Plan Review Details - Permit 07030674
Plan Review Stops For Permit 07030674
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-06-13 Cont ID  
Sent By shill Date 2007-06-13 Time 10:12 Rev Time 0.00
Received By shill Date 2007-06-13 Time 10:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-19 Cont ID  
Sent By shill Date 2007-04-19 Time 18:09 Rev Time 0.00
Received By shill Date 2007-04-19 Time 18:09 Sent To  
Notes
2007-04-19 18:10:39****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)TWO SETS OF PLANS REQUIRED, FBC*106.2.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-06-06 Cont ID  
Sent By btrobaug Date 2007-06-06 Time 15:28 Rev Time 0.33
Received By btrobaug Date 2007-06-06 Time 15:15 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-28 Cont ID  
Sent By btrobaug Date 2007-03-28 Time 08:06 Rev Time 0.33
Received By btrobaug Date 2007-03-28 Time 07:58 Sent To M
Notes
2007-03-28 08:06:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS
 INDICATING RECOMMENDED SETBACKS AND
 ELECTRICAL SPEC'S FOR THE GENERATOR AND
 TRANSFER SWITCH.
  
 2} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-08-17 Cont ID  
Sent By mperson Date 2007-08-17 Time 10:46 Rev Time 0.33
Received By mperson Date 2007-08-17 Time 10:46 Sent To PC
Notes
2007-08-17 10:48:03REVISION: CHANGE 1-1/4" GAV. PIPE IN ATTIC TO 1-1/4"
 CSST.
  
 IF DRYER ROOM IS A CONFINED SPACE, OPENINGS REQUIRED
 PER SECTION 304.5 OR SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-06-12 Cont ID  
Sent By mperson Date 2007-06-12 Time 16:04 Rev Time 0.33
Received By mperson Date 2007-06-12 Time 16:04 Sent To M
Notes
2007-06-12 16:09:33 
  
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-04-10 Cont ID  
Sent By mperson Date 2007-04-10 Time 15:41 Rev Time 0.50
Received By mperson Date 2007-04-10 Time 15:41 Sent To B
Notes
2007-04-10 16:07:59DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS AND GEN/RES PERMIT
 APPLICATION REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE PROVIDE MANUFACTURER'S SPECIFICATIONS
 INDICATING RECOMMENDED SETBACKS TO STRUCTURES AND
 NATURAL GAS BTU LOAD VERIFICATIONS OF GENERATOR. PLEASE
 PROVIDE INFORMATION THAT GENERATOR IS LISTED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL).
  
 2. PLEASE PROVIDE TWO COPIES OF A SITE PLAN OR SURVEY
 THAT CLEARLY MARKS THE LOCATION OF THE PROPOSED
 GENERATOR INDICATING ALL DIMENSIONS FROM PROPERTY LINES
 AND DISTANCES FROM ADJACENT STRUCTURES.
  
 3.A GAS PERMIT CAN NOT BE ISSUED UNTIL
 A GEN/RES PERMIT APPLICATION HAS BEEN
 APPLIED FOR AND APPROVED BY ZONING FOR
 THE GENERATOR LOCATION.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-06 Cont ID  
Sent By adarroug Date 2007-06-06 Time 10:11 Rev Time 0.00
Received By adarroug Date 2007-06-06 Time 10:11 Sent To E
Notes
2007-06-06 10:11:22TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-22 Cont ID  
Sent By adarroug Date 2007-05-22 Time 16:18 Rev Time 0.00
Received By adarroug Date 2007-05-22 Time 16:18 Sent To Z
Notes
2007-05-22 16:18:21TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-24 Cont ID  
Sent By adarroug Date 2007-03-24 Time 13:16 Rev Time 0.00
Received By adarroug Date 2007-03-24 Time 13:16 Sent To E
Notes
2007-03-24 13:16:57TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-19 Cont ID  
Sent By shill Date 2007-04-19 Time 18:10 Rev Time 0.00
Received By shill Date 2007-03-21 Time 15:59 Sent To  
Notes
2007-03-21 15:59:53TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-06-13 Cont ID  
Sent By tgordon Date 2007-06-13 Time 08:22 Rev Time 0.25
Received By tgordon Date 2007-06-13 Time 08:22 Sent To B
Notes
2007-06-13 08:24:07*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION
 ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE
 RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS
 CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 FOLLOW MANUFACTURER'S RECOMMENDED
 CLEARANCES AROUND EQUIPMENT FOR
 SERVICING,AND PROVIDE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-29 Cont ID  
Sent By tgordon Date 2007-03-29 Time 08:09 Rev Time 0.20
Received By tgordon Date 2007-03-29 Time 08:09 Sent To G
Notes
2007-03-29 08:16:00*** DENIED ***
 1) NEED TO SUBMIT TWO COPY'S OF THE SURVEY.
  
 2) NEED TO SHOW ON THE SURVEY THE PROPOSED LOCATION OF
 THE GENERATOR AND THE DISTANCES TO ALL BUILDINGS.
 BUILDING OPENINGS, AND PROPERTY LINES.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-06-01 Cont ID  
Sent By adavila Date 2007-06-01 Time 13:28 Rev Time 0.00
Received By adavila Date 2007-05-23 Time 15:40 Sent To I
Notes
2007-06-01 13:29:13PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-22 Cont ID  
Sent By adavila Date 2007-03-22 Time 12:02 Rev Time 0.00
Received By adavila Date 2007-03-22 Time 11:48 Sent To I
Notes
2007-03-22 12:06:09PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.ONLY ONE (1) COPY OF THE SURVEY WAS PROVIDED.NEED
 TO PROVIDE AN ADDITIONAL COPY OF THE SURVEY.
  
 2.PROPOSED GENERATOR LOCATION WITH SETBACK DIMENSIONS
 SHALL BE PROVIDED ON BOTH COPIES OF SURVEY.PLEASE
 NOTE THAT PER SECTION 94-305(B)(4), MECHANICAL
 EQUIPMENT (GENERATOR) MAY NOT PROJECT MORE THAN FOUR
 FEET INTO A SETBACK.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.