Plan Review Details - Permit 07030665
Plan Review Stops For Permit 07030665
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-04-20 Cont ID  
Sent By shill Date 2007-04-20 Time 18:40 Rev Time 0.00
Received By shill Date 2007-04-20 Time 18:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-05-09 Cont ID  
Sent By btrobaug Date 2007-05-09 Time 10:37 Rev Time 0.75
Received By btrobaug Date 2007-05-09 Time 10:32 Sent To G
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-28 Cont ID  
Sent By btrobaug Date 2007-03-28 Time 07:55 Rev Time 0.33
Received By btrobaug Date 2007-03-28 Time 07:42 Sent To M
Notes
2007-03-28 07:55:49 
  
  
 DENIED/INCOMPLETE INFORMATION.
  
 1} PROVIDE A RISER DIAGRAM PER 215.5
 INCLUDING GENERATOR AND RELATED
 EQUIPMENT.
  
 2} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON
 A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE,
 DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-05-10 Cont ID  
Sent By mperson Date 2007-05-10 Time 08:03 Rev Time 0.45
Received By mperson Date 2007-05-10 Time 08:03 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-04-11 Cont ID  
Sent By mperson Date 2007-04-11 Time 09:06 Rev Time 0.45
Received By mperson Date 2007-04-11 Time 09:06 Sent To B
Notes
2007-04-11 10:37:28DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS AND GEN/RES PERMIT
 APPLICATION REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
  
 THE FOLLOWING CORRECTIONS/INFORMATIONREQUIRED FOR GAS
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC, PLEASE
 REFERENCE THE ATTACHED ISOMETRIC TO THE GAS COMMENTS
 REFLECTING THE PROPOSED GAS SYSTEM. CORRESPONDING
 LENGTHS OF ALL CUT SECTIONS OF PIPE MUST BE INDICATED
 ON THE RESUBMITTED DRAWING. THE ONLY INDICATED PIPING
 MEASUREMENT IS FOR THE UNDERGROUND 1/2" PE. WHAT ARE
 THE CORRESPONDING LENGTHS OF THE ABOVE GROUND PIPING?
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: BOTH THE ABOVE AND UNDERGROUND PIPING MATERIALS
 AND SIZES MUST BE INDICATED ON THE DRAWINGS. ON THE
 SUBMITTED GAS CHECKLIST PIPE/TUBING SPECS. COPPER, PE,
 AND GALV. ARE INDICATED AS PIPING MATERIAL BEING USED
 BUT ON THE SUBMITTED DRAWING ONLY PE AND GALV. ARE
 INDICATED AS BEING USED. PLEASE CORRELATE AND CORRECT
 ON THE RESUBMITTAL
  
 3. SUBMIT MANUFACTURE SPECIFICATION SHEETS FOR THE
 GENERATOR THAT VERIFIES THE BTU LOAD OF GENERATOR AT
 100% RUNNING CAPACITY AND VERIFIES THE BTU LOAD OF
 229,000 INDICATED ON THE DRAWINGS.
  
 4. PLEASE SUBMIT TWO COPIES OF THE ABOVE GROUND LP
 TANK ANCHORING DETAIL FOR THE RESUBMITTAL.
  
 5. CLEARLY SHOW THETYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-08 Cont ID  
Sent By adarroug Date 2007-05-08 Time 14:52 Rev Time 0.00
Received By adarroug Date 2007-05-08 Time 14:51 Sent To P
Notes
2007-05-08 14:52:19TO "MPERSON" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-03 Cont ID  
Sent By adarroug Date 2007-05-03 Time 14:01 Rev Time 0.00
Received By adarroug Date 2007-05-03 Time 14:01 Sent To Z
Notes
2007-05-03 14:01:32TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-24 Cont ID  
Sent By adarroug Date 2007-03-24 Time 12:17 Rev Time 0.00
Received By adarroug Date 2007-03-24 Time 12:17 Sent To E
Notes
2007-03-24 12:17:59TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2007-03-21 Time 15:56 Sent To  
Notes
2007-03-21 15:56:54TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-03-29 Cont ID  
Sent By tgordon Date 2007-03-29 Time 08:27 Rev Time 0.25
Received By tgordon Date 2007-03-29 Time 08:27 Sent To G
Notes
2007-03-29 08:29:05*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION
 ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE
 RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS
 CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 FOLLOW MANUFACTURER'S RECOMMENDED
 CLEARANCES AROUND EQUIPMENT FOR
 SERVICING,AND PROVIDE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 2 Status P Date 2007-05-07 Cont ID  
Sent By adavila Date 2007-05-07 Time 14:18 Rev Time 0.00
Received By adavila Date 2007-05-04 Time 14:18 Sent To I
Notes
2007-05-07 14:19:07PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-22 Cont ID  
Sent By adavila Date 2007-03-22 Time 15:19 Rev Time 0.00
Received By adavila Date 2007-03-22 Time 12:09 Sent To I
Notes
2007-03-22 15:21:45PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.ONLY ONE (1) COPY OF THE SURVEY WAS SUBMITTED WITH
 THIS PERMIT APPLICATION.NEED TO SUBMIT AN ADDITIONAL
 COPY.
  
 2.PROVIDE SETBACK DIMENSIONS FROM PROPERTY LINE TO
 PROPOSED GENERATOR AND GAS TANKS ON BOTH COPIES OF
 SURVEY.
  
 COMMENTS/QUESTIONS CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.