Plan Review Details - Permit 07030651
Plan Review Stops For Permit 07030651
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-09-20 Cont ID  
Sent By rmcdouga Date 2007-09-20 Time 18:54 Rev Time 0.00
Received By rmcdouga Date 2007-09-20 Time 18:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-11 Cont ID  
Sent By rmcdouga Date 2007-09-11 Time 08:27 Rev Time 0.00
Received By rmcdouga Date 2007-09-11 Time 07:09 Sent To  
Notes
2007-09-11 08:27:422004 FBC
 ADDITION
  
 THE STATUS OF THE BUILDING PLAN REVIEW WILL REMAIN AS
 FAILED UNTIL THE FOLLOWING TWO ITEMS ARE ADDRESSED.
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT IS
 REQUIRED.
  
 2)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-06 Cont ID  
Sent By rmcdouga Date 2007-07-06 Time 16:18 Rev Time 0.00
Received By rmcdouga Date 2007-07-06 Time 16:18 Sent To  
Notes
2007-07-06 16:44:09DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE FOOTING SECTION ON SHEET 1 FOR THE MONOLITHIC
 SLAB AT THE PROPOSED ENCLOSED CARPORT DOES NOT SPECIFY
 THE WIDTH AND HEIGHT DIMENSIONS OF THE FOOTER, THE
 FOOTER REINFORCEMENT STEEL, THE HEIGHT ABOVE FINISH
 GRADE OR THE DISTANCE FROM GRADE TO THE BOTTOM THE
 FOOTING. SEE R404.1.6, R403.1.4 AND FBC106.1.2.
  
 4) ON SHEET 2 THE NOTES FOR THE ROOF SHEATHING
 INCORRECTLY SPECIFY 8D COMMON NAILS IN ROOF ZONES 1 AND
 2. SECTION R 803.2.3.1 REQUIRES RING SHANK NAILS IN ALL
 ROOF ZONES.
  
 5) THE ENERGY CALCULATION FORM THAT WAS SUBMITTED
 SPECIFIES R-19 ATTIC INSULATION AND WALL SECTION 1 ON
 SHEET A1 SPECIFIES R-30. PLEASE CORRECT.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-24 Cont ID  
Sent By rmcdouga Date 2007-04-24 Time 14:27 Rev Time 0.00
Received By rmcdouga Date 2007-07-06 Time 16:18 Sent To P
Notes
2007-04-24 14:27:13DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE LEFT ELEVATION DOES NOT INDICATE THE DOOR OR ITS
 WIND PRESSURES AT THE NEW ENCLOSED STORAGE ROOM. A
 WINDOW IS SHOWN AT THIS LOCATION.
  
 4) PROVIDE A FRONT ELEVATION WHICH SHOWS THE WINDOW AND
 WIND PRESSURES AT THE ENCLOSED STORAGE ROOM.
  
 5) THE EMERGENCY EGRESS REQUIREMENTS OF THE ROOMS
 ADJACENT TO THE NEW ADDITION OR ENCLOSED CARPORT MUST
 BE MAINTAINED. INDICATE THE ROOM TYPES AND LOCATIONS OF
 THE EXISTING STRUCTURE ON THE FLOOR PLAN. SEE FBC
 R310.
  
 6) PROVIDE DETAILS OF THE FOOTINGS WHERE THE NEW CBS
 WALLS WILL BE INSTALLED TO ENCLOSE THE EXISTING
 CARPORT. PROVIDE A WALL SECTION AT THIS LOCATION. SHOW
 COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED GRADE.
 CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND
 ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT
 ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY
 VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM)
 ELSEWHERE.
  
 7) THE LOCATION OF THE EXISTING WALLS SHOWN ON THE
 FOUNDATION PLAN AT THE CARPORT DO NOT MATCH THE ONES
 SHOWN ON THE FLOOR PLAN. PLEASE CORRECT.
  
 8) SPECIFY THE BOTTOM CORD LIVE LOAD FOR THE TRUSSES.
 SEE FBC RESIDENTIAL TABLE R301.5.
  
 9) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS.
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER.
  
 THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME
 POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3
 FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
  
 10) ROOF SHEATHING FASTENING IS REQUIRED TO BE IN
 ACCORDANCE WITH SECTION R803.2.3.1 OF 2006 REVISIONS TO
 2004 FBC RESIDENTIAL CODE. WOOD STRUCTURAL PANEL
 SHEATHING SHALL BE FASTENED TO ROOF FRAMING WITH 8D
 RING-SHANK NAILS AT 6 INCHES ON CENTER AT EDGES AND 6
 INCHES ON CENTER AT INTERMEDIATE FRAMING. SPACING OF
 RING-SHANK FASTENERS SHALL BE 4 INCHES ON CENTER IN
 NAILING ZONE 3 FOR 130 MPH OR GREATER DESIGN WIND
 SPEEDS IN ACCORDANCE WITH FIGURE R803.2.3.1. REVISE THE
 NAILING SCHEDULE ON SHEET 2 AND THE NOTE ON WALL
 SECTION 1/A4 ON SHEET 4.
  
 11)THE COMPONENT AND CLADDING ZONES FOR THE HIP ROOF
 SPECIFIED ON SHEET 2 OF THE PLANS IS INCORRECT. ROOF
 ZONE 3 IS INCORRECTLY IDENTIFIED ON THE DIAGRAM. THE
 OUTSIDE CORNERS ARE ZONE 3. SEE FBC FIGURE R301.2(8).
  
 12)THE SIMPSON CATALOG INDICATES THAT THE LATERAL
 L0ADS DO NOT APPLY FOR REDUCED FASTENERS ON THE TRUSS
 CONNECTORS. PER TELEPHONE CONVERSATION WITH SIMPSON'S
 ENGINEERING DEPARTMENT THE REDUCTION CALULATIONS FOR
 UPLIFT SHOULD ONLY BE BASED ON THE NUMBER OF NAILS IN
 THE STRAP AND NOT THE SEAT OF THE HETAL CONNECTORS,
 WHICH REDUCES THE UPLIFT VALUE BY 40 PERCENT. BECAUSE
 THE LATERAL LOADS OF THE TRUSS CONNECTORS IS REQUIRED
 TO RESIST WINDLOADS, ALL OF THE NAILS SPECIFIED FOR THE
 CONNECTOR IN THE CATALOG SHOULD BE USED.
  
 13) THE DESIGN CERTIFICATION INFORMATION LISTED ON
 SHEET 3 CONTAINS SOME ERRORS. THE PROJECT IS LOCATED IN
 THE CITY OF WEST PALM BEACH, THEREFORE, THE CITY'S
 AMENDMENTS AND NOTPALM BEACH COUNTY'S ARE APPLICABLE.
 REPLACE PALM BEACH COUNTY WITH CITY OF WEST PALM BEACH.
 THE WRONG EDITION OF ASCE 7 IS SPECIFIED. REPLACE ASCE
 7-98 WITH ASCE 7-02.
  
 14) THE STRUCTURAL NOTES ON SHEET 2 SPECIFY A 2500 PSF
 SOIL BEARING CAPACITY AND GENERAL NOTE 11 ON SHEET 4
 SPECIFIES A 2000 PSF SOIL BEARING CAPACITY. PLEASE
 CORRECT.
  
 15) ON SHEET 4 GENERAL NOTE 1REFERENCES THE STANDARD
 BUILDING CODE AS AMENDED BY PALM BEACH COUNTY. PLEASE
 REVISE TO FLORIDA BUILDING CODE AS AMENDED BY THE CITY
 OF WEST PALM BEACH.
  
 16) THE TYPICAL DOOR JAMB NOTES ON SHEET 4 SPECIFIES A
 FASTENER SPACING THAT DOES NOT CORRESPOND WITH THE
 SPACING SPECIFIED IN THE OTHER BUCK FASTENING DETAILS.
  
 17)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. SEE RULE 9B-72.
  
 18) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 19) SUBMIT PRODUCT APPROVALS FOR THE TRUSS CONNECTORS
 AND CONCRETE LINTELS.
  
 20) THE PRODUCT APPROVAL SUBMITTED FOR THE JELD-WEN
 DOOR IS FOR DOUBLE OUTSWING DOORS AND THE PLAN
 SPECIFIES A SINGLE OUTSWING DOOR. SUBMIT THE CORRECT
 PRODUCT APPROVAL.
  
 21) THE PRODUCT APPROVAL SUBMITTED FOR THE GAF SHINGLES
 HAS BEEN REVISED BY NOA 05-1115.11. SUBMIT THE NEW NOA
 WITH THE FL COVERSHEET.
  
 22) ALSO SEE RED MARKS ON THE PLANS FOR CORRECTIONS.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-09-19 Cont ID  
Sent By btrobaug Date 2007-09-19 Time 14:24 Rev Time 0.00
Received By btrobaug Date 2007-09-19 Time 14:07 Sent To B
Notes
2007-09-19 14:26:16 
  
 TO ROBERT MCDOUGAL./WRT.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-09-10 Cont ID  
Sent By btrobaug Date 2007-09-10 Time 13:54 Rev Time 0.00
Received By btrobaug Date 2007-09-10 Time 13:06 Sent To M
Notes
2007-09-10 13:58:24 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 2} THERE ARE NO RECEPTACLES SHOWN FOR THE A/C UNITS ON
 THE PLAN, LOCATE SAME.106.1.1 FBC AS AMENDED.
  
 3} THE RISER DIAGRAM HAS A METER MAIN SYMBOL WITH AN
 UNDERGROUND FEED TO WHAT APPEARS TO BE A PANEL, BUT
 THAT PIECE OF EQUIPMENT IS LABELED ?METER COMB.?.
 CLARIFY, SEE COMMENT #1.
  
 4} 210.52(E) OUTDOOR OUTLETS FOR A ONE-FAMILY DWELLING
 AND EACH UNIT OF A TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET ACCESSIBLE AT
 GRADE LEVEL AND NOT MORE THAN 2.0 M (6 1/ 2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING. LOCATE SAME ON THE PLANS.
  
 5} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. WHEN
 INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE PROVIDED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE ALARMS
 SHALL BE INTERCONNECTED AND HARD WIRED. LOCATE SAME ON
 PLANS. ALSO SEE THE DEFINITION OF "SMOKE DETECTORS"
 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS,
 TO AVOID CONFUSION IN THE FIELD. IF USING DETECTORS
 INDICATE THE LOCATIONS OF THE SOUNDING DEVICES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-06-06 Cont ID  
Sent By btrobaug Date 2007-06-06 Time 07:45 Rev Time 0.33
Received By btrobaug Date 2007-06-06 Time 07:35 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-28 Cont ID  
Sent By btrobaug Date 2007-03-28 Time 16:39 Rev Time 0.33
Received By btrobaug Date 2007-03-28 Time 16:29 Sent To B
Notes
2007-03-28 16:39:30 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} PROVIDE A LOAD CALCULATION PER 220.31, FOR THE
 ENTIRE RESIDENCE, INCLUDE ADDED LOADS.
  
 2} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND
 106.3.5.4(8) FBC.
  
 3} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A) (1)
 AND 210.52 (A) (2). SEE REVIEWED SET FOR EXAMPLES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-09-07 Cont ID  
Sent By adarroug Date 2007-09-07 Time 08:30 Rev Time 0.00
Received By adarroug Date 2007-09-07 Time 08:30 Sent To E
Notes
2007-09-07 08:30:41TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-31 Cont ID  
Sent By adarroug Date 2007-08-31 Time 12:28 Rev Time 0.00
Received By adarroug Date 2007-08-31 Time 12:28 Sent To Z
Notes
2007-08-31 12:28:45TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-01 Cont ID  
Sent By adarroug Date 2007-06-01 Time 14:55 Rev Time 0.00
Received By adarroug Date 2007-06-01 Time 14:55 Sent To E
Notes
2007-06-01 14:56:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-25 Cont ID  
Sent By adarroug Date 2007-05-25 Time 14:46 Rev Time 0.00
Received By adarroug Date 2007-05-25 Time 14:46 Sent To Z
Notes
2007-05-25 14:46:23TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-24 Cont ID  
Sent By adarroug Date 2007-03-24 Time 13:22 Rev Time 0.00
Received By adarroug Date 2007-03-24 Time 13:22 Sent To E
Notes
2007-03-24 13:23:06TO "SFR""E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-24 Cont ID  
Sent By rmcdouga Date 2007-04-24 Time 14:27 Rev Time 0.00
Received By rmcdouga Date 2007-03-19 Time 09:10 Sent To  
Notes
2007-03-19 09:10:57TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-09-10 Cont ID  
Sent By tgordon Date 2007-09-10 Time 16:17 Rev Time 0.20
Received By tgordon Date 2007-09-10 Time 16:17 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-06-19 Cont ID  
Sent By tgordon Date 2007-06-19 Time 14:36 Rev Time 0.20
Received By tgordon Date 2007-06-19 Time 14:36 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-03-27 Cont ID  
Sent By tgordon Date 2007-03-27 Time 11:53 Rev Time 0.25
Received By tgordon Date 2007-03-27 Time 11:53 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-06-19 Cont ID  
Sent By mperson Date 2007-06-19 Time 13:04 Rev Time 0.33
Received By mperson Date 2007-06-19 Time 13:04 Sent To M
Notes
2007-06-19 13:12:21****************PROVISO***************
 (A) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A TWO-WAY
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS REVIEWER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-24 Cont ID  
Sent By mperson Date 2007-04-25 Time 16:30 Rev Time 0.45
Received By mperson Date 2007-04-24 Time 16:30 Sent To PC
Notes
2007-04-24 16:55:56DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 2 OF 4 FLOOR PLAN IS INDICATING THE PLUMBING
 FIXTURES IN THE PROPOSED BATHROOM AS BEING A LAVATORY,
 WATER CLOSET AND A TUB. SHEET 4 OF 4 SANITARY ISOMETRIC
 RISER DIAGRAM IS INDICATING THE PLUMBING FIXTURES IN
 THE PROPOSED BATHROOM AS BEING A SINK, WATER CLOSET,
 AND A SHOWER. PLEASE CORRELATE AND CORRECTLY IDENTIFY
 THE PLUMBING FIXTURES IN THE RESUBMITTAL AS PER
 FBC-2004 CHAPTER 1, SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO LOCATION, NATURE, AND THE EXTENT OF THE WORK. PLEASE
 NOTE THAT PLUMBING FIXTURES SHALL BE PROPERLY
 IDENTIFIED AS PER FBC-2004 PLUMBING CHAPTER 4
 FIXTURES.
  
 2. SHEET 4 OF 4 SANITARY ISOMETRIC RISER DIAGRAM IS
 INDICATING A TRAP FOR THE WATER CLOSET. PER FBC-2004
 PLUMBING, SECTION 1002.1 A FIXTURE SHALL NOT BE DOUBLE
 TRAPPED. PLEASE NOTE THAT A WATER CLOSET HAS AN
 INTEGRAL TRAP AND A TRAP NEED NOT BE INDICATED. PLEASE
 CORRECT ON THE RESUBMITTAL AND PLEASE NOTE THIS FOR
 FUTURE SANITARY ISOMETRIC PLUMBING RISER DIAGRAMS.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 3 Status P Date 2007-09-06 Cont ID  
Sent By adavila Date 2007-09-06 Time 16:38 Rev Time 0.00
Received By adavila Date 2007-09-04 Time 16:02 Sent To I
Notes
2007-09-06 16:38:59PER ERIC SCHNEIDER, PRINCIPAL PLANNER.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-05-30 Cont ID  
Sent By adavila Date 2007-05-30 Time 15:47 Rev Time 0.00
Received By adavila Date 2007-05-29 Time 08:14 Sent To I
Notes
2007-05-30 15:47:57PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.PER SECTION 94-486 OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, SINGLE-FAMILY HOMES REQUIRE
 TWO (2) OFF-STREET PARKING SPACES.BY CONVERTING THE
 CARPORT INTO STORAGE, THE RESIDENTIAL UNIT WILL BE
 DEFICIENT ONE (1) PARKING SPACE, AND THEREFORE SHALL BE
 PROVIDED ELSEWHERE ON-SITE.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-22 Cont ID  
Sent By adavila Date 2007-03-22 Time 09:36 Rev Time 0.00
Received By adavila Date 2007-03-22 Time 09:36 Sent To I
Notes
2007-03-22 09:43:55PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.PROPOSED ADDITION SHALL BE SHOWN ON THE SURVEY WITH
 SETBACK DIMENSIONS.
  
 2.SITE PLAN SHALL BE MODIFIED TO REFLECT THE
 CONDITIONS SHOWN ON THE SURVEY (SETBACK DIMENSIONS, LOT
 DEPTH, ETC.)
  
 3.PROVIDE BUILDING HEIGHT DIMENSIONS FROM GRADE.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.
  
  