Plan Review Details - Permit 07030549
Plan Review Stops For Permit 07030549
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-07-19 Cont ID  
Sent By tgordon Date 2007-07-19 Time 11:21 Rev Time 0.20
Received By tgordon Date 2007-07-19 Time 11:21 Sent To  
Notes
2007-07-19 11:24:18SUBMITTED NEW PRODUCT APPROVALS FOR RM ENTERPRISES,
 INC. CONDENSER STANDS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-16 Cont ID  
Sent By shill Date 2007-07-16 Time 11:49 Rev Time 0.00
Received By shill Date 2007-07-16 Time 11:49 Sent To  
Notes
2007-07-16 11:53:53****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)SEE FS553.8425(4), PRODUCTS DEMONSTRATING
 COMPLIANCE SHALL BE AMNUFACTURED UNDER A QUALITY
 ASSURANCE PROGRAM AUDITED BY AN APPROVED QUALITY
 ASSURANCE ENTITY.
  
 2.)ALL INFORMATION REQUIRED BY FAC61G15-23.002 IS
 REQUIRED TO BE ON EACH SHEET.
  
 3.)EITHER EACH SHEET IS TO BE SIGNED, SEALED AND
 DATED OR HAVE AN INDEX SHEET.NOTE TITLE BLOCK
 REQUIREMENTS.SEE FAC61G15-23.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-11-09 Cont ID  
Sent By adarroug Date 2007-11-09 Time 12:46 Rev Time 0.00
Received By adarroug Date 2007-11-09 Time 12:46 Sent To M
Notes
2007-11-09 12:46:37TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-13 Cont ID  
Sent By adarroug Date 2007-07-13 Time 12:15 Rev Time 0.00
Received By adarroug Date 2007-07-13 Time 12:15 Sent To M
Notes
2007-07-13 12:15:18TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-27 Cont ID  
Sent By adarroug Date 2007-06-27 Time 14:49 Rev Time 0.00
Received By adarroug Date 2007-06-27 Time 14:49 Sent To M
Notes
2007-06-27 14:50:03TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-16 Cont ID  
Sent By tgordon Date 2007-03-16 Time 11:23 Rev Time 0.00
Received By tgordon Date 2007-03-15 Time 16:17 Sent To  
Notes
2007-03-15 16:17:22TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-11-13 Cont ID  
Sent By tgordon Date 2007-11-13 Time 14:31 Rev Time 0.30
Received By tgordon Date 2007-11-13 Time 14:31 Sent To  
Notes
2007-11-13 14:32:10REVISION TO MECH. PLAN PAGE M-1.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-07-16 Cont ID  
Sent By tgordon Date 2007-07-16 Time 09:41 Rev Time 0.25
Received By tgordon Date 2007-07-16 Time 09:41 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-06-28 Cont ID  
Sent By tgordon Date 2007-06-28 Time 09:29 Rev Time 2.00
Received By tgordon Date 2007-06-28 Time 09:29 Sent To  
Notes
2007-06-28 09:56:17*** DENIED ***
 1) CONDENSER STANDS APPEAR TO BE PRE-ENGINEERED STANDS
 AND NEED FLORIDA STATE PRODUCT APPROVAL, SEE ATTACHED
 FLORIDA STATUTE 553.842,PLEASE CORRECT.
  
 2) INFORMATION THAT WAS SUBMITTED FOR A/C CONDENSER
 STANDS IS NOT A PRODUCT APPROVAL AND HAS MANY ERRORS ON
 IT (SEE YELLOW HIGH LIGHTS) HAND CHANGES MAY NOT BE
 MADE TO DOCUMENTS, DATE AT SEAL JUN 95, 2007, DOCUMENT
 REFERENCES ASCE 7-98 SHOULD STATE 2002, AND PAGE 3 OF 4
 IS MISSING.
  
 3) THIS IS THE SECOND REQUEST FOR A PRODUCT APPROVAL.
 SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR
 TIMES THE FEE.
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-16 Cont ID  
Sent By tgordon Date 2007-03-16 Time 11:23 Rev Time 0.40
Received By tgordon Date 2007-03-16 Time 11:23 Sent To  
Notes
2007-03-16 11:58:03*** DENIED ***
 1) THE ARCHITECT (EVERETT H. JENNER) NEEDS TO SIGN AND
 SEAL THE PLANS AS HIS INFORMATION IS IN THE TITLE
 BLOCK, SEE FAC 61G1-16.003.
  
 2) PLANS NOTE, WORK TO MEET NATIONAL CODES, NEED TO
 MEET 2004 FBC, PLEASE CORRECT.
  
 3) THIS MECHANICAL SUB-PERMIT CAN NOT PASS REVIEW UNTIL
 THE MASTER PERMIT PASSES REVIEW AS THEIR IS INFORMATION
 ON THE MASTER PLANS THAT IS NEEDED (ARCHITECTURE).
  
 4) PLEASE SUBMIT COOLING LOAD CALCULATIONS, PER 2004
 FBC 13-407.1.ABC.1.
  
 5) PLEASE SHOW DETAILED OUTDOOR AIR CALCULATIONS, PER
 2004 FBC/M 403.3.
  
 6)PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S FOR A/C SYSTEMS AS THE MODEL NUMBERS IN
 THE EQUIPMENT LISTING COULD NOT BE FOUND IN THE ARI
 DIRECTORY.
  
 7) PLEASE SHOW IN THE EQUIPMENT LISTING TOTAL BTU'S,
 SENSIBLE BTU'S, COPPER LINE SIZES, AND OTHER PERTINENT
 INFORMATION.
  
 8) PLEASE SHOW ON PLANS THE INFORMATION FOR THE
 BATHROOM EXHAUST FANS.
  
 9)PLEASE SUBMIT PRODUCT APPROVAL FOR PER-ENGINEERED
 CONDENSER STANDS, SEE FS 553.842(1) AND FAC
 9B-72.010(31)(G).
  
 **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG.
  
 10) PLEASE SHOW CFM'S AT EACH SUPPLY AIR GRILL.
  
 11) PLEASE SHOW RETURN AIR DUCTS AND GRILLS ON PLANS.
  
 12) PLEASE SHOW ON PLANS WERE AND HOW CONDENSATE WATER
 IS TO BE DISPOSED OF, AND SECONDARY DRAIN.
  
 13) PLANS STATE AHU TO SIT ON WOOD PLATFORMS ABOVE
 BATHROOMS, AHU #9 IS NOT OVER A BATHROOM (?), PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  