Plan Review Details - Permit 07030892
Plan Review Stops For Permit 07030892
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-18 Cont ID  
Sent By shill Date 2007-06-18 Time 13:31 Rev Time 0.00
Received By shill Date 2007-06-18 Time 13:31 Sent To HIST
Notes
2007-06-18 13:35:49****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.)PROVIDE A PLAN SHOWING THE LOCATION OF ALL WORK.
  
 2ND REVIEW - DOORS ARE NOT SHOWN ON THE FLOOR PLAN.
 SHOW LOCATIONS.
  
 2.)NON IMPACT PRODUCT APPROVALS WERE SUBMITTED.
 IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2.IF LESS THAN 25% OF THE TOTAL GLAZED AREA
 IS BEING REPLACED, PROVIDE CALCULATIONS FBC EB507.3.
  
 2ND REVIEW - NOT ADDRESSED.NOT ENOUGH INFORMATION WAS
 PROVIDED TO DETERMINE CODE COMPLIANCE.
  
 3.)PROVIDE A DESCRIPTION OF THE EXISTING DOOR (AMOUNT
 OF GLAZING).
  
 4.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72, WWW.FLORIDABUILDING.ORG
  
 5.)ADDRESSED.
  
 6.)PROVIDE PRODUCT APPROVAL ONLY FOR THE DOORS YOU
 ARE INSTALLING.IF MORE THAN ONE TYPE IS BEING
 INSTALLED, SHOW ON THE FLOOR PLAN AND PROVIDE PRODUCT
 APPROVAL FOR EACH.
  
 2ND REVIEW - NOT ADDRESSED.SUBMIT ONLY PRODUCT
 APPROVALS FOR THE DOORS YOU ARE INSTALLING.PRODUCT
 APPROVALS ARE TO BE ON STANDARD OFFICE PAPER (WERE
 SUBMITTED ON NEWSPRINT PAPER, WHICH IS DIFFICULT TO
 SCAN).
  
 NEW COMMENT -
  
 7.)A DECK WAS ADDED TO THE SCOPE OF WORK.SUBMIT A
 SITE PLAN SHOWING THE IMPROVEMENT.PROVIDE STRUCTURAL
 DETAILS, INCLUDING STAIR DIMENSIONS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-31 Cont ID  
Sent By shill Date 2007-03-31 Time 12:03 Rev Time 0.00
Received By shill Date 2007-03-31 Time 12:03 Sent To  
Notes
2007-03-31 12:05:23****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PROVIDE A PLAN SHOWING THE LOCATION OF ALL WORK.
  
 2.)NON IMPACT PRODUCT APPROVALS WERE SUBMITTED.
 IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2.IF LESS THAN 25% OF THE TOTAL GLAZED AREA
 IS BEING REPLACED, PROVIDE CALCULATIONS FBC EB507.3.
  
 3.)PROVIDE A DESCRIPTION OF THE EXISTING DOOR (AMOUNT
 OF GLAZING).
  
 4.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72, WWW.FLORIDABUILDING.ORG
  
 5.)ARE THE CABINETS BEING INSTALLED SAME SIZE, SAME
 LOCATION?IF NOT, PROVIDE A PLAN (EXISTING DEMO AND
 PROPOSED NEW).
  
 6.)PROVIDE PRODUCT APPROVAL ONLY FOR THE DOORS YOU
 ARE INSTALLING.IF MORE THAN ONE TYPE IS BEING
 INSTALLED, SHOW ON THE FLOOR PLAN AND PROVIDE PRODUCT
 APPROVAL FOR EACH.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-03-26 Cont ID  
Sent By swurafti Date 2007-03-26 Time 12:26 Rev Time 0.00
Received By swurafti Date 2007-03-26 Time 12:25 Sent To  
Notes
2007-03-26 12:26:20HISTORIC APPROVED BY GJUDGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-14 Cont ID  
Sent By adarroug Date 2007-05-14 Time 09:53 Rev Time 0.00
Received By adarroug Date 2007-05-14 Time 09:53 Sent To B
Notes
2007-05-14 09:53:33TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-01 Cont ID  
Sent By shill Date 2007-03-31 Time 14:06 Rev Time 0.00
Received By shill Date 2007-03-26 Time 18:21 Sent To  
Notes
2007-03-26 18:21:54SENT TO MISC BOX#1 MMILLER

Review Stop Z ZONING
Rev No 1 Status F Date 2007-06-19 Cont ID  
Sent By choops Date 2007-06-19 Time 16:48 Rev Time 0.00
Received By choops Date 2007-06-19 Time 16:48 Sent To  
Notes
2007-06-19 16:51:01***FAILED***
  
  
 1)SCOPE OF WORK HAS BEEN CHANGED ON ORIGINAL PERMIT
 APPLICATION FROM WHAT HISTORIC PRESERVATION ORIGINALLY
 APPROVED.MUST OBTAIN HISTORIC PRESERVATION APPROVAL.
  
 2)DOOR SCHEMATICS INCONSISTANT.
  
  
 CHRIS HOOPS
 ZONING TECHNICIAN
 561-805-6720