| Plan Review Stops For Permit 07030722 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2007-03-28 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2007-03-28 |
Time |
12:58 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2007-03-28 |
Time |
12:58 |
Sent To |
|
|
| Notes |
| 2007-03-28 12:59:07 | PERMIT ATTACHED TO THE CORRECT ADDRESS. | | | | | | LACRAMIOARA URSU | | | MIS - GIS SUPPORT SPECIALIST | | | CITY OF WEST PALM BEACH | | | OFFICE:822-1239 | | | FAX: 822-1249 | | | E-MAIL:[email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2007-06-28 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2007-06-28 |
Time |
19:44 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2007-06-28 |
Time |
19:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-05-07 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2007-05-07 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2007-05-07 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2007-05-07 16:01:02 | BUILDING REVIEW COMMENTS | | | | | | | | | PROVIDE NEW N.O.C. WITH THE NEW CONTRACTORS NAME | | | LISTED. | | | | | | ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/OWNER'S | | | REP. | | | | | | SHOW ACCESSIBLE ROUTE, 2004 FBC , 11-4.1.6 , PROVIDE | | | ACCESSIBLE SERVICE COUNTER PER , 2004 FBC , 11-7.2. | | | | | | | | | | | | | | | | | | | | | | | | L.MARTINEZ | | | 561-805-6710 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-06-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-06-08 |
Time |
18:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-06-08 |
Time |
17:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-03-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-03-25 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-03-25 |
Time |
11:23 |
Sent To |
|
|
| Notes |
| 2007-03-25 11:58:07 | | | | | | | ****** UNSAT***** | | | | | | ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 | | | IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE | | | ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY | | | THE CITY OF WEST PALM BEACH. | | | | | | | | | 1) NOTE:PLEASE INDICATE THE AIC RATING FOR SERVICE | | | EQUIPMENT.THE RATING IS SHOWN FOR PANEL BUT NOT ON | | | NEW TENANT DISCONNECT. | | | 110.9. | | | FBC 106.1.2 | | | | | | 2) NOTE: PLEASE SEE THAT THE METER SHALL CONTAIN A | | | *FLOATING NEUTRAL* KIT, PLEASE NOT ON PLANS/RISER. | | | 250.6, 240.24 | | | | | | 3) NOTE: PLEASE SEE THE PLANS AND ENERGY CALCULATIONS | | | BOTH CONTAIN *WHITE OUT* IN SEPARATE AREAS FOR THE | | | ADDRESS AND SUITE/UNIT NUMBER.PLANS AND DOCUMENTS MAY | | | NOT CONTAIN *WHITE-OUT* IN ANY FASHION. PLEASE KNOW | | | PLANS WILL ROUTED TO ADDRESSING REVIEWER AND THE | | | UNIT/SUITE NUMBER WILL BE ASSIGNED. PLEASE BE SURE TO | | | WAIT TO REVISE PLANS ONCE A NUMBER HAS BEEN | | | DETERMINED. | | | FS 471.025 | | | | | | 4) NOTE: PLEASE SEE THE MAXIMUM OCCUPANCY SENSOR OVER | | | RIDE TIMES IS 30MINS BASED ON 13-415.1.ABC.1.1,.1.2. | | | PLANS INDICATE 1HR WHICH IS ONLY OK, IF USING TIMER | | | TYPE DEVICES WHICH PERMITS UP TO 4HRS. | | | | | | 5) NOTE: PLEASE CLARIFY ALL LIGHTING ON PLANS AND | | | ENERGY CALCULATIONS. THE WATTAGE BEING SHOWN, IS THIS | | | BASED ON FIXTURE BALLAST ALLOWANCE? DEPENDING ON THE | | | FIXTURE THE WATTAGE OF BALLAST MAY ACTUALLY BE LOWER | | | THAN THE WATTAGE OF BULBS? PLEASE INCLUDE THE BATH LT | | | FIXTURE ON FIXTURE LEGEND. IS THIS A FAN/LT COMBO? | | | PLEASE CLARIFY. 13-415.1.AB.1.1 | | | THIS TENANT SPACE IS USING THE METHOD A FOR WHOLE | | | BUILDING. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2007-06-28 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-06-28 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-06-28 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2007-06-28 15:43:19 | *****APPROVED***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | | BEEN ADDRESSED;PLAN SHEETS 1.0A AND 2.0E WERE | | | STAMPED, INITIALED, AND DATED. | | | | | | | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-04-24 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-04-24 |
Time |
15:43 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-04-24 |
Time |
15:05 |
Sent To |
|
|
| Notes |
| 2007-04-24 15:43:31 | *****DENIED***** | | | | | | | | | | | | 1.REPLACE THE K- RATED FIRE EXTINGUISHER SHOWN AT ONE | | | OF THE TWO EXIT DOORS WITH THE APPROPIATE 2A10BC RATED | | | EXTINGUISHER.FOR CONSISTENCY, SEE GENERAL NOTE #8 ON | | | THE COVER SHEET. | | | | | | 2.BE SPECIFIC IN IDENTIFYING THE MINIMUM INTERIOR | | | FINISH CLASSIFICATION FOR THE WALLS AND CEILING IN THE | | | EXIT, EXIT ACCESS CORRIDOR, AND OTHER SPACES AS CLASS | | | A, CLASS B, OR CLASS C. | | | | | | 3.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE | | | COOKING HOOD INSTALLATION AND FOR THE COOKING HOOD | | | SUPPRESSION SYSTEM. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2007-07-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-07-13 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-07-13 |
Time |
13:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2007-06-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-06-18 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-06-18 |
Time |
15:44 |
Sent To |
|
|
| Notes |
| 2007-06-18 15:47:04 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | 1. SHT 3.0P GAS RISER DIAGRAM. MINIMUM 1" REQUIRED TO | | | THE WATER HEATER. TABLE 402.4(2). SHOW MINIMUM VALVE | | | SIZES FOR EACH GAS EQUIPMENT CONNECTING TO THE 1.5" GAS | | | HEADER PER TABLE 402.4.2. | | | ****RESPONSE NOTED, BUT THE PIPE & VALVE SIZES SHALL BE | | | INDICATED ON THE RISER DIAGRAM. THE SIZE FOR THE WATER | | | HEATER IS INDICATED AS 3/4" IN THE LOAD CALCULATIONS | | | AND THE OVEN IS INDICATED AS 1/2" IN THE LOAD | | | CALCULATIONS. THE OVEN IS REQUIRED TO BE 1-1/4" IF THE | | | LOAD CALCULATION IS 375,000 BTU'S AS SHOWN, BUT THE NEW | | | SPECIFICATION SHEET FOR EXCALIBER OVEN INDICATES THAT | | | THE BTU LOAD IS 225,000 BTU'S. IF THE LATTER IS USED, | | | THEN A MINIMUM 1" VALVE IS REQUIRED. | | | | | | 2. OK | | | | | | | | | 3. THE MANUF. SPECIFICATION SHEETS FOR THE HOBART | | | DOUBLE OVEN SHOWS A BTU RATING OF 318,000 BTU'S, BUT | | | THE RISER DIAGRAM INDICATES 375,000BTU'S. PLEASE | | | CLARIFY. SECTION 106.1.1. | | | ****RESPONSE NOTED, BUT THE NEW OVEN, (EXCALIBER), BTU | | | LOAD DOES NOT REFLECT THE LOAD CALCULATIONS ON SHT | | | 3.0P. PLEASE CORRELATE INFORMATION FROM THE MANUF. AND | | | THE LOAD CALCULATION. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2007-07-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-04-07 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-04-07 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2007-06-18 15:42:02 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | 1. SHT 3.0P GAS RISER DIAGRAM. MINIMUM 1" REQUIRED TO | | | THE WATER HEATER. TABLE 402.4(2). SHOW MINIMUM VALVE | | | SIZES FOR EACH GAS EQUIPMENT CONNECTING TO THE 1.5" GAS | | | HEADER PER TABLE 402.4.2. | | | | | | 2. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE GAS | | | WATER HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | | | | 3. THE MANUF. SPECIFICATION SHEETS FOR THE HOBART | | | DOUBLE OVEN SHOWS A BTU RATING OF 318,000 BTU'S, BUT | | | THE RISER DIAGRAM INDICATES 375,000BTU'S. PLEASE | | | CLARIFY. SECTION 106.1.1. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-07-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-06 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-06 |
Time |
08:55 |
Sent To |
|
|
| Notes |
| 2007-07-06 08:55:53 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-05-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-17 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-17 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2007-06-01 16:43:47 | TO "COMM" BD#60 | | 2007-05-17 08:41:10 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-05-07 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2007-05-07 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2007-03-24 |
Time |
12:58 |
Sent To |
|
|
| Notes |
| 2007-03-24 13:00:15 | TO "COMM" BD#18 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-07-13 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-07-13 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-07-13 |
Time |
15:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-06-13 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-06-13 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-06-07 |
Time |
19:47 |
Sent To |
|
|
| Notes |
| 2007-06-13 09:52:57 | -----------------DENIED-------------------- | | | | | | A CALL WAS PLACED AND A MESSAGE LEFT FOR MR TWOMEY (ON | | | 6/7/07) TO ASK QUESTIONS REGARDING THE RESUBMITTAL BUT | | | NO RETURN CALL WAS RECEIVED. | | | | | | 1. PRODUCT APPROVAL INSTALLATION INSTRUCTIONS DO NOT | | | MATCH THOSE SHOWN ON PLAN. IF STANDS ARE TO BE | | | INSTALLED PER THEIR PRODUCT APPROVAL, PLEASE MAKE THE | | | PLAN MATCH THE INSTRUCTIONS. FBC 106.1.1. | | | | | | 2. RESPONSE TO PREVIOUS REVIEW COMMENTS STATES THAT THE | | | HOOD SYSTEM IS "NOT TO BE INSTALLLED AT THIS TIME." | | | THIS IS A COMMERCIAL KITCHEN AND WILL NOT BE CODE | | | COMPLIANT WITHOUT A COMMERCIAL KITCHEN HOOD VENTILATION | | | SYSTEM. FBC,M 507.2 | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-04-16 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-04-16 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-04-13 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2007-04-16 16:33:31 | -----------------DENIED-------------------- | | | | | | FBC 2004 W/2006 REVISIONS | | | FBC CH. 1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. EQUIPMENT STAND DETAIL: PRE-ENGINEERED EQUIPMENT | | | STANDS ARE STRUCTURAL ELEMENTS AS DEFINED IN FAC 9B-72 | | | AND AS SUCT, PRODUCT APPROVAL IS REQUIRED. | | | | | | 2. RTU MOUNTING DETAIL: PLEASE PROVIDE WIND LOAD | | | CALCULATIONS FOR RTU WITH ATTACHMENT DETAILS BY A | | | FLORIDA LICENSED STRUCTURAL ENGINEER IN SUFFICIENT | | | DETAIL. WHAT IS GAUGE OF STRAP? WHAT IS THICKNESS OF | | | 3X3 ANGLE? FBC 106.1.2. | | | | | | 3. SEPARATE PERMITS ARE REQUIRED FOR KITCHEN HOODS, | | | HOOD SUPPRESSION SYSTEMS AND WALK IN COOLERS/FREEZERS. | | | | | | REVIEWED BY: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2007-07-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-07-13 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-07-13 |
Time |
13:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-06-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-06-18 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-06-18 |
Time |
15:28 |
Sent To |
|
|
| Notes |
| 2007-06-18 15:37:43 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | WPB MUNICIPAL CODE | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. OK | | | 2. OK | | | | | | 3. SHT 3.0P GAS RISER DIAGRAM. MINIMUM 1" REQUIRED TO | | | THE WATER HEATER. TABLE 402.4(2). SHOW MINIMUM VALVE | | | SIZES FOR EACH GAS EQUIPMENT CONNECTING TO THE 1.5" GAS | | | HEADER PER TABLE 402.4.2. | | | ****RESPONSE NOTED, BUT THE PIPE & VALVE SIZES SHALL BE | | | INDICATED ON THE RISER DIAGRAM. THE SIZE FOR THE WATER | | | HEATER IS INDICATED AS 3/4" IN THE LOAD CALCULATIONS | | | AND THE OVEN IS INDICATED AS 1/2" IN THE LOAD | | | CALCULATIONS. THE OVEN IS REQUIRED TO BE 1-1/4" IF THE | | | LOAD CALCULATION IS 375,000 BTU'S AS SHOWN, BUT THE NEW | | | SPECIFICATION SHEET FOR EXCALIBER OVEN INDICATES THAT | | | THE BTU LOAD IS 225,000 BTU'S. IF THE LATTER IS USED, | | | THEN A MINIMUM 1" VALVE IS REQUIRED. | | | | | | 4. OK | | | | | | | | | 5. THE MANUF. SPECIFICATION SHEETS FOR THE HOBART | | | DOUBLE OVEN SHOWS A BTU RATING OF 318,000 BTU'S, BUT | | | THE RISER DIAGRAM INDICATES 375,000BTU'S. PLEASE | | | CLARIFY. SECTION 106.1.1. | | | ****RESPONSE NOTED, BUT THE NEW OVEN, (EXCALIBER), BTU | | | LOAD DOES NOT REFLECT THE LOAD CALCULATIONS ON SHT | | | 3.0P. PLEASE CORRELATE INFORMATION FROM THE MANUF. AND | | | THE LOAD CALCULATION. | | | | | | 6. OK | | | 7. OK | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-04-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-04-09 |
Time |
09:27 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-04-07 |
Time |
17:02 |
Sent To |
|
|
| Notes |
| 2007-04-09 09:58:47 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | WPB MUNICIPAL CODE | | | | | | 1. SHTS A1.1 & 1.1ANO WATER SUPPLY OR WASTE DRAIN | | | SIZE INDICATED FORITEMS 1, 2, 8, 16 & 44. PLEASE | | | CLARIFY. SECTION 106.1.1. | | | | | | 2. GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY | | | ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO | | | (561) 822-2272, FAX (561) 822-2287, OR [email protected]. | | | MUNICIPAL CODE ARTICLE III SEWERS & SEWAGE DISPOSAL | | | SECTION 90-124(7)(A) THRU (G). | | | | | | 3. SHT 3.0P GAS RISER DIAGRAM. MINIMUM 1" REQUIRED TO | | | THE WATER HEATER. TABLE 402.4(2). SHOW MINIMUM VALVE | | | SIZES FOR EACH GAS EQUIPMENT CONNECTING TO THE 1.5" GAS | | | HEADER PER TABLE 402.4.2. | | | | | | 4. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE GAS | | | WATER HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | | | | 5. THE MANUF. SPECIFICATION SHEETS FOR THE HOBART | | | DOUBLE OVEN SHOWS A BTU RATING OF 318,000 BTU'S, BUT | | | THE RISER DIAGRAM INDICATES 375,000BTU'S. PLEASE | | | CLARIFY. SECTION 106.1.1. | | | | | | 6. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | | SECS. 502 THRU 505. (FOR THE WATER HEATER). | | | | | | 7. SHT P3.0P SANITARY RISER DIAGRAM. SEPARATE DRAIN | | | LINES ARE REQUIRED FOR THE ICE MAKER, AND THE ICE | | | STORAGE BIN. SECTION 802. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|