Plan Review Details - Permit 07030722
Plan Review Stops For Permit 07030722
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-03-28 Cont ID  
Sent By lursu Date 2007-03-28 Time 12:58 Rev Time 0.00
Received By lursu Date 2007-03-28 Time 12:58 Sent To  
Notes
2007-03-28 12:59:07PERMIT ATTACHED TO THE CORRECT ADDRESS.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-06-28 Cont ID  
Sent By lmartine Date 2007-06-28 Time 19:44 Rev Time 0.00
Received By lmartine Date 2007-06-28 Time 19:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-07 Cont ID  
Sent By lmartine Date 2007-05-07 Time 15:51 Rev Time 0.00
Received By lmartine Date 2007-05-07 Time 15:51 Sent To  
Notes
2007-05-07 16:01:02BUILDING REVIEW COMMENTS
  
  
 PROVIDE NEW N.O.C. WITH THE NEW CONTRACTORS NAME
 LISTED.
  
 ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/OWNER'S
 REP.
  
 SHOW ACCESSIBLE ROUTE, 2004 FBC , 11-4.1.6 , PROVIDE
 ACCESSIBLE SERVICE COUNTER PER , 2004 FBC , 11-7.2.
  
  
  
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-06-08 Cont ID  
Sent By dpalmer Date 2007-06-08 Time 18:52 Rev Time 0.00
Received By dpalmer Date 2007-06-08 Time 17:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-25 Cont ID  
Sent By dpalmer Date 2007-03-25 Time 11:57 Rev Time 0.00
Received By dpalmer Date 2007-03-25 Time 11:23 Sent To  
Notes
2007-03-25 11:58:07 
  
 ****** UNSAT*****
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
  
 1) NOTE:PLEASE INDICATE THE AIC RATING FOR SERVICE
 EQUIPMENT.THE RATING IS SHOWN FOR PANEL BUT NOT ON
 NEW TENANT DISCONNECT.
 110.9.
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE THAT THE METER SHALL CONTAIN A
 *FLOATING NEUTRAL* KIT, PLEASE NOT ON PLANS/RISER.
 250.6, 240.24
  
 3) NOTE: PLEASE SEE THE PLANS AND ENERGY CALCULATIONS
 BOTH CONTAIN *WHITE OUT* IN SEPARATE AREAS FOR THE
 ADDRESS AND SUITE/UNIT NUMBER.PLANS AND DOCUMENTS MAY
 NOT CONTAIN *WHITE-OUT* IN ANY FASHION. PLEASE KNOW
 PLANS WILL ROUTED TO ADDRESSING REVIEWER AND THE
 UNIT/SUITE NUMBER WILL BE ASSIGNED. PLEASE BE SURE TO
 WAIT TO REVISE PLANS ONCE A NUMBER HAS BEEN
 DETERMINED.
 FS 471.025
  
 4) NOTE: PLEASE SEE THE MAXIMUM OCCUPANCY SENSOR OVER
 RIDE TIMES IS 30MINS BASED ON 13-415.1.ABC.1.1,.1.2.
 PLANS INDICATE 1HR WHICH IS ONLY OK, IF USING TIMER
 TYPE DEVICES WHICH PERMITS UP TO 4HRS.
  
 5) NOTE: PLEASE CLARIFY ALL LIGHTING ON PLANS AND
 ENERGY CALCULATIONS. THE WATTAGE BEING SHOWN, IS THIS
 BASED ON FIXTURE BALLAST ALLOWANCE? DEPENDING ON THE
 FIXTURE THE WATTAGE OF BALLAST MAY ACTUALLY BE LOWER
 THAN THE WATTAGE OF BULBS? PLEASE INCLUDE THE BATH LT
 FIXTURE ON FIXTURE LEGEND. IS THIS A FAN/LT COMBO?
 PLEASE CLARIFY. 13-415.1.AB.1.1
 THIS TENANT SPACE IS USING THE METHOD A FOR WHOLE
 BUILDING.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-06-28 Cont ID  
Sent By mawillia Date 2007-06-28 Time 15:48 Rev Time 0.00
Received By mawillia Date 2007-06-28 Time 15:34 Sent To  
Notes
2007-06-28 15:43:19*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEETS 1.0A AND 2.0E WERE
 STAMPED, INITIALED, AND DATED.
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-04-24 Cont ID  
Sent By mawillia Date 2007-04-24 Time 15:43 Rev Time 0.00
Received By mawillia Date 2007-04-24 Time 15:05 Sent To  
Notes
2007-04-24 15:43:31*****DENIED*****
  
  
  
 1.REPLACE THE K- RATED FIRE EXTINGUISHER SHOWN AT ONE
 OF THE TWO EXIT DOORS WITH THE APPROPIATE 2A10BC RATED
 EXTINGUISHER.FOR CONSISTENCY, SEE GENERAL NOTE #8 ON
 THE COVER SHEET.
  
 2.BE SPECIFIC IN IDENTIFYING THE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR THE WALLS AND CEILING IN THE
 EXIT, EXIT ACCESS CORRIDOR, AND OTHER SPACES AS CLASS
 A, CLASS B, OR CLASS C.
  
 3.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 COOKING HOOD INSTALLATION AND FOR THE COOKING HOOD
 SUPPRESSION SYSTEM.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-6722

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-07-13 Cont ID  
Sent By kstevens Date 2007-07-13 Time 13:43 Rev Time 0.00
Received By kstevens Date 2007-07-13 Time 13:43 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-06-18 Cont ID  
Sent By kstevens Date 2007-06-18 Time 15:44 Rev Time 0.00
Received By kstevens Date 2007-06-18 Time 15:44 Sent To  
Notes
2007-06-18 15:47:04DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT 3.0P GAS RISER DIAGRAM. MINIMUM 1" REQUIRED TO
 THE WATER HEATER. TABLE 402.4(2). SHOW MINIMUM VALVE
 SIZES FOR EACH GAS EQUIPMENT CONNECTING TO THE 1.5" GAS
 HEADER PER TABLE 402.4.2.
 ****RESPONSE NOTED, BUT THE PIPE & VALVE SIZES SHALL BE
 INDICATED ON THE RISER DIAGRAM. THE SIZE FOR THE WATER
 HEATER IS INDICATED AS 3/4" IN THE LOAD CALCULATIONS
 AND THE OVEN IS INDICATED AS 1/2" IN THE LOAD
 CALCULATIONS. THE OVEN IS REQUIRED TO BE 1-1/4" IF THE
 LOAD CALCULATION IS 375,000 BTU'S AS SHOWN, BUT THE NEW
 SPECIFICATION SHEET FOR EXCALIBER OVEN INDICATES THAT
 THE BTU LOAD IS 225,000 BTU'S. IF THE LATTER IS USED,
 THEN A MINIMUM 1" VALVE IS REQUIRED.
  
 2. OK
  
  
 3. THE MANUF. SPECIFICATION SHEETS FOR THE HOBART
 DOUBLE OVEN SHOWS A BTU RATING OF 318,000 BTU'S, BUT
 THE RISER DIAGRAM INDICATES 375,000BTU'S. PLEASE
 CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE NEW OVEN, (EXCALIBER), BTU
 LOAD DOES NOT REFLECT THE LOAD CALCULATIONS ON SHT
 3.0P. PLEASE CORRELATE INFORMATION FROM THE MANUF. AND
 THE LOAD CALCULATION.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-07-13 Cont ID  
Sent By kstevens Date 2007-04-07 Time 15:40 Rev Time 0.00
Received By kstevens Date 2007-04-07 Time 15:41 Sent To  
Notes
2007-06-18 15:42:02DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT 3.0P GAS RISER DIAGRAM. MINIMUM 1" REQUIRED TO
 THE WATER HEATER. TABLE 402.4(2). SHOW MINIMUM VALVE
 SIZES FOR EACH GAS EQUIPMENT CONNECTING TO THE 1.5" GAS
 HEADER PER TABLE 402.4.2.
  
 2. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE GAS
 WATER HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC 402.2.
  
  
 3. THE MANUF. SPECIFICATION SHEETS FOR THE HOBART
 DOUBLE OVEN SHOWS A BTU RATING OF 318,000 BTU'S, BUT
 THE RISER DIAGRAM INDICATES 375,000BTU'S. PLEASE
 CLARIFY. SECTION 106.1.1.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-06 Cont ID  
Sent By adarroug Date 2007-07-06 Time 08:55 Rev Time 0.00
Received By adarroug Date 2007-07-06 Time 08:55 Sent To  
Notes
2007-07-06 08:55:53WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-17 Cont ID  
Sent By adarroug Date 2007-05-17 Time 08:40 Rev Time 0.00
Received By adarroug Date 2007-05-17 Time 08:40 Sent To  
Notes
2007-06-01 16:43:47TO "COMM" BD#60
2007-05-17 08:41:10WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-07 Cont ID  
Sent By lmartine Date 2007-05-07 Time 16:01 Rev Time 0.00
Received By lmartine Date 2007-03-24 Time 12:58 Sent To  
Notes
2007-03-24 13:00:15TO "COMM" BD#18

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-07-13 Cont ID  
Sent By rregueir Date 2007-07-13 Time 09:40 Rev Time 0.00
Received By rregueir Date 2007-07-13 Time 15:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-06-13 Cont ID  
Sent By rregueir Date 2007-06-13 Time 09:54 Rev Time 0.00
Received By rregueir Date 2007-06-07 Time 19:47 Sent To  
Notes
2007-06-13 09:52:57-----------------DENIED--------------------
  
 A CALL WAS PLACED AND A MESSAGE LEFT FOR MR TWOMEY (ON
 6/7/07) TO ASK QUESTIONS REGARDING THE RESUBMITTAL BUT
 NO RETURN CALL WAS RECEIVED.
  
 1. PRODUCT APPROVAL INSTALLATION INSTRUCTIONS DO NOT
 MATCH THOSE SHOWN ON PLAN. IF STANDS ARE TO BE
 INSTALLED PER THEIR PRODUCT APPROVAL, PLEASE MAKE THE
 PLAN MATCH THE INSTRUCTIONS. FBC 106.1.1.
  
 2. RESPONSE TO PREVIOUS REVIEW COMMENTS STATES THAT THE
 HOOD SYSTEM IS "NOT TO BE INSTALLLED AT THIS TIME."
 THIS IS A COMMERCIAL KITCHEN AND WILL NOT BE CODE
 COMPLIANT WITHOUT A COMMERCIAL KITCHEN HOOD VENTILATION
 SYSTEM. FBC,M 507.2
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-16 Cont ID  
Sent By rregueir Date 2007-04-16 Time 16:33 Rev Time 0.00
Received By rregueir Date 2007-04-13 Time 10:47 Sent To  
Notes
2007-04-16 16:33:31-----------------DENIED--------------------
  
 FBC 2004 W/2006 REVISIONS
 FBC CH. 1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. EQUIPMENT STAND DETAIL: PRE-ENGINEERED EQUIPMENT
 STANDS ARE STRUCTURAL ELEMENTS AS DEFINED IN FAC 9B-72
 AND AS SUCT, PRODUCT APPROVAL IS REQUIRED.
  
 2. RTU MOUNTING DETAIL: PLEASE PROVIDE WIND LOAD
 CALCULATIONS FOR RTU WITH ATTACHMENT DETAILS BY A
 FLORIDA LICENSED STRUCTURAL ENGINEER IN SUFFICIENT
 DETAIL. WHAT IS GAUGE OF STRAP? WHAT IS THICKNESS OF
 3X3 ANGLE? FBC 106.1.2.
  
 3. SEPARATE PERMITS ARE REQUIRED FOR KITCHEN HOODS,
 HOOD SUPPRESSION SYSTEMS AND WALK IN COOLERS/FREEZERS.
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-07-13 Cont ID  
Sent By kstevens Date 2007-07-13 Time 13:43 Rev Time 0.00
Received By kstevens Date 2007-07-13 Time 13:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-06-18 Cont ID  
Sent By kstevens Date 2007-06-18 Time 15:28 Rev Time 0.00
Received By kstevens Date 2007-06-18 Time 15:28 Sent To  
Notes
2007-06-18 15:37:43DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
  
 3. SHT 3.0P GAS RISER DIAGRAM. MINIMUM 1" REQUIRED TO
 THE WATER HEATER. TABLE 402.4(2). SHOW MINIMUM VALVE
 SIZES FOR EACH GAS EQUIPMENT CONNECTING TO THE 1.5" GAS
 HEADER PER TABLE 402.4.2.
 ****RESPONSE NOTED, BUT THE PIPE & VALVE SIZES SHALL BE
 INDICATED ON THE RISER DIAGRAM. THE SIZE FOR THE WATER
 HEATER IS INDICATED AS 3/4" IN THE LOAD CALCULATIONS
 AND THE OVEN IS INDICATED AS 1/2" IN THE LOAD
 CALCULATIONS. THE OVEN IS REQUIRED TO BE 1-1/4" IF THE
 LOAD CALCULATION IS 375,000 BTU'S AS SHOWN, BUT THE NEW
 SPECIFICATION SHEET FOR EXCALIBER OVEN INDICATES THAT
 THE BTU LOAD IS 225,000 BTU'S. IF THE LATTER IS USED,
 THEN A MINIMUM 1" VALVE IS REQUIRED.
  
 4. OK
  
  
 5. THE MANUF. SPECIFICATION SHEETS FOR THE HOBART
 DOUBLE OVEN SHOWS A BTU RATING OF 318,000 BTU'S, BUT
 THE RISER DIAGRAM INDICATES 375,000BTU'S. PLEASE
 CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE NEW OVEN, (EXCALIBER), BTU
 LOAD DOES NOT REFLECT THE LOAD CALCULATIONS ON SHT
 3.0P. PLEASE CORRELATE INFORMATION FROM THE MANUF. AND
 THE LOAD CALCULATION.
  
 6. OK
 7. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-09 Cont ID  
Sent By kstevens Date 2007-04-09 Time 09:27 Rev Time 0.00
Received By kstevens Date 2007-04-07 Time 17:02 Sent To  
Notes
2007-04-09 09:58:47DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 WPB MUNICIPAL CODE
  
 1. SHTS A1.1 & 1.1ANO WATER SUPPLY OR WASTE DRAIN
 SIZE INDICATED FORITEMS 1, 2, 8, 16 & 44. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 2. GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY
 ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO
 (561) 822-2272, FAX (561) 822-2287, OR [email protected].
 MUNICIPAL CODE ARTICLE III SEWERS & SEWAGE DISPOSAL
 SECTION 90-124(7)(A) THRU (G).
  
 3. SHT 3.0P GAS RISER DIAGRAM. MINIMUM 1" REQUIRED TO
 THE WATER HEATER. TABLE 402.4(2). SHOW MINIMUM VALVE
 SIZES FOR EACH GAS EQUIPMENT CONNECTING TO THE 1.5" GAS
 HEADER PER TABLE 402.4.2.
  
 4. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE GAS
 WATER HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC 402.2.
  
  
 5. THE MANUF. SPECIFICATION SHEETS FOR THE HOBART
 DOUBLE OVEN SHOWS A BTU RATING OF 318,000 BTU'S, BUT
 THE RISER DIAGRAM INDICATES 375,000BTU'S. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 6. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505. (FOR THE WATER HEATER).
  
 7. SHT P3.0P SANITARY RISER DIAGRAM. SEPARATE DRAIN
 LINES ARE REQUIRED FOR THE ICE MAKER, AND THE ICE
 STORAGE BIN. SECTION 802.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved