| 2007-05-30 11:57:27 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY |
| | OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | 1.)THERE ARE TWO WIND LOAD DESIGN SPECIFICATIONS IN |
| | THE PERMIT PACKAGE.ONE WAS PRODUCED WITH SOFTWARE, |
| | THE OTHER WAS PROVIDED BY A STRUCTURAL ENGINEER. |
| | ENGINEERING IN ACCORDANCE WITH ASCE7-02 IS REQUIRED FOR |
| | DESIGN PRESSURES FOR BUILDINGS OVER 60' IN HEIGHT, |
| | FBC1609.1.1.THEREFORE, YOU CANNOT USE THE PRESSURES |
| | PRODUCED BY THE WIND LOAD SOFTWARE.PLEASE REMOVE THE |
| | "DESIGN PRESSURE CALCULATION" FROM THE PACKAGE AND USE |
| | THE PRESSURES SPECIFIED BY THE ENGINEER (WHICH ARE |
| | HIGHER) FOR THIS PROJECT. |
| | |
| | 2.)TWO DIFFERENT INSTALLATION SCHEDULES WERE |
| | PROVIDED.ONE STATES THAT THE SUBSTRATE IS CONCRETE |
| | BLOCK, THE OTHER STATES POURED CONCRETE.SUBMIT ONLY |
| | ONE INSTALLATION SCHEDULE, TWO COPIES.TWO SETS |
| | SUBMITTED OF THE CONCRETE BLOCK SCHEDULE, ONLY ONE FOR |
| | THE INSTALLATION SCHEDULE WITH THE POURED CONCRETE |
| | SUBSTRATE.TWO IDENTICAL COMPLETE SETS, COLLATED, |
| | SHOULD ALWAYS BE SUBMITTED FOR PERMITTING. |
| | |
| | 3.)THE INSTALLATION SCHEDULES USE THE DESIGN |
| | PRESSURES PRODUCED BY THE SOFTWARE.YOU MUST USE THE |
| | DESIGN PRESSURES SPECIFIED BY THE STRUCTURAL ENGINEER, |
| | WHICH ARE HIGHER.REVISE THE INSTALLATION SCHEDULE |
| | ACCORDINGLY. |
| | |
| | 4.)THE INSTALLATION SCHEDULE STATES THAT SHUTTER SPAN |
| | IS 9'.ON THE PRODUCT APPROVAL, YOU HAVE CIRCLED |
| | ANCHOR SPACING FOR AN 8'0" SPAN, -60PSF DESIGN |
| | PRESSURE.THE ENGINEER SPECIFIES -62.27 FOR ONE OF THE |
| | OPENINGS, SO YOU MUST USE THE -75PSF COLUMN FOR THAT |
| | OPENING.IF THE SPAN (WHICH SHOULD BE THE BLADE |
| | LENGTH) IS OVER 8', USE THE 9' COLUMN.PLEASE CLARIFY |
| | THE SPAN AS THE MOUNTING DETAIL TO BE USED IS NOT |
| | CLEAR. |
| | |
| | 5.)THE COLUMN ON THE INSTALLATION SCHEDULE MARKED |
| | "SHUTTER MOUNTING:CONNECTION TYPE PER PRODUCT |
| | APPROVAL" IS TO INDICATE WHICH MOUNTING DETAIL YOU ARE |
| | USING.ON THIS PRODUCT APPROVAL, IT WOULD BE DETAILS A |
| | THROUGH L.IT IS NOT CLEAR WHICH MOUNTING DETAIL YOU |
| | ARE USING AS SEVERAL HAVE BEEN CIRCLED ON THE PRODUCT |
| | APPROVAL. |
| | |
| | 6.)THE PRODUCT APPROVAL HAS H, FLOOR MOUNTING |
| | CIRCLED, WITH 8.5 ANCHORING ALSO CIRCLED.THE |
| | INSTALLATION SCHEDULE DOES NOT SPECIFY 8.5 ANCHOR |
| | SPACING.ANYTHING CIRCLED ON THE PRODUCT APPROVAL |
| | SHOULD CORRELATE WITH THE JOB AND INSTALLATION |
| | SCHEDULE. |
| | |
| | |