| Plan Review Stops For Permit 07030902 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2007-12-26 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2007-12-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2007-12-26 |
Time |
12:47 |
Sent To |
|
|
| Notes |
| 2007-12-26 12:49:31 | THE PLANS DO NOT SHOW THE "TEMPORARY WOODEN STAGE" THAT | | | IS BEING USED FROM TIME TO TIME FOR THE PAST YEAR. | | | | | | PLEASE PROVIDE CONSTRUCTION DETAILS AND DESIGN LOADS | | | INCLUDING THE MEANS OF HANDICAP ACCESSIBILITY, (FBC | | | 11-4.33.5) FOR THE "TEMPORARY STAGE" DECLARED ON THE | | | PERMIT APPLICATION.SEE FBC 106.1. | | | | | | PROVIDE BETTER DETAILS FOR THE CANOPY AND DEMONSTRATE | | | COMPLIANCE WITH THE WIND RESISTANCE REQUIREMENTS OF FBC | | | 1609.1 AND 3105. | | | | | | PROVIDE COMPLETE DETAILS FOR THE ELECTRICAL | | | INSTALLATION.FBC 106.1 | | | | | | RE: ENGINEER GORDON BUCK'S INSPECTION OF THE | | | FOUNDATION.THE LETTER DOES NO DISCLOSE THE DEPTH, | | | WIDTH AND HEIGHT OF THE INSTALLED FOOTINGS WAS | | | INVESTIGATED.IT IS SILENT ON ASCERTAINING SOIL | | | BEARING CAPACITY.IT DOES NOT SPEAK TO THE | | | INSTALLATION OF THE ANCHOR BOLTS.PLEASE INCLUDE THAT | | | INFORMATION WITH YOUR INSPECTION REPORT. | | | | | | HAROLD H PISKURA | | | (561) 805-6711 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2008-01-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-11-28 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-11-28 |
Time |
11:01 |
Sent To |
PC |
|
| Notes |
| 2008-01-04 15:08:42 | BUILDING PLAN REVIEW | | | PERMIT: 07030902 | | | ADD: 700 S. ROSEMARY AVE. | | | CONT: VENTURA | | | TEL: (561)856-6655 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 3RD | | | ACTION: DENIED | | | | | | 1)THE FOUNDATION REQUIREMENTS ARE OK, HOWEVER, THE | | | SIGN, SEAL AND DATED ENGINEERED DRAWINGS FOR THE CANOPY | | | IS REQUIRED SHOWING HOW THE REQUIREMENTS OF FBC SECTION | | | 3105 AND 1609 WILL BE ACHIEVED IN REGUARD TO ANCHORAGE | | | AGAINST OVERTURNING, UPLIFT AND SLIDING. | | | | | | 2)FBC 11-4.33.5 ACCESS TO PERFORMING AREAS. | | | PROVIDE VERIFICATION THAT THE PORTABLE RAMP | | | APPROVED FOR THE EXISTING STAGE WILL WORK FOR THE | | | INCREASED HEIGHT OF THE NEW TEMPORARY WOODEN STAGE. THE | | | ACCESSIBILITY RAMP MUST BE IN PLACE AT THE TIME OF | | | INSPECTION. | | | | | | 11.4.8.5. HANDRAILS: IF A RAMP HAS A RISE GREATER THAN | | | 6" OR A HORIZONTAL PROJECTION GREATER THAN 72", THEN IT | | | SHALL HAVE HANDRAILS ON BOTH SIDES. | | | | | | 11-4.8.2 SLOPE & RISE. THE LEAST POSSIBLE SLOPE SHALL | | | BE USED FOR ANY RAMP. THE MAXIMUM SLOPE FOR A RAMP IN | | | NEW CONSTRUCTION SHALL BE 1 TO 12. THE MAXIMUM RISE FOR | | | RUN SHALL BE 30" (SEE FIGURE 16). FOR MORE INFORMATION | | | SEE FBC 11-4.8 | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-07-20 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-07-20 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-07-19 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2007-07-20 11:27:33 | BUILDING PLAN REVIEW | | | PERMIT:07030902 | | | ADD: 700 S.ROSEMARY AVE. | | | CONT: VENTURA CONSTRUCTION | | | TEL: (561)856-6655 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 2ND | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | NO RESPONSE*****NOT ADDRESSED FROM PREVIOUS REVIEW. | | | | | | 2)61G1-16.004 TITLE BLOCK. | | | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR | | | INTERIOR DESIGN DRAWINGS AND SPECIFICATION | | | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A | | | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | | (2) FIRM LICENSE NUMBER. | | | (3) NAME OR IDENTIFICATION OF PROJECT. | | | (4) DATE PREPARED. | | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING | | | THE DOCUMENT. | | | | | | 3)471.023 (2)FOR THE PURPOSES OF THIS SECTION, A | | | CERTIFICATE OF AUTHORIZATION SHALL BE REQUIRED FOR ANY | | | BUSINESS ORGANIZATION OR OTHER PERSON PRACTICING UNDER | | | A FICTITIOUS NAME, OFFERING ENGINEERING SERVICES TO THE | | | PUBLIC. HOWEVER, WHEN AN INDIVIDUAL IS PRACTICING | | | ENGINEERING IN HIS OR HER OWN GIVEN NAME, HE OR SHE | | | SHALL NOT BE REQUIRED TO BE LICENSED UNDER THIS | | | SECTION. | | | | | | 4)61G15-23.002 (2)ENGINEERS SHALL LEGIBLY INDICATE | | | THEIR NAME, ADDRESS, AND LICENSE MUMBER ON EACH SHEET. | | | IF PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING | | | BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME | | | AND LICENSE NUMBER, AS WESS AS, THE NAME, ADDRESS, AND | | | CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING | | | BUSINESS ON EACH SHEET. ETC. | | | | | | NEW***** | | | | | | 5) 110.2* W. P. B. ADMINISTRATIVE | | | CODE, INFORMATION THAT IS REQUIRED FOR | | | RECORD KEEPING | | | A) THE EDITION OFTHE CODE UNDER WHICH | | | THE PROJECT IS DESIGNED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601. | | | D) THE OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED | | | | | | . ------------------------------------- | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-04-16 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-04-16 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-16 |
Time |
11:23 |
Sent To |
PC |
|
| Notes |
| 2007-04-16 15:25:25 | BUILDING PLAN REVIEW | | | PERMIT:07030902 | | | ADD: 700 S.ROSEMARY AVE. | | | CONT: VENTURA CONSTRUCTION | | | TEL: (561) | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW 1ST | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)61G1-16.004 TITLE BLOCK. | | | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR | | | INTERIOR DESIGN DRAWINGS AND SPECIFICATION | | | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A | | | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | | (2) FIRM LICENSE NUMBER. | | | (3) NAME OR IDENTIFICATION OF PROJECT. | | | (4) DATE PREPARED. | | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING | | | THE DOCUMENT. | | | | | | 3)471.023 (2)FOR THE PURPOSES OF THIS SECTION, A | | | CERTIFICATE OF AUTHORIZATION SHALL BE REQUIRED FOR ANY | | | BUSINESS ORGANIZATION OR OTHER PERSON PRACTICING UNDER | | | A FICTITIOUS NAME, OFFERING ENGINEERING SERVICES TO THE | | | PUBLIC. HOWEVER, WHEN AN INDIVIDUAL IS PRACTICING | | | ENGINEERING IN HIS OR HER OWN GIVEN NAME, HE OR SHE | | | SHALL NOT BE REQUIRED TO BE LICENSED UNDER THIS | | | SECTION. | | | | | | 4)61G15-23.002 (2)ENGINEERS SHALL LEGIBLY INDICATE | | | THEIR NAME, ADDRESS, AND LICENSE MUMBER ON EACH SHEET. | | | IF PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING | | | BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME | | | AND LICENSE NUMBER, AS WESS AS, THE NAME, ADDRESS, AND | | | CERTIFICATE OF AUTHORIZATION NUMBER OF THE ENGINEERING | | | BUSINESS ON EACH SHEET. ETC. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-12-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-19 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-19 |
Time |
16:31 |
Sent To |
Z |
|
| Notes |
| 2007-12-19 16:31:46 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-10-11 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-11 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-11 |
Time |
15:32 |
Sent To |
Z |
|
| Notes |
| 2007-10-11 15:32:26 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-07-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-16 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-16 |
Time |
09:15 |
Sent To |
Z |
|
| Notes |
| 2007-07-16 09:15:56 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-04-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-10 |
Time |
13:18 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-10 |
Time |
13:18 |
Sent To |
B |
|
| Notes |
| 2007-04-10 13:18:25 | TO "MISC" BOX#2 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2007-04-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
dpolen |
Date |
2007-03-27 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2007-03-27 15:30:53 | PLACED IN ZONING BOX |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2007-12-20 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2007-12-20 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2007-12-20 |
Time |
15:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2007-10-11 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2007-10-11 |
Time |
18:33 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2007-10-11 |
Time |
18:33 |
Sent To |
I |
|
| Notes |
| 2007-10-11 18:34:20 | FAILED | | | | | | APPROVAL OF A MINOR PD AMENDMENT IS REQUIRED FOR THE | | | MODIFICATIONS TO THE PLAZA FOR THE STAGE, INCLUDING THE | | | STAGE COVER AND RELATED FEATURES. (REPEAT COMMENT). | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-07-18 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2007-07-18 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2007-07-18 |
Time |
12:55 |
Sent To |
I |
|
| Notes |
| 2007-07-18 13:00:12 | FAILED | | | | | | APPROVAL OF A MINOR PD AMENDMENT IS REQUIRED FOR THE | | | MODIFICATIONS TO THE PLAZA FOR THE STAGE, INCLUDING THE | | | STAGE COVER AND RELATED FEATURES. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-04-10 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2007-04-10 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2007-04-10 |
Time |
10:53 |
Sent To |
I |
|
| Notes |
| 2007-04-10 10:57:35 | FAILED | | | | | | 1) A MINOR AMENDMENT IS REQUIRED FOR THE MODIFICATIONS | | | TO THE PLAZA.THE MINOR AMEDMENT APPLICATION IS | | | AVAILABLE FROM THE PLANNING AND ZONING DEPARTMENT. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. |
|
|