Plan Review Details - Permit 07030701
Plan Review Stops For Permit 07030701
Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2008-06-07 Cont ID  
Sent By amorse Date 2008-06-07 Time 08:54 Rev Time 0.00
Received By amorse Date 2008-06-07 Time 08:54 Sent To PC
Notes
2008-06-07 08:55:59 
  
 PASSED
  
 BUILDING REVISION OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2008-04-14 Cont ID  
Sent By amorse Date 2008-04-14 Time 14:58 Rev Time 0.00
Received By amorse Date 2008-04-14 Time 14:58 Sent To E
Notes
2008-04-14 15:26:27 
  
  
 DENIED
  
 1)PROVIDE ALL MISSING PRODUCT APPROVALS, PLEASE NOTE
 THAT ROOF AND PREVIOUS SIMPSON TIE PRODUCT APPROVALS
 WERE ONLY STAMPED WITH PERMIT NUMBER THEY HAVE YET TO
 BE DATE STAMPED, ALSO ALWAYS SUBMIT ONE COPY OF OLD
 SHEETS FOR REFERENCE. WAS THE ELECTRICAL APPROVED ? ALL
 SHEETS AND APPROVALS MUST BE TOGETHER FOR REVISION TO
 PASS.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2008-03-18 Cont ID  
Sent By amorse Date 2008-03-18 Time 14:50 Rev Time 0.00
Received By amorse Date 2008-06-07 Time 08:56 Sent To E
Notes
2008-03-18 14:57:15 
  
 DENIED
  
 RESUB OF REVISION
  
 1)NO LISTING FOR SIMPSON TIE A33 COULD THIS BE
 A34/A35 PER THE PRODUCT APPROVAL THAT WAS SUBMITTED, IF
 SO PLEASE CORRECT DRAWINGS TO REFLECT.
  
 2)PROVIDE ROOF PITCH AND MEAN ROOF HEIGHT TO
 DETERMINE UPLIFT VALUE FOR ROOF TILE
  
 3)ELECTRICAL PLAN SHOWN ON SHEET SUP-2 THEREFORE AN
 ELECTRICAL REVIEW IS REQUIRED, DRAWINGS WILL BE SENT TO
 ELECTRICAL REVIEWER AND FURTHER COMMENTS MAY ARISE
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-02-26 Cont ID  
Sent By amorse Date 2008-02-26 Time 16:12 Rev Time 0.00
Received By amorse Date 2008-02-26 Time 16:12 Sent To PC
Notes
2008-02-26 16:34:00 
  
 DENIED
  
 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. PLEASE INCREASE VALUE OF PERMIT
 TO INCLUDE THE FOUNDATIONS, DECK, PERGOLA, ELECTRICAL
 AND ROOF EXTENSION THAT WILL COVER THE FUTURE SPA.
  
 2)PROVIDE 2 COPIES OF ALL PRODUCT APPROVALS REQUIRED
 BY NEW WORK, ROOF TILE AND SIMPSON TIE
 STRAPS/CONNECTORS. IN LUE OF PRODUCT APPROVALS
 STRAPS/CONNECTORS MAY BE LISTED IN A SCHEDULE ON THE
 DRAWINGS COMPLETE WITH THE STATEWIDE PRODUCT APPROVAL
 NUMBERS OR SUBMIT SIMPSON TIE?S COMPLETE FLORIDA INDEX
 WITH CONNECTORS TO BE USED HIGHLIGHTED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-02-26 Cont ID  
Sent By amorse Date 2008-02-26 Time 15:52 Rev Time 0.00
Received By amorse Date 2008-02-26 Time 15:52 Sent To PC
Notes
2008-02-26 16:03:33 
  
 REVISION PAGES A-1 THROUGH A-3 HAVE BEEN APPROVED.
 PAGES SUP1 AND SUP2WERE REMOVED FROM SUBMITTALAND
 DUE TO CHANGES IN THE SCOPE OF WORK HAVE BEEN DENIED
 PLEASE SEE BUILDINGREVIEW NUMBER 6 FOR COMMENTS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-10-30 Cont ID  
Sent By mperson Date 2007-10-30 Time 14:13 Rev Time 0.00
Received By amorse Date 2007-10-30 Time 17:55 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-25 Cont ID  
Sent By amorse Date 2007-09-25 Time 17:23 Rev Time 0.00
Received By amorse Date 2007-09-25 Time 17:23 Sent To  
Notes
2007-09-25 17:52:17 
  
 DENIED
  
 1)EXISTING BUILDINGS OF HISTORIC VALUE TO THE CITY OF
 WEST PALM BEACH ARE NOT EXEMPT BY F.S. 267.021 AND THE
 EXEMPTION UNDER 13-101.5 FBC DOES NOT APPLY TO EXISTING
 BUILDINGS THAT ARE RENOVATED. F.S. 267.021 PERTAINS TO
 HISTORIC PROPERTIES AS DEEMED BY THE DIVISION OF
 HISTORICAL RESOURCES OF THE DEPARTMENT OF STATE TO BE
 OF INTRINSIC OR ARCHAEOLOGICAL VALUE TO THE STATE, OR
 REGISTERED TO THE NATIONAL REGISTER OF HISTORICAL
 PLACES. IF THIS PROPERTY COMPLIES WITH THIS STATUTE
 PLEASE SUBMIT LETTER OF CONFIRMATION FROM THE ABOVE
 DEPT. IF THIS DOES NOT COMPLY WITH THE STATUTE PLEASE
 PROVIDE 2 COPIES OF ENERGY CALC'S AS REQUESTED.
  
 2)PER 713.13(2) F.S. IF THE IMPROVEMENT DESCRIBED IN
 THE NOC HAS NOT COMMENCED WITHIN 90 DAYS OF RECORDING,
 THE NOTICE IS VOID. PLEASE RE RECORD NOC.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
2007-06-28 16:10:42 

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-05 Cont ID  
Sent By amorse Date 2007-06-05 Time 18:08 Rev Time 0.00
Received By amorse Date 2007-06-05 Time 18:08 Sent To PC
Notes
2007-06-05 18:24:32 
  
 DENIED
  
 1)IN AN EXISTING BUILDING A DESIGN PROFESSIONAL MUST
 ELECT THE LEVEL OF ALTERATION PER 301.5 OF EXISTING
 BUILDING CODE AND STATE ALONG WITH THE TYPE OF
 CONSTRUCTION ON THE DRAWINGS
  
 2)THE WORK BEING PERMITTED IS A LEVEL 2 ALTERATION
 PER 304.1 FBC EXTG. PLEASE SEE ATTACHED COPIES OF
 CHAPTER 3 CLASSIFICATION OF WORK (SECTION 304) AND AS
 SUCH ARE REQUIRED TO COMPLY WITH 601.3 FBC EXTG. THE
 ONLY EXCEPTIONS FOR OPERABLE WINDOWS ARE FOR LIGHT,
 ENERGY AND VENTILATION NONE IS GIVEN FOR EMERGENCY
 EGRESS.
  
 3)SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL ***** 2ND REQUEST*****
  
 4)PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING THE NOTICE IS
 VOID PLEASE RERECORD NOC ******NOTE THIS ITEM MAY BE
 DONE AT TIME OF PERMIT PICKUP********
  
 5)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS
 OF NEW DRAWINGS AND INCLUDE 1 COPY OF THE OLD PAGES
 ONLY FOR REFERENCE
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-21 Cont ID  
Sent By tgordon Date 2007-05-25 Time 15:32 Rev Time 0.00
Received By amorse Date 2007-04-21 Time 13:07 Sent To PC
Notes
2007-04-21 13:07:26 
  
 DENIED
  
 1)CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION,NATURE, AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE PER 106.1.1
 FBC*
 SUBMITTAL SHALL CONTAIN AT MINIMUM AN EXISTING/DEMO
 PLAN SHOWING BUILDING AS IT IS AN WHAT WALLS, PLUMBING,
 ELECTRICAL AND MECHANICAL CHANGES ARE BEING MADE
  
 2)STRUCTURAL REQUIREMENTS SHALL INCLUDE A WALL
 SECTION FROM FOUNDATION THROUGH ROOF, INCLUDING
 ASSEMBLY AND MATERIALS, CONNECTOR TABLES, WIND
 REQUIREMENTS, AND STRUCTURAL CALCULATIONS PER 106.3.5.4
 (6) FBC*
 STRUCTURAL DETAILSARE REQUIRED FOR ANY STRUCTURAL
 WORK SUCH AS NEW STEEL CORNER POSTS, ADDED ROOF
 OVERHANG, ETC.
  
 3)PROVIDE DETAILS ON TYPE OF EXISTING CONSTRUCTION,
 REMOVAL OF STUCCO AND LATH LENDS ITSELF TO WOOD FRAME
 ?
  
 4)PROVIDE WIND DESIGN DATA ON DRAWINGS PER 1603.1.4
 FBC
  
 5)NEW BEDROOM WINDOWS TO MEET EMERGENCY EGRESS
  
 6)SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 7)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED. PLEASE NOTE THE
 FLORIDA APPROVAL NUMBERS ARE MARKED AT THE TOP OF THE
 NOA'S
  
 8)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 9)PROVIDE PRODUCT APPROVAL FOR NEW ENTRY DOOR
  
 10)DRAWINGS TO COMPLY WITH THE LATEST CODE, PLACE
 NOTE ON PLANS THAT THEY CONFORM TO THE 2004 FLORIDA
 BUILDING CODE WITH 2006 REVISIONS
  
 11)CORRECT OWNER AND ADDRESS AS PAPA SHOWS ONLY ONE
 OWNER AND ONE ADDRESS
  
 12)MORE COMMENTS MAY BE FORTHCOMING WHEN REQUIRED
 DRAWINGS ARE SUBMITTED.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-06-02 Cont ID  
Sent By btrobaug Date 2008-06-02 Time 09:20 Rev Time 0.00
Received By btrobaug Date 2008-06-02 Time 08:24 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-04-15 Cont ID  
Sent By btrobaug Date 2008-04-15 Time 15:48 Rev Time 0.00
Received By btrobaug Date 2008-04-15 Time 15:48 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-03-19 Cont ID  
Sent By btrobaug Date 2008-03-19 Time 15:52 Rev Time 0.00
Received By btrobaug Date 2008-03-19 Time 15:52 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-02-19 Cont ID  
Sent By btrobaug Date 2008-02-19 Time 08:52 Rev Time 0.00
Received By btrobaug Date 2008-02-19 Time 07:51 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-09-11 Cont ID  
Sent By btrobaug Date 2007-09-11 Time 08:18 Rev Time 0.00
Received By btrobaug Date 2007-09-11 Time 08:07 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-05-23 Cont ID  
Sent By btrobaug Date 2007-05-23 Time 09:24 Rev Time 0.50
Received By btrobaug Date 2007-05-23 Time 08:45 Sent To P
Notes
2007-05-23 09:24:42 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GENERATOR, SEE
 ATTACHED REQUIREMENTS FOR THAT PERMIT.
  
 1} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CORRECT ALL NOTES TO REFLECT THIS
 CHANGE.
  
 2} INDICATE IF THE SERVICE RISER ON THE PLAN IS PART OF
 THIS APPLICATION OR EXISTING.
  
 3} IF THE SERVICE IS NEW: PER 110.9 AND 110.10: OBTAIN
 THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 4} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). INDICATE BATH CIRCUIT IN
 THE PANEL SCHEDULE. THE MASTER BATH NEEDS ANOTHER
 RECEPTACLE TO MEET SPACING PER 210.52(D).
  
 5} ONE RECEPTACLE NEEDS TO BE ADDED IN THE MASTER
 BEDROOM PER 210.52(A)(2).
  
 6} PER R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS
 REQUIRED IN NEW DWELLINGS AND WHEN REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR. SEE ARTICLE FOR COMPLETE
 TEXT.ALSO SEE THE DEFINITION OF "SMOKE DETECTORS"
 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS,
 TO AVOID CONFUSION IN THE FIELD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-28 Cont ID  
Sent By btrobaug Date 2007-03-28 Time 17:18 Rev Time 0.25
Received By btrobaug Date 2007-03-28 Time 17:15 Sent To M
Notes
2007-03-28 17:18:09 
  
 DENIED/INCOMPLETE INFORMATION
  
 AN ELECTRICAL PERMIT IS REQUIRED FOR THE SCOPE OF WORK
 INDICATED ON THE APPLICATION. SUBMIT PLANS DETAILING
 ALL ELECTRICAL WORK BEING DONE.106.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2007-10-30 Cont ID  
Sent By mperson Date 2007-10-30 Time 13:36 Rev Time 0.00
Received By mperson Date 2007-10-30 Time 13:36 Sent To B
Notes
2007-10-30 13:42:53CONTRACTOR INFORMATION
 NOTE: SHEET A-2 ON THE PLANS INDICATE A GAS RANGE/OVEN
 WITH HOOD.
 GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2007-09-24 Cont ID  
Sent By mperson Date 2007-09-24 Time 15:05 Rev Time 0.00
Received By mperson Date 2007-09-24 Time 15:05 Sent To M
Notes
2007-09-24 15:10:36CONTRACTOR INFORMATION
 NOTE: SHEET A-2 ON THE PLANS INDICATE A GAS RANGE/OVEN
 WITH HOOD.
 GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL INSPECTION.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-03-20 Cont ID  
Sent By swurafti Date 2007-03-20 Time 09:31 Rev Time 0.00
Received By swurafti Date 2007-03-20 Time 09:31 Sent To  
Notes
2007-03-20 09:31:35HISTORIC APPROVED BY JPAPA

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-06-11 Cont ID  
Sent By adarroug Date 2008-06-11 Time 16:39 Rev Time 0.00
Received By adarroug Date 2008-06-11 Time 16:39 Sent To M
Notes
2008-06-11 16:40:15TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-05-22 Cont ID  
Sent By adarroug Date 2008-05-22 Time 11:19 Rev Time 0.00
Received By adarroug Date 2008-05-22 Time 11:19 Sent To Z
Notes
2008-05-22 11:19:32TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-04-04 Cont ID  
Sent By adarroug Date 2008-04-04 Time 14:40 Rev Time 0.00
Received By adarroug Date 2008-04-04 Time 14:40 Sent To P
Notes
2008-04-04 14:41:18TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-04-03 Cont ID  
Sent By adarroug Date 2008-04-03 Time 13:37 Rev Time 0.00
Received By adarroug Date 2008-04-03 Time 13:37 Sent To Z
Notes
2008-04-03 13:37:39TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-03-10 Cont ID  
Sent By adarroug Date 2008-03-10 Time 10:58 Rev Time 0.00
Received By adarroug Date 2008-03-10 Time 10:58 Sent To Z
Notes
2008-03-10 10:58:59TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-02-12 Cont ID  
Sent By adarroug Date 2008-02-12 Time 11:35 Rev Time 0.00
Received By adarroug Date 2008-02-12 Time 11:35 Sent To E
Notes
2008-02-12 11:36:45TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-10-17 Cont ID  
Sent By adarroug Date 2007-10-17 Time 09:47 Rev Time 0.00
Received By adarroug Date 2007-10-17 Time 09:47 Sent To M
Notes
2007-10-17 09:47:30TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-09-10 Cont ID  
Sent By adarroug Date 2007-09-10 Time 10:29 Rev Time 0.00
Received By adarroug Date 2007-09-10 Time 10:29 Sent To E
Notes
2007-09-10 10:29:38TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-04 Cont ID  
Sent By adarroug Date 2007-09-04 Time 15:54 Rev Time 0.00
Received By adarroug Date 2007-09-04 Time 15:54 Sent To Z
Notes
2007-09-04 15:54:49TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-14 Cont ID  
Sent By adarroug Date 2007-05-14 Time 15:07 Rev Time 0.00
Received By adarroug Date 2007-05-14 Time 15:07 Sent To E
Notes
2007-05-14 15:07:35TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-27 Cont ID  
Sent By spalmer Date 2007-03-27 Time 17:36 Rev Time 0.00
Received By spalmer Date 2007-03-27 Time 17:36 Sent To  
Notes
2007-03-27 17:36:36SFR "ELEC"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-04-21 Time   Rev Time 0.00
Received By adarroug Date 2007-03-23 Time 08:46 Sent To  
Notes
2007-03-23 08:47:08TO "Z" BOX

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2008-05-29 Cont ID  
Sent By rkussner Date 2008-05-29 Time 09:31 Rev Time 0.00
Received By rkussner Date 2008-05-29 Time 09:31 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-04-04 Cont ID  
Sent By rkussner Date 2008-04-04 Time 17:33 Rev Time 0.00
Received By rkussner Date 2008-04-04 Time 17:29 Sent To  
Notes
2008-04-04 17:52:151.PROVIDE SOD AND IRRIGATION IN THE RIGHTS-OF-WAY.
 IRRIGATION IS REQUIRED THROUGHOUT THE SITE.
 2.THE FICUS HEDGE ALONG THE CITY SIDEWALK SHALL BE
 REMOVED.IT RESTRICTS VISIBILITY AT THE CORNER. 3.
 PROVIDE THE LANDSCAPE CALCULATIONS FOR SINGLE FAMILY ON
 THE LANDSCAPE PLAN.
 4.THE RIVER ROCK PARKING COURT IS NOT ACCEPTABLE. IT
 MUST BE A NONDUSTING SURFACE.
 5.PLEASE PROVIDE THE SCIENTIFIC NAME FOR ALL PROPOSED
 PLANT MATERIAL.SOME OF THE COMMON NAMES USED ARE
 UNFAMILIAR.
 6.THOUGH MULCH IS ALLOWED, IT SHOULD NOT BE USED
 ENTIRELY AS A GROUND COVER.IT SHOULD BE USED IN
 CONJUNCTION WITH LIVE SHRUBS AND GROUND COVER OR
 DROUGHT TOLERANT SOD.
 7.ALL EXISTING PLANT MATERIAL SHALL BE CLEARLY
 IDENTIFIED AND NEW PLANT MATERIAL SHALL BE DISPLAYED IN
 A PLANT SCHEDULE WITH THE PLANT NAME, QUANTITY, SIZE
 AND SPACING.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-06-12 Cont ID  
Sent By tgordon Date 2008-06-12 Time 09:44 Rev Time 0.30
Received By tgordon Date 2008-06-12 Time 09:44 Sent To P
Notes
2008-06-12 09:47:49REVISION TO MECHANICAL PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2008-06-05 Cont ID  
Sent By tgordon Date 2008-06-05 Time 09:16 Rev Time 1.30
Received By tgordon Date 2008-06-05 Time 09:16 Sent To B
Notes
2008-06-05 09:34:21PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** REVISION TO PLANS **
 *** DENIED ***
  
 1) THE MECHANICAL PLAN STILL SHOWS WHAT MAY BE A GAS
 TANKLESS WATER HEATER IN THE CLOSET WITH THE AIR
 HANDLER, BUT THE ELECTRICAL PLAN SHOWS THE GAS TANKLESS
 WATER HEATER OUT DOORS. PLEASE CORRECT THE PLANS SO THE
 ELECTRICAL AND MECHANICAL COINCIDE WITH EACH-OTHER AND
 ARE CORRECT. PER 2004 FBC 106.1.1.
  
 2) THE MECHANICAL PLAN SHOWS THE AIR HANDLER IN A
 CLOSET WITH THE CLOTHES WASHER AND DRYER, THE
 ELECTRICAL PLAN SHOWS THE AIR HANDLER IN IT'S OWN
 LITTLE CLOSET. WHICH IS CORRECT? THE TWO PLANS MUST
 COINCIDE, PLEASE CORRECT, PER 2004 FBC 106.1.1.
  
 3) A COMPLETE PLANS REVIEW CAN NOT BE DONE WHEN THE
 PLANS CONTRADICT THEMSELVES. CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE AND RELEVANT LAWS, PER 2004 F.B.C.
 106.1.1.
  
 4) PLEASE SHOW THE SIZE OF THE RETURN AIR GRILL TO THE
 AIR HANDLER.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-02-22 Cont ID  
Sent By tgordon Date 2008-02-22 Time 08:56 Rev Time 0.30
Received By tgordon Date 2008-02-22 Time 08:56 Sent To B
Notes
2008-02-22 08:56:51*** PROVISO ***
 1) PER 2004 FBC/R M1602 RETURN AIR, M1602.2 PROHIBITED
 SOURCES.
 OUTSIDE OR RETURN AIR FOR A FORCED-AIR HEATING OR
 COOLING SYSTEM SHALL NOT BE TAKEN FROM THE FOLLOWING
 LOCATIONS:
 #5. A ROOM OR SPACE CONTAINING A FUEL-BURNING
 APPLIANCE WHERE SUCH ROOM OR SPACE SERVES AS THE SOLE
 SOURCE OF RETURN AIR.
  
 2) PER 2004 FBC/R M2005.2 PROHIBITED LOCATIONS.
 FUEL-FIRED WATER HEATERS SHALL NOT BE INSTALLED IN A
 ROOM USED AS A STORAGE CLOSET. WATER HEATERS LOCATED IN
 A BEDROOM OR BATHROOM SHALL BE INSTALLED IN A SEALED
 ENCLOSURE SO THAT COMBUSTION AIR WILL NOT BE TAKEN FROM
 THE LIVING SPACE. DIRECT-VENT WATER HEATERS ARE NOT
 REQUIRED TO BE INSTALLED WITHIN AN ENCLOSURE.
  
 3) GAS WATER HEATER SHALL COMPLY WITH 2004 FBC/R
 G2407.1 COMBUSTION, VENTILATION AND DILUTION AIR. AND
 G2407.4 MAKEUP AIR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-10-22 Cont ID  
Sent By mperson Date 2008-02-19 Time 14:08 Rev Time 0.40
Received By tgordon Date 2007-10-22 Time 10:43 Sent To P
Notes
2007-10-22 11:09:38*** PROVISO ***
 1) PER 2004 FBC/R M1602 RETURN AIR, M1602.2 PROHIBITED
 SOURCES.
 OUTSIDE OR RETURN AIR FOR A FORCED-AIR HEATING OR
 COOLING SYSTEM SHALL NOT BE TAKEN FROM THE FOLLOWING
 LOCATIONS:
 #5. A ROOM OR SPACE CONTAINING A FUEL-BURNING
 APPLIANCE WHERE SUCH ROOM OR SPACE SERVES AS THE SOLE
 SOURCE OF RETURN AIR.
  
 2) PER 2004 FBC/R M2005.2 PROHIBITED LOCATIONS.
 FUEL-FIRED WATER HEATERS SHALL NOT BE INSTALLED IN A
 ROOM USED AS A STORAGE CLOSET. WATER HEATERS LOCATED IN
 A BEDROOM OR BATHROOM SHALL BE INSTALLED IN A SEALED
 ENCLOSURE SO THAT COMBUSTION AIR WILL NOT BE TAKEN FROM
 THE LIVING SPACE. DIRECT-VENT WATER HEATERS ARE NOT
 REQUIRED TO BE INSTALLED WITHIN AN ENCLOSURE.
  
 3) GAS WATER HEATER SHALL COMPLY WITH 2004 FBC/R
 G2407.1 COMBUSTION, VENTILATION AND DILUTION AIR. AND
 G2407.4 MAKEUP AIR.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-09-24 Cont ID  
Sent By tgordon Date 2007-09-24 Time 16:39 Rev Time 0.30
Received By tgordon Date 2007-09-24 Time 16:39 Sent To B
Notes
2007-09-24 16:49:45PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 5-25-07 NOTE #2. PLEASE
 SUBMIT COOLING LOAD CALCULATIONS, SEE FBC/R M1401.3.
 (THE HISTORICAL EXEMPTION IS FOR ENERGY CALCULATIONS
 NOT COOLING LOAD CALCULATIONS).
  
 2) THE AIR HANDLER HAS A 8" X 12" DUCT FEEDING TWO 12"
 DUCTS THIS WOULD APPEAR TO BE A RESTRICTION OF AIR,
 PLEASE SUBMIT MANUAL D CALCULATIONS FOR RESIDENTIAL
 DUCT DESIGN OR ANOTHER APPROVED METHOD, PER 2004 FBC/R
 M1601.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-05-25 Cont ID  
Sent By tgordon Date 2007-05-25 Time 14:39 Rev Time 0.50
Received By tgordon Date 2007-05-25 Time 14:39 Sent To B
Notes
2007-05-25 15:02:12*** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-101.2.3.
  
 2) PLEASE SUBMITCOOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-607.1.ABC.1.
  
 3) SHOW ON MECHANICAL PLANS THE LOCATION OF THE A/C
 CONDENSER UNIT AND THE CLOTHES DRYER VENT AND WERE IT
 WILL TERMINATE. BE ADVISED CLOTHES DRYER VENT
 TERMINATION MAY NOT BE NEAR THE A/C CONDENSER UNIT, SEE
 2004 FBC/M 501.2 .
  
 4) PLEASE SHOW ON THE MECHANICAL PLANS EQUIPMENT
 SCHEDULE, THE TOTAL AND SENSIBLE COOLING BTU'S.
  
 5) SEE MECH. PLANS THE SUPPLY AIR DUCT FROM ONE MIXING
 BOX TO THE OTHER SHOWS 530 CFM BUT NO DUCT SIZE, PLEASE
 CORRECT.
  
 6) SEE MECH. PLANS, THE 8X12 SUPPLY AIR DUCT LEAVING
 THE AIR HANDLER IS TO SMALL AS IT IS FEEDING TWO DUCTS
 12" AND A 530 CFM?, PLEASE CORRECT.
  
 7) SEE MECH. PLANS A 12' SUPPLY AIR DUCT IS FEEDING A
 14X14 SUPPLY DUCT, THIS WOULD REDUCE THE AIR VELOCITY
 QUITE A BIT, PLEASE CHECK AND CORRECT.
  
 8) THE RETURN AIR GRILL IN THE HALLWAY TO THE AIR
 HANDLER NEEDS TO BE SIZED.
  
 9) THE 20X4 RETURN AIR TRANSFER GRILL TO THE MASTER
 SUITE IS TO SMALL, SEE 2004 FBC/R M1602.4 (B) AND (C)
 EXCEPT. PLEASE CORRECT.
  
 *** 2004 FBC/R M1602.4BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-29 Cont ID  
Sent By tgordon Date 2007-03-29 Time 15:56 Rev Time 0.20
Received By tgordon Date 2007-03-29 Time 15:56 Sent To P
Notes
2007-03-29 16:00:32*** DENIED ***
 1) NO MECHANICAL A/C PLANS WERE SUBMITTED FOR
 REVIEW. PLEASE SUBMIT MECHANICAL A/C PLANS
 FOR REVIEW AS PERMIT APPLICATION STATES UPGRADE TO
 MECHANICAL. SEE 2004 FBC CITY WPB AMEND. 106.3.5.4
 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 9 Status P Date 2008-06-12 Cont ID  
Sent By mperson Date 2008-06-12 Time 10:15 Rev Time 0.00
Received By mperson Date 2008-06-12 Time 10:15 Sent To  
Notes
2008-06-12 10:29:47REVISION: NEW SHEETS ONLY NO PLUMBING CHANGES
  
 ****************PROVISO****************
 (A) 802.2 DOMESTIC DISHWASHING MACHINES SHALL
 DISCHARGE INTO A WYE-BRANCH FITTING ON THE TAILPIECE OF
 THE KITCHEN SINK OR THE DISHWASHER CONNECTION OF A FOOD
 WASTE GRINDER.
  
 (B) PER FBC-2004 PLUMBING, SECTION 704.5
 DEAD ENDS: IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 A DEMO PLUMBING PERMIT REQUIRED AND
 INSPECTION REQUIRED OF DEMO WORK PRIOR
 TO COVERING DEMO WORK WITH FINNISH
 WALLS, CIELINGS, OR POURED CONCRETE
 SLABS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 8 Status F Date 2008-06-04 Cont ID  
Sent By mperson Date 2008-06-04 Time 16:15 Rev Time 0.00
Received By mperson Date 2008-06-04 Time 16:15 Sent To M
Notes
2008-06-04 16:52:25PLUMBING PLAN REVIEW:
 REVISION DENIED OF NON-NUMBERED LANDSCAPE AND
 IRRIGATION PLAN SHEETS:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE FOR THE
 NEWLY SUBMITTED NON-NUMBERED LANDSCAPE AND IRRIGATION
 PLAN.
  
 1. THE NON-NUMBERED LANDSCAPE AND IRRIGATION PLAN
 SHEETS REQUIRE A TITLE BLOCK FROM THE LANDSCAPE
 ARCHITECT.
 FAC-61G1-16.004 TITLE BLOCK:
 A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED
 SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
 NOTE: THE FOLLOWING INFORMATION IS MISSING FROM THE
 PLAN SHEETS (1), (2) AND (6). PLEASE COMPLY WITH THE
 REQUIRED INFORMATION ON THE REVISION RESUBMITTAL OF
 THESE SHEETS.
  
 2. THE SUBMITTED IRRIGATION PLANS SHALL CLEARLY
 INDICATE THE FOLLOWING (NOTE: AN EQUIPMENT INDEX IS
 HELPFUL TO IDENTIFY ITEMS ON THE PLANS):
  
 A} CONTROL PANEL
 B} RAIN SENSOR
 C} TIME CLOCK
 D} WATER SOURCE
 A- IF ITS CITY WATER, PLEASE INDICATE SO ON PLANS
 ALONG WITH THE BACKFLOW PREVENTER LOCATION.
 B- IF ITS A WELL, PLEASE INDICATE SO ON THE PLANS
 ALONG WITH THE PUMP LOCATION.
 C- IF ITS PUMPED FROM A LAKE/CANAL, PLEASE INDICATE
 SO ON THE PLANS ALONG WITH THE PUMP LOCATION.
  
 3. HAND WRITTEN CHANGES TO SIGNED AND SEALED PLANS IS
 UNACCEPTABLE. PER (W.P.B. AS AMENDED) SECTION 106.1.3
 QUALITY OF BUILDING PLANS. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR
 PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY
 MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE,
 CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 7 Status P Date 2008-06-04 Cont ID  
Sent By mperson Date 2008-06-04 Time 15:40 Rev Time 0.00
Received By mperson Date 2008-06-04 Time 15:40 Sent To M
Notes
2008-06-04 15:47:11REVISION #3 FOR SHEET A-2 DATED 4/17/08 AND REVISION #4
 FOR SHEET A-3 DATED 5/8/08: "OK" NEW SHEETS WITH NO
 PLUMBING CHANGES.
  
 ****************PROVISO****************
 (A) 802.2 DOMESTIC DISHWASHING MACHINES SHALL
 DISCHARGE INTO A WYE-BRANCH FITTING ON THE TAILPIECE OF
 THE KITCHEN SINK OR THE DISHWASHER CONNECTION OF A FOOD
 WASTE GRINDER.
  
 (B) PER FBC-2004 PLUMBING, SECTION 704.5
 DEAD ENDS: IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 A DEMO PLUMBING PERMIT REQUIRED AND
 INSPECTION REQUIRED OF DEMO WORK PRIOR
 TO COVERING DEMO WORK WITH FINNISH
 WALLS, CIELINGS, OR POURED CONCRETE
 SLABS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 6 Status F Date 2008-04-07 Cont ID  
Sent By mperson Date 2008-04-07 Time 16:04 Rev Time 0.00
Received By mperson Date 2008-04-07 Time 16:04 Sent To PC
Notes
2008-04-07 16:20:44PLUMBING PLAN REVIEW:
 PRODUCT APPROVAL DENIED:
  
 PLAN REVIEW (PRODUCT APPROVAL) UNDER THE 2004 FLORIDA
 BUILDING CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 1. THE SUBMITTED PRODUCT APPROVAL FOR THE SHOWER PAN
 LINER HAS BEEN DENIED. THE SUBMITTED PRODUCT APPROVAL
 FOR THE SHOWER PAN LINER IS NOT COMPLIANT WITH FBC
 PLUMBING THE FOLLOWING SECTIONS.
  
 417.5.2 SHOWER LINING.
 FLOORS UNDER SHOWER COMPARTMENTS, EXCEPT WHERE
 PREFABRICATED RECEPTORS HAVE BEEN PROVIDED, SHALL BE
 LINED AND MADE WATER TIGHT UTILIZING MATERIAL COMPLYING
 WITH SECTIONS 417.5.2.1 THROUGH 417.5.2.4 . SUCH LINERS
 SHALL TURN UP ON ALL SIDES AT LEAST 2 INCHES (51 MM)
 ABOVE THE FINISHED THRESHOLD LEVEL. LINERS SHALL BE
 RECESSED AND FASTENED TO AN APPROVED BACKING SO AS NOT
 TO OCCUPY THE SPACE REQUIRED FOR WALL COVERING, AND
 SHALL NOT BE NAILED OR PERFORATED AT ANY POINT LESS
 THAN 1 INCH (25 MM) ABOVE THE FINISHED THRESHOLD.
 LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED
 TOWARD THE FIXTURE DRAINS AND BE SECURELY FASTENED TO
 THE WASTE OUTLET AT THE SEEPAGE ENTRANCE, MAKING A
 WATER-TIGHT JOINT BETWEEN THE LINER AND THE OUTLET.
  
 417.5.2.1 PVC SHEETS.
 PLASTICIZED POLYVINYL CHLORIDE (PVC) SHEETS SHALL BE A
 MINIMUM OF 0.040 INCH (1.02 MM) THICK, AND SHALL MEET
 THE REQUIREMENTS OF ASTM D 4551. SHEETS SHALL BE JOINED
 BY SOLVENT WELDING IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS.
  
 417.5.2.2 CHLORINATED POLYETHYLENE (CPE) SHEETS.
 NONPLASTICIZED CHLORINATED POLYETHYLENE SHEET SHALL BE
 A MINIMUM 0.040 INCH (1.02 MM) THICK, AND SHALL MEET
 THE REQUIREMENTS OF ASTM D 4068. THE LINER SHALL BE
 JOINED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS.
  
 417.5.2.3 SHEET LEAD.
 SHEET LEAD SHALL NOT WEIGH LESS THAN 4 POUNDS PER
 SQUARE FOOT (19.5 KG/M 2 ) COATED WITH AN ASPHALT PAINT
 OR OTHER APPROVED COATING. THE LEAD SHEET SHALL BE
 INSULATED FROM CONDUCTING SUBSTANCES OTHER THAN THE
 CONNECTING DRAIN BY 15-POUND (6.80 KG) ASPHALT FELT OR
 ITS EQUIVALENT. SHEET LEAD SHALL BE JOINED BY BURNING.
  
  
 417.5.2.4 SHEET COPPER.
 SHEET COPPER SHALL CONFORM TO ASTM B 152 AND SHALL NOT
 WEIGH LESS THAN 12 OUNCES PER SQUARE FOOT (3.7 KG/M 2
 ). THE COPPER SHEET SHALL BE INSULATED FROM CONDUCTING
 SUBSTANCES OTHER THAN THE CONNECTING DRAIN BY 15-POUND
 (6.80 KG) ASPHALT FELT OR ITS EQUIVALENT. SHEET COPPER
 SHALL BE JOINED BY BRAZING OR SOLDERING.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-02-19 Cont ID  
Sent By mperson Date 2008-02-19 Time 13:49 Rev Time 0.00
Received By mperson Date 2008-02-19 Time 13:49 Sent To M
Notes
2008-02-19 13:51:08REVISION #2 DATED 2/6/08: "OK" NEW SHEETS WITH NO
 PLUMBING CHANGES.
  
 ****************PROVISO****************
 (A) 802.2 DOMESTIC DISHWASHING MACHINES SHALL
 DISCHARGE INTO A WYE-BRANCH FITTING ON THE TAILPIECE OF
 THE KITCHEN SINK OR THE DISHWASHER CONNECTION OF A FOOD
 WASTE GRINDER.
  
 ****************PROVISO****************
 PER FBC-2004 PLUMBING, SECTION 704.5
 DEAD ENDS: IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 A DEMO PLUMBING PERMIT REQUIRED AND
 INSPECTION REQUIRED OF DEMO WORK PRIOR
 TO COVERING DEMO WORK WITH FINNISH
 WALLS, CIELINGS, OR POURED CONCRETE
 SLABS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-10-30 Cont ID  
Sent By mperson Date 2007-10-30 Time 13:30 Rev Time 0.00
Received By mperson Date 2007-10-30 Time 13:30 Sent To G
Notes
2007-10-30 13:36:15****************PROVISO****************
 (A) 802.2 DOMESTIC DISHWASHING MACHINES SHALL
 DISCHARGE INTO A WYE-BRANCH FITTING ON THE TAILPIECE OF
 THE KITCHEN SINK OR THE DISHWASHER CONNECTION OF A FOOD
 WASTE GRINDER.
  
 ****************PROVISO****************
 PER FBC-2004 PLUMBING, SECTION 704.5
 DEAD ENDS: IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 A DEMO PLUMBING PERMIT REQUIRED AND
 INSPECTION REQUIRED OF DEMO WORK PRIOR
 TO COVERING DEMO WORK WITH FINNISH
 WALLS, CIELINGS, OR POURED CONCRETE
 SLABS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-09-24 Cont ID  
Sent By mperson Date 2007-09-24 Time 14:26 Rev Time 0.00
Received By mperson Date 2007-09-24 Time 14:26 Sent To G
Notes
2007-09-24 14:29:32****************PROVISO****************
 (A) 802.1.6 DOMESTIC DISHWASHING MACHINES SHALL
 DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK
 INTO A STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH
 SECTION 802.2 OR DISCHARGE INTO A WYE-BRANCH FITTING ON
 THE TAILPIECE OF THE KITCHEN SINK OR THE DISHWASHER
 CONNECTION OF A FOOD WASTE GRINDER.
  
 ****************PROVISO****************
 PER FBC-2004 PLUMBING, SECTION 704.5
 DEAD ENDS: IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 A PLUMBING PERMIT REQUIRED AND
 INSPECTION REQUIRED OF DEMO WORK PRIOR
 TO COVERING DEMO WORK WITH FINNISH
 WALLS, CIELINGS, OR POURED CONCRETE
 SLABS.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-05-25 Cont ID  
Sent By mperson Date 2007-05-25 Time 11:01 Rev Time 0.45
Received By mperson Date 2007-05-25 Time 11:01 Sent To M
Notes
2007-05-25 13:03:47DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET A-3 SANITARY RISER: PER FBC-2004 CHAPTER 1,
 SECTION 106.3.5.4 RESIDENTIAL (ONE AND TWO-FAMILY)
 PLEASE SUBMIT A PLUMBING SANITARY ISOMETRIC RISER
 DIAGRAM INDICATING ALL WASTE, VENTS, TRAPS AND SIZES
 WITH CLEANOUT LOCATIONS.
 NOTE: NOT ALL WASTE, VENTS, AND TRAPS ARE SIZED. PLEASE
 CORRECT THIS ON THE RESUBMITTAL.
  
 2. SHEET A-3 SANITARY RISER: THE WASHING MACHINE NEEDS
 TO DISCHARGE DOWNSTREAM OF THE EXISTING WET VENTED BATH
 2 BATHROOM GROUP.
 NOTE: PER FBC-2004, PLUMBING, SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
  
 3. SHEET A-3 SANITARY RISER: THE WASHING MACHINE
 BRANCH DRAIN AND STACK ARE SIZED WRONG. PLEASE CORRECT
 THE FOLLOWING FOR THE WASHING MACHINE PER FBC-2004
 PLUMBING
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER. PLEASE CORRECT THE SIZING ON THE
 RESUBMITTAL.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE THE WASHING MACHINE
 STANDPIPE ON THE RESUBMITTAL.
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE THREE
 INCH (3"). PLEASE INDICATE THIS ON THE RESUBMITTAL.
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: PLEASE INDICATE THE WASHING MACHINE CLEANOUT AT
 FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.).
  
 4. SHEET A-3 SANITARY RISER:
 FBC-2004 PLUMBING
 (A) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE AN
 APPROVED TWO-WAY CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
  
 5. SHEET A-3 SANITARY RISER: TRAPS ARE REQUIRED FOR
 THE PROPOSED SHOWER IN BATH 2 AND THE MASTER BATH
 SHOWER PER FBC-2004 PLUMBING, SECTION 1002.1.
  
 6. SHEET A-3 SANITARY RISER: THE DISHWASHER DRAIN IS
 INDICATED WRONG.
 (A) 802.2 DISHWASHER SHALL DISCHARGE INTO A
 WYE-BRANCH FITTING ON THE TAILPIECE OF THE KITCHEN SINK
 OR THE DISHWASHER CONNECTION OF A FOOD WASTE GRINDER.
 PLEASE CORRECT THIS ON THE RESUBMITTAL.
  
 7. SHEET A-3 SAINTARY RISER: PLEASE INDICATE THE
 PIPING TO THE WATER CLOSETS WITH QUARTER BENDS ON THE
 RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-09 Cont ID  
Sent By mperson Date 2007-04-09 Time 13:33 Rev Time 0.33
Received By mperson Date 2007-04-09 Time 13:33 Sent To B
Notes
2007-04-09 13:42:46DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTIONS/INFORMATIONREQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. MORE INFORMATION IS REQUIRED. PLEASE
 INDICATE ON THE DRAWING THE EXISTING PLUMBING LAYOUT,
 AND ON A SEPERATE DRAWING PLEASE INDICATE THE NEW
 PROPOSED
 PLUMBING LAYOUT.
 A} IF PLUMBING LAYOUT IS THE SAME
 WITH NO CHANGES, PLEASE INDICATE THIS ON
 THE DRAWING.
 B} IF PLUMBING LAYOUT IS THE
 SAME AND THE PLUMBING FIXTURES ARE TO BE
 CHANGED, PLEASE INDCATE ON THE DRAWING.
 "EXACT FIXTURE CHANGE OUT ONLY."
 C} IF THE NEW PROPOSED PLUMBING LAYOUT IS DIFFERENT
 FROM THE EXISTING PLEASE FOLLOW WHAT IS REQUIRED IN
 COMMENT #2.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWOFAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 5 Status P Date 2008-05-29 Cont ID  
Sent By eschneid Date 2008-05-29 Time 11:21 Rev Time 0.00
Received By eschneid Date 2008-05-29 Time 11:21 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2008-04-07 Cont ID  
Sent By adavila Date 2008-04-07 Time 10:39 Rev Time 0.00
Received By adavila Date 2008-04-04 Time 10:39 Sent To I
Notes
2008-04-07 10:39:54PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. REPEAT COMMENT - PROVIDE LANDSCAPE AND IRRIGATION
 PLANS SHOWING COMPLIANCE WITH ARTICLE XIV.
 A. LANDSCAPE PLAN SHALL INCLUDE A DATA TABLE COMPARING
 THE AMOUNT OF LANDSCAPING REQUIRED PER THE ZONING AND
 LAND DEVELOPMENT REGULATIONS VS. WHAT IS PROPOSED.
 B. PROVIDE A LIST OF ALL PROPOSED LANDSCAPE MATERIALS,
 TO INCLUDE SPECIES, HEIGHT AND SPREAD DIMENSIONS, AND
 QUANTITIES.
 C. PURSUANT TO SECTION 94-446(2), ALL LANDSCAPED AREAS,
 EXCLUDING REESTABLISHED NATIVE NONINVASIVE PLANT AREAS,
 SHALL BE PROVIDED WITH A PERMANENT AUTOMATIC IRRIGATION
 SYSTEM.AN IRRIGATION PLAN SHALL BE SUBMITTED AS PART
 OF THIS PERMIT APPLICATION.
 D. A FICUS HEDGE IS BEING PROPOSED OVER THE PEDESTRIAN
 WALKWAY.PLEASE REVISE.
  
 2. LANDSCAPE PLAN DOES NOT MATCH SITE PLAN.
 A. ACCORDING TO THE SITE PLAN, GRAVEL PARKING IS BEING
 PROPOSED ON THE WEST SIDE OF THE NEW RAISED DECK.
 HOWEVER, ACCORDING TO THE LANDSCAPE PLAN, CYPRESS MULCH
 IS BEING PROPOSED AT THIS SAME LOCATION.PLEASE
 REVISE.
 B. PLEASE NOTE THAT PER SECTION 94-485(E), ALL PARKING
 AND LOADING SPACES, ACCESS DRIVES, AND MANEUVERING
 LANES SHALL BE PAVED WITH A NONDUSTING SURFACE IN
 COMPLIANCE WITH STANDARDS SPECIFIED BY THE CITY.
 NEITHER GRAVEL, RIVER ROCK, OR MULCH MAY BE USED FOR
 PARKING.
 C. CONCRETE PATIO AREA IS NOT DEFINED IN THE SITE
 PLAN.
  
 3. PURSUANT TO SECTION 94-305(E), AT ANY ROAD
 INTERSECTION, VISIBILITY SHALL NOT BE OBSCURED BY THE
 CONSTRUCTION, PLACEMENT, OR MAINTENANCE OF A STRUCTURE
 WALL, SIGN, FENCE, BERM, PLANT MATERIAL, SHRUBS, OR ANY
 SIMILAR ITEM BETWEEN 18 INCHES OR 8 FEET IN HEIGHT
 WITHIN THE VISIBILITY TRIANGLE.THE VISIBILITY
 TRIANGLE SHALL BE PROVIDED ON ALL PLANS SHOWING
 COMPLIANCE WITH THIS REQUIREMENT.
  
 4. PURSUANT TO SECTION 94-442(B)(1), ALL OPEN SPACE,
 EXCLUDING VEHICULAR AND PEDESTRIAN CIRCULATION FEATURES
 AND SURFACE PARKING, SHALL BE COVERED WITH GRASS,
 GROUND COVER, SHRUBBERY, OR OTHER SUITABLE PLANT
 MATERIAL.PROVIDE DETAILS OF WHAT THE CYPRESS MULCH
 AREAS ARE GOING TO BE USED FOR.IF THIS IS TO BE OPEN
 SPACE OR YARD, THEN MULCH MAY NOT BE USED.
  
 5. PLEASE NOTE THAT ALL PROPOSED WALLS AND FENCES SHALL
 BE APPROVED ON A SEPARATE PERMIT.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 3 Status F Date 2008-03-14 Cont ID  
Sent By adavila Date 2008-03-14 Time 12:55 Rev Time 0.00
Received By adavila Date 2008-03-11 Time 12:04 Sent To B
Notes
2008-03-14 12:56:17PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PROVIDE TWO COPIES OF A SIGNED AND SEALED SURVEY
 SHOWING ALL EASEMENTS AND RIGHTS-OF-WAY.SURVEY SHALL
 BE WITHIN ONE YEAR OLD.
  
 2. PURSUANT TO SECTION 94-441(C)(2), RENOVATIONS,
 REPAIR, ALTERATION OR REDEVELOPMENT WHICH EXCEED 50
 PERCENT OF THE VALUE OF THE STRUCTURE SHALL COMPLY WITH
 THE REQUIREMENTS OF ARTICLE XIV OF THE ZONING AND
 LANDSCAPE REGULATIONS.PROVIDE LANDSCAPE AND
 IRRIGATION PLANS SHOWING COMPLIANCE WITH ARTICLE XIV.
 PLEASE CONTACT ROBERT KUSSNER, LANDSCAPE PLANNER, FOR
 ANY QUESTIONS REGARDING THE LANDSCAPE REGULATIONS.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-09-07 Cont ID  
Sent By adavila Date 2007-09-07 Time 12:58 Rev Time 0.00
Received By adavila Date 2007-09-05 Time 14:15 Sent To I
Notes
2007-09-07 12:58:34PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 1 Status P Date 2007-03-26 Cont ID  
Sent By adavila Date 2007-03-26 Time 17:49 Rev Time 0.00
Received By adavila Date 2007-03-26 Time 17:49 Sent To I
Notes
2007-03-26 17:51:28PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  
 PLEASE NOTE THAT A SEPARATE PERMIT SHALL BE PROVIDED
 FOR THE PROPOSED SPA, DECK AND BBQ AREA.


Account Summary | Usage Policy | Privacy Policy