 NOTE ALSO THE REQUIREMENTS FOR COVER SHEET AND OR INDEX
 PAGES OTHERWISE EACH SHEET WILL NEED TO BE SEALED.
 61G15-23.002
 A COVER OR INDEX SHEET FOR ENGINEERING SPECIFICATIONS
 MAY BE USED AND THAT SHEET MUST BE SIGNED, SEALED AND
 DATED BY THOSE PROFESSIONAL ENGINEERS IN RESPONSIBLE
 CHARGE OF THE PRODUCTION AND PREPARATION OF EACH
 SECTION OF THE ENGINEERING SPECIFICATION WITH
 SUFFICIENT INFORMATION ON THE COVER SHEET OR INDEX SO
 THAT THE USER WILL BE AWARE OF EACH PORTION OF THE
 SPECIFICATIONS FOR WHICH EACH PROFESSIONAL ENGINEER IS
 RESPONSIBLE. ENGINEERING REPORTS MUST BE SIGNED, SEALED
 AND DATED ON A SIGNATURE PAGE OR COVER LETTER BY EACH
 PROFESSIONAL ENGINEER WHO IS IN RESPONSIBLE CHARGE OF
 ANY PORTION OF THE REPORT. A PROFESSIONAL ENGINEER MAY
 ONLY SEAL AN ENGINEERING REPORT, PLAN, PRINT OR
 SPECIFICATION IF THAT PROFESSIONAL ENGINEER WAS IN
 RESPONSIBLE CHARGE OF THE PREPARATION AND PRODUCTION OF
 THE ENGINEERING DOCUMENT AND THE PROFESSIONAL ENGINEER
 HAS THE EXPERTISE IN THE ENGINEERING DISCIPLINE USED IN
 PRODUCING THE ENGINEERING DOCUMENT IN QUESTION.
  
 6) COMPLIED.
  
 7A) COMPLIED.
  
 7B) 2ND REQUEST THE LIFE SAFETY PLAN HAVE THE WRONG
 WINDCRITERIA, PLEASE CORRECT TO
 ASCE 7-02.
  
 8-9) COMPLIED
  
 10) SHEET 1-16C INDICATES DOOR TYPED-3(3) LOCATIONS
 WHERE THE DOOR IS CREATING THE OPENING PROTECTIVE 45MIN
 DOOR FOR THE ATRIUM, SHEET I-DR-1 DOES NOT INDICATE
 THIS AS A RATED DOOR, THE PLAN DOES INDICATE D3L AS A
 45MINUTE RATED DOOR. TABLE 715.3.
  
 11-15) COMPLIED
  
 16)PLEASE PROVIDE ADDITIONAL INFORMATION ON THE GLASS
 HANDRAILS AND GUARDS SEE 2407.
 2407.1.1 LOADS. THE PANELS AND THEIR SUPPORT SYSTEM
 SHALL BE DESIGNED TO WITHSTAND THE LOADS SPECIFIED IN
 SECTION 1607.7 . A SAFETY FACTOR OF FOUR SHALL BE
 USED.
  
 2407.1.2 SUPPORT.
 EACH HANDRAIL OR GUARD SECTION SHALL BE SUPPORTED BY A
 MINIMUM OF THREE GLASS BALUSTERS OR SHALL BE OTHERWISE
 SUPPORTED TO REMAIN IN PLACE SHOULD ONE BALUSTER PANEL
 FAIL. GLASS BALUSTERS SHALL NOT BE INSTALLED WITHOUT AN
 ATTACHED HANDRAIL OR GUARD.
  
 THIS WORK MUST BE COMPLETED BY A FLORIDA REGISTER
 PRACTICING ENGINEER.
 FL ADMINISTRATIVE CODE 61G15-23.002(2)
 . ENGINEERING REPORTS MUST BE SIGNED, SEALED AND DATED
 ON A SIGNATURE PAGE OR COVER LETTER BY EACH
 PROFESSIONAL ENGINEER WHO IS IN RESPONSIBLE CHARGE OF
 ANY PORTION OF THE REPORT. A PROFESSIONAL ENGINEER MAY
 ONLY SEAL AN ENGINEERING REPORT, PLAN, PRINT OR
 SPECIFICATION IF THAT PROFESSIONAL ENGINEER WAS IN
 RESPONSIBLE CHARGE OF THE PREPARATION AND PRODUCTION OF
 THE ENGINEERING DOCUMENT AND THE PROFESSIONAL ENGINEER
 HAS THE EXPERTISE IN THE ENGINEERING DISCIPLINE USED IN
 PRODUCING THE ENGINEERING DOCUMENT IN QUESTION.
 17-28) COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-09-20 Cont ID  
Sent By jwitmer Date 2007-09-20 Time 07:02 Rev Time 5.55
Received By jwitmer Date 2007-09-20 Time 07:02 Sent To  
Notes
2007-09-20 07:03:35525 OKEECHOBEE BLVD
 INTECH
 SEPT.19, 2007
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07030932
 ADD: 525 OKEECHOBEE BLVD PENTHOUSE A & B
 CONT: CENTEX/ BALFOUR BEATTY
 TEL: (954)214-9415
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) NOTE IN SOME TITLE BLOCKS THERE IS YCJ DESIGN AND
 OTHER TITLE BLOCKS YJ ARCHITECTURAL DESIGNS ( YOUSEF
 JALALI) , PLEASE SEE THE FOLLOWING FLORIDA STATUTES FOR
 ARCHITECTS AND INTERIOR DESIGNERS:
  
 3A)Y J ARCHITECTURAL DESIGN WILL REQUIRE A
 CERTIFICATE OF AUTHORIZATION, FLORIDA STATE STATUTE
 481.219(2) (ARCHITECT),THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT PRACTICING UNDER
 A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ARCHITECTURAL SERVICES, SHALL INCLUDE THE
 CERTIFICATE OF AUTHORIZATION NUMBER.
  
 3B) YCJ DESIGN, FLORIDA S. S. 481.219(3)(INTERIOR
 DECORATORS)FOR THE PURPOSES OF THIS SECTION, A
 CERTIFICATE OF AUTHORIZATION SHALL BE REQUIRED FOR A
 CORPORATION, LIMITED LIABILITY COMPANY, PARTNERSHIP, OR
 PERSON OPERATING UNDER A FICTITIOUS NAME, OFFERING
 INTERIOR DESIGN SERVICES TO THE PUBLIC JOINTLY OR
 SEPARATELY. HOWEVER, WHEN AN INDIVIDUAL IS PRACTICING
 INTERIOR DESIGN IN HER OR HIS OWN NAME, SHE OR HE SHALL
 NOT BE REQUIRED TO BE CERTIFIED UNDER THIS SECTION.
  
 3C) PLEASE SEE FLORIDA STATE STATUTE 481.2131 (INTERIOR
 DESIGNERS) PRACTICE REQUIREMENTS; DISCLOSURE OF
 COMPENSATION FOR PROFESSIONAL SERVICES.
  
 3D) THE CONSULTING STRUCTURAL ENGINEER NAIM& ASSOCIATES
 ARE THE ONLY STRUCTURAL ENGINEERING FIRM LISTED ON THE
 SHEET, NO INDIVIDUAL ENGINEER HAS SIGNED AND SEALED THE
 PLANS.FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002(2)
  
 3E) ) 61G15-23.002(2)FL. ADMIN. CODE. PLANS SIGNED &
 SEALED BY A PROFESSIONAL ENGINEER
 SHALL INCLUDE EITHER:
 - THE NAME,ADDRESS AND LICENSE NUMBER OF THE ENGINEER
 OR,
 - THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING
 (471.025 F.S. AND471.023 F.S.).
  
 4)SECOND REQUEST, SHEET S-1 DOES NOT APPEAR IN THE
 INDEX SHEET. STRUCTURAL SHEET S-1 WILL REQUIRE A RAISED
 IMPRESSION TYPE SEAL NOT A STAMPED SEAL. FLORIDA
 ADMINISTRATIVE CODE 61G15-23.001, THE DESIGN
 PROFESSIONAL MUST BE A LICENSED ENGINEER IN THE STATE
 OF FLORIDA. FL S. S.471.025. THE RESPONSE INDICATES
 THAT THE STRUCTURAL SHEETS WILL HAVE A RAISED
 IMPRESSION SEAL BY A LICENSED ENGINEER IN FLORIDA BUT
 THIS SET OF PLANS THE CONSULTING STRUCTURAL ENGINEER
 NAIM& ASSOCIATES ARE THE ONLY STRUCTURAL ENGINEERING
 FIRM LISTED ON THE SHEET, NO INDIVIDUAL ENGINEER HAS
 SIGNED AND SEALED THE PLANS.
 FLORIDA ADMINISTRATIVE CODE 61G15-23.002(2).PLANS
 SIGNED & SEALED BY A PROFESSIONAL ENGINEER SHALL
 INCLUDE EITHER THE NAME, ADDRESS AND LICENSE NUMBER OF
 THE ENGINEER OR, THE NAME AND LICENSE NUMBER OF THE
 ENGINEER AND THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS
 THROUGH WHICH THE ENGINEER IS PRACTICING
  
 5) SECOND REQUEST, THE SAME HOLDS TRUE FOR THE
 CALCULATIONS SUBMITTED FOR THE STAIRS BETWEEN THE 15TH
 & 16TH FLOOR. MUST BE A LICENSED ENGINEER FOR THE STATE
 OF FLORIDA AND IF THE ENGINEER OF RECORD DOES NOT SEAL
 EACH SHEET THEN A SEALED COVER SHEET LISTING HOW MANY
 PAGES ARE COVERED UNDER THIS SEAL. 61G15-23.002.
  
 6) COMPLIED.
  
 7A) LS-01 THERE IS A DISCREPANCY IN FLOOR AREA FROM THE
 LIFE SAFETY PLAN & THE ENERGY CALCS PLEASE CORRECT.
  
 7B) LIFE SAFETY PLANS HAVE THE WRONG WIND CRITERIA
 PLEASE CORRECT THE REFERENCE TO ASCE 7-98.
 8)COMPLIED.
  
 9) COMPLIED.
  
 10) SECOND REQUEST, SHEET 1-16C INDICATE TWO TYPE OF
 DOORS THAT WILL BE PENETRATING THE 1 HR RATED WALL DOOR
 TYPED-6 WHICH DOES HAVE 45 MINUTE RATING AND DOOR TYPE
 D-3 WHICH DOES NOT PLEASE CORRECT. TABLE 715.3.
  
 11) SECOND REQUEST, RESPONSE INDICATES THE NOTE IS
 ADDED TO THE GENERAL NOTES NOT NUMBER 58, SHEET I-G.1
 THE GENERAL NOTES ONLY GO UP TO 44.PLEASE TAKE NOTE
 OF : 404.7 INTERIOR FINISH. THE INTERIOR FINISH OF
 WALLS AND CEILINGS OF THE ATRIUM SHALL NOT BE LESS THAN
 CLASS B WITH NO REDUCTION IN CLASS FOR SPRINKLER
 PROTECTION.
  
 12) COMPLIED.
  
 13-15) COMPLIED.
  
 16) 2ND REQUEST, A FLORIDA REGISTERED ENGINEER,
 PLEASE PROVIDE ADDITIONAL INFORMATION ON THE GLASS
 HANDRAILS AND GUARDS SEE 2407.
 2407.1.1 LOADS.
 THE PANELS AND THEIR SUPPORT SYSTEM SHALL BE DESIGNED
 TO WITHSTAND THE LOADS SPECIFIED IN SECTION 1607.7 . A
 SAFETY FACTOR OF FOUR SHALL BE USED.
  
 2407.1.2 SUPPORT.
 EACH HANDRAIL OR GUARD SECTION SHALL BE SUPPORTED BY A
 MINIMUM OF THREE GLASS BALUSTERS OR SHALL BE OTHERWISE
 SUPPORTED TO REMAIN IN PLACE SHOULD ONE BALUSTER PANEL
 FAIL. GLASS BALUSTERS SHALL NOT BE INSTALLED WITHOUT AN
 ATTACHED HANDRAIL OR GUARD.
  
 17)COMPLIED.
  
 18) SECOND REQUEST, THE RESPONSE SHEET INDICATES A NOTE
 59 WAS ADDED TO THE GENERAL COMMENTS? THE GLASS WALL IS
 ALSO CONSIDERED A HAZARDOUS LOCATION 15TH AND 16TH
 FLOORS. SEE 2406.3(7)
 7.GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE
 PANEL, OTHER THAN IN THOSE LOCATIONS DESCRIBED IN
 PRECEDING ITEMS 5 AND 6, WHICH MEETS ALL OF THE
 FOLLOWING CONDITIONS:
 7.1.EXPOSED AREA OF AN INDIVIDUAL PANE GREATER
 THAN 9 SQUARE FEET (0.84 M 2 );
 7.2.EXPOSED BOTTOM EDGE LESS THAN 18 INCHES (457
 MM) ABOVE THE FLOOR;
 7.3.EXPOSED TOP EDGE GREATER THAN 36 INCHES (914
 MM) ABOVE THE FLOOR; AND
 7.4.ONE OR MORE WALKING SURFACE(S) WITHIN 36
 INCHES (914 MM) HORIZONTALLY OF THE PLANE OF THE
 GLAZING.
 EXCEPTION: SAFETY GLAZING FOR ITEM 7 IS NOT REQUIRED
 FOR THE FOLLOWING INSTALLATIONS:
 1.A PROTECTIVE BAR 1? INCHES (38 MM) OR MORE IN
 HEIGHT, CAPABLE OF WITHSTANDING A HORIZONTAL LOAD OF 50
 POUNDS PLF (730 N/M) WITHOUT CONTACTING THE GLASS, IS
 INSTALLED ON THE ACCESSIBLE SIDES OF THE GLAZING 34
 INCHES TO 38 INCHES (864 MM TO 965 MM) ABOVE THE
 FLOOR.
  
 19-23B) COMPLIED.
  
 24) A NEW COMMENT, E2.1 INDICATES WORK BEING COMPLETED
 ON THE 17TH FLOOR AND E2.2 INDICATES THE 16TH FLOOR,
 PLEASE CORRECT THIS DISCREPANCY.
  
 25) A NEW COMMENT,I-15.C ROOMS 1543& 1544 BOTH ARE
 INDICATED AS COMPUTER EQUIPMENT ROOMS SEE ELECTRICAL
 COMMENTS AS TO THE 1 HR FIRE RATING REQUIREMENTS.
  
 26) ENERGY CALCULATIONS PLEASE PROVIDE THE INFORMATION
 FOR THE SKYLIGHTS TO BE INSTALLED ON THE
 ROOF OF THE 16TH FLOOR. ADDITIONAL INFORMATION REQUIRED
 106.1.2*
 27) SHEET I-15.R PLEASE CORRECT THIS SHEET TITLE BLOCK
 IT APPEARS WHITE OUT WAS USED IN THE TITLE BLOCK AND
 THEN HAND DRAWN NUMERALS.
  
 28) SHEETS S-1 AND S-2 INDICATE NEW STAIRS AND FLOOR
 BEAMS COMMUNICATING BETWEEN THE FLOORS, AS PART OF A
 THRESHOLD BUILDING THE FOLLOWING ITEMS WILL NEED TO BE
 ADDRESSED:
  
 28A)105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A "STRUCTURAL
 INSPECTION PLAN"
 PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 28B) THE SHELL BUILDING HAS NOT ACHIEVED A CERTIFICATE
 OF COMPLETION, THE STRUCTURAL PLANS FOR THIS TENANT
 SPACE SHALL BE REVIEWED BY THE ENGINEER OF RECORD FOR
 THE " BASE BUILDING"
 AND BE STAMPED WITH THEIR SHOP DRAWING STAMP THEY ARE
 APPROVING THE PLANS AND WORK TO BE COMPLETED UNDER THIS
 PERMIT BEFORE THEIR CERTIFICATE OF COMPLETION HAS BEEN
 ISSUED.
  
 28C) THE SAME HOLDS TRUE FOR THE ARCHITECTURAL SHEETS,
 THE DESIGNER OF RECORD FOR THE BUILDING SHALL REVIEW
 AND AFFIX THEIR SHOP DRAWING STAMP TO THESE PLANS WITH
 THEIR APPROVAL.
  
 28D) SINCE THERE WILL NEED TO BE A THRESHOLD INSPECTOR
 ON SITE, A THIRD SET OF PLANS, SUBMITTALS AND OR OTHER
 DOCUMENTS WILL NEED TO BE SUBMITTED BEFORE ISSUANCE OF
 THIS PERMIT.
  
 28E) SINCE THE STEEL BEAMS ARE NEW ELEMENTS AND NEED TO
 INDICATE FIRE PROOFING AS TO TABLE 601 FLOOR AND BEAM 3
 HR RATING SEE FOOTNOTE "G" 1 HR REDUCTION FOR FIRE
 SPRINKLED BUILDINGS.
 PLEASE SHOW COMPLIANCE.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-06-06 Cont ID  
Sent By jwitmer Date 2007-06-06 Time 13:47 Rev Time 5.55
Received By jwitmer Date 2007-06-06 Time 13:47 Sent To PC
Notes
2007-06-06 16:46:06BUILDING PLAN REVIEW
 PERMIT: 07030932
 ADD: 525 OKEECHOBEE BLVD PENTHOUSE A & B
 CONT: CENTEX
 TEL: (954)214-9415
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)Y J ARCHITECTURAL DESIGN WILL REQUIRE A CERTIFICATE
 OF AUTHORIZATION,) 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT PRACTICING UNDER
 A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ARCHITECTURAL SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION NUMBER.ADD THE
 NUMBER TO EACH SHEET.
  
 4)STRUCTURAL SHEET S-1 WILL REQUIRE A RAISED
 IMPRESSION TYPE SEAL NOT A STAMPED SEAL. FAC
 61G15-23.001 THE SEAL IS ALSO A CALIFORNIA SEAL THE
 DESIGN PROFESSIONAL MUST BE A LICENSED ENGINEER IN THE
 STATE OF FLORIDA. 471.025
  
 5) THE SAME HOLDS TRUE FOR THECALCULATIONS SUBMITTED
 FOR THE STAIRS BETWEEN THE 15TH & 16TH FLOOR. MUST BE A
 LICENSED ENGINEER FOR THE STATE OF FLORIDA AND
 IF THE ENGINEER OF RECORD DOES NOT SEAL EACH SHEET THEN
 A SEALED COVER SHEET LISTING HOW MANY PAGES ARE COVERED
 UNDER THIS SEAL. 61G15-23.002.
  
 6) LS-01 / LS-02 PLEASE UPDATE APPLICABLE CODE TO THE
 2004FBC W 2006 AMENDMENTS, PLEASE CORRECT.
  
 7) LS-01 BOTTOM RIGHT OF SHEET THERE IS A DISCREPANCY
 IN ONE AREA THE PLAN INDICATES THIS SHEET REPRESENTS
 THE 15TH FLOOR WHILE LESS THAN SIX INCHES AWAY THE
 PLAN
  
 INDICATES WORK ON THE 16TH FLOOR, PLEASE CORRECT.
  
 8)SHEET I-G.1 PLEASE CORRECT THE REFERENCES MADE TO
 EITHER THE LOS ANGLES BUILDING CODE OR THE UBC AND CODE
 REFERENCE NUMBERS.
  
 9) SHEET 1-16C THE 2 AREAS THAT ARE CONSIDERED AS
 ATRIUMS DO NOT HAVE RATED WALLS NOR DOORS, PLEASE
 COMPLY WITH:
 404.5 ENCLOSURE OF ATRIUMS.
 ATRIUM SPACES SHALL BE SEPARATED FROM ADJACENT SPACES
 BY A 1-HOUR FIRE BARRIER WALL.
 EXCEPTIONS:
 1.A GLASS WALL FORMING A SMOKE PARTITION WHERE
 AUTOMATIC SPRINKLERS ARE SPACED 6 FEET (1829 MM) OR
 LESS ALONG BOTH SIDES OF THE SEPARATION WALL, OR ON THE
 ROOM SIDE ONLY IF THERE IS NOT A WALKWAY ON THE ATRIUM
 SIDE, AND BETWEEN 4 INCHES AND 12 INCHES (102 MM AND
 305 MM) AWAY FROM THE GLASS AND SO DESIGNED THAT THE
 ENTIRE SURFACE OF THE GLASS IS WET UPON ACTIVATION OF
 THE SPRINKLER SYSTEM. THE GLASS SHALL BE INSTALLED IN A
 GASKETED FRAME SO THAT THE FRAMING SYSTEM DEFLECTS
 WITHOUT BREAKING (LOADING) THE GLASS BEFORE THE
 SPRINKLER SYSTEM OPERATES.
 2.A GLASS-BLOCK WALL ASSEMBLY IN ACCORDANCE WITH
 SECTION 2110 AND HAVING A ?-HOUR FIRE PROTECTION
 RATING.
 3.THE ADJACENT SPACES OF ANY THREE FLOORS OF THE
 ATRIUM SHALL NOT BE REQUIRED TO BE SEPARATED FROM THE
 ATRIUM WHERE SUCH SPACES ARE INCLUDED IN COMPUTING THE
 ATRIUM VOLUME FOR THE DESIGN OF THE SMOKE CONTROL
 SYSTEM.
  
 10) SHEET 1-16C INDICATE TWO TYPE OF DOORS THAT WILL BE
 PENETRATING THE 1 HR RATED WALL DOOR TYPED-6 WHICH DOES
 HAVE 45 MINUTE RATING AND DOOR TYPE D-3 WHICH DOES NOT
 PLEASE CORRECT. TABLE 715.3.
  
 11)PLEASE TAKE NOTE OF : 404.7 INTERIOR FINISH. THE
 INTERIOR FINISH OF WALLS AND CEILINGS OF THE ATRIUM
 SHALL NOT BE LESS THAN CLASS B WITH NO REDUCTION IN
 CLASS FOR SPRINKLER PROTECTION.
  
 12)SHEET 1-15C DOES INDICATE THE 1 HR RATED
 PARTITIONS AT THE ATRIUM AREAS BUT THERE IS NO DOOR
 SHEDULE IF TAKEN FROM SHEET 1-16.C D-3 IS NOT RATED
 PLEASE CORRECT.
  
 13) PLEASE REVIEW LS-02 THE NORTHEAST CORNER OF THE
 BUILDING INDICATES THE DISTANCE TO AN EXIT AS 204 FT.
 404.8 TRAVEL DISTANCE, THE SOUTHEAST CORNER THIS
 DISTANCE WILL BE GREATER. IN OTHER THAN THE LOWEST
 LEVEL OF THE ATRIUM , WHERE THE REQUIRED MEANS OF
 EGRESS IS THROUGH THE ATRIUM SPACE, THE PORTION OF EXIT
 ACCESS TRAVEL DISTANCE WITHIN THE ATRIUM SPACE SHALL
 NOT EXCEED 200 FEET .
  
 14) 7-06-07 THIS COMMENT HAS BEEN RESOLVED, NO SMOKE
 CONTROL WILL BE REQUIRED, SINCE NOT PAT OF AN MEANS OF
 EGRESS, SEE 404EXCEPTIONS, 707.2 EXCEPTION # 7.
  
  
  
 15) THERE IS A DISCREPANCY IN THE PLANS THE
 ARCHITECTURAL , STRUCTURAL, ELECTRICAL AND FIRE ALARM
 ALL INDICATE WORK ON THE 15THAND 16TH FLOORS, WHERE
 AS THE
 FIRE SPRINKLER AND MECHANICAL PLANS INDICATE THE 17TH
 AND 18TH FLOORS. PLEASE CORRECT.
  
 16)PLEASE PROVIDE ADDTIONAL INFORMATION ON THE GLASS
 HANDRAILS AND GUARDS SEE 2407.
 2407.1.1 LOADS.
 THE PANELS AND THEIR SUPPORT SYSTEM SHALL BE DESIGNED
 TO WITHSTAND THE LOADS SPECIFIED IN SECTION 1607.7 . A
 SAFETY FACTOR OF FOUR SHALL BE USED.
  
 2407.1.2 SUPPORT.
 EACH HANDRAIL OR GUARD SECTION SHALL BE SUPPORTED BY A
 MINIMUM OF THREE GLASS BALUSTERS OR SHALL BE OTHERWISE
 SUPPORTED TO REMAIN IN PLACE SHOULD ONE BALUSTER PANEL
 FAIL. GLASS BALUSTERS SHALL NOT BE INSTALLED WITHOUT AN
 ATTACHED HANDRAIL OR GUARD.
  
 17)PLEASE PROVIDE AT WHAT SLOPE IN DEGREES THE GLASS
 WALL IS FROMVERTICAL, IF THE SLOPE IS MORE THAN 15
 DEGREES SEE 2405.2 .
  
 18) THE GLASS WALL IS ALSO CONSIDERED A HAZARDOUS
 LOCATION 15TH AND 16TH FLOORS. SEE 2406.3(7)
 7.GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE
 PANEL, OTHER THAN IN THOSE LOCATIONS DESCRIBED IN
 PRECEDING ITEMS 5 AND 6, WHICH MEETS ALL OF THE
 FOLLOWING CONDITIONS:
 7.1.EXPOSED AREA OF AN INDIVIDUAL PANE GREATER
 THAN 9 SQUARE FEET (0.84 M 2 );
 7.2.EXPOSED BOTTOM EDGE LESS THAN 18 INCHES (457
 MM) ABOVE THE FLOOR;
 7.3.EXPOSED TOP EDGE GREATER THAN 36 INCHES (914
 MM) ABOVE THE FLOOR; AND
 7.4.ONE OR MORE WALKING SURFACE(S) WITHIN 36
 INCHES (914 MM) HORIZONTALLY OF THE PLANE OF THE
 GLAZING.
 EXCEPTION: SAFETY GLAZING FOR ITEM 7 IS NOT REQUIRED
 FOR THE FOLLOWING INSTALLATIONS:
 1.A PROTECTIVE BAR 1? INCHES (38 MM) OR MORE IN
 HEIGHT, CAPABLE OF WITHSTANDING A HORIZONTAL LOAD OF 50
 POUNDS PLF (730 N/M) WITHOUT CONTACTING THE GLASS, IS
 INSTALLED ON THE ACCESSIBLE SIDES OF THE GLAZING 34
 INCHES TO 38 INCHES (864 MM TO 965 MM) ABOVE THE
 FLOOR.
  
  
 19) SHEET I-E.2 STAIRWELL SECTION THE HANDRAIL AT THE
 TOP LANDING IS MISSING : 11-4.9.4(2) IF HANDRAILS ARE
 NOT CONTINUOUS, THEY SHALL EXTEND AT LEAST 12 INCHES
 (305 MM) BEYOND THE TOP RISER AND AT LEAST 12 INCHES
 (305 MM) PLUS THE WIDTH OF ONE TREAD BEYOND THE BOTTOM
 RISER. AT THE TOP, THE EXTENSION SHALL BE PARALLEL WITH
 THE FLOOR OR GROUND SURFACE. AT THE BOTTOM, THE
 HANDRAIL SHALL CONTINUE TO SLOPE FOR A DISTANCE OF THE
 WIDTH OF ONE TREAD FROM THE BOTTOM RISER; THE REMAINDER
 OF THE EXTENSION SHALL BE HORIZONTAL [SEE FIGURE 19 (C)
 AND FIGURE 19 (D)]. HANDRAIL EXTENSIONS SHALL COMPLY
 WITH SECTION 11-4.4 .
  
 20) SHEET I-E.2 HANDRAILS: 11-4.9.4(5) TOP OF HANDRAIL
 GRIPPING SURFACE SHALL BE MOUNTED BETWEEN 34 INCHES AND
 38 INCHES (865 MM AND 965 MM) ABOVE STAIR NOSING.
  
 21)PLANS DO NOT PROVIDE THE DISTANCE FROM THE
 VERTICAL GLASS GUARD RAILING AND THE HANDRAIL?
 11-4.9.4(3) THE CLEAR SPACE BETWEEN HANDRAILS AND WALL
 SHALL BE 1?".
  
 22) THE SAME STAIR ELEMENTS WILL NEED TO BE ADDRESSED
 ON THE NORTHWEST STAIR AND HAND RAILS AS LISTED IN
 ITEMS 19-21, THE CUT SECTIONS OF THIS STAIRARE NOT
 CLEAR AND THESE ITEMS CAN NOT BE VISSIBLY ADDRESSED.
  
 23)ARE THE SKYLIGHTS PART OF THIS PERMIT OR ARE THEY
 PART OF THE SHELL BUILDING? IF PART OF THIS PERMIT THE
 FOLLOWING WILL BE REQUIRED: FL BLD CODE 1609.1.4:
 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS,MISSING REPORTS
 ARE AS
 FOLLOWS: A ) SKYLIGHTS
  
 23A)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE
 STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 23B)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 12 Status P Date 2008-09-30 Cont ID  
Sent By dpalmer Date 2008-09-30 Time 15:00 Rev Time 0.00
Received By dpalmer Date 2008-09-30 Time 15:00 Sent To  
Notes
2008-09-30 15:00:55*** REDLINED PLANS**
  
 NEED REVISED LIGHTING PERFORMANCE CALCULATIONS BEFORE
 FINAL.
 NEED REVISED 15TH FLOOR LIGHTING CONTACTOR SCHEDULE.
 THE 16TH FLOOR WAS SUBMITTED HOWEVER NOT THE 15TH
 FLOOR.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2008-08-29 Cont ID  
Sent By dpalmer Date 2008-08-29 Time 13:36 Rev Time 0.00
Received By dpalmer Date 2008-08-29 Time 13:36 Sent To  
Notes
2008-08-29 13:37:14NOTES FROM PREVIOUS REVIEWS, CIRCUITS AMY NEED FINAL
 REVISIONS.
 ONLY SHEETS 3.2 AND 6.2 WERE SUBMITTED.

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2008-07-31 Cont ID  
Sent By dpalmer Date 2008-07-31 Time 11:56 Rev Time 0.00
Received By dpalmer Date 2008-07-31 Time 11:56 Sent To  
Notes
2008-07-31 11:57:16** DENIED**
  
  
 REV #13
  
 1) NOTE: PLEASE SEE COMMENTS FROM PREVIOUS REVIEW WHICH
 ARE STILL IN NEED OF ADDRESSING.
  
 2) NOTE: PLEASE SUBMIT REVISED PLANS WITH REVISED PANEL
 SCHEDULES AS THE NEW CIRCUITS AND REVISED CIRCUITS ON
 PLANS DO NOT COORDINATE WITH THE RECORD SET OF PLANS ON
 FILE.
 408.4, ETC
 FBC 106.5, 106.1.1
  
 3) NOTE: PLEASE REVISE SYMBOL LEGEND ON PLANS WITH NEW
 ITEMS NOW ADDED.
 FBC 106.1.1,
  
  
 ** IF THERE ARE ANY QUESTIONS OR IF THE COMMENTS ARE
 NOT CLEAR IN ANY MANOR PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2008-07-18 Cont ID  
Sent By dpalmer Date 2008-07-18 Time 11:23 Rev Time 0.00
Received By dpalmer Date 2008-07-18 Time 11:23 Sent To  
Notes
2008-07-18 11:24:00** DENIED **
  
 ** REVISIONS SUBMITTED.
 SOME SHEETS ARE OK HOWEVER SHEET E2.2 HAS NOTES BELOW.
 RESPONSE LETTER FROM DESIGNER MENTIONS A SHEET 3.2
 HOWEVER NO SHEET 3.2 WAS SUBMITTED.
 SHEETS 4.1,4.2 AND 6.2 OK
  
 1) NOTE: PLEASE SEE NEW NOTE #12 ON 2.2 WHICH STATES
 LIGHTING CONTROLS/SYSTEM BY OTHERS HOWEVER TO DATE NO
 PLANS OR PERMIT APPLICATION HAS BEEN SUBMITTED. IF THE
 LIGHTING CONTROLS ARE GOING TO BE BY OTHER THEN PLANS
 WILL NEED TO BE SUBMITTED ALONG WITH PERMIT
 APPLICATION.
 13-415.1.ABC.1.1,.1.2,.1.3.
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2008-07-15 Cont ID  
Sent By dpalmer Date 2008-07-15 Time 15:16 Rev Time 0.00
Received By dpalmer Date 2008-07-15 Time 15:13 Sent To PC
Notes
2008-07-15 15:17:07REV 9-10, 6.1 AND 6.2

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-05-30 Cont ID  
Sent By dpalmer Date 2008-05-30 Time 16:57 Rev Time 0.00
Received By dpalmer Date 2008-05-30 Time 16:57 Sent To PC
Notes
2008-05-30 16:58:15REV 3.1,3.2,,5.2,6.1,6.2

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-05-01 Cont ID  
Sent By dpalmer Date 2008-05-01 Time 15:39 Rev Time 0.00
Received By dpalmer Date 2008-05-01 Time 15:39 Sent To  
Notes
2008-05-01 15:39:37REV FOR E-5.2 #8ONLY.
 FEEDERS ON MAIN SERVICE RISER ON 16TH FLOOR ONLY.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-03-18 Cont ID  
Sent By dpalmer Date 2008-03-18 Time 08:44 Rev Time 0.00
Received By dpalmer Date 2008-03-18 Time 08:44 Sent To  
Notes
2008-03-18 08:44:44REV 2.1,2.2,3.1,3.2,4.1,4.2, 6.1 AND 6.2

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-02-09 Cont ID  
Sent By dpalmer Date 2008-02-09 Time 08:10 Rev Time 0.00
Received By dpalmer Date 2008-02-11 Time 20:21 Sent To  
Notes
2008-02-11 08:10:44PASSED, STILL NEEDS ADDRESSING REVIEW FOR ADDITION OF
 SUITE/UNIT NUMBERS WHICH ARE STILL NOT IN SYSTEM. AN
 E-MAIL WAS SENT TO THE ADDRESSING REVIEWER 2/8 AT ABOUT
 8:30PM.
 PLANS DO NEED FIRE AND MECHANICAL REVIEWS AS THERE ARE
 NEW SHEETS IN ALL THREE SETS FOR BOTH TRADES SINCE LAST
 REVIEW.
2008-02-08 20:21:032008-02-08 20:21:03
  
 IN ELECTRIC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-12-11 Cont ID  
Sent By dpalmer Date 2007-12-11 Time 12:58 Rev Time 0.00
Received By dpalmer Date 2007-12-10 Time 14:14 Sent To  
Notes
2007-12-11 12:58:222007-12-11 12:58:22
  
 **** DENIED 3RD REVIEW ****
  
 ** PLEASE SEE SOME ITEMS FROM THE PREVIOUS TWO REVIEWS
 ARE STILL IN OF ADDRESSING.
 ** PLEASE SEE THERE NOW NEW COMMENTS WHICH WERE NOT ON
 PREVIOUS REVIEW AS THERE ARE ITEMS ON PLANS AND RISER
 WHICH WERE NEW AND REVISED.
  
  
 1) NOTE:PLEASE SEE COMPLIANCE WITH THE FBC CHAPTER 13
 HAS NOT YET BEEN ACHIEVED.
 PLEASE SEE THERE ARE SEVERAL ITEMS FROM THE PREVIOUS
 REVIEW NOTES WHICH ARE STILL IN NEED OF ADDRESSING.
 PLEASE SEE THE PLANS ARE STILL INDICATING A SUBSTANTIAL
 AMOUNT OF LIGHTING FIXTURES AND WATTAGES ON THE NEW
 LIGHTING CALCULATIONS WHICH DO NOT CORRELATE WITH PLANS
 OR WITH THE MINIMUM REQUIREMENTS AS SET-FORTH IN THE
 FLORIDA BUILDING CODE.
 PLEASE SEE SOME EXAMPLES WILL BE GIVEN HOWEVER THIS IS
 NO WAY ALL LOCATIONS IN WHICH INCONSISTENCIES EXISTS.
 PLEASE SEE 13-415.2.ABC.1.2 WHICH WAS SPECIFICALLY
 NOTED ON PREVIOUS REVIEWS FOR TRACK LIGHTING. PLEASE
 SEE THE MINIMUM VA WHICH MUST BE USED FOR LINE VOLTAGE
 LIGHTING SHALL BE BASED ON THE WATTAGE OF EACH FIXTURE
 OR 30VA PER FT OF LINEAR FT OF TRACK SHOWN ON PLANS,
 WHICH EVER IS HIGHER.
 PLEASE SEE THE PLANS ON ID DRAWINGS AS THE LIGHTING VA
 SHOWN ON TABLES DOES NOT COORDINATE EVEN FOR THE NUMBER
 OF FIXTURES BASED ON THE WATTAGE ON THE FIXTURE
 LEGEND.
  
 PLEASE SEE 1544, 1543, 1546 FOR EXAMPLE: THIS SHOWS A
 TOTAL OF 14 FIXTURES, EACH AT 50WATTS EACH, WHICH IS
 700VA, YET THE TABLE SHOWS 600VA. PLEASE KNOW AS NOTED
 ABOVE THE VA MUST BE BASED ON THE FIXTURES OR THE
 LINEAR FT OF TRACK AT 30VA PER FT WHICH EVER IS HIGHER.
 BASED ON THE LINEAR FEET OF TRACK AS SHOWN ON PLANS THE
 VA PER FT FOR MINIMUM REQUIREMENTS IS MUCH HIGHER THAN
 THE NUMBER OF FIXTURES AND WATTAGES OF EACH.
  
 PLEASE SEE FOR EXAMPLE: THE AREA AS NOTED AS 1636, SAME
 AS ABOVE FOR TRACK AND OTHER AREAS ON PLANS HOWEVER NOT
 ALL AREAS ARE BEING NOTED.
  
 PLEASE SEE FOR EXAMPLE: PLEASE KNOW ANY LOW VOLTAGE
 SYSTEMS, SUCH AS THE *Q* FIXTURES ARE REQUIRED TO USE
 THE VA OUTPUT OF ANY TRANSFORMERS AS THESE INDICATE A
 COLD CATHODE FIXTURES DESIGNATION. THE CALCULATION
 SHEETS NOTE THESE AS 28VA PER FIXTURE? PLEASE SEE THE
 FIXTURE LEGEND FOR THE *Q* FIXTURE IS BLANK AT THIS
 TIME THEREFORE VERIFICATION OF COMPLIANCE MAY NOT BE
 DONE.
  
 PLEASE SEE FOR EXAMPLE: THE ROOM DESIGNATIONS ON
 CALCULATION SHEETS FOR 16TH FLOOR ARE NOT COMPLETE,
 SOME ROOM ARE NOT LABELED ON CALCULATIONS. (CAN NOT
 VERIFY AT THIS TIME).
  
 PLEASE SEE FOR EXAMPLE: PLEASE SEE ROOM/AREA 1578 AS NO
 LIGHTING FIXTURES ARE SHOWN ON PLANS ON ID PLANS OR ON
 E-SHEETS. THIS WAS GONE OVER IN MEETING WITH THE
 ARCHITECT AND ELECTRICAL DESIGNER AND FIXTURES WERE
 GOING TO BE ADDED?
  
 PLEASE SEE FOR EXAMPLE: AREA 1564 AS 27 TYPE *X*
 FIXTURES ARE IN CALCULATIONS AND 29 OF THESE SAME TYPES
 FOR THIS SAME AREA ARE ON PLANS THEREFORE SHOWING A
 SHORTAGE IN TOTAL WATTAGES.
  
 PLEASE SEE FOR EXAMPLE: AREA 1660 AS TYPE *F* FIXTURES
 ARE SHOWING 16 ON ID SHEETS AND YET THE ELECTRICAL
 PLANS SEEM TO INDICATE 17-J-BOXES FOR FIXTURES?
  
 PLEASE SEE FOR EXAMPLE: PLEASE SEE AREA 1575 AS THE
 PLANS AND LAYOUTS ON ID PLANS AND ELECTRICAL PLANS ARE
 NOT THE SAME.
 PLEASE COORDINATE.
  
 PLEASE SEE FOR EXAMPLE: AREA 1564 AS THE ID PLANS
 INDICATE A TYPE *X* FIXTURE ON CEILING IN BETWEEN SOME
 OFFICE DOORS, YET THE ELECTRICAL PLANS DO NOT SHOW
 THESE. THIS WILL ALSO BE NOTED IN THE NEXT COMMENT FOR
 CONTROLS OF LIGHTING.
  
 PLEASE PROVIDE A TOTAL OF DESIGN WATTAGE AND
 ALLOWANCES. THE 1.72 AND 1.55 AS SHOWN ON ID PLANS
 EXCEED THAT OF ALLOWANCES. PLEASE SHOW HOW THESE MAY BE
 OVER AND HOW THIS WAS FIGURED. PLEASE ALSO KEEP IN MIND
 AS THE TOTALS FOR FIXTURES AND FIXTURES SUCH AS TRACK
 LIGHTING WILL ADJUST SIGNIFICANTLY THIS WILL AFFECT THE
 OVER ALL CALCULATIONS.
 THE MAXIMUM DESIGN ALLOWANCES FOR BASE BUILDING MUST BE
 MET. IF THE BASE BUILDING DESIGN TEAM/ENGINEERING FIRM
 OF RECORD HAS DESIGNED A MAXIMUM OF 1.1 PER SQ FT FOR
 OFFICE AREA THEN THIS MUST BE FOLLOWED. ALLOWANCES ON
 ORIGINAL METHOD *B* ASSUMPTIONS MUST MEET FBC CHAPTER
 13 AND -13-415.1.B ETC
 THE LIGHTING POWER DENSITIES CALCULATIONS AND DESIGNS
 IS THE RESPONSIBILITY OF THE ELECTRICAL DESIGNER OF
 RECORD PER FAC 61G15-33.004. PLEASE ADJUST PLANS AND
 CALCULATIONS ACCORDINGLY. FS 471.003
  
 ** PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2. PLEASE
 SEE SOME OF THE ITEMS AS NOTED ABOVE WERE LOCATED ON
 PLANS, HOWEVER NOT ALL ARE NOTED. THERE ARE OTHER
 AREAS.
  
  
  
 2) NOTE: PLEASE SEE CONTROLS FOR LIGHTING STILL NEED
 SOME ADJUSTMENTS TO MEET 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
  
 PLEASE SEE FOR EXAMPLE: AREA 1564, 1540, 1558 ETC FOR
 TYPE *X* FIXTURES WHICH ARE SHOWN ON ID PLANS SHEET
 I-15.R, YET ELECTRICAL PLANS FOR LIGHTING EITHER E2.1
 OR POWER E3.1 INDICATES ANY OF THESE FIXTURES.
  
 PLEASE SEE FOR EXAMPLE: PLEASE SEE AREAS 1638 AND 1634
 AS TYPE *Q* FIXTURES CONTAIN A NOTE #8 FOR A J-BOX TO
 BE PROVIDED FOR ELECTRICAL CONNECTION YET NO CONTROLS
 FOR LIGHTING COULD BE FOUND? NO ADDITIONAL NOTES FOR
 LIGHTING CONTROL PANEL, OCCUPANCY SENSORS, OVER-RIDE
 DEVICES ETC WERE FOUND ON PLANS.
  
 PLEASE SEE FOR EXAMPLE: AREA 1564 AS HALLWAY LIGHTING
 FOR *J* FIXTURES DO NOT CONTAIN THE NOTE #2 FOR CONTROL
 AS NOTED ON OTHER AREAS FOR THIS SAME TYPE OF
 FIXTURES.
  
 ** PLEASE SEE THAT SOME OF THE ABOVE ARE NOTED FOR
 EXAMPLE, HOWEVER NOT ALL ARE NOTED.
  
 3) NOTE: PLEASE SEE THE POWER PLANS ARE MISSING
 ELECTRICAL PANELS AND DISCONNECTS NOT SHOWN. PLEASE SEE
 FOR EXAMPLE: SHEET E3.1 WHICH SHOWS PANELS BEING NOTED,
 HOWEVER THESE ARE NOT SHOWN ON LAYOUT. PLEASE SEE FOR
 EXAMPLE: THE ELECTRICAL ROOM 1577 WHICH INDICATES THE
 TRANSFORMER BEING INSTALLED IN THIS ROOM YET DISCONNECT
 WHICH IS SHOWN ON RISER IS SHOWN ON PLANS?
 PLEASE SEE THIS IS THE SAME FOR MAIN ELECTRICAL ROOM ON
 THE 16TH FLOOR.
  
 4) NOTE: PLEASE COORDINATE PLANS WITH DOORS AND ROOM
 LOCATIONS AS SHOWN ON PLANS.
 PLEASE SEE ELECTRICAL PLANS FOR PANELS ON FLOOR 16 AS
 ONE ELECTRICAL PANEL DOES NOT SEEM IT IS LOCATED IN
 ROOM OR ON WALL IT SEEMS TO BE PARTIALLY IN WALL?
 PLEASE SEE FOR EXAMPLE: THE AREA FOR ACCESS TO THE MAIN
 ELECTRICAL ROOM IN 1542 ON SHEET E3.1 SHOWS WHAT
 APPEARS TO BE COUNTER SPACES BEING INSTALLED IN FRONT
 OF DOOR. THIS MUST BE A MISPRINT OF SOME TYPE. I-15C
 DOES NOT SHOW THIS COUNTER SPACE BEING EXTENDED AROUND
 THE CORNER.
 110.26
 PLEASE SEE THE AREA 1575 WHERE THE CLOSET/DOOR/ACCESS
 IS NOT THE SAME ON ID PLANS AND ELECTRICAL.
 PLEASE COORDINATE PLANS AND ADJUST.
 FBC 106.1.2, 106.3.5.1.2
  
 5) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS
 FOR THE IT ROOM EQUIPMENT WHICH CORRELATE WITH THE
 PLANS AND RISER DIAGRAM.
 PLEASE SEE FOR EXAMPLE: THE SHEET LABELED DRAWING
 ISX-40K40R2G1XF-SD SHOWS A TRANSFORMER AND EQUIPMENT
 WHICH IS NOT SHOWN ON OR A PART OF THE ELECTRICAL
 RISER.
 PLEASE COORDINATE ALL EQUIPMENT.
 110.3, 90.7
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE PREVIOUS NOTE #11 WITH RESPECT TO
 TAPPED CONDUCTORS ON THE SECONDARY SIDE OF THE
 TRANSFORMER(S).
 PLEASE SEE 240.21, 240.4, 310.16 AS THE 500MCM AS SHOWN
 ARE ONLY RATED FOR 380AMPS PER 110.14 AND 310.16.
 PLEASE KNOW THE CONDUCTORS MUST TERMINATE IN OVER
 CURRENT PROTECTION WHICH LIMITS THE LOAD ON THE
 CONDUCTORS.THIS MAY NOT GO TO THE NEXT STANDARD SIZE
 AS OVER CURRENT PROTECTION DOES NOT CORRELATE WITH
 240.6
 PLEASE ADJUST.
  
 7) NOTE: PLEASE SEE PREVIOUS NOTE #13 AND PLEASE
 CLARIFY THE LOADING OF THE CIRCUITS AS NOTED PER 645.A
 ** PREVIOUS NOTE **
 THE PLANS INDICATE A PANEL ER, THE PANEL SCHEDULE
 SHEETS INDICATE A PANEL ER HOWEVER THIS IS NOT INCLUDED
 ON THE RISER DIAGRAM.
 PLEASE VERIFY 645.5A AND INDICATE WHERE THE 125% HAS
 BEEN FIGURED.
  
 8) NOTE: PLEASE SEE PREVIOUS NOTE #16 AS THE NOTE
 MENTIONED IT WOULD REMAIN AS NEW ELECTRICAL EQUIPMENT
 FOR SERVICE WOULD BE ADDED TO PLANS AND RISER AND TO
 PLEASE BE SURE THE AIC RATINGS WERE INCLUDED FOR ALL.
 PLEASE SEE NOT INFORMATION FOR NEW MAINS ON THE
 SECONDARY SIDE OF THE TRANSFORMER WAS INCLUDED. THIS IS
 ALSO FOR AIC RATINGS.
 PLEASE ADJUST AND COMPLETE.
 110.9,
 FBC 106.1.2
 ** PREVIOUS REVIEW NOTE **
 16) NOTE: PLEASE INDICATE THE AIC RATINGS FOR ALL NEW
 ELECTRICAL SERVICE EQUIPMENT. THIS NOTE IS TO REMAIN AS
 THERE ARE ITEMS WHICH WILL BE CHANGING, NOT INCLUDED AT
 THIS TIME WHICH MAY ALSO REQUIRE THE RATINGS TO BE
 INDICATED.
 110.9, FBC 106.1.2
  
 9) NOTE: PLEASE BE SURE ALL NEW REVISED SHEETS CONTAIN
 STAMPS FROM THE BASE BUILDING DESIGN TEAM WHOM IS STILL
 RESPONSIBLE FOR THIS BUILDING UNTIL SUCH TIME THE
 CERTIFICATE OF OCCUPANCY (CO) IS ISSUED.
 10) NOTE: PLEASE KNOW ONE COPY OF ID PLANS FOR LIGHTING
 AND ELECTRICAL HAS BEEN RETAINED BY THIS OFFICE. PLEASE
 SEE FS 553.80(2)(B).
 THE FEE WAS ASSESSED DUE TO PLUMBING REVIEW REPEAT
 COMMENTS ALREADY ON PROJECT. THE FEE IS NOT ASSESSED
 PER TRADE.
 THE FEE OF $38,175.51 IS DUE BEFORE RE-SUBMITTAL OF
 PLANS. THIS IS ONLY BEING NOTED FOR INFORMATION. **
 PLEASE BE SURE TO COORDINATE ALL PLANS WITH RESPECT TO
 LIGHTING CALCULATIONS
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-12-10 17:12:012007-12-10 17:12:01
 REVIEW COMMENCED AND NOTES TO FOLLOW.
2007-12-03 13:01:3012/3/07 13:01:30
 PROJECT ON HOLD, RESUBMITTAL FEES WERE NOT PAID. CALLED
 AND SPOKE TO TERESAFROM BALFOUR BEATTY. ALSO LEFT
 MESSAGE ON JAMES TURNER'S VOICEMAIL. DV PALMER

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-09-11 Cont ID  
Sent By dpalmer Date 2007-09-11 Time 07:51 Rev Time 0.00
Received By dpalmer Date 2007-09-07 Time 20:13 Sent To  
Notes
2007-09-11 19:04:50 
2007-09-11 07:51:062007-09-11 07:51:06
  
 *** DENIED 2ND REVIEW ***
  
  
 ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM THE
 PREVIOUS REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
 THERE ARE ALSO SEVERAL NEW COMMENTS BASED ON CHANGES TO
 PLANS AND NEW INFORMATION NOW SHOWN/SUBMITTED WHICH WAS
 NOT ON PREVIOUS PLANS.
  
 ** PLEASE KNOW THAT SOME OF THE PRELIMINARY COMMENTS
 BELOW DO NOT APPLY TO KAMM CONSULTING ENGINEERS.
  
 1) NOTE:AS REQUESTED ON PREVIOUS REVIEW PLEASE BE
 SURE ALL ADOPTED RELEVANT CODES ARE STATED ON PLANS.
 PLEASE SEE SHEETS I-16 LS AND I-15 LS WHICH INDICATE A
 2004 NATIONAL ELECTRICAL CODE AND A LIFE SAFETY CODE
 WHICH IS SHOWN AS 2004 ALSO.
 PLEASE ADJUST.
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE THE FOLLOWING ADOPTED CODES SHOULD BE STATED
 ON PLANS AS THE STATE ADOPTED NEW CODES AS OF DECEMBER
 8TH, 2006.
 PLEASE SEE THE WRONG NEC WAS STATED.
 2004 FBC W/2006 REVISIONS,
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72.
 SOME OF THESE ARE STATED ON THE FRONT ARCHITECTURAL
 SHEETS AND SOME ARE NOT. PLEASE ALSO INCLUDE THE STATED
 CODE ON THE ELECTRICAL PLANS.
 ** PLEASE KNOW THAT ANY OTHER CODES WHICH MAY BE STATED
 FROM OTHER TRADES SHOULD BE NOTED BY OTHER TRADES.
  
 2) NOTE:PLEASE SEE MISSING LICENSE INFORMATION FOR
 THE YJ DESIGN, PER FLORIDA STATUTES 481.221/471.023
 PLEASE SEE FAC WHICH REQUIRES ALL INFORMATION ON TITLE
 BLOCKS FOR SAID FIRM PER 61G1-16.004.
 THIS WAS THE SAME AS PREVIOUS REVIEW. THE RESPONSE
 LETTER MENTIONS THIS WAS DONE AND DOES LIST A LICENSE
 NUMBER OF SOME TYPE HOWEVER THE NUMBER AS LISTED IS NOT
 LISTED WITH THE STATE OF FLORIDA DEPARTMENT OF BUSINESS
 AND PROFESSIONAL REGULATION.
 *THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE
 REVIEWER(S).
  
 3) NOTE: PLEASE SEE *S* SHEETS WHICH CONTAIN A *RUBBER
 STAMP* BY THE ENGINEER WHICH IS REQUIRED TO BE A RAISED
 IMPRESSION TYPE SEAL IN THE STATE OF FLORIDA PER
 FAC61G15-23.001.
 PLEASE SEE TWO SETS DO NOT CONTAIN ANY SIGNATURE OR
 SEAL OF ANY KIND AND THE THIRD SET STILL INDICATES A
 *RUBBER STAMP* FOR THE ENGINEER.
 PLEASE ALSO SEE THE SEAL WHICH IS FROM THE STATE OF
 CALIFORNIA. THIS MUST BE LICENSED IN THE STATE OF
 FLORIDA.
 PLEASE ALSO SEE MISSING INFORMATION REQUIRED IN TITLE
 BLOCKS FOR FIRM LICENSE NUMBER ALSO KNOW AS THE
 CERTIFICATE OF AUTHORIZATION NUMBER, THE PRINTED NAME
 AND LICENSE NUMBER OF DESIGNER OF RECORD.
 ** THIS COMMENT AND INFORMATION WAS FORWARDED TO THE
 BUILDING REVIEWER.
  
 4) NOTE: PLEASE SEE COMPLIANCE WITH THE FBC CHAPTER 13
 HAS NOT YET BEEN ACHIEVED.
 PLEASE SEE THERE ARE SEVERAL ITEMS FROM THE PREVIOUS
 REVIEW NOTES WHICH ARE STILL IN NEED OF ADDRESSING.
 PLEASE SEE THE PLANS ARE STILL INDICATING A SUBSTANTIAL
 AMOUNT OF *STANDARD* LIGHTING SWITCHES WHERE CONTROLS
 OF SOME TYPE ARE NEEDED.
 13-415.1.ABC.1.1. (SEE AREAS ON PLANS WHICH CONTAIN
 REDLINED LOCATIONS)
 PLEASE SEE THERE ARE NUMEROUS LIGHTING CONTROLS MISSING
 WHICH REQUIRES THE OCCUPANT TO VISUALLY SEE THE
 LIGHTING IN WHICH IS BEING OVER
 RIDDEN.13-415.1.ABC.1.1, .1.2.
 PLEASE SEE THERE ARE A SUBSTANTIAL AMOUNT OF LIGHTING
 FIXTURES WITH OUT ANY LIGHTING CONTROLS AS REQUIRED PER
 13-415.1.ABC.1.1, .1.2 AND .1.3. ::
 FOR EXAMPLE PLEASE SEE ALL LIGHTING WHICH IS BEING
 SHOWN ON POWER PLANS WHICH IS NOT LOCATED ON LIGHTING
 PLANS AND CONTAINS NOT CONTROLS AS REQUIRED. SEE ONE
 FIXTURE ALONE WOULD BE FIXTURE TYPE *F*. PLEASE SEE
 THERE ARE SEVERAL FIXTURES WITH THIS SAME SCENARIO.
 THERE IS NO INFORMATION SUBMITTED FOR ROOMS SUCH AS
 ROOMS 1604, 1634 ETC THESE ROOMS REQUIRE INFORMATION
 FOR LIGHTING CONTROLS PER THE SAME SECTIONS AS NOTED.
 THIS IS REQUIRED AT THIS TIME.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED DO NOT
 CORRELATE WITH THE LIGHTING OR POWER PLANS FOR THE
 NUMBER OF FIXTURES, THE TYPES OF LIGHTING FIXTURES, AND
 THE WATTAGE OF LIGHTING FIXTURES. ONE EXAMPLE IS THE
 FACT THE ENERGY CALCULATIONS INDICATE ONLY TWO TYPES OF
 LIGHT FIXTURES YET THE FIXTURE LEGEND INDICATES MORE
 THAN TWENTY DIFFERENT KIND OF FIXTURES. (PLEASE SEE
 COMMENTS WITH RESPECT TO LIGHTING FIXTURES ON PLANS
 WHICH ARE NOT ON LEGEND).
 PLEASE SEE THE TOTAL AMOUNT OF LIGHTING FIXTURES ON
 PLANS IS SUBSTANTIALLY HIGHER THAN THE 235 TOTAL SHOWN
 ON ENERGY CALCULATIONS. IN FACT THERE ARE HUNDREDS OF
 FIXTURES NOT INCLUDED ON THE INPUT DATA REPORT WHICH
 ARE INDEED ON PLANS AND ARE REQUIRED ON THE IDR> PLEASE
 SEE THE ENERGY CALCULATIONS ARE STILL ONLY INDICATING
 ONLY SQ FT FOR ONE FLOOR AND THE SQ FT WHICH IS SHOWN
 ON PLANS IS NOT THE SAME AS ON ENERGY CALCULATIONS.
 PLEASE SEE THE LIGHTING CONTACTORS ON PLANS CONTAIN A
 REFERENCE NUMBER, THIS REFERENCE NUMBER IS E2.1 WHICH
 IS FOR 15TH FLOOR LIGHTING. THIS IS NOT POSSIBLE FOR
 16TH FLOOR.
 PLEASE SEE THERE ARE PLACES WHICH OVER RIDES FOR COMMON
 AREA ARE NEEDED. (EXAMPLE, EXIT FROM EXECUTIVE
 VESTIBULE) **PLEASE KNOW AS THERE ARE COMMENTS BELOW
 WITH RESPECT TO THIS ENTRANCE AND LOCATION, PLEASE KNOW
 THAT POSSIBLE LOCATION MAY CHANGE).
 PLEASE SEE TRACK LIGHTING PER 13-415.2.ABC .1.2. PLEASE
 CLARIFY LIGHTING CONTROL PANELS CONTROLLING LIGHTING
 OUTSIDE SPACE WHICH IS NOT PERMITTED PER
 13-415.1.ABC.1.1. (BUILDING SIGN?)
 PLEASE SEE THERE ARE NUMEROUS LIGHTING FIXTURES WHICH
 CONTAIN NO CONTROLS WHICH ARE REQUIRED PER
 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 ** ONCE AGAIN AS THERE ARE NUMEROUS ITEMS STILL MISSING
 WHICH ARE REQUIRED A FULL AND COMPLETE REVIEW OF
 SYSTEMS CAN NOT BE DONE AT THIS TIME.
 ******************************************************
 * *
 ** PREVIOUS NOTE FROM FIRST REVIEW **
 PLEASE SEE FBC 2004 W/ 2006 REVISIONS FOR CHAPTER 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.,
 13-415.1.AB.1, 13-415.2, 13-415.2.ABC.1.2
 PLEASE SEE SEVERAL AREAS WHICH ARE MISSING THE REQUIRED
 OVER RIDE DEVICES, OR OTHER TYPE DEVICES REQUIRED FOR
 CONTROL OF LIGHTING.
 PLEASE SEE SEVERAL LOCATIONS WHICH LIGHTING CONTROL IS
 REQUIRED FOR AREAS IN WHICH THE OCCUPANT CAN SEE THE
 LIGHTING WHICH IS BEING CONTROLLED.
 PLEASE SEE THE NORTH-SIDE ENTRANCE INTO THE 15TH FLOOR
 WHICH SHOWS NO CONTROL.
 PLEASE SEE THE SOUTH-SIDE ENTRANCE ON THE 16TH FLOOR
 WHICH SHOWS NO CONTROL.
 PLEASE SEE SEVERAL ROOMS WHICH CONTAIN ONLY A STANDARD
 WALL SWITCH.
 PLEASE SEE THE DETAIL FOR EACH CONTROL PANEL DOES NOT
 PROVIDE ENOUGH DETAILS FOR PROPOSED SYSTEM AND OVER
 RIDES.
 PLEASE SEE THAT NO MAXIMUM TIMES FOR OVER RIDES ARE
 STATED ON LEGEND.
 PLEASE SEE THAT NO CONTROLS ARE SHOWN FOR NUMEROUS
 LOCATIONS OF ACCENT LIGHTING.
 PLEASE SEE THAT THE CIRCUITING SHOWN ON THE LIGHTING
 CONTROL PANELS DO NOT CORRELATE WITH THE PLANS AS THERE
 ARE SEVERAL LIGHTING CIRCUITS ON PLANS NOT ON THE LCP.
 PLEASE SEE THAT THE LIGHTING WHICH IS BEING SHOWN UNDER
 A SEPARATE VOLTAGE OTHER THAN THE 277/480V WILL BE
 REQUIRED TO BE UNDER SEPARATE SYSTEM YET TO BE SHOWN.
 PLEASE SEE THAT THE LIGHTING SHOWN ON PLANS DO NOT
 CORRELATE WITH THE SUBMITTED ENERGY CALCULATIONS
 SUBMITTED FOR THE NUMBER OF FIXTURES, THE TYPE OF
 FIXTURES, THE WATTAGE ON THE FIXTURES ETC. THERE WERE
 ONLY TWO TYPES OF FIXTURES ON THE ENERGY CALCULATIONS
 SUBMITTED WHEN THERE IS AS MANY AS 20+ DIFFERENT TYPES
 OF FIXTURES?
 PLEASE INDICATE THE ZONES WHERE APPLICABLE.
 PLEASE SEE THE SQUARE FOOT LIMITS. PLEASE SEE THE
 ENERGY CALCULATIONS INDICATE A TOTAL OF 21,425 SQ. FT
 AND THE PLANS INDICATE A TOTAL OF 25,157 SQ FT PER
 FLOOR. PLEASE COORDINATE PLANS AND CALCULATIONS. PLEASE
 SEE BATHROOMS DO NOT PROVIDE DEVICES FOR SAFE COVERAGE
 FOR CONTROL OF LIGHTING.
  
 5) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS
 FOR THE IT ROOM EQUIPMENT. THIS WAS NOT SUBMITTED AS
 RESPONSE LETTER MENTIONS.
 PLEASE SEE THE DISCONNECTING MEANS AS PER NFPA-75
 10.4.7, AND NEC 645.10 COULD NOT BE LOCATED. PLEASE SEE
 THE REQUIRED RATING FOR THIS ROOM IS NOT MEETING THE
 MINIMUM WALL CONSTRUCTION STANDARDS OF CHAPTER 3 OF
 NFPA-75. PLEASE SEE AREA OF EXITING AND ENTRANCE FROM
 EXECUTIVE ELEVATOR WHICH IS SHOWN A PART OF THE IT ROOM
 WHICH DOES NOT SEEM THIS WOULD BE PERMITTED AND ALSO
 INFORMATION BASED ON THE FM200 SYSTEM. THIS
 INFORMATION IS ALSO BE GIVEN TO THE OTHER TRADES FOR
 SPECIFIC REVIEW COMMENTS FROM THOSE TRADES. **PART OF
 PREVIOUS NOTE **
 PLEASE SUBMIT INFORMATION FOR THE TWO SYSTEMS WHICH
 APPEAR TO SHOW SOME SORT OF SHUNT TRIP BUT NOT SURE HOW
 THIS PROPOSED SYSTEM DEVICES ARE BEING INSTALLED TO
 PROVIDE THIS SHUNT OF ALL REQUIRED.
 **PLEASE SEE REVIEW COMMENTS FROM OTHER TRADES WHICH
 MAY AFFECT PLANS WITH RESPECT TO RATING OF WALLS, ROOM,
 ETC. PLEASE SEE NFPA-75
 FBC 106.1.2, NEC 90.7, 110.3
  
 6) NOTE: PLEASE PROVIDE THE PHOTO-METRICS FOR STAIR
 AREAS ( NOT EXIT STAIR TOWERS) IN THE SPACE FROM 16TH
 FLOOR TO THE 15TH FLOOR. PROVIDE LEVELS UNDER NORMAL
 AND LEVELS UNDER EMERGENCY CONDITIONS. SOME WERE
 SUBMITTED HOWEVER THE LEVEL(S) FOR EACH IS NOT
 SPECIFIED.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2.
  
 7) NOTE: PLEASE SEE SHEET E2.1 WHICH INDICATES LIGHTING
 FOR FLOOR 17 IN TITLE BLOCK? THIS SEEMS TO BE A
 MISPRINT WHICH SHOULD READ 15TH FLOOR AS SHOWN ON
 PLANS. THIS IS THE SAME COMMENT FROM PREVIOUS REVIEW.
 FBC 106.1.2
  
 8) NOTE: PLEASE SEE THE FIXTURE TYPES AS LISTED ON
 LEGEND ARE NOT THE SAME FOR FIXTURES ON PLANS.
 *EXAMPLE: PLEASE SEE MANY OF THE EMERGENCY FIXTURES ARE
 SHOWN WITH DESIGNATIONS FOR NORMAL FIXTURE TYPES.
 PLEASE SEE SOME OF THE STRIP LIGHTING IS BEING SHOWN
 HAVING CIRCUITS TO FIXTURES WHICH ARE BEING SHOWN FROM
 TWO SEPARATE SERVICES/SYSTEMS.
 PLEASE SEE THE EMERGENCY LIGHTING FIXTURES ARE BEING
 SHOWN COMING FROM A *HOUSE PANEL* OF SORTS AND THE
 OCCUPANT/TENANT HAS NO ACCESS IN TURNING THESE FIXTURES
 OR BRANCH CIRCUITS OFF IN AN EMERGENCY OR OTHER
 SITUATION. A DISCONNECTING MEANS IN THE ELECTRICAL ROOM
 AT A MINIMUM WOULD BE REQUIRED AND LABELED AS SUCH. THE
 STRIP FIXTURES WHICH CONTAIN FEEDS FROM TWO SEPARATE
 PANELS AND SYSTEMS
 ARE NOT PERMITTED.
  
 9) NOTE: PLEASE PROVIDE INFORMATION ON DOOR CLOSURES
 WHICH ARE REQUIRED TO MEET NFPA-101 7.2.1.5. THESE ARE
 STILL BEING REFERENCED ON PLANS AND IN NOTES FOR DOORS,
 MAGNETIC LOCKS/CLOSURES/HOLDERS ETC.
 IF NOT INCLUDED, THEN PLEASE ADJUST PLANS ACCORDINGLY.
  
 10) NOTE: PLEASE SUBMIT AND COMPLETE THE PANEL
 SCHEDULE(S) LOAD CALCULATIONS ON PLANS. PLEASE INCLUDE
 ALL CONTINUOUS LOADS AT 125%. PLEASE KNOW THAT ANY
 ELECTRICAL WATER HEATERS UNDER THE 2005 NEC ARE NOW
 ALSO REQUIRED TO BE SHOWN AT 125%. 422.13
 220.12, 220.14, 220.42,220.43 220.44 ETC.
 RESPONSE MENTIONS THIS WAS DONE, HOWEVER IT IS UNCLEAR
 WHERE/HOW LOADS ARE DERIVED.
 FBC 106.3.5.1.2
  
 11) NOTE: PLEASE SEE THE PLANS ARE NOW INDICATING
 INFORMATION ON TRANSFORMERS FOR LOCATIONS COMPARED TO
 ELECTRICAL ROOMS ETC WHICH WAS NOT ON PREVIOUS PLANS.
 PLEASE SEE THE TAPPED CONDUCTORS ON THE LOAD SIDE OF
 THE TRANSFORMERS NEED TO BE INCREASED AS THEY DO NOT
 MEET 240.21, 408.36, 240.4 AND 310.16.
 PLEASE KNOW THAT TAPPED CONDUCTORS SHALL TERMINATE IN
 OVER CURRENT PROTECTION WHICH LIMITS THE LOAD ON THE
 CONDUCTORS.
 ON THE SECONDARY SIDE OF A TRANSFORMER WHEN THE
 CONDUCTORS DO NOT CORRELATE WITH THE STANDARD OVER
 CURRENT PROTECTION DEVICE PER 240.6 IT IS NOT PERMITTED
 TO GO TO THE NEXT SIZE UP.
 PLEASE ADJUST.
 PLEASE ALSO SEE THE SAME SECTIONS IN 240.21 AS THE
 LOCATIONS OF THE TRANSFORMERS COMPARED TO THE
 DISCONNECTING MEANS AND TERMINATION OF THE CONDUCTORS
 EXCEED THE LENGTH OF CONDUCTORS PERMITTED. PLEASE
 ADJUST THE LOCATIONS OF THE TRANSFORMERS OR ADDED OVER
 CURRENT PROTECTION/DISCONNECTING MEANS ON THE SECONDARY
 SIDE OF THE TRANSFORMERS.
 PLEASE BE SURE ALL CLEARANCES ARE MET PER 110.26
  
 12) NOTE: PLEASE SEE 110.26 AS THE ELECTRICAL PANELS IN
 THE TENANT ELECTRICAL ROOM DO NOT MEET THE MINIMUM
 CLEARANCES PER SCALE ON PLANS.
  
 13) NOTE: THE PLANS INDICATE A PANEL ER, THE PANEL
 SCHEDULE SHEETS INDICATE A PANEL ER HOWEVER THIS IS NOT
 INCLUDED ON THE RISER DIAGRAM.
 PLEASE VERIFY 645.5A AND INDICATE WHERE THE 125% HAS
 BEEN FIGURED.
  
 14) NOTE: PLEASE SEE THERE ARE SEVERAL STANDARD
 LIGHTING FIXTURES WHICH CONTAIN THE NOTE WHICH MENTIONS
 TO WIRED TO EMERGENCY CIRCUIT YET THE FIXTURE IS NOT AN
 EMERGENCY FIXTURE.
 PLEASE SEE FOR EXAMPLE ROOM 1657 ON SHEET E2.2 (NOT THE
 ONLY LOCATION)
  
 15) NOTE: PLEASE INDICATE HOW THE CONDUCTORS ARE RUN,
 SIZED AND CONNECTED TO THE IT EQUIPMENT. PLEASE SEE
 2003 NFPA-75 AND INSTALLATION STANDARDS.
 PER 645.5
  
 16) NOTE: PLEASE INDICATE THE AIC RATINGS FOR ALL NEW
 ELECTRICAL SERVICE EQUIPMENT. THIS NOTE IS TO REMAIN AS
 THERE ARE ITEMS WHICH WILL BE CHANGING, NOT INCLUDED AT
 THIS TIME WHICH MAY ALSO REQUIRE THE RATINGS TO BE
 INDICATED.
 110.9, FBC 106.1.2
  
 17) NOTE: PLEASE KNOW AS THE BUILDING IS STILL UNDER
 CONSTRUCTION AND THE RESPONSIBILITY OF THE BASE
 BUILDING DESIGN TEAM, PLANS SHALL BEAR A *SHOP DRAWING*
 REVIEW STAMP OF SOME TYPE. THESE ITEMS WHICH ARE BEING
 DESIGNED INTO A SHELL BUILDING NEED TO BE KNOWN TO THE
 BASE BUILDING DESIGN TEAM FOR SEVERAL ITEMS INCLUDING
 ENERGY LOADS, ELECTRICAL LOADS ETC.
 THIS HAS BEEN CONFIRMED WITH THE BUILDING OFFICIAL.
  
 18) NOTE: PLEASE SEE ONE SET OF PLANS HAS NUMEROUS
 LOCATIONS REDLINED FOR MANY OF THE NOTES ABOVE HOWEVER
 NOT ALL.
  
 19) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE BEING GIVEN AT THIS TIME.
 THIS OFFICE MAY RETAIN SET(S) OF PLANS.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-10 07:11:232007-09-10 07:11:23
  
 IN PROGRESS
2007-09-09 14:57:282007-09-09 14:57:28
  
 NOTES TO FOLLOW ONCE REVIEW IS COMPLETED.
2007-09-07 20:14:222007-09-07 20:14:22
  
 IN ELEC FOR REVIEW. REVIEW TO COMMENCE ON 9/8

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-19 Cont ID  
Sent By dpalmer Date 2007-04-19 Time 16:08 Rev Time 0.00
Received By dpalmer Date 2007-04-19 Time 08:49 Sent To  
Notes
2007-04-19 16:09:15** UNSAT **
  
 ** PLEASE SEE ANY REFERENCES TO THE FBC CHAPTER 1 ARE
 THE ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
 ** PLEASE KNOW THAT SOME OF THE PRELIMINARY COMMENTS
 BELOW DO NOT APPLY TO KAMM CONSULTING ENGINEERS.
  
 1) NOTE: PLEASE SEE THE FOLLOWING ADOPTED CODES SHOULD
 BE STATED ON PLANS AS THE STATE ADOPTED NEW CODES AS OF
 DECEMBER 8TH, 2006.
 PLEASE SEE THE WRONG NEC WAS STATED.
 2004 FBC W/2006 REVISIONS,
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72.
 SOME OF THESE ARE STATED ON THE FRONT ARCHITECTURAL
 SHEETS AND SOME ARE NOT. PLEASE ALSO INCLUDE THE STATED
 CODE ON THE ELECTRICAL PLANS.
 ** PLEASE KNOW THAT ANY OTHER CODES WHICH MAY BE STATED
 FROM OTHER TRADES SHOULD BE NOTED BY OTHER TRADES.
  
 2) NOTE: PLEASE SEE MISSING LICENSE INFORMATION FOR THE
 YJ DESIGN, PER FLORIDA STATUTES 481.221/471.023 PLEASE
 SEE FAC WHICH REQUIRES ALL INFORMATION ON TITLE BLOCKS
 FOR SAID FIRM PER 61G1-16.004.
 *THIS IS REQUIRED FOR ALL TRADES AND FOR ALL SHEETS
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 3) NOTE: PLEASE SEE *S* SHEETS WHICH CONTAIN A *RUBBER
 STAMP* BY THE ENGINEERWHICH IS REQUIRED TO BE AN
 RAISED IMPRESSION TYPE SEAL IN THE STATE OF FLORIDA PER
 FAC61G15-23.001.
 PLEASE ALSO SEE THE SEAL WHICH IS FROM THE STATE OF
 CALIFORNIA. THIS MUST BE LICENSED IN THE STATE OF
 FLORIDA.
 PLEASE ALSO SEE MISSING INFORMATION REQUIRED IN TITLE
 BLOCKS FOR FIRM LICENSE NUMBER ALSO KNOW AS THE
 CERTIFICATE OF AUTHORIZATION NUMBER, THE PRINTED NAME
 AND LICENSE NUMBER OF DESIGNER OF RECORD.
 ** THIS IS REQUIRED FOR ALL SHEETS AND DOCUMENTS DONE
 BY THIS ENGINEER WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 4) NOTE: PLEASE SEE FBC 2004 W/ 2006 REVISIONS FOR
 CHAPTER 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.,
 13-415.1.AB.1, 13-415.2, 13-415.2.ABC.1.2
 PLEASE SEE SEVERAL AREAS WHICH ARE MISSING THE REQUIRED
 OVER RIDE DEVICES, OR OTHER TYPE DEVICES REQUIRED FOR
 CONTROL OF LIGHTING.
 PLEASE SEE SEVERAL LOCATIONS WHICH LIGHTING CONTROL IS
 REQUIRED FOR AREAS IN WHICH THE OCCUPANT CAN SEE THE
 LIGHTING WHICH IS BEING CONTROLLED.
 PLEASE SEE THE NORTH-SIDE ENTRANCE INTO THE 15TH FLOOR
 WHICH SHOWS NO CONTROL.
 PLEASE SEE THE SOUTH-SIDE ENTRANCE ON THE 16TH FLOOR
 WHICH SHOWS NO CONTROL.
 PLEASE SEE SEVERAL ROOMS WHICH CONTAIN ONLY A STANDARD
 WALL SWITCH.
 PLEASE SEE THE DETAIL FOR EACH CONTROL PANEL DOES NOT
 PROVIDE ENOUGH DETAILS FOR PROPOSED SYSTEM AND OVER
 RIDES.
 PLEASE SEE THAT NO MAXIMUM TIMES FOR OVER RIDES ARE
 STATED ON LEGEND.
 PLEASE SEE THAT NO CONTROLS ARE SHOWN FOR NUMEROUS
 LOCATIONS OF ACCENT LIGHTING.
 PLEASE SEE THAT THE CIRCUITING SHOWN ON THE LIGHTING
 CONTROL PANELS DO NOT CORRELATE WITH THE PLANS AS THERE
 ARE SEVERAL LIGHTING CIRCUITS ON PLANS NOT ON THE LCP.
 PLEASE SEE THAT THE LIGHTING WHICH IS BEING SHOWN UNDER
 A SEPARATE VOLTAGE OTHER THAN THE 277/480V WILL BE
 REQUIRED TO BE UNDER SEPARATE SYSTEM YET TO BE SHOWN.
 PLEASE SEE THAT THE LIGHTING SHOWN ON PLANS DO NOT
 CORRELATE WITH THE SUBMITTED ENERGY CALCULATIONS
 SUBMITTED FOR THE NUMBER OF FIXTURES, THE TYPE OF
 FIXTURES, THE WATTAGE ON THE FIXTURES ETC. THERE WERE
 ONLY TWO TYPES OF FIXTURES ON THE ENERGY CALCULATIONS
 SUBMITTED WHEN THERE IS AS MANY AS 20+ DIFFERENT TYPES
 OF FIXTURES?
 PLEASE INDICATE THE ZONES WHERE APPLICABLE.
 PLEASE SEE THE SQUARE FOOT LIMITS. PLEASE SEE THE
 ENERGY CALCULATIONS INDICATE A TOTAL OF 21,425 SQ. FT
 AND THE PLANS INDICATE A TOTAL OF 25,157 SQ FT PER
 FLOOR. PLEASE COORDINATE PLANS AND CALCULATIONS. PLEASE
 SEE BATHROOMS DO NOT PROVIDE DEVICES FOR SAFE COVERAGE
 FOR CONTROL OF LIGHTING.
  
 ** PLEASE KNOW THAT DUE TO NUMEROUS ITEMS FOR CHAPTER
 13 COMPLIANCE, A FULL REVIEW OF ALL SYSTEMS AND DEVICES
 CAN NOT BE DONE AT THIS TIME.
  
 5) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS
 FOR THE IT ROOM EQUIPMENT.
 PLEASE SEE MISSING DISCONNECTING MEANS FOR POWER OF ALL
 PER 645.10.
 PLEASE SUBMIT INFORMATION FOR THE TWO SYSTEMS WHICH
 APPEAR TO SHOW SOME SORT OF SHUNT TRIP BUT NOT SURE HOW
 THIS PROPOSED SYSTEM DEVICES ARE BEING INSTALLED TO
 PROVIDE THIS SHUNT OF ALL REQUIRED.
 **PLEASE SEE REVIEW COMMENTS FROM OTHER TRADES WHICH
 MAY AFFECT PLANS WITH RESPECT TO RATING OF WALLS, ROOM,
 ETC. PLEASE SEE NFPA-75
 FBC 106.1.2, NEC 90.7, 110.3
  
 6) NOTE: PLEASE PROVIDE THE PHOTO-METRICS FOR STAIR
 AREAS ( NOT EXIT STAIR TOWERS) IN THE SPACE FROM 16TH
 FLOOR TO THE 15TH FLOOR. PLEASE SEE NFPA-101 7.8.1.3,
 7.9.2.2.
  
 7) NOTE: PLEASE SEE SHEET E2.1 WHICH INDICATES LIGHTING
 FOR FLOOR 17? THIS SEEMS TO BE A MISPRINT WHICH SHOULD
 READ 15TH FLOOR AS SHOWN ON PLANS.
 FBC 106.1.2
  
 8) NOTE: PLEASE PROVIDE ALL ROOM ARE AREA DESIGNATIONS
 ON PLANS AND COMPLETE PANEL SCHEDULES TO COORDINATE
 WITH THE NUMERICAL OR NAME DESIGNATIONS FOR THESE ROOMS
 AND AREAS. PLEASE SEE THE FOLLOWING TEXT WHICH IS
 EXTRACTED DIRECTLY FROM THE NEC 408.4.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO
 REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 9) NOTE: PLEASE PROVIDE INFORMATION ON DOOR CLOSURES
 WHICH ARE REQUIRED TO MEET NFPA-101 7.2.1.5
  
 10) NOTE: PLEASE SUBMIT AND COMPLETE THE PANEL
 SCHEDULE(S) LOAD CALCULATIONS ON PLANS. PLEASE INCLUDE
 ALL CONTINUOUS LOADS AT 125%. PLEASE KNOW THAT ANY
 ELECTRICAL WATER HEATERS UNDER THE 2005 NEC ARE NOW
 ALSO REQUIRED TO BE SHOWN AT 125%. 422.13
 220.12, 220.14, 220.42, 220.44 ETC.
 PLEASE SEE SOME OF THE ELECTRICAL PANELS ARE BLANK AT
 THIS TIME, OR ONLY SOME LOADS ARE SHOWN ON PANELS.
 PLEASE COMPLETE.
 FBC 106.3.5.1.2
  
 11) NOTE: PLEASE PROVIDE GROUNDING ATTACHMENT AND
 CONDUCTOR SIZES FOR THE NEW TRANSFORMERS.
 250.50, 250.66, 250.20,250.30
  
 12) NOTE: PLEASE SEE THE PLANS DO NOT INDICATE ANY
 SIZES FOR THESE NEW TRANSFORMER AND SEVERAL ITEMS TO
 REVIEW FOR ELECTRICAL CODE COMPLIANCE CAN NOT BE DONE
 AT THIS TIME.
 PLEASE COMPLETE.
 FBC 106.3.5.1.2
  
 13) NOTE: PLEASE SEE 422.17 FOR WATER HEATERS WHICH MAY
 NOT BE IN STORAGE ROOM LOCATIONS ALONG WITH
 COMBUSTIBLES AND EASILY IGNITABLE MATERIALS. PLEASE SEE
 THE CODE REQUIRES SEPARATION OF THESE ITEMS. PLEASE
 ADJUST PLANS ACCORDINGLY.
  
 14) NOTE: PLEASE OBTAIN THE MOST RECENT REVISED RISER
 DIAGRAM FOR THE BASE BUILDING AS IT IS CURRENTLY SHOWN
 ON PLANS, DOES NOT MATCH.
 FBC 106.1.2
  
 15) NOTE: PLEASE INDICATE HOW THE CONDUCTORS ARE RUN,
 SIZED AND CONNECTED TO THE IT EQUIPMENT.
 PER 645.5
  
 16) NOTE: PLEASE INDICATE THE AIC RATINGS FOR ALL NEW
 ELECTRICAL SERVICE EQUIPMENT.
 110.9, FBC 106.1.2
  
 17) NOTE: PLEASE CLARIFY THE KITCHEN AREA WHICH
 CONTAINS A *HOT/DISP* NOTE? WHAT IS THIS?
 FBC 106.1.2
  
 18) NOTE: PLEASE INDICATE IF THERE ARE ANY WATER
 HEATING UNITS FOR KITCHEN AREA ?
  
 19) NOTE: PLEASE CLARIFY THE PANEL L16, AND L16C AS MCB
 PANELS. THIS IS PERMITTED HOWEVER NOT CLEAR?
 ONLY NOTED AS PLANS DO NOT NEED TO BE REVISED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-04-19 10:48:46REVIEW COMMENCED ON 4/19
2007-04-15 20:09:01IN ELEC FOR REVIEW,

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status F Date 2008-11-03 Cont ID  
Sent By mawillia Date 2008-11-03 Time 16:04 Rev Time 0.00
Received By mawillia Date 2008-11-03 Time 16:00 Sent To  
Notes
2008-11-03 16:04:52*****UNACCEPTABLE*****
  
 THE REVISED FIRE ALARM DRAWINGS SHOULD HAVE BEEN
 SUBMITTED UNDER THE FIRE ALARM PERMIT (08010646) NOT
 THE GENERAL CONTRACTOR'S PERMIT (07030932) AS PER THE
 SUBMITTED APPLICATION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status P Date 2008-10-03 Cont ID  
Sent By mwennerg Date 2008-10-03 Time 11:12 Rev Time 0.00
Received By mwennerg Date 2008-10-03 Time 11:12 Sent To  
Notes
2008-10-03 11:13:39REVISION #15 DATED 8/8/08 STAMPED SHEETS E2.1, E2.2,
 FA0.1, FA2.1 AND FA2.2.

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2008-09-04 Cont ID  
Sent By mwennerg Date 2008-09-04 Time 14:33 Rev Time 0.00
Received By mwennerg Date 2008-09-04 Time 14:33 Sent To  
Notes
2008-09-04 14:34:16REVISION #14 DATED 8/4/08 STAMPED SHEET FA2.2.

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2008-08-12 Cont ID  
Sent By mwennerg Date 2008-08-12 Time 14:48 Rev Time 0.00
Received By mwennerg Date 2008-08-12 Time 14:48 Sent To  
Notes
2008-08-12 14:49:39REVISION DATED 7/3/08. STAMPED SHEETS FA0.1, FA2.1,
 FA2.2. DAMPERS SHALL BE TESTED FOR CLOSURE PRIOR TO
 FINAL INSPECTION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-07-22 Cont ID  
Sent By mawillia Date 2008-07-22 Time 10:01 Rev Time 0.00
Received By mawillia Date 2008-07-22 Time 09:33 Sent To  
Notes
2008-07-22 10:01:39*****REVISION #11, DATED 06/11/08, APPROVED
  
 REVISED PLAN SHEETS FA2.1 AND FA2.2 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-04-04 Cont ID  
Sent By mawillia Date 2008-04-04 Time 16:29 Rev Time 0.00
Received By mawillia Date 2008-04-04 Time 15:59 Sent To  
Notes
2008-04-04 16:18:00*****REVISION #7, DATED 2/26/08, APPROVED
  
 REVISED PLAN SHEETS E2.1, E2.2, AND FA0.1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-02-19 Cont ID  
Sent By mwennerg Date 2008-02-19 Time 11:03 Rev Time 0.00
Received By mwennerg Date 2008-02-19 Time 11:03 Sent To  
Notes
2008-02-19 11:05:17PLANS PASSED ON 12/19/07 AND STAMPED ON THIS DATE. MORE
 FA SPEAKER AUDIBILITY MAY BE REQUIRED ON 15TH FL AREAS
 1556 & 1558.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-12-19 Cont ID  
Sent By mawillia Date 2007-12-19 Time 12:55 Rev Time 0.00
Received By mawillia Date 2007-12-19 Time 12:33 Sent To  
Notes
2007-12-19 12:53:05*****PROVISO*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;THE APPROPIATE PLAN SHEETS TO BE
 FIRE-STAMPED WHEN THE OTHER PLAN REVIEWERS' COMMENTS
 HAVE BEEN SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-09-18 Cont ID  
Sent By mawillia Date 2007-09-18 Time 22:54 Rev Time 0.00
Received By mawillia Date 2007-09-18 Time 21:33 Sent To  
Notes
2007-09-19 00:04:58*****DENIED*****
 *COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW WHICH
 STILL NEEDS TO BE ADDRESSED:
  
 01.IN ADDITION TO THE 2003 EDITION OF NFPA 101, THE
 FLORIDA FIRE PREVENTION CODE (2004 EDITION) SHALL BE
 REFERENCED.PLAN SHEET I-16-LS &I -15-LS UNDER LIFE
 SAFETY AND CODE COMPLIANCE INCORRECTLY REFERS TO THE
 2004 EDITION OF NFPA 101
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 TO APPLICABLE CODES UNDER LIFE AND CODE COMPLIANCE
 SUMMARY ON SHEET I-16-LS AND/OR I-15-LS
  
 03.ACCUMULATIONS OF COMBUSTIBLE WASTE MATERIALS,
 DUST, AND DEBRIS SHALL BE REMOVED FROM THE SITE AT THE
 END OF EACH OF SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATION.ADD TO GENERAL NOTES (SHEET
 I-G.1)
  
 04.THE SCOPE OF WORK (ON THE 15TH AND 16TH FLOORS)
 SHALL NOT INTERFERE OR HINDER ACCESS TO OR EGRESS FROM
 OTHER FLOORS AND/OR AREAS OF THE BUILDING.ADD TO
 SHEET I-G.1
  
 05.DOORS LEADING DIRECTLY TO THE CORRIDORS SHALL BE
 AN APPROVED, LISTED, AND LABELED FIRE DOOR AND ASSEMBLY
 IN ACCORDANCE WITH NFPA 80.ADD/SHOW ON THE APPROPIATE
 PLAN SHEET WHERE THIS HAS BEEN ACKNOWLEDGEDSHEET
 I-DR-1 ?
  
 09.ON SHEET E2.1, THE DESCRIPTION IS FOR THE 17TH
 FLOOR.PER YOUR APPLICATION, THE SCOPE OF WORK IS FOR
 THE 15TH AND 16TH FLOOR. DELETE REFERENCE TO THE 17TH
 FLOOR
  
 11.TWO (OF THE FOUR) SPECIFICATION/DETAIL SHEETS ARE
 NOT LEGIBLE ENOUGH FOR REVIEW.PLEASE SEE SHEET FS0.1
  
  
 *NEW COMMENT
  
 A.SHEET INDEX ON SHEET I-G.1 IS INCOMPLETE.ALTHOUGH
 SHEETS S-1 THRU FS2.3 WERE INCLUDED IN THE PLAN SET, NO
 REFLECTIONS OF THESE SHEETS IN THE SHEET INDEX
  
 B.CARD READERS(CR) AS SHOWN ON SHEET I-DR-1ON DOOR
 D6W SHALL NOT BE INCLUDED IN THIS PROJECTED SCOPE OF
 WORK.PLEASE BE ADVISED THAT SEPARATE PLANS AND PERMIT
 WILL BE REQUIRED FOR ENTRANCE/EGRESS ACCESS CONTROL
 SYSTEMS PROVIDED THAT THE CRITERIA AS PER NFPA 101
 7.2.1.6.2 ARE MET.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-06-05 Cont ID  
Sent By mawillia Date 2007-06-05 Time 11:40 Rev Time 0.00
Received By mawillia Date 2007-06-05 Time 09:30 Sent To  
Notes
2007-06-05 11:01:41*****DENIED*****
  
  
 01.IN ADDITION TO THE 2003 EDITION OF NFPA 101, THE
 FLORIDA FIRE PREVENTION CODE (2004 EDITION) SHALL BE
 REFERENCED.
  
 02.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 03.ACCUMULATIONS OF COMBUSTIBLE WASTE MATERIALS,
 DUST, AND DEBRIS SHALL BE REMOVED FROM THE SITE AT THE
 END OF EACH OF SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATION.
  
 04.THE SCOPE OF WORK (ON THE 15TH AND 16TH FLOORS)
 SHALL NOT INTERFERE OR HINDER ACCESS TO OR EGRESS FROM
 OTHER FLOORS AND/OR AREAS OF THE BUILDING.
  
 05.DOORS LEADING DIRECTLY TO THE CORRIDORS SHALL BE
 AN APPROVED, LISTED, AND LABELED FIRE DOOR AND ASSEMBLY
 IN ACCORDANCE WITH NFPA 80.
  
 06.SPECITY THE INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS AND CEILINGS IN THE EXITS, EXIT ACCESS CORRIDORS,
 AND ALL OTHER SPACES IN TERMS OF CLASS A, CLASS B, OR
 CLASS C.
  
 07.ON SHEETI-G-1, GENERAL NOTE 13, PLEASE EXPLAIN
 THE REFERENCE TO THE CITY OF LOS ANGELES DEPARTMENT OF
 BUILDING AND SAFETY.
  
 08.ON SHEETE0.1 UNDER ELECTRICAL SPECIFICATIONS,
 PART 1 -SECTION C,THE 2003 EDITION OF NFPA 101 SHALL
 BE REFERENCED.
  
 09.ON SHEET E2.1, THE DESCRIPTION IS FOR THE 17TH
 FLOOR.PER YOUR APPLICATION, THE SCOPE OF WORK IS FOR
 THE 15TH AND 16TH FLOOR.
  
 10.AS PER WEST PALM BEACH FIRE PREVENTION, DUCT SMOKE
 DETECTORS SHALL ACTIVATE A GENERAL FIRE ALARM.AMEND
 FIRE ALARM NOTE #17 ON SHEET FA0.1.
  
 11.TWO (OF THE FOUR) SPECIFICATION/DETAIL SHEETS ARE
 NOT LEGIBLE ENOUGH FOR REVIEW.
  
 12.ON SHEET FS2.1 (15TH FLOOR FIRE SPRINKLER PLAN) IS
 DESCRIBED IN THE TITLE BLOCK AS THE 17TH FLOOR.
  
 13.ON SHEET FS2.2(16TH FLOOR FIRE SPRINKLER PLAN)
 IS DESCRIBED IN THE TITLE BLOCK AS THE 18TH FLOOR.
  
 14.SHEET FS2.2 IS DESCRIBED IN THE TITLE BLOCK AS THE
 18TH FLOOR.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2008-10-23 Cont ID  
Sent By shill Date 2008-10-23 Time 15:19 Rev Time 0.00
Received By shill Date 2008-10-23 Time 15:19 Sent To B
Notes
2008-10-23 15:20:54TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2008-10-23 Cont ID  
Sent By adarroug Date 2008-10-23 Time 11:14 Rev Time 0.00
Received By adarroug Date 2008-10-23 Time 11:14 Sent To FIRE
Notes
2008-10-23 11:15:54TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2008-10-02 Cont ID  
Sent By adarroug Date 2008-10-02 Time 15:04 Rev Time 0.00
Received By adarroug Date 2008-10-02 Time 15:04 Sent To B
Notes
2008-10-02 15:05:02TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2008-09-10 Cont ID  
Sent By adarroug Date 2008-09-10 Time 11:13 Rev Time 0.00
Received By adarroug Date 2008-09-10 Time 11:13 Sent To  
Notes
2008-09-10 11:13:25TO "COMM" BD#41

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2008-08-15 Cont ID  
Sent By adarroug Date 2008-08-15 Time 13:36 Rev Time 0.00
Received By adarroug Date 2008-08-15 Time 13:36 Sent To  
Notes
2008-08-15 13:36:23TO "COMM" BD#28

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2008-07-15 Cont ID  
Sent By adarroug Date 2008-07-15 Time 08:22 Rev Time 0.00
Received By adarroug Date 2008-07-15 Time 08:22 Sent To  
Notes
2008-07-15 08:22:41WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2008-07-03 Cont ID  
Sent By adarroug Date 2008-07-03 Time 10:45 Rev Time 0.00
Received By adarroug Date 2008-07-03 Time 10:45 Sent To B
Notes
2008-07-03 10:45:40TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2008-06-20 Cont ID  
Sent By adarroug Date 2008-06-20 Time 11:22 Rev Time 0.00
Received By adarroug Date 2008-06-20 Time 11:22 Sent To  
Notes
2008-06-23 10:16:23TO "COMM" BD#57
2008-06-20 11:22:51WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-06-20 Cont ID  
Sent By adarroug Date 2008-06-20 Time 11:08 Rev Time 0.00
Received By adarroug Date 2008-06-20 Time 11:08 Sent To B
Notes
2008-06-20 11:09:17TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-06-17 Cont ID  
Sent By adarroug Date 2008-06-17 Time 16:42 Rev Time 0.00
Received By adarroug Date 2008-06-17 Time 16:42 Sent To E
Notes
2008-06-17 16:42:32TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-06-10 Cont ID  
Sent By adarroug Date 2008-06-10 Time 15:32 Rev Time 0.00
Received By adarroug Date 2008-06-10 Time 15:32 Sent To B
Notes
2008-06-10 15:32:30TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-06-04 Cont ID  
Sent By adarroug Date 2008-06-04 Time 11:32 Rev Time 0.00
Received By adarroug Date 2008-06-04 Time 11:32 Sent To E
Notes
2008-06-04 11:33:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-05-16 Cont ID  
Sent By adarroug Date 2008-05-16 Time 09:51 Rev Time 0.00
Received By adarroug Date 2008-05-16 Time 09:51 Sent To P
Notes
2008-05-16 09:51:36TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-05-12 Cont ID  
Sent By adarroug Date 2008-05-12 Time 15:04 Rev Time 0.00
Received By adarroug Date 2008-05-12 Time 15:04 Sent To B
Notes
2008-05-12 15:05:21TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-05-08 Cont ID  
Sent By adarroug Date 2008-05-08 Time 12:53 Rev Time 0.00
Received By adarroug Date 2008-05-08 Time 12:53 Sent To B
Notes
2008-05-08 12:54:10TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-04-29 Cont ID  
Sent By adarroug Date 2008-04-29 Time 10:52 Rev Time 0.00
Received By adarroug Date 2008-04-29 Time 10:52 Sent To B
Notes
2008-04-29 10:52:43TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-04-18 Cont ID  
Sent By adarroug Date 2008-04-18 Time 11:35 Rev Time 0.00
Received By adarroug Date 2008-04-18 Time 11:35 Sent To  
Notes
2008-04-18 11:36:00TO "COMM" BD#14

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-03-10 Cont ID  
Sent By adarroug Date 2008-03-10 Time 16:36 Rev Time 0.00
Received By adarroug Date 2008-03-10 Time 16:15 Sent To  
Notes
2008-03-10 16:36:25TO "COMM" BD#54

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-01-28 Cont ID  
Sent By adarroug Date 2008-01-28 Time 14:10 Rev Time 0.00
Received By adarroug Date 2008-01-28 Time 14:10 Sent To  
Notes
2008-01-28 14:20:48TO "COMM" BD#3--EXPEDITED--PLANS ON RACK/2 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-11-28 Cont ID  
Sent By adarroug Date 2007-11-28 Time 09:33 Rev Time 0.00
Received By adarroug Date 2007-11-28 Time 09:33 Sent To  
Notes
2007-11-29 11:12:59TO "COMM" BD#29--EXPEDITED--PLANS ON RACK 4 ROLLS
2007-11-28 09:34:37WAITING FOR "COMM" BD--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-08-24 Cont ID  
Sent By adarroug Date 2007-08-24 Time 15:48 Rev Time 0.00
Received By adarroug Date 2007-08-24 Time 15:48 Sent To  
Notes
2007-09-04 08:49:24TO "COMM" BD#7/PLANS ON RACK--1 ROLL--EXPEDITED PERMIT
2007-08-24 15:48:21WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-08-24 Cont ID  
Sent By jwitmer Date 2007-06-06 Time 13:48 Rev Time 0.00
Received By adarroug Date 2007-03-27 Time 17:49 Sent To  
Notes
2007-06-06 16:44:35BUILDING PLAN REVIEW
 PERMIT: 07030932
 ADD: 525 OKEECHOBEE BLVD PENTHOUSE A & B
 CONT: CENTEX
 TEL: (954)214-9415
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)Y J ARCHITECTURAL DESIGN WILL REQUIRE A CERTIFICATE
 OF AUTHORIZATION,) 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT PRACTICING UNDER
 A FICTITIOUS NAME, A CORPORATION, OR A PARTNERSHIP,
 OFFERING ARCHITECTURAL SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION NUMBER.ADD THE
 NUMBER TO EACH SHEET.
  
 4)STRUCTURAL SHEET S-1 WILL REQUIRE A RAISED
 IMPRESSION TYPE SEAL NOT A STAMPED SEAL. FAC
 61G15-23.001 THE SEAL IS ALSO A CALIFORNIA SEAL THE
 DESIGN PROFESSIONAL MUST BE A LICENSED ENGINEER IN THE
 STATE OF FLORIDA. 471.025
  
 5) THE SAME HOLDS TRUE FOR THECALCULATIONS SUBMITTED
 FOR THE STAIRS BETWEEN THE 15TH & 16TH FLOOR. MUST BE A
 LICENSED ENGINEER FOR THE STATE OF FLORIDA AND
 IF THE ENGINEER OF RECORD DOES NOT SEAL EACH SHEET THEN
 A SEALED COVER SHEET LISTING HOW MANY PAGES ARE COVERED
 UNDER THIS SEAL. 61G15-23.002.
  
 6) LS-01 / LS-02 PLEASE UPDATE APPLICABLE CODE TO THE
 2004FBC W 2006 AMENDMENTS, PLEASE CORRECT.
  
 7) LS-01 BOTTOM RIGHT OF SHEET THERE IS A DISCREPANCY
 IN ONE AREA THE PLAN INDICATES THIS SHEET REPRESENTS
 THE 15TH FLOOR WHILE LESS THAN SIX INCHES AWAY THE
 PLAN
  
 INDICATES WORK ON THE 16TH FLOOR, PLEASE CORRECT.
  
 8)SHEET I-G.1 PLEASE CORRECT THE REFERENCES MADE TO
 EITHER THE LOS ANGLES BUILDING CODE OR THE UBC AND CODE
 REFERENCE NUMBERS.
  
 9) SHEET 1-16C THE 2 AREAS THAT ARE CONSIDERED AS
 ATRIUMS DO NOT HAVE RATED WALLS NOR DOORS, PLEASE
 COMPLY WITH:
 404.5 ENCLOSURE OF ATRIUMS.
 ATRIUM SPACES SHALL BE SEPARATED FROM ADJACENT SPACES
 BY A 1-HOUR FIRE BARRIER WALL.
 EXCEPTIONS:
 1.A GLASS WALL FORMING A SMOKE PARTITION WHERE
 AUTOMATIC SPRINKLERS ARE SPACED 6 FEET (1829 MM) OR
 LESS ALONG BOTH SIDES OF THE SEPARATION WALL, OR ON THE
 ROOM SIDE ONLY IF THERE IS NOT A WALKWAY ON THE ATRIUM
 SIDE, AND BETWEEN 4 INCHES AND 12 INCHES (102 MM AND
 305 MM) AWAY FROM THE GLASS AND SO DESIGNED THAT THE
 ENTIRE SURFACE OF THE GLASS IS WET UPON ACTIVATION OF
 THE SPRINKLER SYSTEM. THE GLASS SHALL BE INSTALLED IN A
 GASKETED FRAME SO THAT THE FRAMING SYSTEM DEFLECTS
 WITHOUT BREAKING (LOADING) THE GLASS BEFORE THE
 SPRINKLER SYSTEM OPERATES.
 2.A GLASS-BLOCK WALL ASSEMBLY IN ACCORDANCE WITH
 SECTION 2110 AND HAVING A ?-HOUR FIRE PROTECTION
 RATING.
 3.THE ADJACENT SPACES OF ANY THREE FLOORS OF THE
 ATRIUM SHALL NOT BE REQUIRED TO BE SEPARATED FROM THE
 ATRIUM WHERE SUCH SPACES ARE INCLUDED IN COMPUTING THE
 ATRIUM VOLUME FOR THE DESIGN OF THE SMOKE CONTROL
 SYSTEM.
  
 10) SHEET 1-16C INDICATE TWO TYPE OF DOORS THAT WILL BE
 PENETRATING THE 1 HR RATED WALL DOOR TYPED-6 WHICH DOES
 HAVE 45 MINUTE RATING AND DOOR TYPE D-3 WHICH DOES NOT
 PLEASE CORRECT. TABLE 715.3.
  
 11)PLEASE TAKE NOTE OF : 404.7 INTERIOR FINISH. THE
 INTERIOR FINISH OF WALLS AND CEILINGS OF THE ATRIUM
 SHALL NOT BE LESS THAN CLASS B WITH NO REDUCTION IN
 CLASS FOR SPRINKLER PROTECTION.
  
 12)SHEET 1-15C DOES INDICATE THE 1 HR RATED
 PARTITIONS AT THE ATRIUM AREAS BUT THERE IS NO DOOR
 SHEDULE IF TAKEN FROM SHEET 1-16.C D-3 IS NOT RATED
 PLEASE CORRECT.
  
 13) PLEASE REVIEW LS-02 THE NORTHEAST CORNER OF THE
 BUILDING INDICATES THE DISTANCE TO AN EXIT AS 204 FT.
 404.8 TRAVEL DISTANCE, THE SOUTHEAST CORNER THIS
 DISTANCE WILL BE GREATER. IN OTHER THAN THE LOWEST
 LEVEL OF THE ATRIUM , WHERE THE REQUIRED MEANS OF
 EGRESS IS THROUGH THE ATRIUM SPACE, THE PORTION OF EXIT
 ACCESS TRAVEL DISTANCE WITHIN THE ATRIUM SPACE SHALL
 NOT EXCEED 200 FEET .
  
 14)404.4 SMOKE CONTROL. A SMOKE CONTROL SYSTEM SHALL
 BE INSTALLED IN ACCORDANCE WITH SECTION 909 . 909.22
 ATRIUM .
 909.22.1
 A SMOKE CONTROL SYSTEM SHALL BE DESIGNED TO CONTROL THE
 MIGRATION OF PRODUCTS OF COMBUSTION IN THE ATRIUM
 SPACE. UPON DETECTION OF A FIRE, THE SYSTEM SHALL
 CONTROL THE AIR SUPPLY TO THE FIRE FLOOR AND THE RETURN
 AIR FROM ALL NONFIRE FLOORS IN ACCORDANCE WITH THE
 APPROVED SMOKE CONTROL SYSTEM DESIGN. ANY OTHER
 APPROVED DESIGN WHICH WILL ACHIEVE THE SAME LEVEL OF
 SMOKE CONTROL AS DESCRIBED IN THIS SECTION MAY BE USED
 IN LIEU OF THESE REQUIREMENTS.
  
 909.22.2
 THE SMOKE CONTROL SYSTEM SHALL BE DESIGNED BY AN
 ENGINEERING ANALYSIS THAT DEMONSTRATES THAT THE SMOKE
 LAYER INTERFACE IS MAINTAINED ABOVE THE HIGHEST
 UNPROTECTED OPENING TO ADJOINING SPACES, OR 6 FEET
 ABOVE THE HIGHEST FLOOR LEVEL OPEN TO THE ATRIUM FOR A
 PERIOD EQUAL TO 1.5 TIMES THE CALCULATED EGRESS TIME OR
 20 MINUTES, WHICHEVER IS GREATER.
  
 909.22.3
 THE SMOKE CONTROL SYSTEM SHALL BE INDEPENDENTLY
 ACTIVATED BY THE SPRINKLER SYSTEM WITHIN THE ATRIUM OR
 AREAS OPEN TO THE ATRIUM , BY THE SMOKE DETECTORS
 REQUIRED BY THIS SECTION AND BY MANUAL CONTROLS THAT
 ARE READILY AVAILABLE TO THE FIRE DEPARTMENT. WHEN THE
 SMOKE CONTROL SYSTEM IN OTHER THAN THE ATRIUM IS
 PROVIDED BY MECHANICAL VENTILATION IN ACCORDANCE WITH
 THIS SECTION, MANUAL CONTROLS SHALL ALSO BE PROVIDED AS
 DESCRIBED ABOVE FOR THE ATRIUM SYSTEM. THE MANUAL
 CONTROLS SHALL BE PROVIDED IN A LOCATION APPROVED BY
 THE BUILDING OFFICIAL.
  
 15) THERE IS A DISCREPANCY IN THE PLANS THE
 ARCHITECTURAL , STRUCTURAL, ELECTRICAL AND FIRE ALARM
 ALL INDICATE WORK ON THE 15THAND 16TH FLOORS, WHERE
 AS THE
 FIRE SPRINKLER AND MECHANICAL PLANS INDICATE THE 17TH
 AND 18TH FLOORS. PLEASE CORRECT.
  
 16)PLEASE PROVIDE ADDTIONAL INFORMATION ON THE GLASS
 HANDRAILS AND GUARDS SEE 2407.
 2407.1.1 LOADS.
 THE PANELS AND THEIR SUPPORT SYSTEM SHALL BE DESIGNED
 TO WITHSTAND THE LOADS SPECIFIED IN SECTION 1607.7 . A
 SAFETY FACTOR OF FOUR SHALL BE USED.
  
 2407.1.2 SUPPORT.
 EACH HANDRAIL OR GUARD SECTION SHALL BE SUPPORTED BY A
 MINIMUM OF THREE GLASS BALUSTERS OR SHALL BE OTHERWISE
 SUPPORTED TO REMAIN IN PLACE SHOULD ONE BALUSTER PANEL
 FAIL. GLASS BALUSTERS SHALL NOT BE INSTALLED WITHOUT AN
 ATTACHED HANDRAIL OR GUARD.
  
 17)PLEASE PROVIDE AT WHAT SLOPE IN DEGREES THE GLASS
 WALL IS FROMVERTICAL, IF THE SLOPE IS MORE THAN 15
 DEGREES SEE 2405.2 .
  
 18) THE GLASS WALL IS ALSO CONSIDERED A HAZARDOUS
 LOCATION 15TH AND 16TH FLOORS. SEE 2406.3(7)
 7.GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE
 PANEL, OTHER THAN IN THOSE LOCATIONS DESCRIBED IN
 PRECEDING ITEMS 5 AND 6, WHICH MEETS ALL OF THE
 FOLLOWING CONDITIONS:
 7.1.EXPOSED AREA OF AN INDIVIDUAL PANE GREATER
 THAN 9 SQUARE FEET (0.84 M 2 );
 7.2.EXPOSED BOTTOM EDGE LESS THAN 18 INCHES (457
 MM) ABOVE THE FLOOR;
 7.3.EXPOSED TOP EDGE GREATER THAN 36 INCHES (914
 MM) ABOVE THE FLOOR; AND
 7.4.ONE OR MORE WALKING SURFACE(S) WITHIN 36
 INCHES (914 MM) HORIZONTALLY OF THE PLANE OF THE
 GLAZING.
 EXCEPTION: SAFETY GLAZING FOR ITEM 7 IS NOT REQUIRED
 FOR THE FOLLOWING INSTALLATIONS:
 1.A PROTECTIVE BAR 1? INCHES (38 MM) OR MORE IN
 HEIGHT, CAPABLE OF WITHSTANDING A HORIZONTAL LOAD OF 50
 POUNDS PLF (730 N/M) WITHOUT CONTACTING THE GLASS, IS
 INSTALLED ON THE ACCESSIBLE SIDES OF THE GLAZING 34
 INCHES TO 38 INCHES (864 MM TO 965 MM) ABOVE THE
 FLOOR.
  
  
 19) SHEET I-E.2 STAIRWELL SECTION THE HANDRAIL AT THE
 TOP LANDING IS MISSING : 11-4.9.4(2) IF HANDRAILS ARE
 NOT CONTINUOUS, THEY SHALL EXTEND AT LEAST 12 INCHES
 (305 MM) BEYOND THE TOP RISER AND AT LEAST 12 INCHES
 (305 MM) PLUS THE WIDTH OF ONE TREAD BEYOND THE BOTTOM
 RISER. AT THE TOP, THE EXTENSION SHALL BE PARALLEL WITH
 THE FLOOR OR GROUND SURFACE. AT THE BOTTOM, THE
 HANDRAIL SHALL CONTINUE TO SLOPE FOR A DISTANCE OF THE
 WIDTH OF ONE TREAD FROM THE BOTTOM RISER; THE REMAINDER
 OF THE EXTENSION SHALL BE HORIZONTAL [SEE FIGURE 19 (C)
 AND FIGURE 19 (D)]. HANDRAIL EXTENSIONS SHALL COMPLY
 WITH SECTION 11-4.4 .
  
 20) SHEET I-E.2 HANDRAILS: 11-4.9.4(5) TOP OF HANDRAIL
 GRIPPING SURFACE SHALL BE MOUNTED BETWEEN 34 INCHES AND
 38 INCHES (865 MM AND 965 MM) ABOVE STAIR NOSING.
  
 21)PLANS DO NOT PROVIDE THE DISTANCE FROM THE
 VERTICAL GLASS GUARD RAILING AND THE HANDRAIL?
 11-4.9.4(3) THE CLEAR SPACE BETWEEN HANDRAILS AND WALL
 SHALL BE 1?".
  
 22) THE SAME STAIR ELEMENTS WILL NEED TO BE ADDRESSED
 ON THE NORTHWEST STAIR AND HAND RAILS AS LISTED IN
 ITEMS 19-21, THE CUT SECTIONS OF THIS STAIRARE NOT
 CLEAR AND THESE ITEMS CAN NOT BE VISSIBLY ADDRESSED.
  
 23)ARE THE SKYLIGHTS PART OF THIS PERMIT OR ARE THEY
 PART OF THE SHELL BUILDING? IF PART OF THIS PERMIT THE
 FOLLOWING WILL BE REQUIRED: FL BLD CODE 1609.1.4:
 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS,MISSING REPORTS
 ARE AS
 FOLLOWS: A ) SKYLIGHTS
  
 23A)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE SEE THE
 STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 23B)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
2007-03-30 17:59:50TO COMM BOARD # 53
2007-03-27 17:50:24WAITING FOR COMM BOARD

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2008-09-23 Cont ID  
Sent By rregueir Date 2008-09-23 Time 11:53 Rev Time 0.00
Received By rregueir Date 2008-09-18 Time 13:29 Sent To  
Notes
2008-09-23 11:53:45PAGES M2.1, M2.2 REV.15

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2008-08-28 Cont ID  
Sent By rregueir Date 2008-08-28 Time 09:34 Rev Time 0.00
Received By rregueir Date 2008-08-28 Time 09:34 Sent To  
Notes
2008-08-28 09:34:46PAGE M2.2 REV 14

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2008-08-28 Cont ID  
Sent By rregueir Date 2008-07-10 Time 09:35 Rev Time 0.00
Received By rregueir Date 2008-07-09 Time 16:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-05-12 Cont ID  
Sent By rregueir Date 2008-05-12 Time 16:05 Rev Time 0.00
Received By rregueir Date 2008-05-12 Time 14:38 Sent To PC
Notes
2008-05-12 16:04:59REV.8 PAGES M2.1 AND M2.2

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2008-03-27 Cont ID  
Sent By rregueir Date 2008-03-27 Time 09:22 Rev Time 0.00
Received By rregueir Date 2008-03-27 Time 09:16 Sent To  
Notes
2008-03-27 09:22:16PG M2.1 REV 7 DENIED:
  
 1. THE 14X12 DUCT FROM VAV 15-24 IS PENETRATING A FIRE
 RESISTANCE RATED WALL AT ROOM 1544 WITHOUT OPENING
 PROTECTIVE. SHOW HOW THIS DUCT PENETRATION IS TO BE
 PROTECTED IN ACCORDANCE WITH FBCM 607.5.
  
 2. THE 14X12 DUCT FROM VAV 15-4 IS CROSSING A FIRE
 RESISTANCE RATED WALL AT ROOM 1574 WITHOUT OPENING
 PROTECTIVE. SHOW HOW THIS DUCT PENETRATION OF A RATED
 ASSEMBLY WILL BE PROTECTED IN ACCORDANCE WITH FBCM
 607.5.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-03-27 Cont ID  
Sent By rregueir Date 2008-03-27 Time 09:15 Rev Time 0.00
Received By rregueir Date 2008-03-26 Time 15:47 Sent To  
Notes
2008-03-27 09:16:31PG M2.2 REV.7

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-02-16 Cont ID  
Sent By rregueir Date 2008-02-16 Time 10:04 Rev Time 0.00
Received By rregueir Date 2008-02-16 Time 09:14 Sent To  
Notes
2008-02-16 10:07:12THIS WAS A RESTAMP AS THE SAME VERSION SHEETS WERE
 SUBMITTED AS THE PREVIOUS REVIEW, WHICH HAD PASSED AND
 WERE STAMPED AT THAT TIME. THE PREVIOUSLY STAMPED PAGES
 COLD HAVE BEEN INCLUDED IN THIS SET, SAVING THE TIME
 AND NEED FOR A MECHANICAL REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-12-01 Cont ID  
Sent By rregueir Date 2007-12-01 Time 14:15 Rev Time 0.00
Received By rregueir Date 2007-12-01 Time 11:00 Sent To  
Notes
2007-12-01 13:41:31PASSED PENDING SATISFACTION OF ALL ENERGY CODE
 REQUIREMENTS BY OTHER INTERESTED TRADES.
 ALL BUILDING COMPONENTS AND ENERGY UTILIZING DEVICES
 WHICH ARE SUBJECT TO FBC CHAPTER 13 IN THIS SPACE SHALL
 BE INCORPORATED INTO BASE BUILDING ENERGY CALCULATIONS
 PRIOR TO BASE BUILDING FINAL INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-09-20 Cont ID  
Sent By rregueir Date 2007-09-20 Time 17:10 Rev Time 0.00
Received By rregueir Date 2007-09-19 Time 18:05 Sent To  
Notes
2007-09-19 18:41:41REVIEW #: 2
 ACTION:
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. OK
  
 3. DAMPER IN NON-RATED WALL HAS BEEN REMOVED. HOWEVER,
 PLEASE SEE ELECTRICAL AND POSSIBLY BUILDING REVIEWS AS
 A RATED WALL MAY BE REQUIRED IN THIS LOCATION.
  
 4. EXAMPLE: WORK ROOM 1542 HAS TYPE "B" WALLS ON ALL
 SIDES. BASED ON DETAIL 4 ON PG I-D.1, THE DRYWALL STOPS
 6 INCHES ABOVE THE CEILING, BUT THE WALL INSULATION
 CONTINUES TO THE UNDERSIDE OF THE DECK, THUS IMPEDING
 FREE FLOW OF RETURN AIR FROM THIS SPACE. THIS CONDITION
 WOULD ALSO PRECLUDE THE WALL CAVITY FROM BEING SEALED
 AT THE TOP WITH AN APPROVED AIR BARRIER AS REQUIRED PER
 FBC,M 603.8.
  
 5. OK
  
 6. OK
  
 7. OK
  
 8. OK
  
 9. THERE IS A FLEX DUCT PASSING THROUGH THE RATED WALL
 RIGHT NEXT TO THE NEWLY ADDED 54X12 FIRE DAMPER. THIS
 DUCT PENETRATION DOES JOT SHOW ANY OPENING PROTECTIVES
 AS REQUIRED BY FBC,M 607.5. AND 607.7.
  
 10. THE 72X12 R/A FSD AT ROOMS 1633 AND 1601 IS SHOWN
 HALF WAY OUT OF THE RATED WALL. PLEASE SHOW HOW
 OOPENING PROTECTION IS TO BE MAINTAINED AT THE RATED
 WALL ASSEMBLY. ALSO, SEE NEW COMMENTS RELATED TO NEW
 FSD'D AND SMOKE CONTROL.
  
 11. OK
  
 12. OK
  
 13. OK
  
 14. VAV 16-13, EVEN THOUGH THE SCHEDULE HAS BEEN
 REVISED TO SHOW THE REQUIRED CFM AT 1150, THE FLOOR
 PLAN STILL SHOWS 1350 CFM. THERE ARE FOUR DROPS AT 300
 CFM EACH PLUS ONE DROP AT 150 CFM. PLEASE SHOW
 CORRELATION BETWEEN SCHEDULE AND FLOOR PLANS.
  
 15. OK PENDING FIELD VERIFICATION THAT THERE WILL BE NO
 EXHAUST DUCT UNDER POSITIVE PRESSURE EXPOSED TO THE
 PLENUM. FBC,M 601.3
  
 16. OK
  
 17. OK
  
 18. REGARDLESS OF THE LOCATION OF THE CONDENSERS ON THE
 ROOF, THEY ARE STILL OUTDOOR EQUIPMENT AND THEY ARE
 STILL ON THE ROOF. THEY ARE NOT PART OF THE BASE
 BUILDING SCOPE OF WORK. THEREFORE, CODE COMPLIANCE
 SHALL BE DEMONSTRATED AS PART OF THIS PERMIT
 APPLICATION. SHOW COMPLIANCE WITH FBC,M 301.13, FBC
 1509.7 AND FBC CH.16.
 NOTE: IF PRE-ENGINEERED A/C STANDS ARE USED, PRODUCT
 APPROVAL IS REQUIRED BY FAC RULE 9B-72. FOR MORE
 INFORMATION ON THE FLORIDA PRODUCT APPROVAL SYSTEM
 PLEASE VISIT: WWW.FLORIDABUILDING.ORG
  
 19. OK
  
 20. IT IS AGREED THAT THE COMPUTER ROOM A/C UNITS NEED
 NOT BE INCLUDED IN CALCULATIONS. HOWEVER, AS THE BASE
 BUILDING WAS PERMITTED AS A SHELL BUILDING AND IS NOT
 COMPLETED, COMPLIANCE WITH FBC 13-101.1.6 IS REQUIRED.
 THE ENERGY USAGE OF THIS SPACE SHALL BE INCORPORATED
 INTO THE BASE BUILDING ENERGY CALCULATIONS PRIOR TO
 C.O. OF THE BASE BUILDING.
  
 IN ORDER TO DEMONSTRATE CODE COMPLIANCE, PROVIDE AT A
 MINIMUM AN INPUT DATA REPORT WHICH ACCURATELY REFLECTS
 ALL EQUIPMENT AND DEVICES SHOWN ON PLANS WHICH ARE
 SUBJECT TO FBC CH. 13. THIS INFORMATION SHALL BE
 PROVIDED TO THE DESIGNER OF RECORD FOR BASE BUILDING
 ENERGY CALCULATIONS. THIS DATA SHALL BE REVIEWED BY THE
 BASE BUILDING DESIGNER TO DETERMINE IF THE ENERGY
 USEAGE IN THIS SPACE CONFORMS TO BASE BUILDING
 ASSUMPTIONS AND/OR FALLS WITHIN PARAMETERS WHICH WILL
 ALLOW FINAL REVISED ENERGY CALCULATIONS FOR THE WHOLE
 BUILDING TO COMPLY WITH FBC CH.13.
 NOTE: IT IS RECOMMENDED THAT FOR THIS SPACE THE INPUT
 DATA BE SEPARATED INTO FLOORS AND LABELED "ZONE 15" AND
 "ZONE 16" TO FACILITATE INCORPORATION OF THE DATA INTO
 THE BASE BUILDING CALCULATIONS. PROOF OF ACCEPTANCE BY
 THE BASE BUILDING DESIGNER SHALL BE PROVIDED (A SIGNED
 SHOP DRAWING REVIEW STAMP IS SUFFICIENT) AT TIME OF
 RESUBMITTAL.
  
 NEW COMMENTS:
  
 A. SMOKE CONTROL SEQUENCE, THE STATEMENTS CONTAINED
 WITHIN THE SEQUENCE ARE IN CONFLICT WITH EACH OTHER.
 HOW CAN FLOORS 15 AND 16 BE CONSIDERED A SINGLE ZONE
 WHEN THE SEQUENCE ALSO STATES THAT THE 15TH AND 16TH
 FLOORS ARE TO BE INDEPENDENTLY PRESSURIZED DEPENDING ON
 THE FLOOR OF INCIDENT? IN ORDER FOR FLOORS 15 AND 16 TO
 BE CONSIDERED A SINGLE ZONE, BOTH FLOORS WOULD HAVE TO
 BE PRESSURIZED OR EXHAUSTED AS ONE FLOOR (OR ZONE). IF
 FLOORS 15 AND 16 ARE TO BE CONTROLLED INDEPENDENTLY,
 PROVIDE A SEQUENCE WHICH INCLUDES THE CONTROL OF ALL
 FIRE/SMOKE DAMPERS THAT MAY ALLOW THE FLOORS TO
 COMMUNICATE WITH EACH OTHER VIA THE MONUMENTAL STAIR
 AREA. THIS SYSTEM SHALL BE INCORPORATED INTO THE BASE
 BUILDING SMOKE CONTROL SYSTEM AND BE INCLUDED IN THE
 BASE BUILDING RATIONAL ANALYSIS AS WELL AS THE BASE
 BUILDING SEQUENCE OF OPERATIONS.
  
 B. SUPPLEMENTAL EXHAUST AND SUPPLY FANS, IF PART OF THE
 SMOKE CONTROL SYSTEM, SHALL ALSO BE CONTROLLED BY THE
 BASE BUILDING SYSTEM. RELATED FIRE/SMOKE DAMPERS ARE
 ALSO REQUIRED TO BE CONTROLLED BY THE BASE BUILDING
 SMOKE CONTROL SYSTEM PER FBC,M 513.5.2.
  
 C. NEW EF 15 IS SHOWN ON ROOF, BUT NEW SUPPLY FAN IS
 NOT SHOWN. THE NOTE STATES THAT THE EF AND SF ARE BASE
 BUILDING SUPPLIED. BASE BUILDING REVISED PAGE H1.17
 DATED 8/29/07 DOES NOT SHOW EITHER FAN. THE LOCATIONS
 FOR THESE FANS AS SHOWN ON M2.2 AND M3.1 OF THIS PLAN
 ARE IN CONFLICT WITH BASE BUILDING PLANS. SHOW LOCATIN
 OF FANS ON PLAN IN LOCATIONS WHICH ARE NOT IN CONFLICT
 WITH BASE BUILDING EQUIPMENT AND DEMONSTRATE COMPLIANCE
 WITH FBC,M 401.5.1 AND 501.2.
  
 NOTE: ALL WORK RELATED TO THIS APPLICATION REQUIRES
 APPROVAL BY BASE BUILDING DESIGNER(S) OF RECORD AND MAY
 BE DEMONSTRATED VIA SIGNED SHOP DRAWING REVIEW STAMP
 FROM SAME.
  
 ONE SET OF OLD/VOIDED SHEETS ALONG WITH ONE SET OF NEW
 PLANS ALONG WITH CALCULATIONS HAVE BEEN RETAINED BY
 THIS OFFICE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-25 Cont ID  
Sent By rregueir Date 2007-04-25 Time 13:21 Rev Time 0.00
Received By rregueir Date 2007-04-23 Time 17:35 Sent To  
Notes
2007-04-25 09:26:22--------------DENIED------------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS
 FBC CH 1 AS AMENDED BY THE CITY OF WEST PALM BEACH NFPA
 90A-02
  
 1. M2.1 NOTE #9: NOTE CALLS FOR 12X12 EXHAUST DUCT,
 PLAN SHOWS 10X10 DUCT FROM SHAFT TO LUNCH ROOM. PLEASE
 COORDINATE NOTES AND PLANS. FBC 106.1.1
  
 2. M2.1 NOTE #9: FIRE AND SMOKE DAMPERS ARE REQUIRED
 WHERE EF 9 DUCT PENETRATES RATED SHAFT ON 15TH AND 16TH
 FLOORS. FBC,M 607.5.5.1
  
 3. M2.1: WHAT IS THE PURPOSE OF THE TWO RAFD'S IN THE
 WALL BETWEEN ROOMS 1542 AND 1544? THIS WALL IS SHOWN ON
 SHEET I-15.C AS A TYPE "B" WHICH IS NON-RATED AND ONLY
 EXTENDS 6" ABOVE THE CEILING. PLEASE CLARIFY AND
 COORDINATE WITH ARCHITECTURAL PLANS.
  
 4. I-15.C: VARIOUS WALL TYPES SHOW DRYWALL STOPPING 6"
 ABOVE CEILING WITH INSULATION CONTINUING TO UNDERSIDE
 OF DECK. THIS CONDITION WOULD RESTRICT THE FREE FLOW O
 RETURN AIR BACK TO AIR HANDLING EQUIPMENT, PREVENTING
 BALANCED RETURN AS REQUIRED BY FBC,M 601.4. ALSO, TOPS
 OF OPEN WALL CAVITIES EXPOSED TO PLENUM AREA SHALL BE
 SEALED BY AN APPROVED AIR BARRIER PER FBC,M 603.8.
  
 5. M2.1: VAV 15-10 SHOWS 700 CFM ON FLOOR PLAN, BUT
 SCHEDULE ON M6.1 SHOWS 1250 CFM REQUIRED. WHICH IS
 CORRECT? PLEASE CLARIFY. FBC 106.1.1
  
 6. AHU 1,2 AND RTU 1,2: PLEASE SHOW MEANS AND LOCATION
 OF CONDENSATE DISPOSAL ALONG WITH MEANS OF AUXILIARY
 DRAIN PROTECTION. FBC,M 307.1 THROUGH 307.4.
 NOTE: A/C CONDENSATE SHALL NOT DISCHARGE INTO CITY
 WASTE WATER PIPING PER MUNICIPAL CODE SEC 90-125(B)(5)
  
 7. PLEASE PROVIDE INSTALLATION/HANGING DETAIL FOR AHU 1
 & 2.
  
 8. M2.1 KEY NOTE #5: NO DETAIL COULD BE FOUND REGARDING
 OFFSET OF RATED WALLS ABOVE CEILING FOR FIRE DAMPERS.
 THE FIRE DAMPERS IN QUESTION APPEAR TO BE QUITE DISTANT
 FROM THE LOCATION OF THE RATED WALLS.
  
 9. M2.1: FIRE DAMPER IS NOT SHOWN IN 54X12 DUCT PASSING
 THROUGH RATED WALL BETWEEN ROOM 1551 AND 1553. PLEASE
 SHOW MEANS OF COMPLIANCE WITH FBC,M 607.5.
  
 10. M2.2: FIRE DAMPERS ARE SHOWN TO BE INSTALLED IN
 NON-RATED PARTITIONS BASED ON WALL TYPES AS SHOWN ON
 SHEET I-16.C. SOME FIRE DAMPER ARE SHOWN WHERE NO
 PARTITION OF ANY KIND EXISTS ON ARCHITECTURAL PLANS,
 SUCH AS THE RAFD IN LOBBY 1601. PLEASE COORDINATE
 ARCHITECTURAL AND MECHANICAL PLANS BY DETERMINING WHERE
 FIRE-RATED PARTITIONS ARE TO BE LOCATED (WHETHER
 REQUIRED BY CODE OR DESIGN) AND SHOW FIRE DAMPERS TO BE
 AT THE APPROPRIATE LOCATIONS AS NEEDED. A COMPLETE
 REVIEW IS NOT POSSIBLE AT THIS TIME AND WILL BE
 COMPLETED ONCE THESE DISCREPANCIES ARE ADDRESSED.
  
 11. M2.2 KEY NOTE #6: NO SECTION DETAIL COULD BE
 LOCATED RELATED TO SUPPLY PLENUMS OR DIFFUSERS IN THIS
 AREA.
  
 12. M2.1 AND 2.2 ELEVATOR LOBBIES: PLEASE INDICATE ON
 ARCHITECTURAL PLANS WHICH WALL TYPE IS TO BE USED AT
 LOBBY DOORS TO ENSURE PROPER RETURN AIR FLOW FROM LOBBY
 CEILINGS.
 NOTE: BUILDING CAVITIES USED AS RETURN AIR PLENUMS
 SHALL BE LINED WITH A CONTINUOUS AIR BARRIER MADE OF
 DURABLE NON-POROUS MATERIALS PER FBC,M 603.8. APPROVED
 AIR BARRIERS ARE TO BE AS DEFINED BY FBC,M 603.9.1.
 THIS APPLIES TO ALL CONCRETE BLOCK WALLS AND EXTERIOR
 WALLS EXCEPT THOSE BETWEEN THE MECHANICAL ROOM AND THE
 CONDITIONED SPACE.
  
 13. M2.2 VAV 16-12: 12X10 BRANCH DUCT TAP IS SHOWN IN A
 DIRECTION CONTRARY TO AIRFLOW. PLEASE CORRECT. FBC,M
 603.3
  
 14. M2.2 VAV 16-13: SCHEDULE CALLS FOR REQUIRED 1400
 CFM SUPPLY. FLOOR PLAN SHOWS 1350 CFM. WHICH IS
 CORRECT?
  
 15. M2.2 EF-10: EXHAUST DUCTS UNDER POSITIVE PRESSURE
 SHALL NOT PASS THROUGH DUCTS OR PLENUMS PER FBC,M
 601.3.
  
 16. M2.2 VAV 16-17: SCHEDULE CALLS FOR REQUIRED 1950
 CFM SUPPLY. FLOOR PLAN SHOWS 2000 CFM SUPPLY. WHICH IS
 CORRECT?
  
 17. M2.2: RETURN AIR INTAKE ON SOUTH SIDE OF MECHANICAL
 ROOM SHOWS TWO DUCT SMOKE DETECTORS. ARE BOTH TO BE
 INSTALLED? PLEASE CLARIFY. FBC 106.1.1
  
 18. M0.1 NOTE #23: NO INFORMATION REGARDING WIND LOADS
 FOR OUTDOOR EQUIPMENT COULD BE FOUND FROM ARCHITECT OR
 STRUCTURAL ENGINEER.
  
 19. 15TH AND 16TH FLOOR CEILING AREA TO BE USED AS
 RETURN AIR PLENUMS. PLEASE VERIFY THAT EXISTING ROOF IS
 INSULATED TO MIN. R-19 AND EXTERIOR WALL SECTIONS
 EXPOSED TO PLENUM ARE INSULATED PER FBC TABLE
 13-410.1.ABC.2.2 IN ACCORDANCE WITH FBC,M 603.8.
  
 20. ENERGY CALCULATIONS:
 A) CALCULATIONS APPEAR TO BE FOR ONLY THE 16TH FLOOR.
 PLEASE ADJUST TO INCLUDE CALCULATIONS FOR ENTIRE
 PROJECT.
 B) SCHEDULE ON M6.2 SHOWS 2500 CFM OUTDOOR AIR PER
 FLOOR. ENERGY CALCS FOR 16TH FL ONLY SHOWS 2040. PLEASE
 ADJUST CALCULATIONS TO SHOW ACTUAL VALUE.
 C) AIR SYSTEM SIZING: PAC-16 IS A CHILLED WATER AHU OR
 A WATER COOLED PACKAGE UNIT? PLEASE CONFIRM WITH
 EXISTING BUILDING CONDITIONS
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 12 Status P Date 2008-09-10 Cont ID  
Sent By kstevens Date 2008-09-10 Time 17:45 Rev Time 0.00
Received By kstevens Date 2008-09-10 Time 17:45 Sent To  
Notes
2008-09-10 17:45:54REVISION OK -- SHT P3.2.

Review Stop P PLUMBING
Rev No 11 Status F Date 2008-08-18 Cont ID  
Sent By kstevens Date 2008-08-18 Time 07:55 Rev Time 0.00
Received By kstevens Date 2008-08-18 Time 07:54 Sent To  
Notes
2008-08-18 08:00:58DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 1. SHT P3.2 SHOWS CHANGES TO PREVIOUSLY REVIEWED AND
 STAMPED REVISIONS NOT CLOUDED NOR INDICATED AS A CHANGE
 WITH A REVISION NUMBER. PLANS SHOW A WILKINS MODEL 700
 BACKFLOW PREVENTOR. IF INSTALLING AN RPZV BACKFLOW, IT
 SHALL BE LOCATED MAXIMUM 4 FEET ABOVE THE FLOOR FOR
 SERVICING AND CERTIFICATION.ALL CHANGES/REVISIONS TO
 A SHEET SHALL BE INDICATED WITH CLOUDS AND REVISIONS
 NUMBERS. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 10 Status P Date 2008-08-18 Cont ID  
Sent By kstevens Date 2008-08-18 Time 07:54 Rev Time 0.00
Received By kstevens Date 2008-08-15 Time 16:55 Sent To  
Notes
2008-08-18 07:54:55REVISIONS OK--SHTS P0.1, P2.2, P51 & P61

Review Stop P PLUMBING
Rev No 9 Status F Date 2008-07-07 Cont ID  
Sent By kstevens Date 2008-07-07 Time 13:48 Rev Time 0.00
Received By kstevens Date 2008-07-07 Time 13:48 Sent To  
Notes
2008-07-07 13:56:53REVISIONS DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P2.1 REVISION NUMBER 7 NOT FOUND ON THE FLOOR
 PLAN. PLEASE CLARIFY. SECTION 106.1.3.--(NOTE:
 PLEASE TURN OFF THE CLOUDS AND REVISION NUMBERS FROM
 PREVIOUSLY APPROVED REVISIONS TO THE PLANS TO HELP
 EXPEDITE THE PLAN REVIEW OF REVISIONS).
  
 2. SHT P2.2 REVISION NUMBER 11 AT THE FOUNTAIN WAS
 PREVIOUSLY SHOWN AS REVISION NUMBER 7 AND THERE ARE NO
 APPARENT CHANGES. PLEASE CLARIFY. SECTION 106.1.3.--
 FLOOR DRAINS ARE NOT APPROVED INDIRECT WASTE RECEPTORS.
 SECTIONS 802.3 & 802.3.2. THE ICE MACHINE SHALL DRAIN
 TO A FLOOR SINK OR A HUB DRAIN.--(NOTE: PLEASE
 TURN OFF THE CLOUDS AND REVISION NUMBERS FROM
 PREVIOUSLY APPROVED REVISIONS TO THE PLANS TO HELP
 EXPEDITE THE PLAN REVIEW OF REVISIONS).
  
 3. SHT P51 THE WATER FEATURE REVISION 11 IN THE LOWER
 LEFT RISER DIAGRAM WAS PREVIOUSLY SHOWN AS REVISION
 NUMBER 7 AND THERE ARE NO APPARENT CHANGES. PLEASE
 CLARIFY. SECTION 106.1.3.--NO NEW REVISION WAS
 INDICATED TO REFLECT THE REVISION SHOWN ON SHT P2.1.
 PLEASE SUBMIT A REVISION TO THE PROPER RISER DIAGRAM TO
 REFLECT THE CHANGE INDICATED ON SHT P2.1. SECTION
 106.3.5.1.3.--(NOTE: PLEASE TURN OFF THE CLOUDS AND
 REVISION NUMBERS FROM PREVIOUSLY APPROVED REVISIONS TO
 THE PLANS TO HELP EXPEDITE THE PLAN REVIEW OF
 REVISIONS).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop P PLUMBING
Rev No 8 Status F Date 2008-06-03 Cont ID  
Sent By kstevens Date 2008-06-03 Time 08:13 Rev Time 0.00
Received By kstevens Date 2008-06-03 Time 08:12 Sent To  
Notes
2008-06-03 08:20:22DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P3.2 REVISION NUMBER HAS NOT CHANGED FROM
 PREVIOUS REVISION. REVISION NUMBER 7 WAS SUBMITTED
 PREVIOUSLY AND APPROVED ON APRIL 3 2008. EACH
 SUBSEQUENT REVISION SHALL HAVE ITS OWN REVISION NUMBER.
 SECTION 106.1.3.
  
 2. A REVISION IS REQUIRED FOR THE WATER ISOMETRIC RISER
 DIAGRAM THAT REFLECTS THE CHANGES SUBMITTED THIS
 REVISION. PLEASE SUBMIT REQUIRED REVISION. SECTION
 106.3.5.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 7 Status P Date 2008-06-03 Cont ID  
Sent By kstevens Date 2008-06-03 Time 08:11 Rev Time 0.00
Received By kstevens Date 2008-06-02 Time 15:47 Sent To  
Notes
2008-06-03 08:12:45REVISION OK - - SHT P3.1.

Review Stop P PLUMBING
Rev No 6 Status P Date 2008-04-28 Cont ID  
Sent By kstevens Date 2008-04-28 Time 11:04 Rev Time 0.00
Received By kstevens Date 2008-04-28 Time 11:04 Sent To  
Notes
2008-04-28 11:05:11REVISION OK--SHTS P2.2 & P51

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-04-03 Cont ID  
Sent By kstevens Date 2008-04-03 Time 09:48 Rev Time 0.00
Received By kstevens Date 2008-04-03 Time 09:48 Sent To  
Notes
2008-04-03 09:49:34REVISION OK--SHTS P2.2, P3.2, P51 & P61 REVISION #7

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-02-05 Cont ID  
Sent By kstevens Date 2008-02-05 Time 11:33 Rev Time 0.00
Received By kstevens Date 2008-02-05 Time 11:33 Sent To  
Notes
2008-02-05 11:36:23PASSED/PROVISO--30"X48" CLEAR FLOOR SPACES ARE
 REQUIRED AT THE BAR SINKS ON THE 16TH FLOOR SHT 1-16.C

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-11-30 Cont ID  
Sent By kstevens Date 2007-11-30 Time 18:00 Rev Time 0.00
Received By kstevens Date 2007-11-30 Time 07:44 Sent To  
Notes
2007-11-30 07:44:23DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEWS:
  
 1. OK
  
 2. SHT 1-16.C PER TABLE 403.1 3 DRINKING FOUNTAINS ARE
 REQUIRED. PLEASE INDICATE THE LOCATION OF EACH DRINKING
 FOUNTAIN.
 ****RESPONSE NOTED, BUT ON THE 16TH FLOOR PLAN, ONE
 DRINKING FOUNTAIN HAS SANITARY, BUT NO WATER SUPPLY &
 ONE DRINKING FOUNTAIN SHOWS NO SANITARY OR WATER
 SUPPLY. WATER AND DRAINAGE ARE REQUIRED AT EACH
 FIXTURE. SECTIOND 301.3 & 301.4.
 ******NO RESPONSE, BUT THE DRINKING FOUNTAIN IN ROOM
 1633 STILL SHOWS NO WATER SUPPLY. SEE SHEET P3.2.
  
 3. SHT 1-16.C BATHROOM (1608) SHALL BE ACCESSIBLE OR
 ADAPTABLE PER SECTIONS 11-4.22 OR 11-4.1.3(11). PLEASE
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19 & 11-4.21 WITH ALL SUBSECTIONS IF
 BATHROOM IS TO BE ACCESSIBLE. SUBMIT A DETAIL SHOWING
 ALL BACKING FOR GRAB BARS FOR THE W/C & SHOWER, SPACING
 FOR THE W/C, (MIN. 33" WITH THE W/C BEING 18" OFF THE
 WALL AND MIN. 15" OFF THE SHOWER), A TURNING AREA IN
 THE BATHROOM, THE VALVE LOCATION FOR THE SHOWER, AND A
 CURB DETAIL OF THE SHOWER, (MAX 1/2").
 ****NO RESPONSE, NOT ADDRESSED.
 ******NO RESPONSE, AND NO DETAIL HAS BEEN SUBMITTED
 SHOWING THE BACKING REQUIRED FOR THE GRAB BARS FOR THE
 W/C AND SHOWER.
  
 4. SHT 1-16.C THE SINKS IN ROOMS 1613, 1628, 1633, 1643
 & 1674 SHALL BE ACCESSIBLE. PLEASE SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.
 ****NO RESPONSE, NOT ADDRESSED.
 ******NO RESPONSE, BUT THE CLEAR FLOOR SPACE SHALL BE
 SHOWN ON THE FLOOR PLAN FOR EACH SINK. THE FLOOR PLAN
 FOR THE 16TH FLOOR DOES NOT SHOW THE BAR SINKS
 INDICATED ON THE PLUMBING SHEETS. PLEASE CORRELATE THE
 INFORMATION ON THE ARCHITECTUAL SHEETS AND THE PLUMBING
 SHEETS. SHEET 1-PA-2 DETAILS 1&2 ONLY SHOW A 24"
 OPENING UNDER THE SINKS WHERE 30" CLEAR FLOOR SPACE IS
 REQUIRED. SECTIONS 106.1.1 & 11-4.24.5.
  
 5. OK NO WATER OR DRAIN INDICATED AT MEETING WITH
 REPRESENTATIVES OF THE DESIGN TEAM.
 6. OK
 7. OK
  
 8. SUBMIT DETAILS FOR THE MEN'S & WOMEN'S TOILET ROOMS
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.17,
 11-4.18, 11-4.19 & 11-4.22 WITH ALL SUBSECTIONS. ****NO
 RESPONSE, NOT ADDRESSED.--THIS SHALL APPLY FOR THE
 NEW TOILET ROOMS ADDED TO EACH FLOOR ALSO. ******NO
 RESPONSE, BUT DETAILS FOR ROOMS 1672, 1673, 1584 & 1585
 WERE NOT SUBMITTED. THESE TOILET ROOMS SHALL BE
 ACCESSIBLE.
  
 9. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING
 FOUNTAINS. SHOW COMPLIANCE WITH SECTION 11-4.15 WILL
 ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 ****NO RESPONSE, NOT ADDRESSED.
 ******NO RESPONSE. SHOW THE CLEAR FLOOR SPACE FOR ALL
 ACCESSIBLE DRINKING FOUNTAINS. MINIMUM 50% OF THE
 DRINKING FOUNTAINS SHALL BE ACCESSIBLE AND ONLY ONE IS
 INDICATED ACCESSIBLE ON EACH FLOOR.
  
 10. OK
 11. OK
  
 12. SHT 1-15.C THE SINK IN ROOM 1520SHALL BE
 ACCESSIBLE. PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
 ****NO RESPONSE, NOT ADDRESSED.
 ******NO RESPONSE, NOT ADDRESSED.
  
 13. OK (NEW ENGINEER)
 14. OK
 15. OK
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
 28. OK
  
 29. SHT P51 THERMAL EXPANSION CONTROL IS REQUIRED FOR
 THE WATER HEATERS ON THE 15TH & 16TH FLOORS. PLEASE
 INDICATE THE METHOD OF CONTROL. SECTION 607.3.2.
 ****RESPONSE NOTED, BUT CALCULATIONS SHALL BE PROVIDED
 SHOWING THE CORRECT SIZE REQUIRED FOR 130 GALLONS,
 (TOTAL OF BOTH WATER HEATERS). SEE ATTACHED SHEET FOR
 AN EXAMPLE OF CALCULATIONS. INDICATE MANUF. AND MODEL
 WHEN SUMBITTING CALCULATIONS.
 ******NO RESPONSE, NOT ADDRESSED.
  
 30. OK
 31. OK
  
 ***********NEW COMMENTS***********
  
 1B. OK
  
 2B. SHT P61 DELETE THE CHECK VALVES FROM THE WATER
 RISER DIAGRAMS WHERE THE TOILET ROOMS 1573/1581 &
 1663/1665 CONNECT TO THE WATER RISER OR ANY OTHER
 LOCATION ON THE RISER DIAGRAM. CHECK VALVES ARE NOT
 APPROVED FOR BACKFLOW PREVENTION. TABLE 608.1. ******NO
 RESPONSE, BUT THE CHECK VALVES WERE CHANGED TO VACUUM
 BREAKERS. THIS IS NOT THE CORRECT APPLICATION FOR
 VACUUM BREAKERS AND ARE NOT APPROVED. PLEASE DELETE
 FROM THE FLOOR PLAN AND THE RISER DIAGRAM.
  
 3B. SHT P0.1 DETAIL FOR THE PLATFORM MOUNTED WATER
 HEATERS. THE 80 GALLON EWH-2 WILL HAVE A TOTAL WEIGHT
 APPROX. 850 LBS. PLEASE SUBMIT INFORMATION ON THE
 SUPPORT FOR THE PLATFORM ATTACHMENT TO THE WALL. WILL
 THE STUDS BEHIND THE WALL BE STRUCTURAL STUDS OR
 DRYWALL STUDS. PLEASE INDICATE THE GUAGE OF THE STUDS
 AND THE SIZE OF THE BLOCKING THAT THE PLATFORM ANGLE
 BRACKETS WILL ATTACH TO. THIS INFORMATION SHOULD BE
 SUBMITTED BY THE STRUCTURAL ENGINEER. SECTION 106.1.2.
 ******NO RESPONSE, AND THE SECTION OF THE COMMENT ABOUT
 THE STUDS HAS NOT BEEN ADDRESSED.
  
 *****NEW COMMENTS 3RD REVIEW*****
  
 1C. SHT 1-16.C JANITOR MOP SINK IS IN FRONT OF THE DOOR
 TO EXIT JANITOR ROOM 1662. PLEASE CLARIFY. SECTION
 106.1.1.
  
 2C. SHT 1-E.5 DETAILS 5, 4, 3 & 2 TOILET ROOMS TO BE
 ACCESSIBLE. PLEASE DELETE THE NOTE REFERING TO
 ADAPTABILITY. SECTION 11-4.1.3(11). PLEASE SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTIONS 11-4.16,
 11-4.19 & 11-4.22 WITH ALL SUBSECTIONS.
  
 3C. SHT 1-PA.2 DETAIL 5 NOTE "ADA SINK SECTION FOR ALL
 PANTRIES" SHALL INCLUDE THE COFFEE ROOMS AND THE
 EMPLOYEE LOUNGE OR SEPARATE DETAILS WILL BE REQUIRED TO
 SHOW COMPLIANCE WITH SECTION 11-4.24. PLEASE INDICATE
 IN NOTE.
  
 4C. SHT 1-PA.2 DETAILS 1 & 2 SHOWS THE CLEAR FLOOR
 SPACE FOR THE SINK AT 24" WIDE. 30" WIDTH CLEAR FLOOR
 SPACE REQUIRED. SECTION 11-4.24.5.
  
 5C. SHT P0.1 HORIZONTAL DRAINAGE PIPE CHART DOES NOT
 SHOW THE SLOPE. PLEASE INDICATE THE SLOPE PER TABLE
 704.1.
  
 6C. SHTS P2.2 & P3.2 ROOM 1628 DOES NOT SHOW THE BAR
 SINK, BUT IS SHOWN ON THE SANITARY AND WATER ISOMETRIC
 RISER DIAGRAMS. PLEASE CLARIFY. SECTION 106.1.1.
  
 7C. SHT P61 CHECK VALVES HAVE BEEN CHANGED TO VACUUM
 BREAKERS AT THE SUPPLY TO THE TENANT SPACE. VACUUM
 BREAKERS ARE NOT DESIGNED FOR THIS APPLICATION. PLEASE
 DELETE. THE ONLY REQUIREMENT IS A FULL OPEN VALVE PER
 SECTION 606.1(5).
  
 8C. SHT P61 THE WATER LINES DO NOT REFLECT THE FLOOR
 PLANS WHERE THEY HAVE BEEN EXTENDED PAST AND AROUND THE
 "IT" ROOM. PLEASE CORRELATE THE FLOOR PLAN PIPING AND
 THE RISER DIAGRAM PIPING.
  
 9C. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL AND FS 553.80(2)(B).
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL
 VOID SHEETS FROM ALL PLANS AND PLACE ONE SET
 OF THEM LOOSELY ON TOP OF THE COLLATED PLANS
 TO BE REVIEWED. THANK YOU FOR YOU
 ANTICIPATED COOPERATION.
 ******NO RESPONSE, NOT ADDRESSED
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-09-12 Cont ID  
Sent By kstevens Date 2007-09-12 Time 17:07 Rev Time 0.00
Received By kstevens Date 2007-09-10 Time 11:11 Sent To  
Notes
2007-09-12 17:59:50DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. ALL SHEETS. THE BUSINESS NUMBER FOR "YJ
 ARCHITECTURAL DESIGN" IS REQUIRED IN THE TITLE BLOCK.
 FAC 61G1-16.004(2) & FS 481.219, 481.2055.
 ****NO RESPONSE, NOT ADDRESSED. THE FLORIDA STATE DBPR
 FIRM LICENSE NUMBER IS REQUIRED.
  
 2. SHT 1-16.C PER TABLE 403.1 3 DRINKING FOUNTAINS ARE
 REQUIRED. PLEASE INDICATE THE LOCATION OF EACH DRINKING
 FOUNTAIN.
 ****RESPONSE NOTED, BUT ON THE 16TH FLOOR PLAN, ONE
 DRINKING FOUNTAIN HAS SANITARY, BUT NO WATER SUPPLY &
 ONE DRINKING FOUNTAIN SHOWS NO SANITARY OR WATER
 SUPPLY. WATER AND DRAINAGE ARE REQUIRED AT EACH
 FIXTURE. SECTIOND 301.3 & 301.4.
  
 3. SHT 1-16.C BATHROOM (1608) SHALL BE ACCESSIBLE OR
 ADAPTABLE PER SECTIONS 11-4.22 OR 11-4.1.3(11). PLEASE
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19 & 11-4.21 WITH ALL SUBSECTIONS IF
 BATHROOM IS TO BE ACCESSIBLE. SUBMIT A DETAIL SHOWING
 ALL BACKING FOR GRAB BARS FOR THE W/C & SHOWER, SPACING
 FOR THE W/C, (MIN. 33" WITH THE W/C BEING 18" OFF THE
 WALL AND MIN. 15" OFF THE SHOWER), A TURNING AREA IN
 THE BATHROOM, THE VALVE LOCATION FOR THE SHOWER, AND A
 CURB DETAIL OF THE SHOWER, (MAX 1/2").
 ****NO RESPONSE, NOT ADDRESSED.
  
 4. SHT 1-16.C THE SINKS IN ROOMS 1613, 1628, 1633, 1643
 & 1656 SHALL BE ACCESSIBLE. PLEASE SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.
 ****NO RESPONSE, NOT ADDRESSED.
  
 5. SHT 1-16.C MORE INFORMATION IS REQUIRED FOR THE
 PLANTERS. PLEASE INDICATE IF THE PLANTERS WILL HAVE
 WATER SUPPLY OR DRAINAGE CONNECTED TO THEM. SECTION
 106.1.2. IF SO THE DRAINAGE PIPING & SUPPLY PIPING
 SHALL BE SHOWN ON THE FLOOR PLANS AND ON THE RISER
 DIAGRAMS. SECTION 106.3.5.1.3.
 ****NO RESPONSE, NOT ADDRESSED.
  
 6. OK
  
 7. SHT 1-16.C ROOMS 1613 & 1628. PLEASE INDICATE THE
 FIXTURE TYPE, (BS), IN EACH ROOM. SECTION 106.1.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 8. SUBMIT DETAILS FOR THE MEN'S & WOMEN'S TOILET ROOMS
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.17,
 11-4.18, 11-4.19 & 11-4.22 WITH ALL SUBSECTIONS. ****NO
 RESPONSE, NOT ADDRESSED.--THIS SHALL APPLY FOR THE
 NEW TOILET ROOMS ADDED TO EACH FLOOR ALSO.
  
 9. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING
 FOUNTAINS. SHOW COMPLIANCE WITH SECTION 11-4.15 WILL
 ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 ****NO RESPONSE, NOT ADDRESSED.
  
 10. OK
 11. OK
  
 12. SHT 1-15.C THE SINK IN ROOM 1520SHALL BE
 ACCESSIBLE. PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
 ****NO RESPONSE, NOT ADDRESSED.
  
 13. SHT S-1 SHALL BE SEALED WITH AN EMBOSSED OR
 IMPRESSION TYPE SEAL. NAIM & ASSOCIATES SHALL INDICATE
 THEIR BUSINESS NUMBER, (CERTIFICATE OF AUTHORIZATION),
 IN THE TITLE BLOCK. A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID DOCUMENTS
 PROVIDED TO THE OWNER OR THE OWNER'S REPRESENTATIVE, OR
 OTHER DOCUMENTS PREPARED OR ISSUED BY SAID REGISTRANT
 AND BEING FILED FOR PUBLIC RECORD. THE DATE THAT THE
 SIGNATURE AND SEAL IS AFFIXED AS PROVIDED HEREIN SHALL
 BE ENTERED ON SAID PLANS, SPECIFICATIONS, REPORTS, OR
 OTHER DOCUMENTS IMMEDIATELY UNDER THE SIGNATURE OF THE
 PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1) FS 471.025. ENGINEERS
 SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS AND LICENSE
 NUMBER ON EACH SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGINEERS, ENGINEERS
 SHALL LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER,
 AS WELL AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS ON
 EACH SHEET. A TITLE BLOCK WILL SATISFY THIS
 REQUIREMENT. (THE CERTIFICATE OF AUTHORIZATION IS NOT
 INDICATED IN THE TITLE BLOCK).FAC 61G15-23.002(2) -
 FS 471.025.--PLANS APPEAR TO BE SIGNED WITH
 INITIALS. INITIALS ARE NOT APPROVED, THE LEGAL
 SIGNATURE IS REQUIRED. IF INDEED THIS IS THE LEGAL
 SIGNATURE, A SIGNED, SEALED, NOTORIZED LETTER SHALL BE
 SUBMITTED INDICATING THE LEGAL SIGNATURE FOR OUR
 FILES.
 ****NO RESPONSE, NOT ADDRESSED. --NEW SHEET S-2 SHALL
 MEET THE SAME REQUIREMENTS. S-2 NOT SIGNED, SEALED,
 DATED ETC.
  
 14. OK
 15. OK
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
  
 21. SHT P2.2 NOTE INDICATES PLUMBING FIXTURE SCHEDULE
 PROVIDED BY THE ARCHITECT. NO FIXTURE SCHEDULE HAS BEEN
 LOCATED, AND NOTHING TO INDICATED WHAT FIXTURE "BS"
 REPRESENTS.( SEE ROOMS 1613 & 1628).PLEASE INDICATE
 WHERE THE FIXTURE SCHEDULE CAN BE FOUND. SECTION
 106.1.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 22. OK
  
 23. SHT P3.1 PLEASE INDICATE WHAT THE COLD WATER LINE
 TO ROOM 1544 CONNECTS TO. PER SECTION 608, BACKFLOW
 PROTECTION MAY BE REQUIRED.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. NO
 INDICATION AS TO WHAT THE COLD WATER LINE CONNECTS TO.
 ALSO NO DRAIN SHOWN. PLEASE CLARIFY. SECTION 106.1.1.
  
 24. OK
  
 25. SHT P3.2 BACKFLOW PREVENTION IS REQUIRED ON THE
 COLD WATER SUPPLY TO THE WATER WALL. PLEASE INDICATE
 METHOD. SECTION 608.
 ****RESPONSE NOTED, BUT CHECK VALVES ARE NOT APPROVED.
 SEE TABLE 608.1.--A VACUUM BREAKER INSTALLED AT THE
 HIGHEST POINT OF THE SUPPLY LINE TO THE WATER WALL IS
 REQUIRED. (A WATTS MODEL N-36 OR EQUAL IS REQUIRED).
  
 26. OK
 27. OK
 28. OK
  
 29. SHT P51 THERMAL EXPANSION CONTROL IS REQUIRED FOR
 THE WATER HEATERS ON THE 15TH & 16TH FLOORS. PLEASE
 INDICATE THE METHOD OF CONTROL. SECTION 607.3.2.
 ****RESPONSE NOTED, BUT CALCULATIONS SHALL BE PROVIDED
 SHOWING THE CORRECT SIZE REQUIRED FOR 130 GALLONS,
 (TOTAL OF BOTH WATER HEATERS). SEE ATTACHED SHEET FOR
 AN EXAMPLE OF CALCULATIONS. INDICATE MANUF. AND MODEL
 WHEN SUMBITTING CALCULATIONS.
  
 30. OK
 31. OK
  
 ***********NEW COMMENTS***********
  
 1B. SHT P61 UPON REVIEW OF THE WATER RISER DIAGRAM FOR
 THE 15TH FLOOR, POTABLE WATER IS SHOWN TO A/C UNITS.
 THIS IS NOT APPROVED. PLEASE CLARIFY THE USE FOR THE
 WATER TO AN A/C UNIT SECTION 106.1.1.--PER 2003
 NFPA-75 SECTION 5.2* & A.5.2 WATER SHOULD NOT BE IN THE
 SPACE ABOVE THE SUSPENDED CEILING AND OVER INFORMATION
 TECHNOLOGY EQUIPMENT OTHE THAN FOR SPRINKLER SYSTEM
 USE.
  
 2B. SHT P61 DELETE THE CHECK VALVES FROM THE WATER
 RISER DIAGRAMS WHERE THE TOILET ROOMS 1573/1581 &
 1663/1665 CONNECT TO THE WATER RISER OR ANY OTHER
 LOCATION ON THE RISER DIAGRAM. CHECK VALVES ARE NOT
 APPROVED FOR BACKFLOW PREVENTION. TABLE 608.1.
  
 3B. SHT P0.1 DETAIL FOR THE PLATFORM MOUNTED WATER
 HEATERS. THE 80 GALLON EWH-2 WILL HAVE A TOTAL WEIGHT
 APPROX. 850 LBS. PLEASE SUBMIT INFORMATION ON THE
 SUPPORT FOR THE PLATFORM ATTACHMENT TO THE WALL. WILL
 THE STUDS BEHIND THE WALL BE STRUCTURAL STUDS OR
 DRYWALL STUDS. PLEASE INDICATE THE GUAGE OF THE STUDS
 AND THE SIZE OF THE BLOCKING THAT THE PLATFORM ANGLE
 BRACKETS WILL ATTACH TO. THIS INFORMATION SHOULD BE
 SUBMITTED BY THE STRUCTURAL ENGINEER. SECTION 106.1.2.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-05-14 Cont ID  
Sent By kstevens Date 2007-05-14 Time 09:48 Rev Time 0.00
Received By kstevens Date 2007-05-10 Time 14:12 Sent To  
Notes
2007-05-14 11:38:30DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS. THE BUSINESS NUMBER FOR "YJ
 ARCHITECTURAL DESIGN" IS REQUIRED IN THE TITLE BLOCK.
 FAC 61G1-16.004(2) & FS 481.219, 481.2055.
  
 2. SHT 1-16.C PER TABLE 403.1 3 DRINKING FOUNTAINS ARE
 REQUIRED. PLEASE INDICATE THE LOCATION OF EACH DRINKING
 FOUNTAIN.
  
 3. SHT 1-16.C BATHROOM (1608) SHALL BE ACCESSIBLE OR
 ADAPTABLE PER SECTIONS 11-4.22 OR 11-4.1.3(11). PLEASE
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.19 & 11-4.21 WITH ALL SUBSECTIONS IF
 BATHROOM IS TO BE ACCESSIBLE. SUBMIT A DETAIL SHOWING
 ALL BACKING FOR GRAB BARS FOR THE W/C & SHOWER, SPACING
 FOR THE W/C, (MIN. 33" WITH THE W/C BEING 18" OFF THE
 WALL AND MIN. 15" OFF THE SHOWER), A TURNING AREA IN
 THE BATHROOM, THE VALVE LOCATION FOR THE SHOWER, AND A
 CURB DETAIL OF THE SHOWER, (MAX 1/2").
  
 4. SHT 1-16.C THE SINKS IN ROOMS 1613, 1628, 1633, 1643
 & 1656 SHALL BE ACCESSIBLE. PLEASE SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.
  
 5. SHT 1-16.C MORE INFORMATION IS REQUIRED FOR THE
 PLANTERS. PLEASE INDICATE IF THE PLANTERS WILL HAVE
 WATER SUPPLY OR DRAINAGE CONNECTED TO THEM. SECTION
 106.1.2. IF SO THE DRAINAGE PIPING & SUPPLY PIPING
 SHALL BE SHOWN ON THE FLOOR PLANS AND ON THE RISER
 DIAGRAMS. SECTION 106.3.5.1.3.
  
 6. SHT1-16.C PER TABLES 1004.1.2 AND 403.1 4 WATER
 CLOSETS ARE REQUIRED FOR BOTH THE MEN'S AND WOMEN'S
 TOILET ROOMS.
  
 7. SHT 1-16.C ROOMS 1613 & 1628. PLEASE INDICATE THE
 FIXTURE TYPE, (BS), IN EACH ROOM. SECTION 106.1.2.
  
 8. SUBMIT DETAILS FOR THE MEN'S & WOMEN'S TOILET ROOMS
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.17,
 11-4.18, 11-4.19 & 11-4.22 WITH ALL SUBSECTIONS.
  
 9. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING
 FOUNTAINS. SHOW COMPLIANCE WITH SECTION 11-4.15 WILL
 ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
  
 10. SHT 1-15.C PER TABLE 403.1 3 DRINKING FOUNTAINS ARE
 REQUIRED. PLEASE INDICATE THE LOCATION OF EACH DRINKING
 FOUNTAIN.
  
 11. SHT 1-15.C PER TABLES 1004.1.2 AND 403.1 4 WATER
 CLOSETS ARE REQUIRED FOR BOTH THE MEN'S AND WOMEN'S
 TOILET ROOMS.
  
 12. SHT 1-15.C THE SINK IN ROOM 1520SHALL BE
 ACCESSIBLE. PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
  
 13. SHT S-1 SHALL BE SEALED WITH AN EMBOSSED OR
 IMPRESSION TYPE SEAL. NAIM & ASSOCIATES SHALL INDICATE
 THEIR BUSINESS NUMBER, (CERTIFICATE OF AUTHORIZATION),
 IN THE TITLE BLOCK. A PROFESSIONAL ENGINEER SHALL SIGN
 HIS NAME AND AFFIX HIS SEAL TO ALL PLANS,
 SPECIFICATIONS, REPORTS AND FINAL BID DOCUMENTS
 PROVIDED TO THE OWNER OR THE OWNER'S REPRESENTATIVE, OR
 OTHER DOCUMENTS PREPARED OR ISSUED BY SAID REGISTRANT
 AND BEING FILED FOR PUBLIC RECORD. THE DATE THAT THE
 SIGNATURE AND SEAL IS AFFIXED AS PROVIDED HEREIN SHALL
 BE ENTERED ON SAID PLANS, SPECIFICATIONS, REPORTS, OR
 OTHER DOCUMENTS IMMEDIATELY UNDER THE SIGNATURE OF THE
 PROFESSIONAL
 ENGINEER, FAC 61G15-23.002(1) FS 471.025. ENGINEERS
 SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS AND LICENSE
 NUMBER ON EACH SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGINEERS, ENGINEERS
 SHALL LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER,
 AS WELL AS, THE NAME, ADDRESS AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING BUSINESS ON
 EACH SHEET. A TITLE BLOCK WILL SATISFY THIS
 REQUIREMENT. (THE CERTIFICATE OF AUTHORIZATION IS NOT
 INDICATED IN THE TITLE BLOCK).FAC 61G15-23.002(2) -
 FS 471.025.--PLANS APPEAR TO BE SIGNED WITH
 INITIALS. INITIALS ARE NOT APPROVED, THE LEGAL
 SIGNATURE IS REQUIRED. IF INDEED THIS IS THE LEGAL
 SIGNATURE, A SIGNED, SEALED, NOTORIZED LETTER SHALL BE
 SUBMITTED INDICATING THE LEGAL SIGNATURE FOR OUR
 FILES.
  
 14. SHT P2.1 SOME ROOM NUMBERS ON THE PLUMBING SHEETS
 DO NOT REFLECT THE ROOM NUMBERS ON THE ARCHITECTURAL
 SHEETS. (EXAMPLE - 1565(P)/1576(A), 1568(P)/1538(A),
 1538(P)/1539(A) ETC). PLEASE CORRELATE THE INFORMATION
 ON THE PLUMBING SHEETS WITH THE INFORMATION ON THE
 ARCHITECTURAL SHEETS. SECTION 106.1.1.
  
 15. SHT P2.1 PLEASE INDICATE THE USE OF THE FLOOR DRAIN
 IN ROOM 31565(P). PLEASE INDICATE WHAT WILL BE DRAINING
 INTO THE FLOOR DRAIN. SECTION 106.1.2.
  
 16. SHT P2.1 LAVS ARE REQUIRED IN THE ACCESSIBLE STALLS
 OF THE MEN'S AND WOMEN'S TOILET ROOMS. FIGURE 11-30E.
  
 17. SHT P2.1 INDICATE THE LOCATION OF THE 3 REQUIRED
 DRINKING FOUNTAINS. SECTION 106.1.2 & TABLE 403.1.
  
 18. SHT P2.2 PLAN INDICATED AT THE 18TH FLOOR. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 19. SHT P2.2 STUDOR VENTS ARE NOT APPROVED FOR THE
 PUMPS AT THE SINKS IN ROOMS 1613, 1628, 1633 & 1650,
 (SHOWN AS ROOM # 1643 ON SHT 1-16.C). SECTION 917.2.
  
 20. SHT P2.2 LAVS ARE REQUIRED IN THE ACCESSIBLE STALLS
 FOR THE MEN'S & WOMEN'S TOILET ROOMS. FIGURE 30E.
  
 21. SHT P2.2 NOTE INDICATES PLUMBING FIXTURE SCHEDULE
 PROVIDED BY THE ARCHITECT. NO FIXTURE SCHEDULE HAS BEEN
 LOCATED, AND NOTHING TO INDICATED WHAT FIXTURE "BS"
 REPRESENTS.( SEE ROOMS 1613 & 1628).PLEASE INDICATE
 WHERE THE FIXTURE SCHEDULE CAN BE FOUND. SECTION
 106.1.2.
  
 22. SHT P3.1 LAVS ARE REQUIRED IN THE ACCESSIBLE STALLS
 FOR THE MEN'S & WOMEN'S TOILET ROOMS. FIGURE 30E.
  
 23. SHT P3.1 PLEASE INDICATE WHAT THE COLD WATER LINE
 TO ROOM 1544 CONNECTS TO. PER SECTION 608, BACKFLOW
 PROTECTION MAY BE REQUIRED.
  
 24. SHT P3.2 PLAN INDICATED AT THE 18TH FLOOR. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 25. SHT P3.2 BACKFLOW PREVENTION IS REQUIRED ON THE
 COLD WATER SUPPLY TO THE WATER WALL. PLEASE INDICATE
 METHOD. SECTION 608.
  
 26. SHT P3.2 LAVS ARE REQUIRED IN THE ACCESSIBLE STALLS
 FOR THE MEN'S & WOMEN'S TOILET ROOMS. FIGURE 30E.
  
 27. SHT P51 DOMESTIC WATER ISOMETRIC RISER DIAGRAM. THE
 WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURE IN AN "EFFECTIVE RANGE" NOT IN THE CEILING AS
 SHOWN IN SOME AREAS. PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.--A WATER HAMMER ARRESTOR IS REQUIRED
 FOR THE ICE MAKER BY THE WATER HEATER ON THE 16TH
 FLOOR. SECTION 604.9.
  
 28. SHT P51 LAVS ARE REQUIRED IN THE ACCESSIBLE STALLS
 FOR THE MEN'S & WOMEN'S TOILET ROOMS. FIGURE 30E.
 PLEASE SHOW LAVS ON THE FLOOR PLAN AND SHOW PIPING ON
 THE ISOMETRICS. SECTION 106.1.2.
  
 29. SHT P51 THERMAL EXPANSION CONTROL IS REQUIRED FOR
 THE WATER HEATERS ON THE 15TH & 16TH FLOORS. PLEASE
 INDICATE THE METHOD OF CONTROL. SECTION 607.3.2.
  
 30. SHT P51 DOMESTIC WATER ISOMETRIC RISER DIAGRAM 16TH
 FLOOR DOES NOT REFLECT THE FLOOR PLAN BY THE MOP
 SINK/WATER HEATER & TO THE REF. IN ROOM 1633. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 31. SHT P51 16TH FLOOR SANITARY ISOMETRIC RISER DIAGRAM
 SHOWS STUDOR VENTS (AAV'S) AT THE PUMPS FOR THE KITCHEN
 SINKS AND AT THE "BS" FIXTURES. THESE ARE NOT APPROVED
 PER SECTION 917.2. THESE PUMP VENTS SHALL BE CONNECTED
 TO THE VENT SYSTEMS.--TRAPS ARE REQUIRED FOR ALL
 THE KITCHEN SINKS AND "BS" FIXTURES. SECTION 1002.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]