Plan Review Details - Permit 07030885
Plan Review Stops For Permit 07030885
Review Stop AD ADDRESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2007-05-23 Cont ID  
Sent By lursu Date 2007-05-23 Time 13:39 Rev Time 0.00
Received By lursu Date 2007-05-23 Time 13:39 Sent To  
Notes
2007-05-23 13:41:44THE APPLICANT'S REPRESENTATIVE CLARIFIED , ON MAY 22,
 THAT THE JOB LOCATION IS ATUNIT 206 - PHYSICIANS
 WEIGHT LOSS -UNDER THE ADDRESS OF 8983 OKEECHOBEE
 BLVD # 206 .PLEASE REVISE SITE PLANS AND APPLICATIONS
 WITH THE CORRECT SITE ADDRESS.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-04-11 Cont ID  
Sent By lursu Date 2007-04-11 Time 16:11 Rev Time 0.00
Received By lursu Date 2007-04-11 Time 10:39 Sent To  
Notes
2007-04-11 16:11:12SITE ADDRESS USED ON THE APPLICATION IS 8989 OKEECHOBEE
 BLVD # 206 .THIS SITE ADDRESS IS USED FOR THE ENTIRE
 PLAZA AS THE MAIN ADDRESS , HOWEVER THREE BUILDINGS
 HAVING THREE UNIQUE ADDRESSES ARE LOCATED ON THIS
 PARCEL WITH PCN = 74424320080030000.THEY ARE 8955
 OKEECHOBEE BLVD ,8983 OKEECHOBEE BLVDAND 8993
 OKEECHOBEE BLVD .PLEASE CLARIFY IN WHICH OF THESE
 BUILDINGS UNIT 206 IS LOCATED.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-06-16 Cont ID  
Sent By mjacobs Date 2007-06-16 Time 07:01 Rev Time 0.00
Received By mjacobs Date 2007-06-16 Time 06:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-05-29 Cont ID  
Sent By mjacobs Date 2007-05-29 Time 06:44 Rev Time 0.00
Received By mjacobs Date 2007-05-25 Time 14:21 Sent To PC
Notes
2007-05-25 16:57:29BUILDING PLAN REVIEW
 PERMIT:07030885
 ADD:8989
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)THE VALUE IS LOW. IF IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR
 PLUMBING SYSSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED, FOR PERMITTING
 PURPOSES, INCLUDE THE TOTAL VALUE OF THE PROJECT
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*.
  
 3) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-31 Cont ID  
Sent By mjacobs Date 2007-03-31 Time 10:40 Rev Time 0.00
Received By mjacobs Date 2007-03-31 Time 06:53 Sent To  
Notes
2007-03-31 10:40:01BUILDING PLAN REVIEW
 PERMIT: 07030885
 ADD: 8989 OKEECHOBEE BLVD
 CONT: KULKA CONST.
 TEL: (954)984-9293
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 OF THE BUILDING PERMIT.
 -------------------------------------
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
  
  
 3)SEE 2004 FLORIDA EXISTING BUILDING CODE CH,3 AND
 INDICATE THE TYPE OF ALTERATION BASE ON THE SCOPE OF
 WORK.
  
 4)THE VALUE IS LOW. IF IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF BUILDING ALTERATION,
 STRUCTURE,ELECTRICAL, GAS, MECHANICAL OR PLUMBING
 SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING
 PURPOSES, INCLUDE THE TOTAL VALUE OF THE PROJECT
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 5)FBC 11-7.2(2)COUNTERS THAT MAY NOT HAVE A CASH
 REGISTER BUT AT WHICH GOODS OR SERVICES ARE SOLD OR
 DISTRIBUTED EITHER (1) A PORTION OF THE MAIN COUNTER IS
 A MINIMUM OF 36 INCHES IN LENGTH AND A MAXIMUM HEIGHT
 OF 36 INCHES OR ONE OF THE OTHER OPTIONS MENTION IN
 THIS SECTION. SHOW THE ELEVATION DETAIL COMPLYING WITH
 THIS SECTION.
  
 6)THE PARTITION LEGEND ON SHEET A-1.0DOES NOT
 CORRESPOND WITHE THE FLOOR PLAN. THE LEGEND HAS WALL
 TYPES 1 AND 2. HOWEVER, THE FLOOR PLAN SHOWS WALL TYPES
 1 AND 1A. INCATE CLEARLY ON THE DRAWINGS WHERE WALL
 DETAIL #3 WILL BE CONSTRUCTED.
 FBC.106.1.1CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE CODE AND RELEVANT LAWS,ORDINANCES,
 RULES AND REGULATIONS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 7) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 8)WILL THE LOW WALLS BE ATTATCHED TO THE CEILING OR
 WILL THEY BE FREE STANDING?
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-06-08 Cont ID  
Sent By dpalmer Date 2007-06-08 Time 19:55 Rev Time 0.00
Received By dpalmer Date 2007-06-08 Time 19:01 Sent To  
Notes
2007-06-08 19:55:38** UNSAT 3RD REVIEW *
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS STILL
 NEED TO BE ADDRESSED. PLEASE SEE NEW COMMENTS BASED ON
 PLANS SUBMITTED.
  
 1) NOTE: PLEASE SEE COMPLIANCE WITH FBC 2004 CHAPTER
 13, 13-415.1.ABC.1.1, AND .1.2 HAS NOT BEEN MET.
 PLEASE SEE NO TIMES ON DEVICES AS NOTED.
 PLEASE SEE NO TIMES ON SYSTEM OR OVER RIDES AS TIMER
 TYPE OF SYSTEM IS BEING NOTED AND SHOWN.
 PLEASE SEE THAT A STRAIGHT 7-DAY DIGITAL TIMERS WITH
 OUT OVER RIDE CONTROLS AND AUTOMATED SHUT OFF AT
 SPECIFIC TIMES DOES NOT MEET CODE.
 PLEASE SEE SPACES FOR DEVICES.
 PLEASE SEE QUOTING ASHAE IN LIEU OF DETAIL FOR CODE
 COMPLIANCE CAN NOT BE ACCEPTED.
 PLEASE SEE THE CODES AS QUOTED FOR ASHAE, AS THE 2004
 FBC , W/2006 REVISIONS IS THE LATEST ADOPTED CODE.
  
 2) NOTE: PLEASE SEE CODES AS QUOTED. PLANS INDICATE THE
 2005 NFPA-72 (MISPRINT, SHOULD READ 2002).
 PLEASE SEE BOTH2002 AND 2005 NFPA-70 (NEC0 IS STATED
 ON PLANS.
 PLEASE ADJUST.
  
 3) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE AS NOTED ABOVE IN
 NOTE #1.
 PLEASE SEE THE FLORIDA STATUTES REQUIRES A 4X FEE
 ASSESSED FOR PLAN REVIEW WHEN CODE COMMENTS ARE
 REPEATED. THIS FEE IS 30% OF THE BASE PERMIT FEE OF THE
 PORTION ATTRIBUTED TO PLAN REVIEW. THIS 30% OF THE BASE
 FEE OF $760 IS $228 TIMES FOUR, WHICH IS $912.00 IS DUE
 BEFORE PLANS CAN BE RE-SUBMITTED FOR REVIEW.
 PLEASE SEE THAT THE PHONE NUMBER AND E-MAIL ADDRESS HAS
 BEEN ON PREVIOUS NOTES ON REVIEWS FOR QUESTIONS OR
 COMMENTS. IT IS RECOMMENDED THAT IF THERE ARE ANY
 QUESTIONS OR COMMENTS, TO PLEASE CALL TO GO OVER
 PLANS.
  
 ** ONCE AGAIN, IF THERE ARE ANY QUESTIONS, COMMENTS OR
 NOTES ARE NOT TYPED IN ANY MANOR WHICH IS UNCLEAR, TO
 PLEASE CONTACT THIS OFFICE/REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-05-07 Cont ID  
Sent By dpalmer Date 2007-05-07 Time 15:38 Rev Time 0.00
Received By dpalmer Date 2007-05-07 Time 15:07 Sent To  
Notes
2007-05-07 15:38:34* UNSAT 2ND REVIEW**
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED.
  
  
 1) NOTE: PLEASE SEE THE 2004 FBC W/ 2006 REVISION AS
 THE NEW LIGHTING CONTROLS SHALL BE 13-415.1.ABC.1.1,
 .1.2 AND .1.3.
 PLEASE INDICATE SCHEDULING FOR THE NEW SYSTEM WHICH IS
 BEING SHOWN.
 PLEASE SEE THE PANEL SCHEDULE INDICATES NOTES FOR SOME
 OCCUPANCY TYPE DEVICES, HOWEVER SYMBOL LEGEND DOES NOT
 CONTAIN INFORMATION FOR THIS.
 PLEASE SHOW THE LOCATION OF OVER RIDE DEVICE(S). PLEASE
 SEE THAT 13-415.1.ABC.1.1, AND .1.2 REQUIRES THE DEVICE
 TO BE LOCATED SO THAT THE OCCUPANT CAN SEE THE LIGHTING
 IN WHICH IS BEING OVER RIDDEN OR CONTROLLED.
 PLEASE SEE ROOMS AND AREAS WHICH CONTAIN FLOOR TO
 CEILING HEIGHT PARTITIONS IS REQUIRED TO CONTAIN AN
 OVER RIDE DEVICE OF SOME TYPE.
 PLEASE BE SURE ALL DEVICES CONTAIN/LIST THE MAXIMUM
 TIME PERMITTED ON OVER RIDE.(ALREADY INDICATED FOR MAIN
 OVER-RIDE).
 * PREVIOUS REVIEW NOTES **
 PLEASE SEE THIS IS REQUIRED EVEN IF THE LIGHTING
 FIXTURES ARE BEING SHOWN AS EXISTING NEW WALLS/BUILD
 OUT AND CONTROLS ARE BEING INSTALLED.
 PLEASE SEE THAT DEPENDING ON THE TYPE OF CONTROL
 DEVICES OR SYSTEM INSTALLED PLEASE INDICATE TIMES ON
 DEVICES OF TIMERS, OC SENSORS, TYPES ETC.
  
 2) NOTE: PLEASE SEE THE NOTES ON PREVIOUS REVIEW WHICH
 REQUESTED ALL OLD/VOIDED SHEETS TO BE REMOVED FROM SETS
 AND NEW REVISED SHEETS TO BE INSERTED INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. THIS WAS NOT DONE, NEW
 SHEETS WERE SUBMITTED LOOSELY.
  
 3) NOTE: PREVIOUS REVIEW REQUESTED NEW PERMIT
 APPLICATION AS NOTED. THIS WAS NOT SUBMITTED.
 PLEASE SUBMIT A NEW UPDATE PERMIT APPLICATION WHEN
 PLANS ARE RE-SUBMITTED . PLEASE SEE THE PERMIT
 APPLICATION SUBMITTED IS DATED FROM 2001. THIS HAS
 SINCE BEEN REVISED. A NEW BLANK PERMIT APPLICATION IS
 BEING ATTACHED TO NOTES AS WELL AS THIS CAN BE
 DOWNLOADED FROM OUR ONLINE WEBSITE.
 THIS IS REQUIRED.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-31 Cont ID  
Sent By dpalmer Date 2007-03-31 Time 17:31 Rev Time 0.00
Received By dpalmer Date 2007-03-31 Time 17:12 Sent To  
Notes
2007-03-31 17:31:57* UNSAT **
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE MISSING SIGN CIRCUIT PER 600.5,
 PLEASE INDICATE MINIMUM LOADS REQUIRED. ADJUST LOAD
 CALCULATIONS.
  
 3) NOTE: PLEASE ALSO SEE 210.62 FOR MISSING WINDOW
 RECEPTACLES LOADS PER 220.43. PLEASE SEE LOADS ARE
 BASED ON THE 200VA PER LINEAR FOOT.
 PLEASE ADJUST.
  
 4) NOTE: PLEASE SEE THE 2004 FBC W/ 2006 REVISION AS
 THE NEW LIGHTING CONTROLS SHALL BE 13-415.1.ABC.1.1,
 .1.2 AND .1.3.
 PLEASE SEE THIS IS REQUIRED EVEN IF THE LIGHTING
 FIXTURES ARE BEING SHOWN AS EXISTING NEW WALLS/BUILD
 OUT AND CONTROLS ARE BEING INSTALLED.
 PLEASE SEE THAT DEPENDING ON THE TYPE OF CONTROL
 DEVICESOR SYSTEM INSTALLED PLEASE INDICATE TIMES ON
 DEVICES OF TIMERS, OC SENSORS, TYPES ETC.
  
 5) NOTE: PLEASE SEE PLANS APPEAR TO SHOW THE EMERGENCY
 AND EXIT LIGHTS BEING WIRED PER 700.12E, HOWEVER THE
 PANEL SCHEDULE SHOWS THESE ON A DEDICATED CIRCUIT.
 PLEASE COORDINATE CIRCUITING AND PANEL SCHEDULE. FBC
 106.1.2
  
 6) NOTE: PLEASE SEE RISER SHOWS PANEL AS 150AMP AND THE
 PANEL SCHEDULE SHOWS THIS AS 200AMPS.
 PLEASE CORRELATE.
 FBC 106.1.2
  
 7) NOTE: PLEASE SUBMIT A NEW UPDATE PERMIT APPLICATION
 WHEN PLANS ARE RESUBMITTED . PLEASE SEE THE PERMIT
 APPLICATION SUBMITTED IS DATED FROM 2001. THIS HAS
 SINCE BEEN REVISED. A NEW BLANK PERMIT APPLICATION IS
 BEING ATTACHED TO NOTES AS WELL AS THIS CAN BE
 DOWNLOADED FROM OUR ONLINE WEBSITE.
 THIS IS REQUIRED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-06-12 Cont ID  
Sent By mawillia Date 2007-06-12 Time 17:42 Rev Time 0.00
Received By mawillia Date 2007-06-12 Time 17:23 Sent To  
Notes
2007-06-12 17:39:12*****APPROVED*****
  
 ALL COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED, HOWEVER, THE APPROPIATE PLAN SHEET(S) WILL
 BE STAMPED WHEN ALL OTHER PLAN REVIEWERS HAVE BEEN
 SATISFIED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-05-10 Cont ID  
Sent By mawillia Date 2007-05-10 Time 12:20 Rev Time 0.00
Received By mawillia Date 2007-05-10 Time 12:11 Sent To  
Notes
2007-05-10 12:20:43*****DENIED*****
  
 THE FOLLWING COMMENTS TAKEN FROM THE PREVIOUS PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
  
 2.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING SUPPLIES & MATERIALS SHALL NOT INTERFERE
 OR HINDER WITH ACCESS TO OR EGRESS FROM THE PROPERTY OR
 VICINITY THEREOF (INCLUDING STREETS, ROADS, AND FIRE
 LANES).
  
 3.WILL THE INSTALLATION OF THE NEW PARTITION WALLS
 AND DOORS IMPACT THE DISTRIBUTION PATTERN OF THE FIRE
 SPRINKLER HEADS?IF SO, SEPARATE PLANS AND PERMIT WILL
 BE REQUIRED FOR THE FIRE SPRINKLER REMODEL.
  
 4.WHEN/IF IT IS NECESSARY TO SHUT DOWN THE FIRE
 PROTECTION SYSTEM, THE FIRE DEPARTMENT WILL BE NOTIFIED
 WHEN IT IS SHUT DOWN AND WHEN IT IS RETURNED TO
 SERVICE.
  
 5.INDICATE THE INTERIOR FINISH CLASSIFICATION FOR THE
 NEW WALLS AND CEILING TILES AS CLASS A, CLASS B, OR
 CLASS C.BE SPECIFIC
  
 6.ALL REQUIRED EXIT COMPONENTS WITHIN THE STRUCTURE
 SHALL BE MAINTAINED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH ITEM
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-04-04 Cont ID  
Sent By mawillia Date 2007-04-04 Time 16:09 Rev Time 0.00
Received By mawillia Date 2007-04-04 Time 15:18 Sent To  
Notes
2007-04-04 16:08:42*****DENIED*****
  
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
  
 2.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING SUPPLIES & MATERIALS SHALL NOT INTERFERE
 OR HINDER WITH ACCESS TO OR EGRESS FROM THE PROPERTY OR
 VICINITY THEREOF (INCLUDING STREETS, ROADS, AND FIRE
 LANES).
  
 3.WILL THE INSTALLATION OF THE NEW PARTITION WALLS
 AND DOORS IMPACT THE DISTRIBUTION PATTERN OF THE FIRE
 SPRINKLER HEADS?IF SO, SEPARATE PLANS AND PERMIT WILL
 BE REQUIRED FOR THE FIRE SPRINKLER REMODEL.
  
 4.WHEN/IF IT IS NECESSARY TO SHUT DOWN THE FIRE
 PROTECTION SYSTEM, THE FIRE DEPARTMENT WILL BE NOTIFIED
 WHEN IT IS SHUT DOWN AND WHEN IT IS RETURNED TO
 SERVICE.
  
 5.INDICATE THE INTERIOR FINISH CLASSIFICATION FOR THE
 NEW WALLS AND CEILING TILES AS CLASS A, CLASS B, OR
 CLASS C.BE SPECIFIC
  
 6.ALL REQUIRED EXIT COMPONENTS WITHIN THE STRUCTURE
 SHALL BE MAINTAINED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH ITEM
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-05 Cont ID  
Sent By adarroug Date 2007-06-05 Time 11:23 Rev Time 0.00
Received By adarroug Date 2007-06-05 Time 11:23 Sent To  
Notes
2007-06-05 11:23:41WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-03 Cont ID  
Sent By shill Date 2007-05-03 Time 13:24 Rev Time 0.00
Received By shill Date 2007-05-03 Time 13:24 Sent To  
Notes
2007-05-07 13:09:10TO "BOB"#1
2007-05-03 13:24:37WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-04 Cont ID  
Sent By mawillia Date 2007-04-04 Time 15:18 Rev Time 0.00
Received By mawillia Date 2007-03-26 Time 17:12 Sent To  
Notes
2007-03-31 17:12:57TO BOB BOARD #17

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-06-12 Cont ID  
Sent By tgordon Date 2007-06-12 Time 15:16 Rev Time 0.25
Received By tgordon Date 2007-06-12 Time 15:16 Sent To  
Notes
2007-06-12 15:20:34MECHANICAL PLAN HAS PASSED REVIEW BUT AS IT IS ON THE
 SAME PAGE AS THE ELECTRICAL PLAN THAT NEEDS CORRECTIONS
 MECHANICAL WILL BE STAMPED WHEN THEY PASS ELECTRICAL
 REVIEW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-05-08 Cont ID  
Sent By tgordon Date 2007-05-08 Time 09:28 Rev Time 0.30
Received By tgordon Date 2007-05-08 Time 09:28 Sent To  
Notes
2007-05-08 09:38:01*** DENIED ***
 1) 12"RETURN AIR TRANSFER DUCTS FROM WAITING ROOM NEEDS
 TO BE 14" AND 12" RETURN AIR TRANSFER DUCT FROM MANAGER
 OFFICE NEEDS TO BE 16", SEE 2004 FBC/M 601.4 (A),
 PLEASE CORRECT.
  
 *** 2004 FBC/M 601.4. BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND ONE HALF TIMES
 THE CROSS SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY
 DUCT ENTERING THE ROOM OR SPACE IT'S SERVING AND THE
 DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE PROPER RETURN
 AIR BALANCE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-29 Cont ID  
Sent By tgordon Date 2007-03-29 Time 12:05 Rev Time 0.35
Received By tgordon Date 2007-03-29 Time 12:05 Sent To  
Notes
2007-03-29 12:10:16*** DENIED ***
 1) SEE MECHANICAL PLANS PAGE A-2.0. NEED TO PROVIDE FOR
 RETURN AIR TO THE MANAGER'S OFFICE, CONSULT ROOM #1 AND
 2, AND THE WAITING ROOM, SEE 2004 FBC/M 601.4.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-03-31 Cont ID  
Sent By jleech Date 2007-03-31 Time 06:27 Rev Time 0.00
Received By jleech Date 2007-03-31 Time 06:27 Sent To  
Notes
2007-03-31 06:28:03NO PLUMBING SHOWN ON PLANS


Account Summary | Usage Policy | Privacy Policy