Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-08-22 Cont ID  
Sent By btrobaug Date 2007-08-22 Time 18:16 Rev Time 0.00
Received By btrobaug Date 2007-08-22 Time 18:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-07-24 Cont ID  
Sent By btrobaug Date 2007-07-24 Time 10:18 Rev Time 0.00
Received By btrobaug Date 2007-07-24 Time 08:37 Sent To PC
Notes
2007-07-24 10:18:28 
  
  
  
 DENIED
  
 THE DESCRIPTION ON THE APPLICATION IS FOR A SERVICE
 RELOCATION, THERE ARE PLANS SUBMITTED FOR REWIRING THE
 UNIT(S).REMOVE PLANS THAT ARE NOT PERTINENT TO THE
 APPLICATION DESCRIPTION. IF THE UNITS ARE TO BE
 REWIRED, CHANGE THE DESCRIPTION AND INCREASE THE VALUE.
 THE CONTRACTOR OF RECORD MUST MAKE ALL CHANGES RELATING
 TO THESE DOCUMENTS.
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERKS DESK, AND PAY THE
 DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 THERE WILL BE NO REVIEW DONE FOR THE UNITS UNTILL THEY
 ARE PART OF THE DESCRIPTION OF WORK AND THE VALUE IS
 ADJUSTED TO REFLECT THE SAME.
  
 2} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE PER 215.5, SEE METER TO DISCONNECTS.
  
 3} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED.
  
 4} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.66. INDICATE THE SIZE ON THE RISER.
  
 5}PROVIDE A PANEL SCHEDULE PER 408.4. INCLUDE OCP AND
 CONDUCTOR SIZES. PLEASE SEE NEW VERBAGE FOR 2005 NEC:
 "THE IDENTIFICATION SHALL INCLUDE SUFFICIENT DETAIL TO
 ALLOW EACH CIRCUIT TO BE DISTINGUISHED FROM ALL
 OTHERS." ONE MUST BE SUBMITTED FOR BOTH UNITS IF BEING
 REWIRED.
  
 6} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 7}A GROUNDING ELECTRODE CONDUCTOR IS REQUIRED AT THE
 SEPARATE STRUCTURE PER 250.32, SIZED PER 250.66. SHOW
 ALL EQUIPMENT ON THE RISER.
  
 8} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE
 PLANS PER 106.1.1 FBC AS AMENDED.
  
 9} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW PER 106.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-28 Cont ID  
Sent By btrobaug Date 2007-06-28 Time 15:50 Rev Time 0.00
Received By btrobaug Date 2007-06-28 Time 15:21 Sent To PC
Notes
2007-06-28 15:31:19 
  
 DENIED
  
 THE DESCRIPTION ON THE APPLICATION IS FOR A SERVICE
 RELOCATION., THERE ARE PLANS SUBMITTED FOR REWIRING THE
 UNIT(S).RMOVE PLANS THAT ARE NOT PERTINENT TO THE
 APPLICATION DESCRIPTION.
  
 SAME COMMENT AS PREVIOUS REVIEW
 1} PLEASE SUBMIT A SITE PLAN INDICATING THE LOCATION OF
 THE METER, MAIN DISCONNECT {WITH AIC RATING} ON THE
 RESIDENCE.215.5 NEC.
  
 NEW COMMENTS
 2} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE PER 215.5,LOAD CALCULATIONS PER 220,
 SERVICE EQUIPMENT AND PANEL LOCATIONS PER 106.3.5.4
 FBC..
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-04-03 Cont ID  
Sent By btrobaug Date 2007-04-03 Time 15:48 Rev Time 0.50
Received By btrobaug Date 2007-04-02 Time 07:44 Sent To I
Notes
2007-04-02 07:48:26 
  
  
 DENIED/INCOMPLETE INFORMATION
  
 THE SCOPE OF WORK ON THE APPLICATION REQUIRES AN
 ELECTRICAL CONTRACTOR APPLY FOR A PERMIT. THE OWNER IS
 A LISTED AS A CORPORATION, AND NOT ELIGIBLE FOR AN
 OWNER/BUILDER PERMIT PER CHAPTER 489, PART I FS.
  
 PLEASE SUBMIT A SITE PLAN INDICATING THE LOCATION OF
 THE METER, MAIN DISCONNECT {WITH AIC RATING} ON THE
 RESIDENCE.215.5 NEC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-09 Cont ID  
Sent By btrobaug Date 2007-08-09 Time 08:51 Rev Time 0.00
Received By btrobaug Date 2007-08-09 Time 08:51 Sent To E
Notes
2007-08-09 08:52:18TO ME./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-18 Cont ID  
Sent By adarroug Date 2007-07-18 Time 16:15 Rev Time 0.00
Received By adarroug Date 2007-07-18 Time 16:15 Sent To E
Notes
2007-07-18 16:15:35TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-20 Cont ID  
Sent By adarroug Date 2007-06-20 Time 14:43 Rev Time 0.00
Received By adarroug Date 2007-06-20 Time 14:43 Sent To E
Notes
2007-06-20 14:43:45TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-03 Cont ID  
Sent By btrobaug Date 2007-04-03 Time 15:48 Rev Time 0.00
Received By btrobaug Date 2007-03-26 Time 18:15 Sent To PC
Notes
2007-03-26 18:16:03TO ELEC BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved