| 2007-04-16 18:02:43 | BUILDING REVIEW CHECKLIST: |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | |
| | 2- AFTER DRAWINGS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY TO PAY IMPACT FEES. BRING BACK STAMPED PLANS AND |
| | COPY OF PAID RECEIPT. |
| | |
| | 3- SHEET A1: |
| | A) BUILDING DIMENSIONS AND SETBACKS DON'T MATCH |
| | THOSE DIMENSIONS SHOWN ON SURVEY. REVISE AS REQUIRED. |
| | B) REVISE INFORMATION GIVEN:* THIS IS NOT A |
| | MULTIFAMILY DWELLING.** THERE IS NOT NEW PORCH. SEE |
| | PLANS. |
| | C) REVISE DESIGN DATA: * DESIGN CONSIDERATION IS FOR |
| | IS FOR INTERIOR ZONES AND END ZONES, NOT INTERIOR AND |
| | EXTERIOR ZONES. REVISE AS REQUIRED.** UPDATE BUILDING |
| | CODE. SEE FBC 2004. |
| | D) THIS IS PENN STREET, NOT AVENUE. REVISE AS |
| | REQUIRED. |
| | |
| | 4- SHEET A2: |
| | A) BUILDING DIMENSIONS DON'T MATCH SURVEY. REVISE AS |
| | REQUIRED. |
| | B) SPECIFY SAFETY GLASS FOR NEW BATHROOM WINDOW. |
| | SEC. R308.42004 FLORIDA RESIDENTIAL CODE. |
| | C) SPECIFY ATTIC ACCESS LOCATION AND SIZE. SEC. R807 |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | D) REVISE DESIGN DATA INFORMATION. SEE ITEM 3(C) |
| | ABOVE. |
| | E) WALL LEGEND CALLS FOR 2X4 BEARING WALL, WHILE |
| | FLOOR PLAN SHOWS 2X6 BEARING WALL. REVISE AS REQUIRED. |
| | |
| | F) REVISE GENERAL CONSTRUCTION NOTE REGARDING |
| | CONCRETE BLOCK COMPRESSIVE STRENGTH. SEE SEC. R606.4 |
| | 2004 FLORIDA RESIDENTIAL CODE AND REVISE AS REQUIRED. |
| | |
| | G) WIND LOAD AFFIDAVIT CHART: * CLARIFY WHY INTERNAL |
| | PRESSURE COEFFICIENT IS 0.SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004.** AND, REVISE WIND PRESSURES |
| | ZONES, THEY ARE INTERIOR AND END ZONES, NOT INTERIOR |
| | AND EXTERIOR ZONES. |
| | F) PROVIDE COMPLETE INFORMATION FOR STEPS, LANDING, |
| | HANDRAIL AND GUARDRAIL AT REAR AREA BY SLIDING GLASS |
| | DOORS. SEE SEC. R311.5 AND R3122004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 5- SHEET A3: |
| | A) PROVIDE CRAWL SPACE VENTILATION AND ACCESS.SEE |
| | SEC. R4082004 FLORIDA RESIDENTIAL CODE FOR MIN. SIZES |
| | AND LOCATION. |
| | B) TYPICAL WALL FRAMING DETAIL/SECTION DOESN'T APPLY |
| | TO THIS PROJECT. SEE TYPICAL WALL SECTION AND REVISE AS |
| | REQUIRED TO MATCH. |
| | C) TYPICAL WALL SECTION: |
| | * SPECIFY HOW COMPLYING WITH SEC. R3192004 FLORIDA |
| | RESIDENTIAL CODE. |
| | ** SPECIFY HOW COMPLYING WITH SEC. R3202004 |
| | FLORIDA RESIDENTIAL CODE. |
| | *** SPECIFY DESIGN CRITERIAFOR SOIL BEARING |
| | CAPACITY. |
| | **** IT'S NOT CLEAR IF USING PRE-ENGINEERED ROOF |
| | TRUSSES OR CONVENTIONAL ROOF FRAMING. INFORMATION IS |
| | MISLEADING AND DOESN'T MATCH ROOF FRAMING PLAN. |
| | ***** SIMPSON MAS CONNECTOR SPECIFIED TO FASTEN 2X6 |
| | STUD AT BOTTOM DOESN'T WORK FOR THIS APPLICATION. |
| | REVISE AS REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | ****** CLARIFY NOTE REGARDING FOOTING REINFORCEMENT |
| | CONCRETE COVER.3" & 2" COVER AT BOTTOM?. SEE SEC. |
| | R403 OF 2004 FLORIDA RESIDENTIAL CODE FOR MIN. COVERING |
| | REQUIRED. |
| | ******* PROVIDE COMPLETE SPECS FOR FASTENING OF STUD |
| | WALL TO STEM WALL. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | D)PROVIDE INFORMATION FOR STEPS AT SLIDING GLASS |
| | DOORS FROM FAMILY ROOM. |
| | E)PROVIDE SECTION/DETAIL AT 16" DEEP LINTEL THAT |
| | PROVIDE ACCESS FROM ONE SIDE OF HOUSE TO THE OTHER. SEE |
| | FOUNDATION PLAN. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | F)REVISE SIZE OF CRAWL SPACE VENTILATION. |
| | COORDINATE WITH ITEM 3(A) ABOVE. |
| | G)REVISE ATTIC VENTING CALCULATIONS. INCLUDE SIZE |
| | SHOWN ON TYP. WALL SECTION AND SPECIFY NET CLEAR |
| | OPENING. |
| | |
| | 6- SHEET A4: |
| | A) REVISE DESIGN DATA FOR WIND LOADS. SPECIFY |
| | CURRENT CODE AND THERE IS NOT EXTERIOR ZONE. |
| | B) ASTM D-3161 IS NOT A TEST METHOD FOR 140MPH. |
| | REVIEWSUCH STANDARD AND REVISE NOTE AS REQUIRED. |
| | |
| | 7- SHEET A5: |
| | A) REVISE ROOF SHEATHING NAILING SCHEDULE. SEE SEC. |
| | R803.2.3.1 2004 FLORIDA RESIDENTIAL CODE AND REVISE |
| | TYPE OF FASTENER ASREQUIRED. |
| | B) REVISE STRAP TYPE NAILING TABLE.NEED TO SPECIFY |
| | WOOD TO WOOD CONNECTORS OR WOOD TO MASONRY CONNECTORS |
| | AS REQUIRED.EG: CONNECTOR A DOESN'T WORK. NEED WOOD |
| | TO WOOD CONNECTOR.REVISE ALL SCHEDULE AS REQUIRED. |
| | C) PROVIDE COMPLETE DETAIL AND SPECS SHOWING COMPLIANCE |
| | WITH SEC. 2304.3.4 FBC 2004 AND SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. DETAIL FOR TYP. GABLE END WALL |
| | IS INCOMPLETE (THERE ARE DETAILS THAT ARE NOT PROVIDED) |
| | AND DOESN'T COMPLY WITH THIS SECTION. |
| | |
| | 8- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 13-600 FBC 2004. |
| | |
| | 9- ENGINEERING FIRM TO PROVIDE THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER IN ALL DRAWINGS AS REQUIRED BY |
| | SEC. 61G15-23..002 OF FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 10- SPECIFY ALL LOADS INCLUDING LIVE AND DEAD LOADS AS |
| | REQUIRED BY SEC. R301 AND TABLE R301.5OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 11- PROVIDE SOIL TEST REPORT. |
| | |
| | 12- PROVIDE SURVEYWITH ORIGINAL SIGNATURE AS REQUIRED |
| | BY CHAPTER 472FLORIDA STATUTE. |
| | |
| | 13- BRING DRAWINGS FOR HISTORIC APPROVAL AND STAMPING |
| | PRIOR TO SUBMITTING THEM TO THIS OFFICE. |
| | |
| | 14- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72 |
| | FOR: |
| | A) ALL TRUSS CONNECTORS SPECIFIED ON PLANS. |
| | B) ROOF SHINGLES. NOA 04-0820.01 SUBMITTED WAS |
| | SUPERSEDED BY DADE COUNTY. SEE ATTACHED COPY. |
| | |
| | 15- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 16- VALUE DECLARED ON THE PERMIT APPLICATION IS TOO |
| | LOW.OWES $856.50 FOR UPDATED VALUATION AND RADON |
| | FEES. SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |