| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-03-16 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-03-16 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-03-16 |
Time |
11:06 |
Sent To |
PC |
|
| Notes |
| 2007-03-16 11:10:00 | ---------------DENIED------------------ | | | | | | PLAN LACKS SUFFICIENT DETAIL FOR REVIEW. THE FOLLOWING | | | MISSING INFORMATION IS REQUIRED PER FBC 106.3.5.4: | | | | | | ENERGY CALCULATIONS | | | EQUIPMENT SCHEDULE | | | DUCT LAYOUT SIZE/GRILL SIZE (INCLUDE CFM) | | | | | | LIVING AREA 10X10 DROP IS SHOWN AS RETURN, BUT ATTACHES | | | TO SUPPLY TRUNK. PLEASE CLARIFY. | | | SIZE OF FLEX FEEDING SAME 10X10 IS MISSING. PLEASE | | | CLARIFY. | | | | | | THERE IS NO SIZE OR LOCATION OF CENTRALIZED RETURN AIR | | | SHOWN ON PLAN. | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
|