| 2007-04-04 11:48:05 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1.PER FBC-2004, CHAPTER 1, SECTION |
| | 106.1.3, QUALITY OF BUILDING PLANS: THE |
| | BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL |
| | POLICY, STANDARDS FOR PLANS |
| | AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| | CONFORMITY TO ITS RECORD RETENTION |
| | PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, |
| | CLARITY, OR OTHER ITEMS RELATED TO |
| | RECORDS MANAGEMENT. |
| | NOTE: DRAWINGS IN PENCIL ARE UNACCPETABLE PLEASE |
| | RESUBMIT IN INK. |
| | |
| | 2. 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION DOCUMENTS, |
| | SPECIAL INSPECTION AND |
| | STRUCTURAL OBSERVATION PROGRAMS, AND |
| | OTHER DATA SHALL BE SUBMITTED IN TWO OR |
| | MORE SETS WITH EACH APPLICATION FOR A |
| | PERMIT. |
| | NOTE: ONLY ONE DRAWING IN PENCIL WAS SUBMITTED. |
| | |
| | 3.SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: NOT ALL CORRESPONDING LENGTHS ARE INDICATED FOR |
| | THE CUT SECTIONS. ALSO THE LP TANKS, 1ST AND 2ND STAGE |
| | REGULATORS NEED TO BE INDICATED ON THE RESUBMITTED |
| | DRAWINGS. |
| | |
| | 4.SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | NOTE: PLEASE INDICATE THE ABOVE GROUND PIPING MATERIAL |
| | ON THE RESUBMITTAL. |
| | |
| | 5.BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | NOTE: THERE IS NO INDICATION OF THE BTU LOAD OF THE |
| | FUTURE FIRE PLACE ON THE DRAWING.PLEASE INDICATE THIS |
| | ON THE RESUBMITTAL. |
| | |
| | 6.SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: THE SUBMITTED DRAWING INDICATES A TOTAL LENGTH OF |
| | 176 FEET AND ON THE DRAWING 90 FT IS INDICATED. PLEASE |
| | CLARIFY AND CORRELATE DRAWING ON THE RESUBMITTAL. |
| | |
| | 7.SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | NOTE: PLEASE SUBMIT MANUFAFTURER SHEETS FOR THE FIRST |
| | AND SECOND STAGE REGULATORS. |
| | |
| | 8.CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | 9.CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | |
| | 10.FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | NOTE: PLEASE REFERENCE THE ATTACHED CITY OF WEST PALM |
| | BEACH GAS PERMIT APPLICATION REQUIREMENTS FOR FUTURE |
| | GAS PERMIT APPLICATIONS. |
| | |
| | END OF COMMENTS: |
| | |