Plan Review Details - Permit 07030755
Plan Review Stops For Permit 07030755
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-05-22 Cont ID  
Sent By mjacobs Date 2007-05-22 Time 10:23 Rev Time 0.00
Received By mjacobs Date 2007-05-22 Time 08:41 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-25 Cont ID  
Sent By mjacobs Date 2007-04-25 Time 19:00 Rev Time 0.00
Received By mjacobs Date 2007-04-25 Time 17:07 Sent To  
Notes
2007-04-25 18:59:56BUILDING PLAN REVIEW
 PERMIT: 07030755
 ADD: 6200SOUTH DIXIE HWY.
 CONT: VINCELUCAS
 TEL: (561)493-5011
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)IF THE RENOVATION INVOLVES A CHANGE OF OCCUPANCY,
 SEE FBC 110.1.1 AND 110.4.1
  
 4)NOTE:FBC "EXISTING" 501.2AN EXISTING BUILDING
 OR PORTION THEREOF SHALL NOT BE ALTERED SUCH THAT THE
 BUILDING BECOMES LESS SAFE OR ENERGY EFFICIENT THAN ITS
 EXISTING CONDITION, IF IN THE ALTERATION THE CURRENT
 LEVEL OF SAFETY OR SANITATION IS TO BE REDUCED, THE
 PORTION ALTERED SHALL COMFORM TO THE REQUIREMENTS OF
 THE FBC.
  
 5)NOW THE SECOND FLOOR IS SEPERATED FROM THE FIRST
 FLOOR , INDICATE THE USE AND OCCUPANCY / OCCUPANT LOAD
 AND THE SQUARE FOOTAGE OF THE SECOND FLOOR.
  
 6)PROVIDE A DETAIL ELEVATION DRAWING OF THE BALCONY
 AND GUARDRAIL ON THE SECOND FLOOR FOR BOTH STAIRWAYS.
 SEE FBC 1012/11-4.9.4/1607.7.1.1.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-05-22 Cont ID  
Sent By mawillia Date 2007-05-22 Time 11:01 Rev Time 0.00
Received By mawillia Date 2007-05-22 Time 10:59 Sent To  
Notes
2007-05-22 11:01:14*****APPROVED*****
  
  
 PLAN SHEET A-1 WAS RESTAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-04-24 Cont ID  
Sent By mawillia Date 2007-04-24 Time 15:02 Rev Time 0.00
Received By mawillia Date 2007-04-24 Time 14:54 Sent To  
Notes
2007-04-24 14:59:37*****APPROVED*****
  
  
 PLAN SHEET A-1 STAMPED, INITIALED, AND DATED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-14 Cont ID  
Sent By adarroug Date 2007-05-14 Time 16:23 Rev Time 0.00
Received By adarroug Date 2007-05-14 Time 16:23 Sent To B
Notes
2007-05-14 16:23:23TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-04-25 Time   Rev Time 0.00
Received By adarroug Date 2007-03-24 Time 14:39 Sent To  
Notes
2007-03-24 14:47:58TO "COMM" BD#24


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved