| 2007-07-24 10:18:28 | |
| | |
| | |
| | |
| | DENIED |
| | |
| | THE DESCRIPTION ON THE APPLICATION IS FOR A SERVICE |
| | RELOCATION, THERE ARE PLANS SUBMITTED FOR REWIRING THE |
| | UNIT(S).REMOVE PLANS THAT ARE NOT PERTINENT TO THE |
| | APPLICATION DESCRIPTION. IF THE UNITS ARE TO BE |
| | REWIRED, CHANGE THE DESCRIPTION AND INCREASE THE VALUE. |
| | THE CONTRACTOR OF RECORD MUST MAKE ALL CHANGES RELATING |
| | TO THESE DOCUMENTS. |
| | |
| | 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL |
| | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY |
| | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS |
| | AMENDED. |
| | |
| | A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED |
| | UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID. |
| | 108.1 FBC. |
| | |
| | ADJUST THE VALUE AT THE PERMIT CLERKS DESK, AND PAY THE |
| | DIFFERENCE IN FEES PRIOR TO RESUBMITTING. |
| | |
| | THERE WILL BE NO REVIEW DONE FOR THE UNITS UNTILL THEY |
| | ARE PART OF THE DESCRIPTION OF WORK AND THE VALUE IS |
| | ADJUSTED TO REFLECT THE SAME. |
| | |
| | 2} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT |
| | SIZE AND TYPE PER 215.5, SEE METER TO DISCONNECTS. |
| | |
| | 3} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, |
| | STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. |
| | |
| | 4} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH |
| | 250.66. INDICATE THE SIZE ON THE RISER. |
| | |
| | 5}PROVIDE A PANEL SCHEDULE PER 408.4. INCLUDE OCP AND |
| | CONDUCTOR SIZES. PLEASE SEE NEW VERBAGE FOR 2005 NEC: |
| | "THE IDENTIFICATION SHALL INCLUDE SUFFICIENT DETAIL TO |
| | ALLOW EACH CIRCUIT TO BE DISTINGUISHED FROM ALL |
| | OTHERS." ONE MUST BE SUBMITTED FOR BOTH UNITS IF BEING |
| | REWIRED. |
| | |
| | 6} PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 7}A GROUNDING ELECTRODE CONDUCTOR IS REQUIRED AT THE |
| | SEPARATE STRUCTURE PER 250.32, SIZED PER 250.66. SHOW |
| | ALL EQUIPMENT ON THE RISER. |
| | |
| | 8} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE |
| | PLANS PER 106.1.1 FBC AS AMENDED. |
| | |
| | 9} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR |
| | REVIEW PER 106.1 FBC AS AMENDED. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |