Plan Review Details - Permit 07030523
Plan Review Stops For Permit 07030523
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-06-26 Cont ID  
Sent By jwitmer Date 2008-06-26 Time 15:53 Rev Time 1.11
Received By jwitmer Date 2008-06-26 Time 15:53 Sent To  
Notes
2008-06-26 15:55:09REVISION NEW ARCH ALUM DOOR 3100 SEREIES IMPACT WALL
 NOA 05-0906.04

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-04-28 Cont ID  
Sent By jwitmer Date 2008-04-28 Time 10:46 Rev Time 1.22
Received By jwitmer Date 2008-04-28 Time 10:46 Sent To PC
Notes
2008-04-28 10:48:04S-1.1, S2.1 & S-3.1 REVISION# 5.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-01-03 Cont ID  
Sent By jwitmer Date 2008-01-03 Time 15:53 Rev Time 4.44
Received By jwitmer Date 2008-01-03 Time 15:52 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-12-11 Cont ID  
Sent By jwitmer Date 2007-12-11 Time 09:37 Rev Time 0.00
Received By jwitmer Date 2008-01-03 Time 15:54 Sent To  
Notes
2007-12-11 09:37:20PANERA BREAD 3RD REV
 BUILDING PLAN REVIEW
 PERMIT: 07030523
 ADD: 700 S ROSEMARY# 142
 CONT: PEMBERTON BUILDERS
 TEL: (561)718-8624
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 4THREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.NOTE: 713.13(2) IF THE WORK DESCRIBED IN
 THE NOTICE OFCOMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE
 NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE
 THE FIRST INSPECTION.
  
 3A) COMPLIED.
  
 3B) NOTE THIS IS A STATEMENT THAT MUST APPEAR ON THE
 PLANS FOR A THRESHOLD BUILDING!!! THRESHOLD BUILDINGS:
 W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD "CONTAIN A STATEMENT"
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3C)WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION
 SERVICES DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY FL S S553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561) 805-6711 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 3D)FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING
 ANY BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT
 IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING PURSUANT
 TO "A STRUCTURAL INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD".THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 4) NEW NOTE FOR STRUCTURAL CALCULATIONS:
 4A) ONLY TWO SETS OF CALCULATIONS SUBMITTED, FOR
 THRESHOLD BUILDINGS THREE ARE REQUIRED.
 4B) CALCULATIONS DATED JUNE 1, 2007 ONLY 2 SETS THERE
 IS NO SEAL, DATE NOR SIGNATURE ON THE TITLE SHEET NOR
 ANY OF THE REPORT THAT FOLLOWS. PLEASE SEE FL
 ADMINISTRATIVE CODE 61G15-23.002 FOR COVER AND OR INDEX
 SHEET
 REQUIREMENTS AND OR SIGNINGAND SEALING OF EVERY PAGE IN
 THE REPORT.
 4C) CALCULATIONS DATED JUNE 8, 2007 ONLY 2 SETSTHERE
 IS NO SEAL, DATE NOR SIGNATURE ON THE TITLE SHEET NOR
 ANY OF THE REPORT THAT FOLLOWS. PLEASE SEE FL
 ADMINISTRATIVE CODE 61G15-23.002 FOR COVER AND OR INDEX
 SHEET
 REQUIREMENTS AND OR SIGNINGAND SEALING OF EVERY PAGE IN
 THE REPORT.
  
  
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-10-03 Cont ID  
Sent By jwitmer Date 2007-10-03 Time 08:36 Rev Time 1.55
Received By jwitmer Date 2007-10-03 Time 08:36 Sent To  
Notes
2007-10-03 08:56:20PANERA BREAD 3RD REV
 BUILDING PLAN REVIEW
 PERMIT: 07030523
 ADD: 700 S ROSEMARY# 142
 CONT: PEMBERTON BUILDERS
 TEL: (561)718-8624
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.NOTE: 713.13(2) IF THE WORK DESCRIBED IN
 THE NOTICE OFCOMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE
 NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE
 THE FIRST INSPECTION.
  
 3A) IT HAS BEEN BROUGHT TO MY ATTENTION THAT THE SHEET
 G-CS CODE CLASSIFICATION HAS THE BUILDING
 CLASSIFICATION AS A TYPE II UNPROTECTED.THE 5 STORY
 PARKING STRUCTURE IS PART OF THIS BUILDING CREATING A 5
 STORYSTRUCTURE, NOT A 2 STORY STRUCTURE. THIS CREATES
 A TYPE 1-B BUILDING AND ALSO ENACTS THIS AS A
 "THRESHOLD BUILDING".A THRESHOLD INSPECTOR WILL BE
 REQUIRED FOR THE STRUCTURAL PORTION OF THE REMODEL,
 THIS REQUIREMENT REQUIRES (3) SETS OF PLANS , REPORTS,
 AND PRODUCT APPROVALS TO BE SUBMITTED.
  
 3B) THRESHOLD BUILDINGS:W.P.B. AMENDMENT 105.13.4.4
 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE FIRE-SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 3C)WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION
 SERVICES DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY FL S S553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561) 805-6711 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 3D)FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING
 ANY BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT
 IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING PURSUANT
 TO A STRUCTURALINSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST
 BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-02 Cont ID  
Sent By jwitmer Date 2007-08-02 Time 09:53 Rev Time 4.44
Received By jwitmer Date 2007-08-02 Time 07:08 Sent To  
Notes
2007-08-02 10:15:49PANERA BREAD 2ND REV
 BUILDING PLAN REVIEW
 PERMIT: 07030523
 ADD: 700 S ROSEMARY# 142
 CONT: PEMBERTON BUILDERS
 TEL: (561)718-8624
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.NOTE: 713.13(2) IF THE WORK DESCRIBED IN
 THE NOTICE OFCOMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING THEREOF, SUCH NOTICE
 IS NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE
 NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE
 THE FIRST INSPECTION.
  
 3)BUILDING PROVISO: 109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW
 CONSTRUCTION RELATED MATERIALS EQUIPMENT AND DEBRIS TO
 REMAIN LOOSE OR OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE WATCH HAS BEEN
 ISSUED UNTIL THE HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS SHALL BE EITHER REMOVED FROM THE CONSTRUCTION
 SITE OR SECURED IN SUCH A MANNER AS TO MINIMIZE THE
 DANGER OF SUCH CONSTRUCTION MATERIALS, EQUIPMENT AND
 DEBRIS CAUSING DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS. ANY PERSONS WHO FAILS TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTIONMATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 4-5) COMPLIED.
  
 6) 2ND REQUEST, 1609.1.4 PROTECTION OF OPENINGS. IN
 WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT
 RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3
 M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE
 BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT
 RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR
 PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996,
 OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN
 AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M)
 OF GRADE SHALL MEET THE REQUIREMENTS OF THE LARGE
 MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 THE PRODUCT APPROVAL SIGNED OFF BY ARCHITECT LOUISE K
 CRAVER APPARENTLY MISSED THIS IS A NON-RATED ASSEMBLY.
  
 7) 2ND REQUEST,7)FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING,
 ROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 ,
 NOT THE (12) TWELVE COPIES SUBMITTED, OF PRODUCT
 TESTING REPORTS, MISSING REPORTS ARE AS FOLLOWS:A)
 STOREFRONT WINDOWS: YKK SERIES YHS-50 FINOA
 02-0618.08
 12 SETS ONLY 2 ARE REQUIRED, THIS REPORT IS A 1994
 TEST REPORT AND THE FASTENERS TOOK 1 1/3 STEEL
 INCREASES NOT ALLOWED BYTHE 2004 FBC. REQUIRES REVIEW
 BY A FLORIDA PE OR TAKE THE DESIGN PRESSURES LISTED IN
 THE NOA AND DIVIDE BY 1.33 TO COMPLY WITH THE 2004
 FBC.
 PLEASE HIGHLIGHT THE TYPE OF GLAZING TO BE INSTALLED IN
 THESE UNITS. IT APPEARS THAT THERE MAY BE PROBLEMS
 POSSIBLY WITH ZONE 4 AND DIFFERENTLY ZONE 5. PLEASE
 IDENTIFY THESE ZONES.
 SHEET A-2.2 THE WINDOWS NEXT TO THE FRONT ENTRY
 INDICATES ACTUAL CURVED GLAZING, WILL THIS WINDOW BE
 ACTUALLY CURVED? IF SO PROVIDE THE PRODUCT APPROVAL
 WITH TESTING.
 B) MULLIONS- MAY OR MAY NOT BE PART OF THE NOA, A
 SECOND ISSUE IS THE HEIGHT OF THE HORIZONTAL MULLIONS
 ON SHEETS A-5.1 AND A-5.2 IN EITHER CASE ONE OF THE
 WINDOWS ARE
 ILLUSTRATED WRONG EFFECTING THE SQ FT AREA OF THE
 GLAZING.
 THIS SAME AREA OR WINDOWA VERTICAL MULLION APPEARS TO
 BE MISSING.
 C) GLAZED SWING DOORS (EXTERIOR) YKK SERIES 20D NARROW
 STILENOA 03-0801.05
 THE NOA SUBMITTED HAS NO IMPACT TESTING, THIS DOOR IS
 LOCATED IN AN END ZONE (5) , PRESSURES ARE LOW ALSO
 TESTED UNDER THE 1994 CODE. ,THIS REPORT IS A 1994 TEST
 REPORT AND THE FASTENERS TOOK 1 1/3 STEEL INCREASES NOT
 ALLOWED BYTHE 2004 FBC. REQUIRES REVIEW BY A FLORIDA
 PE OR TAKE THE DESIGN PRESSURES LISTED IN THE NOA AND
 DIVIDE BY 1.33 TO COMPLY WITH THE 2004 FBC. SUBMIT ONLY
 (2) SETS OF PRODUCT APPROVALS THAT HAVE LARGE MISSILE
 TESTING. AND MEET THE END ZONE PRESSURES.
 D) EXTERIOR METAL SWING DOORSPRESSURES ARE GOOD FOR
 ZONE 4 ONLY, PLEASE SUBMIT ONLY 2 SETS OFPRODUCT
 APPROVALS.
  
 E) PRE ENGINEERED A/C STANDS PRESSURES ARE GOOD SUBMIT
 ONLY 2 SETS OF PRODUCT APPROVALS
 F) EFIS SYSTEMS PLEASE SUBMIT ONLY 2 PRODUCT
 APPROVALS, HIGHLIGHT WHICH SUBSYSTEM TO BE USED. VERIFY
 PRESSURES.
  
 8) COMPLIED.
  
 9) 2ND REQUEST WPB ADMIN CODE 106.3* PRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. THE RESPONSEINDICATES THE
 NOA?S WERE SIGNED THEY NEED TO BE REVIEWED BY THE
 DESIGNER OF RECORD.
  
 10) 2ND REQUEST,SHEET G-SP2HEADING 815-C
 INSTALLATIONINDICATES A WIND PRESSURE OF 26PSF PLEASE
 SEE TABLE 1609.6.2.1(1)ALSO SEE MULTIPLIERS THE
 SHOPPING CENTER AND PARKING GARAGE ARE CONSIDERED ONE 5
 STORY BUILDING!!!! SEE TABLE 1609.6.2.1(4) FOR
 MULTIPLIERS.,
 PRESSURES SHOULD BE HIGHER AS ON SHEET S3.1.
  
 11-12) COMPLIED.
  
 13) SEMI-COMPLIED, THE OLD VOID SHEETS HAVEN?T BEEN
 REMOVED AS REQUESTED
 UNDER COMMENT # 1.
  
 14) 2ND REQUEST DEALS WITH PROVIDING INFORMATION ON THE
 FREEZER AND WALK-IN COOLERS, RESPONSE INDICATES SHOP
 DRAWINGS WERE SUBMITTED, NOT IN THIS SUBMITTAL:
 2603.4.1.2 COOLER AND FREEZER WALLS.
 FOAM PLASTIC INSTALLED IN A MAXIMUM THICKNESS OF 10
 INCHES (254 MM) IN COOLER AND FREEZER WALLS SHALL: 1.
 HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE
 TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS.
 2.HAVE FLASH IGNITION AND SELF-IGNITION
 TEMPERATURES OF NOT LESS THAN 600?F AND 800?F (316?C
 AND 427?C), RESPECTIVELY.
 3.HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8
 MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT
 ANY POINT.
 4.BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM.
 WHERE THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH
 THE COOLER OR FREEZER AND THAT PART OF THE BUILDING IN
 WHICH IT IS LOCATED SHALL BE SPRINKLED.
  
 2603.4.1.3 WALK-IN COOLERS.
 IN NON-SPRINKLED BUILDINGS, FOAM PLASTIC HAVING A
 THICKNESS THAT DOES NOT EXCEED 4 INCHES (102 MM) AND A
 MAXIMUM FLAME SPREAD INDEX OF 75 IS PERMITTED IN
 WALK-IN COOLERS OR FREEZER UNITS WHERE THE AGGREGATE
 FLOOR AREA DOES NOT EXCEED 400 SQUARE FEET (37 M 2 )
 AND THE FOAM PLASTIC IS COVERED BY A METAL FACING NOT
 LESS THAN 0.032-INCH-THICK (0.81 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL
 THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO
 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A
 THERMAL BARRIER.
  
 15) SEMI-COMPLIED. PLEASE ONLY SUBMIT (2) SETS OF FIRE
 SPRINKLER PLANS FOR THIS REVIEW. THE FIRE SPRINKLER
 CONTRACTOR WILL NEED TO SUPPLY(2) MORE SETS FOR THEIR
 OWN FIRE SPRINKLER PERMITTO BE FILED AT A LATER DATE.
 THE OTHER ISSUE IS UNTIL THE HEIGHT OF THE COOLERS AND
 FREEZERS ARE KNOWN THE UNKNOWN IS THE FIRE SPRINKLERS
 TO BE LOCATED IN THE COOLERS!
  
 16) COMPLIED.
  
 17) SEMI-COMPLIED, PLEASE REMOVE OLD SHEETS AS PER
 COMMENT # 1.
  
 18-20) COMPLIED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 PLAN EXAMINER II BUILDING
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-15 Cont ID  
Sent By jwitmer Date 2007-05-15 Time 15:08 Rev Time 3.33
Received By jwitmer Date 2007-05-15 Time 15:08 Sent To PC
Notes
2007-05-15 16:23:37BUILDING PLAN REVIEW
 PERMIT: 07030523
 ADD: 700 S ROSEMARY# 142
 CONT: PEMBERTON BUILDERS
 TEL: (561)718-8624
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 4) SHEET G-SP1 DESIGN STRESS REFERENECS THE 2003 IBC
 PLEASE CORRECT TO THE 2004 FBC W /2006 REVISIONS
  
 5)THE PLANS DO NOT PROVIDE THE WIND DESIGN CRITERIA
 FOR THE NEW WINDOWS AND DOORS,
 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF. POSITIVE AND NEGATIVE
 ZONE 4 & 5.
  
 6 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 7)FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT WINDOWS
 B) MULLIONS
 C) GLAZED SWING DOORS (EXTERIOR)
 D) EXTERIOR METAL SWING DOORS
 E) PRE ENGINEERED A/C STANDS
 F) EFIS SYSTEMS
  
 8)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 10) SHEET G-SP2HEADING 815-C INSTALLATIONINDICATES
 A WIND PRESSURE OF 26PSF PLEASE SEE TABLE
 1609.6.2.1(1)ALSO SEE MULTIPLIERS THE SHOPPING CENTER
 AND PARKING GARAGE ARE CONSIDERED ONE 5 STORY
 BUILDING!!!! SEE TABLE 1609.6.2.1(4) FOR MULTIPLIERS.
  
 11)1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 12)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 13) THE MEP SHEETS THE ENGINEERS SIGNATURE IS A STAMP
 NOT AN ORIGINAL SIGNATURE,
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 14)PLEASE PROVIDE INFORMATION ON THE FREEZER AND
 WALK-IN COOLERS:
 2603.4.1.2 COOLER AND FREEZER WALLS.
 FOAM PLASTIC INSTALLED IN A MAXIMUM THICKNESS OF 10
 INCHES (254 MM) IN COOLER AND FREEZER WALLS SHALL: 1.
 HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE
 TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS.
 2.HAVE FLASH IGNITION AND SELF-IGNITION
 TEMPERATURES OF NOT LESS THAN 600?F AND 800?F (316?C
 AND 427?C), RESPECTIVELY.
 3.HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8
 MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT
 ANY POINT.
 4.BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM.
 WHERE THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH
 THE COOLER OR FREEZER AND THAT PART OF THE BUILDING IN
 WHICH IT IS LOCATED SHALL BE SPRINKLERED.
  
 2603.4.1.3 WALK-IN COOLERS.
 IN NONSPRINKLERED BUILDINGS, FOAM PLASTIC HAVING A
 THICKNESS THAT DOES NOT EXCEED 4 INCHES (102 MM) AND A
 MAXIMUM FLAME SPREAD INDEX OF 75 IS PERMITTED IN
 WALK-IN COOLERS OR FREEZER UNITS WHERE THE AGGREGATE
 FLOOR AREA DOES NOT EXCEED 400 SQUARE FEET (37 M 2 )
 AND THE FOAM PLASTIC IS COVERED BY A METAL FACING NOT
 LESS THAN 0.032-INCH-THICK (0.81 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL
 THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO
 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A
 THERMAL BARRIER.
  
 15) FOR THE BUILDING AREA INCREASES WERE TAKEN, PLEASE
 PROVIDE FIRE SPRINKLER PLANS FOR THE BUILD OUT AND
 COOLER/ FREEZER.
  
 16)SHEET A2.3 DOESN'T INDICATE COMPLIANCE WITH:
 11-5.2 COUNTERS AND BARS.
 WHERE FOOD OR DRINK IS SERVED AT COUNTERS EXCEEDING 34
 INCHES (865 MM) IN HEIGHT FOR CONSUMPTION BY CUSTOMERS
 SEATED ON STOOLS OR STANDING AT THE COUNTER, A PORTION
 OF THE MAIN COUNTER WHICH IS 60 INCHES (1525 MM) IN
 LENGTH MINIMUM SHALL BE PROVIDED IN COMPLIANCE WITH
 SECTION 11-4.32 OR SERVICE SHALL BE AVAILABLE AT
 ACCESSIBLE TABLES WITHIN THE SAME AREA.
  
 11-5.3 ACCESS AISLES.
 ALL ACCESSIBLE FIXED TABLES SHALL BE ACCESSIBLE BY
 MEANS OF AN ACCESS AISLE AT LEAST 36 INCHES (915 MM)
 CLEAR BETWEEN PARALLEL EDGES OF TABLES OR BETWEEN A
 WALL AND THE TABLE EDGES.
  
 11-5.4 DINING AREAS.
 IN NEW CONSTRUCTION, ALL DINING AREAS, INCLUDING RAISED
 OR SUNKEN DINING AREAS, LOGGIAS, AND OUTDOOR SEATING
 AREAS, SHALL BE ACCESSIBLE. IN ALTERATIONS,
 ACCESSIBILITY TO RAISED OR SUNKEN DINING AREAS, OR TO
 ALL PARTS OF OUTDOOR SEATING AREAS IS NOT REQUIRED
 PROVIDED THAT THE SAME SERVICES AND DECOR ARE PROVIDED
 IN AN ACCESSIBLE SPACE USABLE BY THE GENERAL PUBLIC AND
 ARE NOT RESTRICTED TO USE BY PEOPLE WITH DISABILITIES.
  
 EXCEPTION: NOTHING IN THIS SECTION SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW OCCUPIABLE
 GRADE LEVEL, REGARDLESS OF WHETHER THE CODE REQUIRES AN
 ELEVATOR TO BE INSTALLED IN SUCH BUILDINGS, STRUCTURES
 OR FACILITIES EXCEPT: (1) ELEVATOR PITS, ELEVATOR
 PENTHOUSES, MECHANICAL ROOMS, PIPING OR EQUIPMENT
 CATWALKS, AND AUTOMOBILE LUBRICATION AND MAINTENANCE
 PITS AND PLATFORMS; (2) UNOCCUPIABLE SPACES, SUCH AS
 ROOMS, ENCLOSED SPACES, AND STORAGE SPACES THAT ARE NOT
 DESIGNED FOR HUMAN OCCUPANCY, FOR PUBLIC
 ACCOMMODATIONS, OR FOR WORK AREAS; AND (3) OCCUPIABLE
 SPACES AND ROOMS THAT ARE NOT OPEN TO THE PUBLIC AND
 THAT HOUSE NO MORE THAN FIVE PERSONS INCLUDING, BUT NOT
 LIMITED TO, EQUIPMENT CONTROL ROOMS AND PROJECTION
 BOOTHS. THEREFORE, FACILITIES SUBJECT TO THE ADA MAY BE
 REQUIRED TO PROVIDE VERTICAL ACCESS TO AREAS OTHERWISE
 EXEMPT UNDER SECTION 11-4.1.3 (5), OF THE CODE.
  
 11-5.5 FOOD SERVICE LINES.
 FOOD SERVICE LINES SHALL HAVE A MINIMUM CLEAR WIDTH OF
 36 INCHES (915 MM), WITH A PREFERRED CLEAR WIDTH OF 42
 INCHES (1065 MM) TO ALLOW PASSAGE AROUND A PERSON USING
 A WHEELCHAIR. TRAY SLIDES SHALL BE MOUNTED NO HIGHER
 THAN 34 INCHES (865 MM) ABOVE THE FLOOR (SEE FIGURE
 11-53 ). IF SELF-SERVICE SHELVES ARE PROVIDED, AT LEAST
 50 PERCENT OF EACH TYPE MUST BE WITHIN REACH RANGES
 SPECIFIED IN SECTIONS 11-4.2.5 AND 11-4.2.6 .
  
 17)MPE 1.1 REFRIGARATION STAND SUPPORT INDICATES THAT
 THE STAND WILL BE 24" TALL BUT THE DETAIL INDICATES
 THAT THE BASE PLATE TO CUT THROUGH THE ROOF INSULATION,
 CORIDGATED ROOF DECK AND BEAR DIRECTLY ON THE BAR JOIST
 AT THIS POINT YOU WILL NOT HAVE THE 24" CLEAR HEIGTH
 REQUIRED SEE TABLE 1509.7.
 THE SECOND ISSUE WITH THIS TYPE OF INSTALLATION IS HOW
 WILL THE ROOF SYSTEM BE RESEALED?
  
 18) CHANGE OF USE; 13-101.4.1.1 PREVIOUSLY
 UNCONDITIONED EXISTING BUILDINGS WHICH WERE PERMITTED
 PRIOR TO MARCH 15, 1979 TO WHICH HEATING OR COOLING
 SYSTEMS ARE ADDED SHALL MEET THE PRESCRIPTIVE
 REQUIREMENTS CONTAINED IN METHODS B OR C OF SUBCHAPTER
 13-4 FOR COMMERCIAL APPLICATIONS
  
 19) AWNINGS AND SIGNS REQUIRE A SEPERATE PERMIT.
  
 20) 3105.1.1.2A FIXED FABRIC AWNING OR FABRIC-COVERED
 FRAME SHALL NOT EXTEND OVER PUBLIC PROPERTY MORE THAN
 TWO-THIRDS THE DISTANCE FROM THE PROPERTY LINE TO THE
 NEAREST CURB LINE IN FRONT OF THE BUILDING SITE AS
 MEASURED FROM THE EXTERIOR FACE OF THE BUILDING NOR
 SHALL ANY PORTION BE CLOSER THAN 18 INCHES (457 MM) TO
 THE CURB LINE.
 EXCEPTIONS:
 1.IF INSTALLED OVER 14 FEET (4267 MM) IN HEIGHT,
 IT MAY OCCUPY THE ENTIRE WIDTH OF THE SIDEWALK.
 2.UNLESS OTHERWISE REGULATED BY LOCAL ZONING
 REQUIREMENTS.
 3105.3.1
 FABRIC USED FOR AWNINGS OR FABRIC-COVERED FRAMES SHALL
 BE FLAME RESISTANT IN ACCORDANCE WITH NFPA 701.
 3105.4.2.1
 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING
 CRITERIA:
 1.MINIMUM WIND VELOCITY OF 3-SECOND WIND GUST 90
 MPH
 2.IMPORTANCE FACTOR BASED ON LOW HAZARD TO HUMAN
 LIFE OF 0.77.
 3.EXPOSURE CATEGORY B FOR OR C AS DEFINED IN
 CHAPTER 16 .
  
 3105.4.2.2
 THE WIND DESIGN LOADS FOR ANY FABRIC OR MEMBRANE
 COVERED STRUCTURE DESIGNED WITH A PERMANENT OR
 NONREMOVABLE FABRIC OR MEMBRANE, SHALL BE BASED ON THE
 FOLLOWING CRITERIA:
 1.MINIMUM WIND VELOCITY AS REQUIRED IN CHAPTER 16
 .
 2.IMPORTANCE FACTOR BASED ON LOW HAZARD TO HUMAN
 LIFE OF 0.77.
 3.EXPOSURE CATEGORY B OR C AS DEFINED IN CHAPTER
 16 .
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 PLAN EXAMINER II BUILDING
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-06-16 Cont ID  
Sent By dpalmer Date 2008-06-16 Time 12:12 Rev Time 0.00
Received By dpalmer Date 2008-06-16 Time 12:12 Sent To PC
Notes
2008-06-16 12:13:04ELEC REV 2.2 AND 5.1.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-12-20 Cont ID  
Sent By dpalmer Date 2007-12-20 Time 19:32 Rev Time 0.00
Received By dpalmer Date 2007-12-20 Time 19:32 Sent To  
Notes
2007-12-20 19:33:04TEMP FAILED AS RESUB FEES WERE NOT PAID.
  
 PLEASE CONTACT REVIEWER ONCE FEES ARE PAID.
  
 STAMPED PLANS.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-12-04 Cont ID  
Sent By dpalmer Date 2007-12-04 Time 12:37 Rev Time 0.00
Received By dpalmer Date 2007-12-04 Time 12:37 Sent To  
Notes
2007-12-04 12:37:47** DENIED 4THREVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING
  
 1) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE
 CALCULATIONS ARE IN NEED OF ADDRESSING.
 PLEASE SEE 13-415.2.ABC.1, ONLY LIGHTING WHICH IS
 INTEGRAL FOR SIGNAGE IS EXEMPT.
 PLEASE PROVIDE INFORMATION ON THESE TYPES OF SIGNS AS
 THE LIGHTING T1A AND IT3 IS TRACK LIGHTING. HOW CAN THE
 TRACK LIGHTING BE INTEGRAL?
 PLEASE ALSO SEE OTHER TRACK LIGHTING ON FIXTURE LEGEND
 WHERE FIXTURE WATTAGE IS SHOWN AS N/A. HOW IS THIS
 POSSIBLE WHEN PLANS INDICATE THESE FIXTURES BEING
 INSTALLED?
 PLEASE SEE FIXTURE T1-2 FOR EXAMPLE.
 PLEASE SEE 13-415.2, BASED ON THE MISSING CALCULATIONS,
 THE TOTAL LOOKS LIKE IT WOULD EXCEED THE MAXIMUM
 ALLOWANCES AS SET-FORTH IN THE FLORIDA ENERGY
 CODE/FLORIDA BUILDING CODE.
  
 2) NOTE: PLEASE KNOW A PERMANENT LADDER FOR ACCESS TO
 TRANSFORMER WILL BE REQUIRED. THIS WAS GONE OVER IN
 MEETING WITH OTHER TENANT WHICH IS SHARING THE SPACE
 ABOVE THE ELEVATOR MACHINE ROOM.
 PLEASE VERIFY WITH OTHER TENANT/LANDLORD WHOM IS GOING
 TO HAVE ON PLANS AND INSTALL.
 THIS ITEM CAN BE RED-LINED/NOTED ON PLANS AND DOES NOT
 NEED TO BE ADDRESSED AT THIS TIME UNLESS THE SCOPE OF
 WORK FOR LADDER WILL BE DONE UNDER THIS PERMIT.
 ** NOTED FOR INFORMATION.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-09-28 Cont ID  
Sent By dpalmer Date 2007-09-28 Time 21:31 Rev Time 0.00
Received By dpalmer Date 2007-09-28 Time 19:34 Sent To  
Notes
2007-09-28 21:32:062007-09-28 21:32:06
  
 ** DENIED 3RD REVIEW ***
  
 ** PLEASE SEE THERE ARE SEVERAL COMMENTS FROM PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
  
 ** PLEASE SEE THERE ARE SOME NEW COMMENTS BASED ON
 PLANS AND REVISIONS TO PLANS WHICH INFORMATION IS ONLY
 NOW BEING SUBMITTED. DUE TO CHANGES AND INFORMATION
 WHICH WAS NOT ON PREVIOUS PLANS OR REVIEW, THESE ITEMS
 COULD NOT HAVE COMMENTED ON AS SOME ITEMS AND
 INFORMATION IS NEW TO PLANS AND/OR DESIGN. THESE ITEMS
 WILL BE CLEARLY NOTED.
  
 **PLEASE SEE THERE IS ONE NEW COMMENT BASED ON
 INFORMATION RECENTLY CONFIRMED FROM THE FLORIDA
 BUILDING COMMISSION.
  
  
 1) NOTE: PLEASE SEE COMPLIANCE WITH THE FBC CHAPTER 13
 HAS NOT YET BEEN ACHIEVED.
 PLEASE SEE THE FOLLOWING ITEMS:
 A) PLEASE KNOW AS OF RECENT INFORMATION CONFIRMED WITH
 THE FLORIDA BUILDING COMMISSION, METHOD A ON THE ENERGY
 CALCULATIONS MAY NOT BE USED AS THIS TENANT SPACE IS
 NOT A BUILDING BY THE DEFINITIONS AS SET FORTH IN FBC
 CHAPTER 13 AS WELL AS THE FBC DEFINITIONS. THIS DATE OF
 CONFORMATION WAS 9/24/07.
 PLEASE KNOW AS THE *BUILDING* ALREADY CONTAINS AIR
 CONDITIONING AND AS LONG AS MEETING THE REQUIREMENTS
 FOR MECHANICAL MAKE UP AIR ETC, THE ENERGY CALCULATIONS
 ARE NOT NEEDED FOR ELECTRICAL. PLEASE KNOW HOWEVER THAT
 THE LIGHTING PERFORMANCE CALCULATIONS ARE STILL NEEDED
 AND MAY BE SET UP IN A TABLE FORM USING THE SAME
 INFORMATION ON PLANS AS LONG AT THE LIGHTING LEVELS
 MEET 13-415.2, 13-415.2.C.1, OR 13-415.2.B. PLEASE
 REMEMBER TO SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING.
 PLEASE SEE ANY EXTERIOR LIGHTING WILL BE BASED ON
 13-415.2.ABC.1.3.
 ** PLEASE CALL TO GO OVER.
  
 B) PLEASE SEE THE LIGHTING METHOD OF CONTROLS PER
 13-415.1.ABC.1.1, .1.2 AND .1.3 IS STILL IN QUESTION.
 PLEASE SEE THERE ARE STANDARD SWITCHES SHOWN ON PLANS
 BETWEEN MENS RESTROOM AND KITCHEN AREA. HOW DO THESE
 OPERATE AND FALL INTO THE REQUIREMENTS OF CHAPTER 13?
  
 2) NOTE: PLEASE KNOW THE FIRE SPRINKLER PLANS , SHOP
 DRAWINGS AND SUBMITTALS WILL BE UNDER SEPARATE FIRE
 ALARM AND FIRE SPRINKLER PERMITS. **THIS IS NOTED FOR
 INFORMATION ONLY.
  
 3) NOTE: PLEASE SEE THE SERVICE RISER HAS NOW BEEN
 SUBSTANTIALLY REVISED WHICH NOW INDICATES A EXISTING
 600AMP TENANT MAIN. THIS IS UNCLEAR HOW THIS IS
 POSSIBLE AS STATED ON PREVIOUS REVIEW. THIS SITE WILL
 BE INSPECTED WITHIN THE FIRST WEEK OF OCTOBER AS THE
 PREVIOUS SPACE ONLY HAD ONE TENANT MAIN FOR TWO FLOOR
 AND NOW PLANS FOR THIS SPACE AND NEW TENANT SPACE ABOVE
 BOTH INDICATE ONE EXISTING 400AMP MAIN AND ONE EXISTING
 600AMP MAIN.???
 PLEASE SEE THE RISER MENTIONS THIS IS BEING TAPPED FROM
 AN EXISTING WIRE-WAY WHICH IS FED FROM AN EXISTING
 SERVICE MAIN #2, YET THE LOAD CALCULATIONS WHICH WAS
 REQUESTED ON PREVIOUS REVIEW INDICATE THIS TENANT MAIN
 FOR PANERA BREAD BEING FIGURED FOR *EXISTING SERVICE
 MAIN #3*. ??
 THIS IS TWO DIFFERENT SERVICE MAINS. RISER SHOWS
 *SERVICE MAIN #2* AND LOAD CALCULATIONS SHOW *SERVICE
 MAIN #3*.PLEASE UNDERSTAND AND SEE HOW THIS IS
 COMPLETELY CONFUSING AND UNCLEAR WHERE SERVICE IS BEING
 FED.
 PLEASE SEE THE LOAD SHOWN ON MDP FOR KVA (222.79) IS
 NOT THAT OF THE LOAD BEING SHOWN ON THE LOAD
 CALCULATIONS ON THE SAME SHEET FOR SERVICE MAIN.
 (221.40)
 NO FURTHER REVIEWS ON EITHER BUILD OUT WILL BE DONE
 UNTIL FIELD MEETING AND INSPECTION IS DONE. THIS HAS
 BEEN REQUESTED ON 9/26 WITH CITY PLACE AND WILL NEED TO
 TAKE PLACE AS SOON AS POSSIBLE TO GET SOME CLARITY ON
 ACTUAL INSTALLATION. IT IS SUGGESTED THE ENGINEERING
 FIRM OBTAINS THE ACTUAL INFORMATION ON SERVICE(S) AS
 SHOWN.
 215.5, 230, 220, 240 ETC
 FBC 106.1.2, 106.3.5.1.2
 PLEASE KNOW AS THE SERVICE MAINS, IDENTIFICATION ETC
 CAN NOT YET BE CONFIRMED THE LOAD CALCULATIONS AS
 PREVIOUSLY REQUESTED IN NOTE #9, CAN NOT BE CONFIRMED
 AT THIS TIME.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #13 WHICH
 REQUESTED THE MANUFACTURES SPECS/CUT SHEETS FOR THE
 PROPOSED DISTRIBUTION CENTER. THESE WERE NOW SUBMITTED,
 HOWEVER ONLY THE SHEETS CONTAINS A NOTE WHICH MENTIONS
 THIS IS A UL LISTED SYSTEM. NO SUBMITTALS WHICH ARE
 ACTUAL SPEC/CUT SHEETS FOR EQUIPMENT WERE SUBMITTED
 WHICH SHOW AND INDICATE THE LISTING(S) FROM A NRTL.
 (NATIONALLY RECOGNIZED TESTING LABORATORY). **PLEASE
 SEE THE SHEETS SUBMITTED DO NOT CORRELATE WITH PLANS,
 IN FACT THESE ARE COMPLETELYDIFFERENT FOR OVER
 CURRENT PROTECTION SIZES, ETC.
 * FOR EXAMPLE, PLEASE SEE SPECS/CUT SHEETS SHOW THIS AS
 BEING AN 800AMP MLO (MAIN LUG ONLY) PIECE OF EQUIPMENT,
 YET THE RISER DIAGRAM CLEARLY SHOWS THIS AS BEING AN
 600AMP MCB (MAIN CIRCUIT BREAKER) PANEL-BOARD. THIS
 ALSO SHOWS COMPLETELY DIFFERENT SUB-PANELS WHICH FOR
 INSTANCE A PANEL *M* WHICH IS SHOWN AS 400AMP MLO.
 PANEL *M* ON PLANS/RISER IS 600AMP MCB.
 **PLEASE CORRELATE AND COORDINATE ALL PLANS, RISER,
 DOCUMENTS AND SPECIFICATIONS.
 110.3, 90.7
 FBC 106.1.2, 106.3.5.1.2
  
 5) NOTE: PLEASE SEE PREVIOUS NOTE #15 WHICH GAVE NOTICE
 TO THE 150KVA TRANSFORMER WHICH IS BEING SHOWN ABOVE
 THE OFFICE WHICH IS STRICTLY PROHIBITED BY THE NEC. THE
 PLANS AS SUBMITTED STILL SHOW THIS ABOVE OFFICE WHICH
 WILL NOT BE ACCEPTED BY THIS AHJ.
 AS THE PLANS INDICATE THIS AS A COMPLETELY CLOSED IN
 SPACE WITH CEILING TILES, GRID LIGHTING ETC THIS IS NOT
 ONLY A LIFE SAFETY ISSUE HOWEVER A FIRE AND PROPERTY
 HAZARD.
 PLEASE SEE THE DISCONNECTING MEANS IS REQUIRED TO BE
 READILY ACCESSIBLE AND THE LOCATION AS SHOWN DOES NOT
 MEET THIS EITHER.
 THESE ITEMS WILL BE REVIEWED FOR NUMEROUS NEC CODES. A
 NEW LOCATION WILL NEED TO BE FOUND.
 FBC 106.3.5.1.2, NEC 450.13B, 450.21, 450.9, 110.26,
 408.7 ETC.
 PLEASE ALSO SEE 240.21 AS THE LENGTH OF CONDUCTORS IS
 OF CONCERN TO MEET THIS SECTION OF THE NEC. THE
 LOCATIONS OF TRANSFORMER AND DISCONNECTING MEANS ON THE
 LOAD SIDE WILL NEED TO BE REVIEWED ONCE ADJUSTMENTS ARE
 MADE TO PLANS.
 THE DETAIL ON A-3.1 AND A-4.4 DOES NOT MATCH WITH PLANS
 AS DETAIL ON 4.4 INDICATES THE BOTTOM OF THE OFFICE
 CEILING FLUSH WITH THE UNDERSIDE OF THE SLAB, WHICH CAN
 NOT BE POSSIBLE WHEN THERE IS A RECESSED LIGHT FIXTURE
 WHICH IS SUPPOSE TO BE LOCATED AT THE SAME LOCATION. IT
 IS RECOMMENDED THAT PHONE CALLS BE MADE AND POSSIBLE
 LOCATIONS BE GONE OVER WITH THIS OFFICE BEFORE
 RESUBMITTING PLANS.
  
 6) NOTE:PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE
 SEE THIS IS ONLY A NOTICE GIVEN AT THIS TIME. ** PLEASE
 KNOW ONE SET OF PLANS ARE BEING RETAINED BY THIS OFFICE
 AND WILL BE PLACED WITH PREVIOUSLY RETAINED PLANS.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS WHICH WILL BE
 REQUIRED TO BE REVISED; PLEASE KNOW THAT CODE REVIEW OF
 THESE ITEMS CAN NOT BE DONE AT THIS TIME.
 COMPLETE REVIEW FOR CODE COMPLIANCE CAN ONLY BE BASED
 ON THE PLANS SUBMITTED.
 IT IS RECOMMENDED THAT ALL INFORMATION AS MUCH AS
 POSSIBLE IS GONE OVER BEFORE PLANS ARE RESUBMITTED.
 PLEASE ALSO KNOW THAT ONE COPY OF ELECTRICAL
 PLANS/SPECS SUBMITTED MAY BE RETAINED BY THIS OFFICE
 DUE TO SOME COMMENTS BEING REPEATED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-27 Cont ID  
Sent By dpalmer Date 2007-06-27 Time 19:03 Rev Time 0.00
Received By dpalmer Date 2007-06-27 Time 16:46 Sent To I
Notes
2007-06-27 19:04:35 
  
 *** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE THERE ARESEVERAL COMMENTS FROM PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE
 SEE THERE ARE SOME NEW COMMENTS BASED ON PLANS AND
 REVISIONS TO PLANS WHICH INFORMATION IS ONLY NOW BEING
 SUBMITTED. MOST OF THE COMMENTS ARE FROM THE PREVIOUS
 REVIEW AND WILL BE INDICATED AS SUCH.
  
  
 1) NOTE: PLEASE SEE THE PREVIOUS NOTES FROM MULTIPLE
 REVIEWERS WHICH INDICATED *IMPORTANT*.ONE OF THESE
 NOTES WAS TO *COMPLETELY REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS* AND ONLY INSERT THE NEW REVISED SHEETS INTO
 THE COMPLETED SETS FOR REVIEW AND STAMPING. THIS WAS
 NOT DONE AND ALL OF OLD SHEETS WERE LEFT IN SETS. THESE
 WERE NOT MARKED/LABELED AS VOID OR ANY INDICATION THEY
 WERE NOT CURRENT. PLANS WERE REVIEWED BASED ON REVISION
 DATES. ANY SHEETS WHICH WERE NOT REVISED AND LEFT FROM
 PREVIOUS REVIEW MAY HAVE COMMENTS.
 PLEASE KNOW THIS WILL NOT BE DONE BY THIS OFFICE AND
 OLD PLANS/SHEETS MUST BE REMOVED.
 CALLED ELITE EXPEDITORS AS LISTED ON RE-SUB COVER SHEET
 FOR CONTACT AND INFORMED JENNIFER MELANSON THIS NEEDED
 TO BE DONE. AS PLANS ARE COMING BACK TO ADDRESS CODE
 COMMENTS THIS WILL BE REQUIRED TO BE DONE BEFORE
 RE-SUBMITTAL. IF PLANS ARE SUBMITTED WITHOUT THIS DONE,
 PROCESSING FOR REVIEW WILL NOT BE DONE AND PLANS WILL
 BE PLACED OUT-FRONT FOR PICK UP.
 ** PLEASE ALSO KNOW THAT ONLY TWO COMPLETE SETS ARE
 NEEDED FOR THE SCOPE OF WORK. PLEASE KNOW THIS OFFICE
 WILL STAMP UP TO THREE, HOWEVER PLEASE SEE 12 SETS OF
 ENERGY CALCULATIONS WERE SUBMITTED AND ONLY THREE WILL
 BE STAMPED ONCE CODE COMPLIANT.
 FBC 106.3.1
  
 2) NOTE: PLEASE SEE PLANS MUST CONTAIN THE
 PRE-APPROVED/REVIEWED STAMP AND SIGNATURE ON ALL PLANS
 FROM CITY PLACE MANAGEMENT/LANDLORD BEFORE THEY ARE
 STAMPED BY THE CITY OF WEST PALM BEACH FOR PERMIT
 ISSUANCE. THE PREVIOUS PLANS WERE STAMPED HOWEVER THE
 NEW SHEETS WERE NOT.
 FBC 106.1
  
 3) NOTE: PLEASE SEE THE TITLE BLOCKS FOR ARCHITECTURAL
 SHEETS ARE STILL MISSING THE PRINTED LICENSE NUMBER FOR
 THE ARCHITECT OF RECORD.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE THE ARCHITECTURAL SHEETS ARE MISSING THE
 PRINTED NAME OF THE ARCHITECT ON TITLE BLOCKS AS
 REQUIRED PER FAC61G1-16.004.
 * THIS IS REQUIRED WHETHER OR COMMENT IS MADE BY OTHER
 TRADE(S).
  
 4) NOTE:PLEASE SEE THE PROJECT WAS SUBMITTED BACK
 WITH THE SAME VALUE ON PERMIT APPLICATION AND NO
 CHANGES WERE MADE. THE APPLIED VALUE MUST INCLUDE ALL
 LABOR, MATERIALS, PERMANENTLY INSTALLED EQUIPMENT,
 DESIGN/ENGINEERING/ARCHITECTURAL FEES ETC EVEN IF ANY
 OF THESE ITEMS ARE OWNER SUPPLIED. PLEASE KNOW A VALUE
 WILL BE ASSESSED USING ADOPTED GUIDES PER THE FBC IF AN
 APPROPRIATE VALUE IS NOT ADJUSTED ON APPLICATION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF WORK
 SHALL INCLUDE ALL LABOR AND MATERIALS EVEN IF
 MATERIALS, EQUIPMENT, ETC IS OWNER SUPPLIED AS STATED
 ON PLANS.
 VALUE IS LOW AT THIS TIME. PLEASE ADJUST.
 PLEASE KNOW A VALUE MAY BE ADJUSTED BY THIS OFFICE
 USING ADOPTED DOCUMENTS INTO THE FBC.
 FBC 108.3
  
 5) NOTE: PLEASE SEE COMPLIANCE WITH THE FBC CHAPTER 13
 HAS NOT YET BEEN ACHIEVED. PLEASE SEE EH FOLLOWING
 ITEMS:
 A) PLEASE SEE THE ENERGY CALCULATIONS ARE NOT CORRECT.
  
 B)PLEASE SEE THE NUMBER OF LUMINAIRES NEED TO
 COORDINATE WITH PLANS.
 C) PLEASE SEE THE WATTAGE OF LUMINAIRES NEED TO
 CORRELATE WITH PLANS.
 D) PLEASE SEE THE METHOD OF CONTROLS NEEDS TO CORRELATE
 WITH PLANS.
 E) PLEASE SEE THE OWNER AGENT IS NOT SIGNED ON SHEET 2
 AS REQUIRED.
 F) PLEASE SEE NO TIME OF DAY SCHEDULING WAS SUBMITTED
 AS PREVIOUSLY REQUESTED.
 F) PLEASE SEE NO LOCATION FOR ALL OVER RIDE DEVICES
 WERE SHOWN ON PLANS. THE ONLYOVER RIDE DEVICE AS
 NOTED IS LOCATED AT THE LIGHTING CONTROL PANEL WHICH
 DOES NOT MEET THE CODE.
 H) PLEASE SEE ALL SEPARATE SPACES CONTAINING FLOOR TO
 CEILING HEIGHT PARTITIONS REQUIRES DEVICES: NONE WERE
 SHOWN ON PLANS.
 I) PLEASE SEE MISSING SEPARATE CONTROLS FOR
 DISPLAY/ACCENT LIGHTING.
 J) PLEASE SEE NOT EXTERIOR LIGHTING WAS FIGURED INTO
 THE CALCULATIONS. (PLEASE SEE NOTE #8)
 **PLEASE KNOW AS THIS WAS THE FIRST TIME ANY
 DESIGN/INFORMATION FOR CHAPTER 13 WAS SUBMITTED PLEASE
 ADDRESS THESE COMMENTS AND SEE THE PREVIOUS NOTE BELOW
 FOR ALL CODE SECTIONS AND SEE ALL OF CHAPTER 13 AS
 THERE ARE TOO MANY TO BE STATED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE 2004 FBC W/ 2006 REVISIONS FOR CHAPTER
 13. AT THIS TIME THERE ARE SEVERAL ITEMS MISSING FOR
 REVIEW.
 PLEASE SEE NO SCHEDULING OF SYSTEM WAS SUBMITTED.
 PLEASE SEE NO INFORMATION ON A SYSTEM WAS SUBMITTED.
 PLEASE SEE NO OVER RIDE DEVICES AT THE POINTS OF
 EGRESS/INGRESS INTO SPACE FROM ENTRANCE WIN WHICH THE
 OCCUPANT CAN SEE THE LIGHTING WHICH IS BEING
 CONTROLLED.
 PLEASE SEE NO TIMES ON ANY OVER RIDE DEVICES AND TYPES
 OF DEVICES.
 PLEASE SEE MISSING ENERGY CALCULATIONS.
 PLEASE SEE MISSING LIGHTING PERFORMANCE CALCULATIONS.
 PLEASE SEE MISSING CERTIFICATIONS PER DESIGNER(S) OF
 RECORD.
 PLEASE SEE REQUIRED CALCULATION METHODS FOR TRACK
 LIGHTING. 13-415.2.ABC.1.2
  
 PLEASE SEE 13-103.1, 13-415.1ABC.1, 13-415.1.ABC.1.1,
 .1.2 AND .1.3, 13-415.1.AB.1.1, 13-415.1.A, .B AND .C,
 13-415.2 AND TABLES UNDER THE NEW 2006 REVISIONS. ETC.
  
 6) NOTE: PLEASE SEE THE CD LEVELS SHOWN ON PLANS FOR
 MINIMUM ADA COMPLIANCE DOES NOT MEET THE FBC AS
 PREVIOUSLY STATED IN NOTES.
 PLEASE SEE THE FBC WHICH CONTAINS MORE RESTRICTIVE
 REQUIREMENTS THANNFPA.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) AND STATE
 THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR ADA
 REQUIRED AREAS. DEVICES ARE BEING SHOWN ON LEGEND ONLY.
 PLEASE INCLUDE ON LAYOUT OF PLANS AND DEVICES. PLEASE
 KNOW EVEN THOUGH FIRE SPRINKLER AND FIRE ALARM WORK
 WILL BE REQUIRED TO BE UNDER A SEPARATE PERMIT THE BASE
 FIRE ALARM DEVICES ALONG WITH FIRE PROTECTION WILL BE
 REQUIRED IN BASE PLANS. THIS WILL BE NOTED BY THE FIRE
 AND BUILDING REVIEWER(S) ALSO.
  
 7) NOTE:PLEASE SEE THE RESPONSE MENTIONS THE SIGN
 CIRCUIT WAS REMOVED FROM PANEL? WHY WAS THIS DONE?
 PLEASE SEE THE MINIMUM OF ONE CIRCUIT IS REQUIRED AT
 THE ENTRANCE LOCATION WHETHER OR NOT A SIGN INSTALLED
 AND IS TO BE FROM THE TENANT SPACE PANEL. THE EXISTING
 SIGNS LOCATED AT CITY PLACE ARE FROM EACH TENANT AND
 ONLY THE COMMON AREA SIGNS FOR CITY PLACE NOT THE
 TENANT ARE FROM THE HOUSE PANEL. 600.5
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING SIGN CIRCUIT ON PLANS AND PANEL
 SCHEDULE PER 600.5.
  
 8) NOTE: PLEASE SEE ANY EXTERIOR LIGHTING FOR COMMON
 AREA WALLS ETC ARE FROM CITY PLACE HOUSE. PLEASE SEE
 THE EXTERIOR LIGHTING SHOWN ON THESE PLANS IF UNDER THE
 LANDLORDS PANEL AND AREA WILL BE REQUIRED UNDER
 SEPARATE PERMITS AND PLANS. PLEASE OBTAIN COORDINATION
 FROM THE CITY PLACE MANAGEMENT AND LANDLORD FOR THIS.
 PLEASE ALSO SEE COMMENTS WITH RESPECT TO THE ENERGY
 CALCULATIONS AS THERE WERE NO EXTERIOR LIGHTING FIGURED
 INTO THE CALCULATIONS.
  
 9) NOTE: PLEASE SEE PLANS NOW MENTIONS AND SHOWS AN
 EXISTING 400AMP SERVICE WAS ALREADY PRESENT FOR THIS
 SPACE, HOWEVER THE EXISTING 400AMP SERVICE WAS FOR A
 MUCH LARGER SPACE WHICH IS NOW SPLIT UP TO MORE THAN
 ONE TENANT. PLANS WHICH HAVE ALREADY BEEN SUBMITTED BY
 THE NEW TENANT FOR UPSTAIRS HAS ALREADY INDICATED THE
 *EXISTING 400AMP SERVICE* IS BEING USED FOR THEIR
 SPACE? PLEASE KNOW THE COORDINATION BETWEEN THE TWO
 TENANTS AND THE LANDLORD IS IMPERATIVE FOR THIS. THE
 LOAD CALCULATIONS FOR THE EXISTING 1200AMP SERVICE FOR
 EACH OF THE NEW TENANTS INCLUDING THE LOAD FOR EACH OF
 THE NEW TENANTS WILL BE REQUIRED ON EACH SET OF RECORD
 PLANS.
 THIS INFORMATION IS A MUST AND A COMPLETE BREAKDOWN OF
 THE EXISTING AND NEW WILL BE NEEDED. AN ONSITE MEETING
 MAY ALSO BE ARRANGED TO GO OVER THIS.
 215.5,230,220,240, ETC NEC. THERE ARE TOO MANY SECTIONS
 OF CODE WHICH APPLY SPECIFICALLY TO THIS.
 FBC 106.3.5.1.2
  
 ** PREVIOUS REVIEW NOTE** PLEASE VERIFY SERVICE AS
 SHOWN AS THE RISER MENTIONS THE METER IS BEING DONE BY
 THE LANDLORD?? THIS SCOPE OF WORK HAS NOT BEEN DONE/OR
 APPLIED FOR. PLEASE SEE THE RISER SEEMS TO SHOW THE NEW
 TENANT MAIN AS NEMA 3R WHICH LENDS TO THIS BEING
 LOCATED OUTSIDE? PLEASE KNOW THAT THIS BUILDING
 CONTAINS AN INDOOR ELECTRICAL ROOM WHERE ALL TENANT
 MAIN DISCONNECTS ARE LOCATED. PLEASE PROVIDE A LAYOUT
 FOR LOCATIONS AND LOADS OF THE NEW ON THE EXISTING MAIN
 WITH THE EXISTING LOADS.
 PLEASE KNOW AT THIS TIME THERE ARE ITEMS WHICH CAN NOT
 BE REVIEWED FOR CODE COMPLIANCE.
 PLEASE SEE NEC 220 IN THE 2005 NEC AS THE CALCULATIONS
 AND LOAD SUMMARY FOR THIS SERVICE AND LOADS WITH
 EXISTING SERVICE NEED TO BE SHOWN PER NEW CODE. PLEASE
 SEE PLANS WHICH CONTAIN CODE SECTIONS FROM THE PREVIOUS
 NEC.
 FBC 106.3.5.1.2
  
 10) NOTE: PLEASE SEE RESPONSE MENTIONS TO SEE REVISED
 RISER AND THIS WAS ADDRESSED, HOWEVER THE RISER
 INDICATES *IF*?? PLEASE SEE THIS METER IS INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT AND A FLOATING
 NEUTRAL KIT IS REQUIRED. PERHAPS THIS CAN BE VERIFIED
 BY THE DESIGNER/DESIGN TEAM OF RECORD WHEN SITE VISIT
 IS DONE FOR NOTE #9 ABOVE.
 250.6,250.24.
 FBC 106.3.5.1.2
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE INDICATE A *FLOATING NEUTRAL* IN METER AS
 REQUIRED PER 250.6 AND 250.24. THIS WILL ALLEVIATE ANY
 OBJECTIONABLE CURRENTS.
  
 11) NOTE:PLEASE SEE RESPONSE MENTIONS THE SECTIONS OF
 THE NEC WAS ADDED TO PLANS WHICH IS CORRECT HOWEVER
 PLEASE SEE THE CIRCUITING ON PANEL LP TO BE EXACT STILL
 NOTES THE EM/EXT LTS ON A DEDICATED CIRCUIT? THIS DOES
 NOT CORRELATE WITH THE CIRCUITING AS SHOWN ON PLANS.
 PLEASE ADJUST.
 408.4, FBC 106.1.2
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 700.12E FOR CIRCUITING OF EMERGENCY LIGHTING
 AND EXIT LIGHTING.THE PLAN MENTIONS 701, 701.11F
 WHICH IS NOT APPLICABLE.
 FBC 106.1.2
  
 12) NOTE: PLEASE SEE RESPONSE MENTIONS THE AIC RATINGS
 ARE STATED ON ALL EQUIPMENT HOWEVER THE RATING OF THE
 NEW FUSED MAIN COULD NOT BE LOCATED ON PLANS. PLEASE
 ALSO VERIFY THE RATINGS WHICH ARE SHOWN ON ALL PANELS
 FOR THE PANEL AND BRANCH BREAKERS. PLEASE SEE THE
 RATINGS FOR THE BRANCH BREAKERS AS STATED SEEM HIGH,
 HOWEVER ARE OK AND DO NOT VIOLATE ANY CODE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE ALL EQUIPMENT CONTAINS THE AIC RATINGS
 AS REQUIRED PER 110.9. PLEASE INDICATE FOR THE NEW MAIN
 ON RISER AS SHOWN.
  
 13) NOTE: PLEASE SUBMIT THE MANUFACTURES SPEC/CUT
 SHEETS FOR THIS EQUIPMENT. PLEASE SEE THE NOTE FOR
 CHAPTER 13 AS THE RISER AND EQUIPMENT IN RISER MAY
 CHANGE.
 THE NOTE ON PLANS MENTIONS THE LISTING AND OTHER
 INFORMATION ABOUT CONTACT INFORMATION ETC HOWEVER THE
 REQUEST WAS TO SUBMIT THE DOCUMENTS FOR THIS EQUIPMENT
 AT THIS TIME FOR REVIEW.
 110.3,90.7.
 FBC 106.1.2, 106.3.5.1.2
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE MANUFACTURES SPEC/CUT SHEETS ON THE
 PROPOSED POWER DISTRIBUTION CENTER FOR REVIEW. PLEASE
 BE SURE LISTINGS FROM A NRTL( NATIONALLY RECOGNIZED
 TESTING LABORATORY) IS SHOWN.
 110.3, 90.7.
 FBC 106.1.2.
  
 14) NOTE:THIS NOTE REMAINS AS THE COLOR CODING ADDED
 TO THE NOTES WAS NOT AS STATED ON PREVIOUS REVIEW NOTE>
 THIS IS TO BE BROWN (A) ?PURPLE (B) AND YELLOW (C).
 PLEASE SEE THIS MUST HAVE BEEN A MISPRINT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE COLOR CODING SHALL BE AS FOLLOWS.
 277/480V SYSTEMS, BROWN, PURPLE, YELLOW.
 PLEASE SEE THAT THE NEC HAS *ORANGE* DESIGNATED FOR
 MARKING OF A *HIGH-LEG* IN AN OPEN DELTA SYSTEM WHICH
 IS NOT WHAT IS BEING INSTALLED.
 PLEASE KNOW AS PER LOCAL JURISDICTIONS AND LOCAL WIRING
 AT THE LOCATION OF SAID PROJECT THE COLOR CODING OF THE
 EXISTING SYSTEMS IN THIS BUILDING IS AS NOTED. 90.4
  
 15) NOTE: PLEASE PROVIDE MOTE INFORMATION ON THE
 LOCATION OF THIS VERY LARGE TRANSFORMER. PLEASE SEE THE
 LOCATION DOES NOT SEEM TO GIVE THE WORKING CLEARANCES
 AS REQUIRED PER THE NEC. PLEASE SUBMIT ELEVATION
 DETAILS FOR THIS LOCATION AS THE UNIT SHALL NOT BE
 ENCLOSED, CLOSE TO IGNITABLE MATERIALS, AND MUST MEET
 THE CLEAR SPACE ETC. PLEASE ALSO PROVIDE A STRUCTURAL
 SUPPORT DETAIL FOR MOUNTING OF SAID UNIT. THESE ITEMS
 WILL BE REVIEWED FOR NUMEROUS NEC CODES INCLUDING
 STRUCTURAL INTEGRITY.
 FBC 106.3.5.1.2, NEC 450.13B, 450.21, 450.9, 110.26,
 408.7 ETC.
 PLEASE ALSO SEE 240.21 AS THE LENGTH OF CONDUCTORS IS
 OF CONCERN TO MEET THIS SECTION OF THE NEC. AT THIS
 TIME THE MCB IN THE MDP APPEARS TO BE TOO FAR AWAY
 BASED ON THE LENGTH OF CONDUCTORS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE TRANSFORMER WHICH IS BEING SHOWN ABOVE
 OFFICE IS NOT PERMITTED AT THIS LOCATION PER 450.13B
 AND 450.21B.
 PLEASE PROVIDE MORE DETAILS AND INFORMATION ON TYPE OF
 TRANSFORMER. THE LOCATION IS NOT PERMITTED BASED ON
 PLANS SUBMITTED.
 110.3, 90.7
 FBC 106.3.5.1.2
  
 16) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE
 SEE THIS IS ONLY A NOTICE GIVEN AT THIS TIME. ** PLEASE
 KNOW ONE SET OF PLANS ARE BEING RETAINED BY THIS OFFICE
 AND WILL BE PLACED WITH PREVIOUSLY RETAINED PLANS.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT SHOWN OR
 SUBMITTED FOR REVIEW, THE COMPLETE REVIEW FOR CODE
 COMPLIANCE CAN ONLY BE BASED ON THE PLANS SUBMITTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-27 16:47:22PLANS WERE REMOVED FROM INCOMING AND WILL BE RETURNED
 ONCE ELECTRICAL REVIEW IS DONE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-25 Cont ID  
Sent By dpalmer Date 2007-03-25 Time 14:16 Rev Time 0.00
Received By dpalmer Date 2007-03-25 Time 12:04 Sent To  
Notes
2007-03-25 14:16:34 
  
 ****** UNSAT *****
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
 ** PLEASE SEE THAT THERE COMMENTS MADE TO SHEETS OTHER
 THAN ELECTRICAL BY THIS REVIEWER WHICH WILL BE REQUIRED
 TO BE MET WHETHER OR NOT COMMENTS ARE MADE FORM OTHER
 TRADES.
  
 ** IMPORTANT**
 ONLY ONE SET OF PLANS WILL BE RETURNED.
 DUE TO MANY OF THE COMMENTS BELOW AND THE TYPE OF
 COMMENTS, TWO OF THE THREE SETS OF PLANS SUBMITTED ARE
 BEING RETAINED BY THIS OFFICE.
  
 1) NOTE: PLEASE SEE THAT PLANS HAVE BEEN SUBMITTED FOR
 PERMIT AFTER DECEMBER 8TH, 2006 WHICH PLACES PROJECT
 UNDER THE NEW CODES.
 PLEASE SEE THE FOLLOWING SHALL BE STATED ON THE
 ARCHITECTURAL SHEETS ALONG WITH ELECTRICAL SHEETS.
 PLEASE SEE SHEETS OF PLANS CONTAIN CODES WHICH ARE NOT
 ADOPTED BY THE STATE OF FLORIDA. PLEASE SEE CODES FROM
 IBC, SBCCI ETC
 PLANS INDICATE A 2003 NFPA-70 (NEC) ? PLEASE KNOW THERE
 IS A 2002 AND THEN THE NEW CODE IS THE 2005. PLEASE SEE
 THAT ALL AREAS OF PLANS WHICH REFERENCE THE 2002 NEC
 SHALL ONLY STATE THE 2005. THIS WILL AFFECT MANY AREAS
 OF PLANS. SEE OTHER COMMENTS WITH RESPECT TO THESE.
 PLEASE ALSO BE SURE THE TRADES REFLECT THE CODES
 RELEVANT TO THEIR DESIGNS ON RESPECTIVE SHEETS. 2004
 FBC W/ 2006 REVISIONS (ALL TRADES).
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** PLEASE SEE NOTES ON G-SL INDICATE FEDERAL
 REQUIREMENTS FOR ADA. PLEASE KNOW THAT THE STATE OF
 FLORIDA CONTAINS ITS OWN ADA CODE AS REQUIRED IN
 CHAPTER 11 OF THE 2004 FBC W/2006 REVISIONS.
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WITH
 RESPECT TO OTHER CODES REQUIRED ON PLANS.
  
 2) NOTE: PLEASE SEE THE SHEETS FROM THE ENGINEERING
 FIRM ARE MISSING TITLE BLOCK INFORMATION AS REQUIRED
 PER FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND
 FLORIDA STATUTES 471.023.
 A SEARCH WITH THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION DID NOT FIND ANY RELEVANT
 LICENSE INFORMATION ATTACHED TO ENGINEER..
 PLEASE ALSO KNOW IF THE ENGINEER IS EMPLOYED BY THE
 SAID COMPANY AND COMPANY IS OFFERING ENGINEERING
 SERVICES, THEN A CERTIFICATE OF AUTHORIZATION NUMBER IS
 REQUIRED FOR SAID FIRM.
 PLEASE SEE FS 471.023.
  
 3) NOTE: PLEASE SEEMEP SHEETS DO NOT CONTAIN ORIGINAL
 SIGNATURES WHICHARE REQUIRED PER FS 471.025 AND FAC
 61G15-23.002. THESE CONTAIN A RAISED SEAL HOWEVER THESE
 ARE NOT ORIGINAL SIGNATURES. *ALL THREE SETS CONTAIN
 THE SAME*THE STATE OF FLORIDA REQUIRES AN ORIGINAL
 SIGNATURE. PLEASE SEE SECTION EXTRACTED FORM THE
 FLORIDA STATUTES.
 * ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, REPORTS,
 OR DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND
 BEING FILED FOR PUBLIC RECORD AND ALL FINAL DOCUMENTS
 PROVIDED TO THE OWNER OR THE OWNER'S REPRESENTATIVE
 SHALL BE SIGNED BY THE LICENSEE, DATED, AND SEALED WITH
 SAID SEAL. SUCH SIGNATURE, DATE, AND SEAL SHALL BE
 EVIDENCE OF THE AUTHENTICITY OF THAT TO WHICH THEY ARE
 AFFIXED.*
  
 **THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 4) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS ARE
 MISSING THE PRINTED NAME OF THE ARCHITECT ON TITLE
 BLOCKS AS REQUIRED PER FAC61G1-16.004.
 * THIS IS REQUIRED WHETHER OR COMMENT IS MADE BY OTHER
 TRADE(S).
  
 5) NOTE: PLEASE INCLUDE THE SUITE/UNIT NUMBER ON TITLE
 BLOCKS.
 FAC 61G15-23.002, 61G1-16.004
 FBC 106.1.2, 106.3.5.1.2
  
 6) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK SHALL INCLUDE ALL LABOR AND MATERIALS EVEN IF
 MATERIALS, EQUIPMENT, ETC IS OWNER SUPPLIED AS STATED
 ON PLANS.
 VALUE IS LOW AT THIS TIME. PLEASE ADJUST.
 PLEASE KNOW A VALUE MAY BE ADJUSTED BY THIS OFFICE
 USING ADOPTED DOCUMENTS INTO THE FBC.
 FBC 108.3
  
 7) NOTE: PLEASE SEE THE 2004 FBC W/ 2006 REVISIONS FOR
 CHAPTER 13. AT THIS TIME THERE ARE SEVERAL ITEMS
 MISSING FOR REVIEW.
 PLEASE SEE NO SCHEDULING OF SYSTEM WAS SUBMITTED.
 PLEASE SEE NO INFORMATION ON A SYSTEM WAS SUBMITTED.
 PLEASE SEE NO OVER RIDE DEVICES AT THE POINTS OF
 EGRESS/INGRESS INTO SPACE FROM ENTRANCE WIN WHICH THE
 OCCUPANT CAN SEE THE LIGHTING WHICH IS BEING
 CONTROLLED.
 PLEASE SEE NO TIMES ON ANY OVER RIDE DEVICES AND TYPES
 OF DEVICES.
 PLEASE SEE MISSING ENERGY CALCULATIONS.
 PLEASE SEE MISSING LIGHTING PERFORMANCE CALCULATIONS.
 PLEASE SEE MISSING CERTIFICATIONS PER DESIGNER(S) OF
 RECORD.
 PLEASE SEE REQUIRED CALCULATION METHODS FOR TRACK
 LIGHTING. 13-415.2.ABC.1.2
  
 PLEASE SEE 13-103.1, 13-415.1ABC.1, 13-415.1.ABC.1.1,
 .1.2 AND .1.3, 13-415.1.AB.1.1, 13-415.1.A, .B AND .C,
 13-415.2 AND TABLES UNDER THE NEW 2006 REVISIONS. ETC.
  
 8) NOTE: PLEASE SEE PLANS NOTES FOR GFI PROTECTION
 WHERE CODES ARE ADOPTED HOWEVER PLEASE ACTUALLY SHOW
 WHERE THE PROTECTION WILL BE. PLEASE INDICATE BY THE
 DEVICES OR BREAKERS. QUOTING THE CODE LIEU OF SHOWING
 SPECIFIC DETAIL IS NOT PERMITTED.
  
 9) NOTE: PLEASE INDICATE INTERLOCKS/SHUNT-DEVICES FOR
 ANY LIGHTING ETC WHICH ARE FED TO HOOD.
 NFPA-96
  
 10) NOTE: PLEASE INDICATE TRANSFORMER GROUNDING. THE
 SIZE CONNECTIONS ETC RE REQUIRED TO BE SHOWN, NOT ONLY
 QUOTED CODE.
 250.20,250.30,250.66
  
 11) NOTE: PLEASE CLARIFY HOW THE FEEDERS ON THE LINE
 SIDE OF THE TRANSFORMER CAN CONTAIN A NEUTRAL WHEN THIS
 IS GOING TO BE A SEPARATELY DERIVED SYSTEM? PLEASE SEE
 FEEDER NUMERICAL DESIGNATIONS OF#39 WHICH CONTAINS A
 NEUTRAL.
  
 12) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON LEGEND
 ONLY. PLEASE INCLUDE ON LAYOUT OF PLANS AND DEVICES.
 PLEASE KNOW EVEN THOUGH FIRE SPRINKLER AND FIRE ALARM
 WORK WILL BE REQUIRED TO BE UNDER A SEPARATE PERMIT THE
 BASE FIRE ALARM DEVICES ALONG WITH FIRE PROTECTION WILL
 BE REQUIRED IN BASE PLANS. THIS WILL BE NOTED BY THE
 FIRE AND BUILDING REVIEWER(S) ALSO.
  
 13) NOTE: PLEASE SEE MISSING SIGN CIRCUIT ON PLANS AND
 PANEL SCHEDULE PER 600.5.
  
 14) NOTE: PLEASE VERIFY SERVICE AS SHOWN AS THE RISER
 MENTIONS THE METER IS BEING DONE BY THE LANDLORD?? THIS
 SCOPE OF WORK HAS NOT BEEN DONE/OR APPLIED FOR. PLEASE
 SEE THE RISER SEEMS TO SHOW THE NEW TENANT MAIN AS NEMA
 3R WHICH LENDS TO THIS BEING LOCATED OUTSIDE? PLEASE
 KNOW THAT THIS BUILDING CONTAINS AN INDOOR ELECTRICAL
 ROOM WHERE ALL TENANT MAIN DISCONNECTS ARE LOCATED.
 PLEASE PROVIDE A LAYOUT FOR LOCATIONS AND LOADS OF THE
 NEW ON THE EXISTING MAIN WITH THE EXISTING LOADS.
 PLEASE KNOW AT THIS TIME THERE ARE ITEMS WHICH CAN NOT
 BE REVIEWED FOR CODE COMPLIANCE.
 PLEASE SEE NEC 220 IN THE 2005 NEC AS THE CALCULATIONS
 AND LOAD SUMMARY FOR THIS SERVICE AND LOADS WITH
 EXISTING SERVICE NEED TO BE SHOWN PER NEW CODE. PLEASE
 SEE PLANS WHICH CONTAIN CODE SECTIONS FROM THE PREVIOUS
 NEC.
 FBC 106.3.5.1.2
  
 15) NOTE: PLEASE INDICATE A *FLOATING NEUTRAL* IN METER
 AS REQUIRED PER 250.6 AND 250.24. THIS WILL ALLEVIATE
 ANY OBJECTIONABLE CURRENTS.
  
 16) NOTE: PLEASE SEE 700.12F FOR CIRCUITING OF
 EMERGENCY LIGHTING AND EXIT LIGHTING.THE PLAN
 MENTIONS 701, 701.11F WHICH IS NOT APPLICABLE.
 FBC 106.1.2
  
 17) NOTE: PLEASE BE SURE ALL EQUIPMENT CONTAINS THE AIC
 RATINGS AS REQUIRED PER 110.9. PLEASE INDICATE FOR THE
 NEW MAIN ON RISER AS SHOWN.
  
 18) NOTE: PLEASE SEE NEC 408.4 AS THE CIRCUITS IN PANEL
 SCHEDULES NEED TO BE SPECIFIC TO THE ROOMS AND AREAS IN
 WHICH THEY FEED. PLEASE THE FOLLOWING TEXT WHICH IS
 BEING EXTRACTED FROM THE NEC HANDBOOK.
 **SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO
 REQUIRE THAT THE IDENTIFICATION FOR EVERY CIRCUIT
 SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND
 CLEARLY STATE THE SPECIFIC PURPOSE FOR WHICH THE
 CIRCUIT IS USED. CIRCUITS USED FOR THE SAME PURPOSE
 MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR EXAMPLE,
 SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY OUTLETS IN
 THE KITCHEN, DINING ROOM, AND KITCHEN COUNTERTOPS.
 IDENTIFYING THE CIRCUITS AS SMALL APPLIANCE BRANCH
 CIRCUITS IS NOT ACCEPTABLE; INSTEAD, THEY SHOULD BE
 IDENTIFIED AS ``KITCHEN WALL RECEPTACLES,'' ``DINING
 ROOM FLOOR RECEPTACLE,'' OR ``KITCHEN COUNTERTOP
 RECEPTACLES LEFT OF SINK.'' CIRCUIT DIRECTORIES
 CONTAINING MULTIPLE ENTRIES WITH ONLY ``LIGHTS'' OR
 ``OUTLETS'' DO NOT PROVIDE THE SUFFICIENT DETAIL
 REQUIRED BY THIS SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 19) NOTE: PLEASE SUBMIT THE MANUFACTURES SPEC/CUT
 SHEETS ON THE PROPOSED POWER DISTRIBUTION CENTER FOR
 REVIEW. PLEASE BE SURE LISTINGS FROM A NRTL( NATIONALLY
 RECOGNIZED TESTING LABORATORY) IS SHOWN.
 110.3, 90.7.
 FBC 106.1.2.
  
 20) NOTE: PLEASE SEE THE COLOR CODING SHALL BE AS
 FOLLOWS.
 277/480V SYSTEMS, BROWN, PURPLE, YELLOW.
 PLEASE SEE THAT THE NEC HAS *ORANGE* DESIGNATED FOR
 MARKING OF A *HIGH-LEG* IN AN OPEN DELTA SYSTEM WHICH
 IS NOT WHAT IS BEING INSTALLED.
 PLEASE KNOW AS PER LOCAL JURISDICTIONS AND LOCAL WIRING
 AT THE LOCATION OF SAID PROJECT THE COLOR CODING OF THE
 EXISTING SYSTEMS IN THIS BUILDING IS AS NOTED. 90.4
  
 21) NOTE: PLEASE SEE THAT PANEL M AND RISER IS SHOWING
 A FEED TO A PANEL *S* YET THE PLANS SUBMITTED DO NOT
 SHOW ANY PANEL *S*??
 PLEASE SUBMIT THE COMPLETED PLANS SHOWING THIS PANEL.
 FBC 106.3.5.1.2
  
 22) NOTE: PLEASE SEE THE TRANSFORMER WHICH IS BEING
 SHOWN ABOVE OFFICE IS NOT PERMITTED AT THIS LOCATION
 PER 450.13B AND 450.21B.
 PLEASE PROVIDE MORE DETAILS AND INFORMATION ON TYPE OF
 TRANSFORMER. THE LOCATION IS NOT PERMITTED BASED ON
 PLANS SUBMITTED.
 110.3, 90.7
 FBC 106.3.5.1.2
  
 23) NOTE: PLEASE SEE MISSING ROOFTOP ELECTRICAL PLANS,
 A/C PLANS FOR ELECTRICAL DISCONNECTS, NEW OR EXISTING
 GFI REQUIRED FOR EQUIPMENT ETC.
 440.11, 210.63 .
 PLEASE SUBMIT.
 FBC106.1.2
  
 24) NOTE: PLEASE KNOW ANY LOCK OFF/ON DEVICES SHALL BE
 AN INTEGRAL PART OF THE BREAKER, NOT ONE THAT ONLY
 SNAPS INTO PLACE OR CAN BE EASILY REMOVED OR FALL OFF
 WHEN PANEL COVER IS REMOVED.
 110.3, 90.4.
  
 ** PLEASE KNOW AS THERE IS SUBSTANTIAL INFORMATION
 WHICH WAS NOT SUBMITTED A COMPLETE REVIEW FOR CODE
 COMPLIANCE COULD NOT BE DONE AND THERE MAY VERY WELL BE
 NEW COMMENTS ON THE NEXT REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-04-24 Cont ID  
Sent By mawillia Date 2008-04-24 Time 10:49 Rev Time 0.00
Received By mawillia Date 2008-04-24 Time 10:42 Sent To  
Notes
2008-04-24 10:49:45*****APPROVED*****
  
  
 PLAN SHEETS M2-1, S-1.1, S-2.1, AND S-3.1 WERE
 REVIEWED, HOWEVER NO FIRE-STAMPING NEEDED ON THESE
 SHEETS

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-12-11 Cont ID  
Sent By mawillia Date 2007-12-11 Time 17:44 Rev Time 0.00
Received By mawillia Date 2007-12-11 Time 17:33 Sent To  
Notes
2007-12-11 17:43:40*****PROVISO*****
  
 *THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEETS TO
 BE FIRE STAMPED WHEN ALL OTHER REVIEWERS HAVE BEEN
 SATISFIED.
  
  
 *****APPROVED*****
  
 *THE APPROPIATE PLAN SHEETS WERE STAMPED, INITIALED,
 AND DATED BY ASST FIRE MARSHAL MIKE WENNERGREN ON
 01/03/2008;PLANS WERE SENT TO JIM WITTMER'S DESK.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-10-04 Cont ID  
Sent By mawillia Date 2007-10-04 Time 11:41 Rev Time 0.00
Received By mawillia Date 2007-10-04 Time 10:15 Sent To E
Notes
2007-10-04 11:41:14*****PROVISO*****
  
 *THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEETS TO
 BE FIRE STAMPED WHEN ALL OTHER REVIEWERS HAVE BEEN
 SATISFIED.
  
 *NEW COMMENT:SINCE A NEW SHEET (FP-1) HAS BEEN ADDED
 TO THE PLAN SET, FP-1 SHALL BE ADDED TO THE SHEET INDEX
 LIST ON THE COVER SHEET.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-08-06 Cont ID  
Sent By mwennerg Date 2007-08-06 Time 11:39 Rev Time 0.00
Received By mwennerg Date 2007-08-06 Time 11:39 Sent To  
Notes
2007-08-06 11:47:33***DENIED***
  
 PLEASE SEE SOME COMMENTS FROM LAST REVIEW NOT
 ADDRESSED.
  
 1) NOALL SHEETS SHALL ILLUSTRATE THE APPROPRIATE
 SUITE NUMBER IN TITLE BLOCK.
  
 2) OK
  
 3) OK
  
 4) OK
  
 5) NOPLEASE SHOW ADDRESS ON DRAWINGS.
  
 6) PLEASE ADD NOTE TO DOOR SCHEDULE.
  
 7) NOPLEASE SUBMIT LIFE SAFETY SHEET ILLUSTRATING
 MINIMUM TRAVEL DISTANCES TO EXITS WITH DASHED LINES.
  
 8) OK
  
 9) NOPLEASE SPECIFY INFORMATION REQUESTED IN TERMS OF
 CLASSIFICATION A,B OR C.
  
 10) NOINFORMATION TO BE SUBMITTED WITH BASE PLANS IN
 ADDITION TO SEPARATE PERMITTING.
  
 11) NOINFORMATION TO BE SUBMITTED WITH BASE PLANS IN
 ADDITION TO SEPARATE PERMITTING.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-05-08 Cont ID  
Sent By mawillia Date 2007-05-08 Time 18:17 Rev Time 0.00
Received By mawillia Date 2007-05-08 Time 16:50 Sent To  
Notes
2007-05-08 18:17:05*****DENIED*****
  
  
 01.THE ENTIRE NUMERERICAL ADDRESS INCLUDING THE SUITE
 NUMBER SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
  
 02.ON SHEET G-CS, UNDER APPLICABLE CODES AND
 REGULATIONS, ADD LIFE SAFETY CODE - NFPA 1012003
 EDITION.
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 04.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY
 AS NECESSARY FOR SAFE OPERATION.
  
 05.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS
 SOUTH ROSEMARY AVENUE, DISPLAY THE SUITE NUMBER.AS
 PER WEST PALM BEACH CODE, TENANT SPACE NUMBERS SHALL BE
 NO LESS THA 3" IN HEIGHT AND NO LESS THAN 1" IN WIDTH.
  
 06.ANY DOOR IN A MEANS OF EGRESS FROM AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PROVIDED WITH PANIC HARDWARE OF FIRE EXIT HARDWARE.
  
 07.PROVIDE A LIFE SAFETY PLAN SHEET WHICH INDICATES
 THE TRAVEL DISTANCE TO REACH AN EXIT.THE LOCATION OF
 EXIT LIGHTS, EMERGENCY LIGHTS AND FIRE EXTINGUISHERS
 MAY ALSO BE INCLUDED.
  
 08.COMMERCIAL COOKING EQUIPMENT SHALL BE IN
 ACCORDANCE WITH NFPA 96.SEPARATE PLANS AND PERMIT
 WILL BE REQUIRED FOR THE HOOD INSTALLATION AS WELL AS
 THE HOOD SUPPRESSION SYSTEM.
  
 09.PROVIDE INTERIOR FINISH CLASSIFICATION FOR THE
 WALLS AND CEILINGS.INTERIOR WALL AND CEILING FINISH
 MATERIALS SHALL BE CLASS A OR CLASS B IN EXITS AND EXIT
 ACCESS CORRIDORS, AND CLASS A, CLASS B, OR CLASS C IN
 ALL OTHER AREAS.
  
 10.ALTHOUGH SEPARATE PLANS AND PERMIT WILL BE
 REQUIRED FOR THE FIRE SPRINKLER SYSTEM REMODEL, PROVIDE
 A LAYOUT OF THIS SYSTEM UNDER THIS PERMIT.
  
 11.ALTHOUGH SEPARATE PLANS AND PERMIT WILL BE
 REQUIRED FO THE FIRE ALARM SYSTEM REMODEL, PROVIDE A
 LAYOUT OF THE SYSTEM UNDER THIS PERMIT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2008-01-15 Cont ID  
Sent By kstevens Date 2007-12-21 Time 16:17 Rev Time 0.00
Received By kstevens Date 2007-12-21 Time 16:17 Sent To  
Notes
2008-01-15 16:18:33SEPARATE GAS PERMIT REQUIRED

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2007-12-03 Cont ID  
Sent By kstevens Date 2007-12-03 Time 17:25 Rev Time 0.00
Received By kstevens Date 2007-12-03 Time 17:25 Sent To  
Notes
2007-12-03 17:26:10DENIED - SEE PLUMBING REVIEW THIS DATE CONCERNING THE
 GAS COMMENTS.

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-10-03 Cont ID  
Sent By kstevens Date 2007-10-03 Time 18:04 Rev Time 0.00
Received By kstevens Date 2007-10-03 Time 18:04 Sent To  
Notes
2007-10-03 18:04:24DENIED - SEE PLUMBING REVIEW THIS DATE CONCERNING THE
 GAS COMMENTS.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-07-14 Cont ID  
Sent By kstevens Date 2007-07-14 Time 18:03 Rev Time 0.00
Received By kstevens Date 2007-07-14 Time 18:02 Sent To  
Notes
2007-10-03 18:04:00DENIED - SEE PLUMBING REVIEW THIS DATE CONCERNING THE
 GAS COMMENTS.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-04-26 Cont ID  
Sent By kstevens Date 2007-04-26 Time 17:59 Rev Time 0.00
Received By kstevens Date 2007-04-26 Time 17:59 Sent To  
Notes
2007-10-03 18:02:49DENIED - SEE PLUMBING REVIEW THIS DATE CONCERNING THE
 GAS COMMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-07-11 Cont ID  
Sent By adarroug Date 2008-07-11 Time 15:41 Rev Time 0.00
Received By adarroug Date 2008-07-11 Time 15:41 Sent To P
Notes
2008-07-11 15:42:06TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-06-11 Cont ID  
Sent By adarroug Date 2008-06-11 Time 13:03 Rev Time 0.00
Received By adarroug Date 2008-06-11 Time 13:03 Sent To B
Notes
2008-06-11 13:03:37TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-05-30 Cont ID  
Sent By adarroug Date 2008-05-30 Time 11:03 Rev Time 0.00
Received By adarroug Date 2008-05-30 Time 11:03 Sent To E
Notes
2008-05-30 11:03:51TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-05-27 Cont ID  
Sent By adarroug Date 2008-05-27 Time 12:41 Rev Time 0.00
Received By adarroug Date 2008-05-27 Time 12:41 Sent To P
Notes
2008-05-27 12:44:21TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-04-17 Cont ID  
Sent By adarroug Date 2008-04-17 Time 13:42 Rev Time 0.00
Received By adarroug Date 2008-04-17 Time 13:42 Sent To  
Notes
2008-04-17 13:47:20TO "COMM" BD#44--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-02-26 Cont ID  
Sent By adarroug Date 2008-02-26 Time 09:12 Rev Time 0.00
Received By adarroug Date 2008-02-26 Time 09:12 Sent To P
Notes
2008-02-26 09:13:14TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-12-20 Cont ID  
Sent By dpalmer Date 2007-12-20 Time 18:16 Rev Time 0.00
Received By dpalmer Date 2007-12-20 Time 18:16 Sent To  
Notes
2007-12-20 18:16:44TO COMM BOARD #17

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-11-28 Cont ID  
Sent By adarroug Date 2007-11-28 Time 10:50 Rev Time 0.00
Received By adarroug Date 2007-11-28 Time 10:50 Sent To  
Notes
2007-11-29 11:35:19TO "COMM" BD#19--EXPEDITED--PLANS ON RACK 1 LARGE ROLL
 AND PAPERWORK
2007-11-28 10:50:28WAITING FOR "COMM" BD--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-09-28 Cont ID  
Sent By adarroug Date 2007-09-28 Time 14:25 Rev Time 0.00
Received By adarroug Date 2007-09-28 Time 14:25 Sent To  
Notes
2007-09-28 14:26:20TO "COMM" BD#56--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-15 Cont ID  
Sent By adarroug Date 2007-06-15 Time 08:39 Rev Time 0.00
Received By adarroug Date 2007-06-15 Time 08:39 Sent To  
Notes
2007-06-29 10:37:23TO "COMM" BD#49/PLANS ON RACK--1 LARGE ROLL W/PAPERWORK
2007-06-15 08:39:28WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-24 Cont ID  
Sent By adarroug Date 2007-03-24 Time 12:30 Rev Time 0.00
Received By adarroug Date 2007-03-24 Time 12:30 Sent To  
Notes
2007-03-24 12:31:58TO "COMM" BD#56

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-20 Cont ID  
Sent By dpalmer Date 2007-03-20 Time 17:43 Rev Time  
Received By dpalmer Date   Time   Sent To PC
Notes
2007-03-20 17:43:48**3/20/07 PLANS WERE REMOVED FROM THE COMM BOARD FOR
 THE PERMIT AND PLAN REVIEW PROCESS. FEES WERE NOT PAID
 AND CONTRACTOR DID NOT COME IN TO PAY FEES. CONTRACTOR
 WAS INFORMED TWICE THAT FEES NEEDED TO BE PAID BY THIS
 OFFICE. PLANS WILL BE PLACED IN THE LARGE BINS UNDER
 "P" FOR PICK UP OR TO BE PAID. ONCE FEES ARE PAID THE
 APPLIED DATE WILL CHANGE AND NEW PROCESSING WILL TAKE
 PLACE. DV PALMER.
2007-03-19 14:01:32TO "COMM" BD#24
2007-03-15 14:38:53WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rregueir Date 2008-04-25 Time 11:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-12-01 Cont ID  
Sent By rregueir Date 2007-12-01 Time 10:20 Rev Time 0.00
Received By rregueir Date 2007-11-30 Time 16:57 Sent To  
Notes
2007-12-01 10:12:35REVIEW #: 4TH
 ACTION: PASSED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 MECHANICAL PAGES WHICH WERE REVISED SINCE LAST REVIEW
 HAVE BEEN REVIEWED AND STAMPED.
  
 NOTE: PG M-4.4 WAS PASSED DURING 3RD REVIEW. HOWEVER,
 IT WAS NOT STAMPED DURING THIS REVIEW FOR THE FOLLOWING
 REASONS:
  
 1. THE PRINT QUALITY IS POOR AND THE INFORMATION ON
 PLANS IS MOSTLY ILLEGIBLE. FBC 106.1.3
  
 2. THE PRODUCT APPROVAL INFORMATION SHOWN ON THIS PAGE
 DOES NOT MATCH THE PRODUCT APPROVAL THAT WAS INCLUDED
 IN THE SUBMITTAL PACKAGE. PLEASE SHOW COORDINATION
 PETWEEN PLANS, SUBMITTALS AND SPECIFICATIONS.
 IF THE PRODUCT APPROVAL FOR THE PRE-ENGINEERED A/C
 STANDS WHICH WAS SUBMITTED IS THE CORRECT ONE TO BE
 USED, PG M-4.4 MAY BE REMOVED FROM THE SET AS IT IS NOT
 NECESSARY TO DEMONSTRATE CODE COMPLIANCE. THE PRODUCT
 APPROVAL PACKAGE SUBMITTED WILL BE PART OF THE PERMIT
 RECORD SET OF DOCUMENTS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-10-03 Cont ID  
Sent By rregueir Date 2007-10-01 Time 09:22 Rev Time 0.00
Received By rregueir Date 2007-10-01 Time 10:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-07-16 Cont ID  
Sent By rregueir Date 2007-07-16 Time 13:16 Rev Time 0.00
Received By rregueir Date 2007-07-16 Time 09:44 Sent To  
Notes
2007-07-16 13:03:32---------------DENIED----------------
  
 FBC 2004 W/ 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWIN COMMENTS ARE NUMBERED TO CORRESPOND WITH
 COMMENTS FROM THE PREVIOUS REVIEW, WHICH IS DATED
 4/16/07, FOR THE PURPOSE OF CONTINUITY.
  
 1. THE NOA PROVIDED FOR THE PRE-ENGINEERED A/C STAND
 DOES NOT MATCH THE STAND OR INSTALLATION INSTRUCTIONS
 SHOWN ON MPE-1.1. PLEASE COORDINATE PLANS WITH THE
 COMPONENTS TO BE USED.
  
 2. OK
  
 3. THE 10X10 EXHAUST DUCT; IS THERE A FIRE DAMPER WHERE
 THE DUCT PENETRATES THE ACCESS CORRIDOR WALL? PLEASE
 SEE FBC,M 607.5 AND 607.8.
  
 4. OK
  
 5. WIND LOAD CALCULATIONS WERE PROVIDED. HOWEVER, NO
 ATTACHMENT DETAIL FOR CURB TO STRUCTURE OR EQUIPMENT TO
 CURB COULD BE LOCATED IN PLANS. ALSO. PLEASE SHOW HOW
 SPRING ISOLATION CURB RAILS WILL WORK IN CONJUNCTION
 WITH WIND RESISTANT ATTACHMENTS. FBC,M 301.10 AND
 301.13.
  
 6. OK
  
 7. EF-3 IS STILL SHOWN ON EXHAUST FAN SCHEDULE. WHERE
 IS EF-3 LOCATED? IF IT IS NOT BEING USED, PLEASE REMOVE
 FROM SCHEDULE. FBC 106.1.1
  
 8. PG M-4.1 KITCHEN HOOD EXHAUST DUCTWORK NOTE 1.0
 STATES "18 GAUGE STAINLESS STEEL" BUT THE DETAIL ON
 M-4.2 INDICATES "22 GAUGE G90 GALVANIZED." WHICH IS
 CORRECT? ALSO, NOTE 4.0 STATES THAT THE DUCT IS NOT TO
 PENETRATE FIRE RATED ASSEMBLIES. WILL THIS DDUCT NEED
 TO ENTER A RATED SHAFT TO PASS THROUGH THE 2ND FLOOR TO
 THE ROOF? NOTE: SHAFT ENCLOSURES SHALL BE CLOSED AT THE
 BOTTOM PER FBC 707.11.
  
 9 THROUGH 11: OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-16 Cont ID  
Sent By rregueir Date 2007-04-16 Time 15:36 Rev Time 0.00
Received By rregueir Date 2007-04-14 Time 14:13 Sent To  
Notes
2007-04-16 15:20:52-----------------DENIED-------------------
  
 FBC 2004 W/2006 REVISIONS
 FBC CH 1 AS REVISED BY THE CITY OF WEST PALM BEACH
  
 1. MPE-1.1: MECHANICAL EQUIPMENT AND SUPPORTS EXPOSED
 TO WIND SHALL BE DESIGNED TO RESIST WIND PRESSURES IN
 ACCORDANCE WITH FBC CH 16. PROVIDE WIND LOAD
 CALCULATIONS AND CONNECTION DETAILS CERTIFIED BY A
 STATE LICENSED STRUCTURAL ENGINEER. PRE-ENGINEERED
 EQUIPMENT STANDS ARE STRUCTURAL ELEMENTS AS DEFINED IN
 FAC 9B-72. AS SUCH, PRODUCT APPROVAL IS REQUIRED.
  
 2 MPE-1.1: WHERE EQUIPMENT IS LOCATED WITHIN 10' OF A
 ROOF EDGE, A GUARD SHALL BE PROVIDED PER FBC,M 304.10.
 GUARDS SHALL MEET THE LOADING REQUIREMENTS OF FBC
 1618.4.6.
  
 3. PLEASE SHOW LOCATION OF OUTSIDE AIR DUCTS AND VOLUME
 DAMPERS FEEDING AHU'S 1,2,3. FBC 106.1.1
  
 4. M-3.1: KITCHEN AIR BALANCE SCHEDULE: AHU-3 SHOWS
 1300 CFM SUPPLY, BUT FLOOR PLAN SHOWS 1150 CFM SUPPLY.
 THERE IS ALSSO 300 CFM SUPPLY BEING EXHAUSTED IN
 BATHROOMS. THIS LEAVES A NET 850 CFM SUPPLY WITH 1100
 CFM RETURN. THIS WILL NOT ALLOW THE INDUCTION OF 200
 CFM OUTSIDE AIR AS STATED ON SCHEDULE. PLEASE SHOW HOW
 PROPER AIR BALANCE IS TO BE ACHIEVED. FBC 10601.2.
  
 5. M-3.1 EXHAUST FAN CURB DETAIL: PLEASE SEE PREVIOUS
 COMMENT REGARDING WIND LOADS FOR OUTDOOR EQUIPMENT.
  
 6. M-3.1 EXHAUST FAN CURB DETAIL: WHAT IS THE REASON
 FOR THE GREASE RETENTION SYSTEM ON ROOF? IF THERE IS
 THE EXPECTATION OF THE ACCUMULATION OF GREASE OR
 GREASE-LADEN VAPOR, A TYPE I HOOD IS REQUIRED OVER
 COOKING EQUIPMENT PER FBC,M 507.2 AND NFPA 96.
  
 7. M-3.1 EXHAUST FAN SCHEDULE: WHERE IS EF 3 LOCATED?
 IT IS NOT SHOWN ON PLANS. EF SCHEDULE SHOWS EF 3 AT 550
 CFM BUT RESTAURANT AIR BALANCE SCHEDULE SHOWS EF 3 AT
 400 CFM. PLEASE CLARIFY PER FBC 106.1.1 AND FBC
 106.1.2.
  
 8 M-4.1 KITCHEN HOOD EXHAUST NOTES: THIS INFORMATION IS
 IN CONFLICT WITH DUCT DETAIL ON M-4.2 FROM CAPTIVEAIR.
 PLEASE CLARIFY BY RESOLVING THIS CONFLICT. THIS IS
 ANOTHER INDICATION THET THERE IS AN EXPECTATION OF
 GREASE-LADEN VAPORS FROM THE COOKING EQUIPMENT. PLEASE
 PROVIDE MANUFACTURER'S SUBMITTAL/ INSTALLATION
 INSTRUCTIONS SHOWING LISTING AND TYPE OF EXHAUST
 REQUIRED. FBC 106.1.1
  
 9. M-4.2 MUA UNIT DETAIL SHOWS 250,000 BTU GAS HEATER,
 BUT THIS IS NOT SHOWN ON GAS RISER DIAGRAM. PLEASE
 COORDINATE DRAWINGS.
  
 10. PLEASE SHOW COMPLIANCE WITH FBC CH 13-409.1.ABC.3.2
 THRU .3.4 (ENERGY CODE) REGARDING VENTILATION SYSTEM
 CONTROLS.
  
 11. PLEASE SHOW ALL GAS APPLIANCE VENT TERMINATION
 LOCATIONS.
  
 NOTE: SEPARATE PERMIT REQUIRED FOR WALK-IN
 COOLER/FREEZER.
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 8 Status P Date 2008-07-23 Cont ID  
Sent By kstevens Date 2008-07-23 Time 15:45 Rev Time 0.00
Received By kstevens Date 2008-07-23 Time 15:44 Sent To  
Notes
2008-07-23 15:48:30REVISION OK--SHTS P-2.3 & P-3.1--SHT G-CS NOT
 APPROVED AS IT IS AN EARLIER VERSION OF THE SHEET AS IT
 IS ONLY SHOWING REVISION #4 WHERE AS THE STAMPED SHEET
 ON FILE HAS REVISION #5.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 7 Status F Date 2008-06-27 Cont ID  
Sent By kstevens Date 2008-06-27 Time 07:45 Rev Time 0.00
Received By kstevens Date 2008-06-27 Time 07:45 Sent To  
Notes
2008-06-27 08:04:56REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
  
 1. SHTS P-2.3 & P-3.1 REQUIRE THE CITY PLACE STAMP ON
 ALL SHEETS PRIOR TO SUBMITTAL. THIS IS NOT A CITY WPB
 REQUIREMENT BUT A CITY PLACE REQUIREMENT.
  
 2. SHT P-2.3 REVISION HISTORY IS INCOMPLETE. REVISIONS
 ONE AND TWO HAVE BEEN DELETED FROM THE REVISION INDEX.
 PLEASE SHOW ALL REVISIONS THAT WERE APPROVED
 PREVIOUSLY. SECTION 106.1.3.--REVISIONS SEVEN &
 EIGHT HAVE NOT BEEN FOUND ON THE SHEET. PLEASE CLARIFY
 & CORRELATE REVISION INDEX WITH REVISIONS TO PLANS.
 SECTION 106.1.1.
  
 2. SHT P-3.1 REVISION HISTORY IS INCOMPLETE. REVISION
 HAS BEEN DELETED FROM THE REVISION INDEX. PLEASE SHOW
 ALL REVISIONS THAT WERE APPROVED PREVIOUSLY. SECTION
 106.1.3.--REVISIONS SEVEN & EIGHT HAVE NOT BEEN
 FOUND ON THE SHEET.--REVISION TEN SHOWN ON THE PLAN
 IS NOT INDICATED ON THE REVISION INDEX. PLEASE CLARIFY
 & CORRELATE REVISION INDEX WITH REVISIONS TO PLANS.
 SECTION 106.1.1.
  
 3. SHT P-3.1 SANITARY IS SHOWN CONNECTING TO EXISTING
 GREASE LINE. SANITARY SHALL CONNECT TO THE SANITARY
 RISER. SECTION 1003.1.
  
 4. SHT P-3.1 INDICATE THE PIPE SIZE FOR THE P-7 FIXTURE
 FOR THE THREE COMPARTMENT SINK. TABLE 906.1.
  
 5. SHT P-3.1 SHOW HOW THE GREASE LINES CONNECT TO THE
 RISER. AS SHOWN THEY DO NOT REFLECT THE FLOOR PLAN.
 SECTIONS 106.1.1 & 706.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 6 Status F Date 2008-03-19 Cont ID  
Sent By kstevens Date 2008-03-19 Time 14:26 Rev Time 0.00
Received By kstevens Date 2008-03-19 Time 14:26 Sent To  
Notes
2008-03-19 14:37:12REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT P-2.3 NO HAND WRITTEN CHANGES ON SIGNED, SEALED
 DATED PLANS. SECTION 106.1.3.--IDENTIFY RISERS FOR
 THE GREASE SYSTEM AND THE SANITARY SYSTEM AT THE END OF
 THE SYSTEMS PAST THE LAV IN THE WOMEN'S TOILET ROOM AND
 PAST THE MOP SINK ON THE GREASE SYSTEM BY THE WALK IN
 COOLER. SECTIONS 106.1.1 & 106.1.2.
  
 2. SHTS P-2.3 & P-3.1 THE TELEPHONE NUMBER FOR THE
 ENGINEERING FIRM IS REQUIRED IN THE TITLE BLOCK OF EACH
 SHEET. FAC 61G15-23.002(2) & FS 471.025. PLEASE SHOW
 REQUIRED PHONE NUMBER.
  
 3. SHT P-3.1 RISER DIAGRAM DOES NOT REFLECT THE FLOOR
 PLAN. BOTH RISERS ARE INDICATED AS GREASE RISERS.--
 THE GREASE RISER FROM THE 2ND FLOOR DOES NOT CONNECT TO
 THE GREASE RISER.--FLOOR SINK P-7 IS NOT SHOWN FOR
 FIXTURE 13B.--THE OFFSET AT THE END OF THE GREASE
 SYSTEM PRIOR TO THE RISER TO THE SECOND FLOOR IS NOT
 INDICATED ON THE RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-12-27 Cont ID  
Sent By kstevens Date 2007-12-21 Time 11:02 Rev Time 0.00
Received By kstevens Date 2007-12-21 Time 11:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2007-12-03 Cont ID  
Sent By kstevens Date 2007-12-03 Time 17:18 Rev Time 0.00
Received By kstevens Date 2007-12-03 Time 17:18 Sent To  
Notes
2007-12-03 17:24:52DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WEST PALM BEACH MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEWS:
 **FROM PREVIOUS REVIEWS:
  
 1. OK
 2. OK
 3. OK
  
 4. SHT EQ-2.1, THE 2 PAGE "WORKSHEETS" FROM DBPR HOTEL
 AND RESTURANT DIVISION PLAN REVIEW SHALL BE ATTACHED TO
 EACH SHEET STAMPED BY THE FOOD SERVICE ON EACH SET OF
 PLANS. SECTION 102.2.1.
 ****RESPONSE NOTED, BUT WORKSHEETS HAVE NOT BEEN
 ATTACHED TO STAMPED SHEET. -MINIMUM TWO STAMPED
 SHEETS REQUIRED FOR PLAN REVIEW. (ONLY ONE SHEET
 STAMPED BY DBPR FOUND)
 ******RESPONSE NOTED, BUT THE TWO PAGE "SPECIFICATION
 WORKSHEETS" HAVE NOT BEEN ATTACHET TO THE SHEET
 REVIEWED AND STAMPED BY DBPR AS REQUIRED. PLEASE ATTACH
 WORKSHEETS.
 **RESPONSE NOTED, BUT SHT G-CS IS ON THE FRONT OF THE
 SET AND IS NOT STAMPED BY DBPR. EQ-2.1 IS NOW A NEW
 SHEET SIGNED, SEALED & DATED AFTER THE LAST PLUMBING
 PLAN REVIEW. THE TWO PAGE "SPECIFICATION WORKSHEETS"
 ARE NOT ATTACHED. PLEASE COMPLY WITH THE ORIGINAL
 COMMENT.
  
 5. ALL MEP SHEETS. THE ORIGINAL SIGNATURE OF THE
 ENGINEER IS REQUIRED WHEN THE SEAL IS AFFIXED. THE
 STAMPED SIGNATURE IS NOT APPROVED. FAC
 61G15-23.002(1)(2) & FS 471.025.
 ****RESPONSE NOTED, BUT THE SIGNATURE IS SO MUCH
 DIFFERENT THAT A SIGNED, SEALED, DATED, NOTORIZED
 LETTER SHALL BE SUBMITTED INDICATING THE LEGAL
 SIGNATURE OF THE PROFESSIONAL ENGINEER AS WELL AS A
 PICTURE I.D. WITH THE ENGINEERS SIGNATURE FOR OUR
 FILES.
 ******RESPONSE NOTED, BUT THE LETTER IS NOT SEALED AS
 REQUESTED. PLEASE SEAL THE LETTER INDICATING THE LEGAL
 SIGNATURE.
 **RESPONSE NOTED, BUT NO NEW LETTER WAS FOUND.
  
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
  
 15. SHT P-3.2 THE FOLLOWING GAS REQUIREMENTS SHALL BE
 SUBMITTED:
  
 A. OK
 B. OK
  
 C. OK
 D. OK
 E. OK
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE MANUF. SHEETS FOR THE
 DOUBLE RACK OVEN IS NOT CLEAR AND LEGIBLE ON SHEET #3
 AND UL LISTING DOES NOT INDICATE WHAT IT WAS LISTED
 FOR. PLEASE SUBMIT A COPY OF THE UL LISTING FOR THIS
 PRODUCT.
 ******RESPONSE NOTED, BUT NEW MANUF SHEETS HAVE NOT
 BEEN SUBMITTED, NOR HAS THE UL LISTING INFORMATION.
 PLEASE SUBMIT REQUIRED INFORMATION.
 **RESPONSE NOTED, BUT THE MANUF. SHEETS FOR THE OVEN DO
 NOT REFLECT THE BTU'S INDICATED ON THE RISER DIAGRAM.
 THE MANUF. SPECIFICATION SHEETS FOR THE WATER HEATERS
 ARE NOT IN THE PACKAGE OF REQUIRED INFORMATION. PLEASE
 SUBMIT ALL MANUF. SPECIFICATION SHEETS AND MAKE SURE
 THEY REFLECT THE BTU LOAD INDICATED ON THE RISER
 DIAGRAM. INDICATE THE MODEL NUMBER ON THE SPECIFICATION
 SHEETS SUBMITTED.
  
 G. N/A
 H. N/A
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
  
 ********NEW COMMENT********
  
 1B. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-10-03 Cont ID  
Sent By kstevens Date 2007-10-03 Time 17:31 Rev Time 0.00
Received By kstevens Date 2007-10-03 Time 17:31 Sent To  
Notes
2007-10-03 17:56:24DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WEST PALM BEACH MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
 ******FROM PREVIOUS REVIEWS:
  
 1. OK
 2. OK
  
 3. SHT G-ADA SHOW THE FOLLOWING ACCESSIBILITY
 REQUIREMENTS:
 A. 11-4.16.5 FLUSH CONTROLS __W/C
 ****RESPONSE NOTED, BUT NO INDICATION OF COMPLIANCE TO
 ADDRESS THE FLUSH CONTROLS FOR THE W/C IN RESPONSE.
 PLEASE SHOW COMPLIANCE FOR THE FLUSH CONTROLS
 B. OK
  
 4. SHT EQ-2.1, THE 2 PAGE "WORKSHEETS" FROM DBPR HOTEL
 AND RESTURANT DIVISION PLAN REVIEW SHALL BE ATTACHED TO
 EACH SHEET STAMPED BY THE FOOD SERVICE ON EACH SET OF
 PLANS. SECTION 102.2.1.
 ****RESPONSE NOTED, BUT WORKSHEETS HAVE NOT BEEN
 ATTACHED TO STAMPED SHEET. -MINIMUM TWO STAMPED
 SHEETS REQUIRED FOR PLAN REVIEW. (ONLY ONE SHEET
 STAMPED BY DBPR FOUND)
 ******RESPONSE NOTED, BUT THE TWO PAGE "SPECIFICATION
 WORKSHEETS" HAVE NOT BEEN ATTACHET TO THE SHEET
 REVIEWED AND STAMPED BY DBPR AS REQUIRED. PLEASE ATTACH
 WORKSHEETS.
  
 5. ALL MEP SHEETS. THE ORIGINAL SIGNATURE OF THE
 ENGINEER IS REQUIRED WHEN THE SEAL IS AFFIXED. THE
 STAMPED SIGNATURE IS NOT APPROVED. FAC
 61G15-23.002(1)(2) & FS 471.025.
 ****RESPONSE NOTED, BUT THE SIGNATURE IS SO MUCH
 DIFFERENT THAT A SIGNED, SEALED, DATED, NOTORIZED
 LETTER SHALL BE SUBMITTED INDICATING THE LEGAL
 SIGNATURE OF THE PROFESSIONAL ENGINEER AS WELL AS A
 PICTURE I.D. WITH THE ENGINEERS SIGNATURE FOR OUR
 FILES.
 ******RESPONSE NOTED, BUT THE LETTER IS NOT SEALED AS
 REQUESTED. PLEASE SEAL THE LETTER INDICATING THE LEGAL
 SIGNATURE.
  
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
  
 15. SHT P-3.2 THE FOLLOWING GAS REQUIREMENTS SHALL BE
 SUBMITTED:
  
 A. OK
 B. OK
  
 C. OK
 D. OK
 E. OK
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE MANUF. SHEETS FOR THE
 DOUBLE RACK OVEN IS NOT CLEAR AND LEGIBLE ON SHEET #3
 AND UL LISTING DOES NOT INDICATE WHAT IT WAS LISTED
 FOR. PLEASE SUBMIT A COPY OF THE UL LISTING FOR THIS
 PRODUCT.
 ******RESPONSE NOTED, BUT NEW MANUF SHEETS HAVE NOT
 BEEN SUBMITTED, NOR HAS THE UL LISTING INFORMATION.
 PLEASE SUBMIT REQUIRED INFORMATION.
  
 G. N/A
 H. N/A
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
  
 ********NEW COMMENT********
  
 1B. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-07-14 Cont ID  
Sent By kstevens Date 2007-07-14 Time 16:49 Rev Time 0.00
Received By kstevens Date 2007-07-14 Time 13:54 Sent To  
Notes
2007-07-14 16:49:01DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WEST PALM BEACH MUNICIPAL CODE
  
 *******FROM PREVIOUS REVIEW*******
  
 1. OK
 2. OK
  
 3. SHT G-ADA SHOW THE FOLLOWING ACCESSIBILITY
 REQUIREMENTS:
 A. 11-4.16.5 FLUSH CONTROLS __W/C
 B. 11-4.19.5 FAUCETS __LAVS
 ****RESPONSE NOTED, BUT THE CUT SHEETS WERE NOT
 LOCATED, THE REQUIREMENT FOR THE FLUSH CONTROLS IS THAT
 THE CONTROLS SHALL BE ON THE WIDE SIDE OF THE TOILET.
 THE REQUIREMENT FOR THE FAUCETS IS THAT THEY BE LEVER
 TYPE, PUSH TYPE, ELECTRONIC ETC. THESE REQUIREMENTS
 SHALL BE SHOWN ON THE PLANS AS CUT SHEETS CAN BE LOST
 ON THE JOB.
  
 4. SHT EQ-2.1, THE 2 PAGE "WORKSHEETS" FROM DBPR HOTEL
 AND RESTURANT DIVISION PLAN REVIEW SHALL BE ATTACHED TO
 EACH SHEET STAMPED BY THE FOOD SERVICE ON EACH SET OF
 PLANS. SECTION 102.2.1.
 ****RESPONSE NOTED, BUT WORKSHEETS HAVE NOT BEEN
 ATTACHED TO STAMPED SHEET. -MINIMUM TWO STAMPED
 SHEETS REQUIRED FOR PLAN REVIEW. (ONLY ONE SHEET
 STAMPED BY DBPR FOUND)
  
 5. ALL MEP SHEETS. THE ORIGINAL SIGNATURE OF THE
 ENGINEER IS REQUIRED WHEN THE SEAL IS AFFIXED. THE
 STAMPED SIGNATURE IS NOT APPROVED. FAC
 61G15-23.002(1)(2) & FS 471.025.
 ****RESPONSE NOTED, BUT THE SIGNATURE IS SO MUCH
 DIFFERENT THAT A SIGNED, SEALED, DATED, NOTORIZED
 LETTER SHALL BE SUBMITTED INDICATING THE LEGAL
 SIGNATURE OF THE PROFESSIONAL ENGINEER AS WELL AS A
 PICTURE I.D. WITH THE ENGINEERS SIGNATURE FOR OUR
 FILES.
  
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
  
 14. SHT P-3.2 THE HOT & COLD WATER SUPPLIES TO FIXTURE
 13A ARE REVERSED. HOT IS SHOWN ON THE RIGHT AND COLD IS
 SHOWN ON THE LEFT. PLEASE CORRECT. SECTION 607.4.--
 ****ALL OF THE COMMENTS HAVE BEEN ADDRESSED EXCEPT THE
 ABOVE PORTION.
  
 15. SHT P-3.2 THE FOLLOWING GAS REQUIREMENTS SHALL BE
 SUBMITTED:
  
 A. OK
  
 B. TYPE OF GAS, (LP OR NATURAL).
 ****RESPONSE NOTED, BUT INFORMATION IS REQUIRED ON THE
 PLANS.
  
 C. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES. MATERIAL IS INDICATED AS
 EITHER THREADED OR WELDED ON SHT P-3.1. IF THE PIPING
 WILL BE WELDED, THE WELDING CERTIFICATION AND WELDING
 PROCEDURE WILL BE REQUIRED AT THE TIME OF GAS PERMIT
 APPLICATION.
 ****RESPONSE NOTED, BUT NOT ADDRESSED. THE NOTE STILL
 INDICATES IT CAN BE THREADED OR WELDED PIPE. UNTILL THE
 PIPE TYPE IS IDENTIFIED AS EITHER SCREW PIPE OR WELD
 PIPE THE PERMIT CAN NOT BE ISSUED.
  
 D. OK
 E. OK
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE MANUF. SHEETS FOR THE
 DOUBLE RACK OVEN IS NOT CLEAR AND LEGIBLE ON SHEET #3
 AND UL LISTING DOES NOT INDICATE WHAT IT WAS LISTED
 FOR. PLEASE SUBMIT A COPY OF THE UL LISTING FOR THIS
 PRODUCT.
  
 G. N/A
 H. N/A
 16. OK
 17. OK
  
 18. SHT P-4.1 THE 10 GALLON HOT WATER STORAGE TANK
 REQUIRES A RELIEF VALVE PER SECTION 504.4 AND SHALL BE
 INSTALLED PER 504.4.1. THE RELIEF LINE SHALL DISCHARGE
 PER SECTION 504.6.1. SUBMIT A DETAIL INDICATING
 COMPLIANCE. IF THE STORAGE TANK IS INSTALLED ABOVE THE
 GROUND FLOOR SPACE, IT SHALL BE INSTALLED IN A PAN AND
 SHALL HAVE A PAN DRAIN LINE. SECTIONS 504.7, 504.7.1 &
 504.7.2. PLEASE CLARIFY AND SUBMIT DETAILS IF
 REQUIRED.
 ****RESPONSE NOTED, BUT THE PAN DRAIN CAN NOT DRAIN
 INTO A FLOOR DRAIN, FLOOR DRAINS ARE NOT APPROVED
 INDIRECT WASTE RECEPTORS. A FLOOR SINK OR A HUB DRAIN
 IS REQUIRED PER SECTIONS 802.3 & 802.3.2.
  
 19. SHT P-4.1 THE WATER HEATER SCHEMATIC SHALL SHOW ALL
 PIPE SIZES FOR THE WATER LINES AND THE GAS LINES.--
 SCHEMATIC SHOWS 2" GAS HEADER, THIS SHALL REFLECT THE
 GAS RISER DIAGRAM.
 ****RESPONSE NOTED, BUT THE PIPEING SHOWN ON THE WATER
 HEATER SCHEMATIC IS NOT SHOWN ON SHEETS P2.4 OR P3.2.
 ALSO THE GAS HEADER ON THE RISER DIAGRAM DOES NOT
 REFLECT THE WATER HEATER SCHEMATIC. THE SCHEMATIC SHOWS
 1-1/2" PIPE BEING PIPED IN FROM THE LEFT OF THE HEATERS
 AND THE SCHEMATIC SHOWS THE GAS PIPING IN FROM THE
 RIGHT SIDE AND IS SHOWN AS 2" PIPE. PLEASE CORRELATE
 RISER AND SCHEMATIC AND SHOW ALL PIPE SIZES.
  
 20. OK
  
 21. THE GREASE LINE SHALL DRAIN TO A GREASE
 INTERCEPTOR. THE INTERCEPTOR SHALL BE SIZED BY THE
 ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE CONTACT RODNEY
 COMPO AT (561) 822-2272 OR CALVIN WILLIAMS AT (561)
 822-2284. THEIR FAX NUMBER IS (561) 822-2287 OR THEY
 CAN BE REACHED BY E-MAIL [email protected] OR
 [email protected]. CITY CODE 90-124(7). ****RESPONSE
 NOTED, WAITING FOR WRITTEN NOTICE FROM R. COMPO.
  
 ********NEW COMMENT********
  
 1B. ALL SHEETS SHALL BE STAMPED FOR APPROVAL BY CITY
 PLACE MANAGEMENT PRIOR TO RESUBMITTING.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-27 Cont ID  
Sent By kstevens Date 2007-04-27 Time 17:38 Rev Time 0.00
Received By kstevens Date 2007-04-26 Time 17:29 Sent To  
Notes
2007-04-27 18:56:07DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WEST PALM BEACH MUNICIPAL CODE
  
 1. ALL SHEETS. INDICATE THE TENANT UNIT/SPACE NUMBER IN
 THE TITLE BLOCK ALONG WITH THE ADDRESS. SECTION 106.1.
  
 2. SHT EC-2.1 THE EXISTING FLOOR PLAN SHOWS NO EXISTING
 PLUMBING, BUT SHT A-2.0 INDICATES REMOVAL OF EXISTING
 PLUMBING LINES. PLEASE SHOW WHERE THE PLUMBING LINES
 WILL BE DEMO'D SO THE FIELD INSPECTOR CAN ASSURE THE
 LINES ARE DEMO'D PROPERLY AND NO DEAD ENDS ARE LEFT.
 SECTIONS 106.1.1 & 704.5.
  
 3. SHT G-ADA SHOW THE FOLLOWING ACCESSIBILITY
 REQUIREMENTS:
 A. 11-4.16.5 FLUSH CONTROLS __W/C
 B. 11-4.19.5 FAUCETS __LAVS
  
 4. SHT EQ-2.1, THE 2 PAGE "WORKSHEETS" FROM DBPR HOTEL
 AND RESTURANT DIVISION PLAN REVIEW SHALL BE ATTACHED TO
 EACH SHEET STAMPED BY THE FOOD SERVICE ON EACH SET OF
 PLANS. SECTION 102.2.1.
  
 5. ALL MEP SHEETS. THE ORIGINAL SIGNATURE OF THE
 ENGINEER IS REQUIRED WHEN THE SEAL IS AFFIXED. THE
 STAMPED SIGNATURE IS NOT APPROVED. FAC
 61G15-23.002(1)(2) & FS 471.025.
  
 6. ALL MEP SHEETS. THE CERTIFICATE OF AUTHROIZATION
 NUMBER OF THE ENGINEERING BUSINESS IS REQUIRED IN THE
 TITLE BLOCK OF EACH SHEET. THE FLORIDA STATE WEBSITE OF
 THE DBPR INDICATES THAT THE STATUS OF THE CA NUMBER IS
 CLOSED. (SEE ATTACHED SHEET FROM WEBSITE). PLEASE
 SECURE A CA NUMBER PRIOR TO RESUBMITTING FOR REVIEW AT
 WPB. FAC 61G15-23.002(2) & FS 471.025.
  
 7. SHT P-2.1 GENERAL PLUMBING NOTE #6 INDICATES THE
 SLEEVE TO BE 1" MINIMUM LARGER THAN THE PIPE PASSING
 THRU THE WALL. PER SECTION 305.5 THE SLEEVES SHALL BE 2
 PIPE SIZES GREATER THAN THE PIPE PASSING THROUGH THE
 WALL. PLEASE CORRECT THE PLUMBING NOTE.
  
 8. SHT P-2.3 THE DISH WASHER, (27A), SHALL CONNECT TO
 THE SANITARY SYSTEM, NOT THE GREASE SYSTEM AS SHOWN.
 MUNICIPAL CODE SECTION 90-124(7)(B). PLEASE CHANGE ON
 THE FLOOR PLAN AND THE RISER DIAGRAM.
  
 9. SHT P-2.4 THE GAS LINE STARTS OUT 1-1/2" THEN
 REDUCES TO 1-1/4"AND THEN IS INDICATED AS 1-1/2" AT
 THE OVEN. PLEASE CLARIFY. TABLE 402.4(2).
  
 10. SHT P-2.4 SHOW THE GAS TO THE WATER HEATERS WITH
 ALL OFFSETS ETC. SECTION 106.1.1.
  
 11. SHT P-2.4 NO COLD WATER DROP NOR HOT WATER RISER
 FOR THE WATER HEATERS ARE INDICATED ON THE WATER
 PIPING. PLEASE CLARIFY. SECTION 106.1.1.
  
 12. SHT P-3.1 THE FLOOR SINK (P-7 FOR THE DISH WASHER,
 (27A), TO BE CONNECTED TO THE SANITARY SYSTEM AND NOT
 THE GREASE SYSTEM. (SEE COMMENT #8).
  
 13. SHT P-3.1 SECTION 15400 PLUMBING NOTES 1.0 STATES
 DESIGN BASED ON INTERNATIONAL PLUMBING CODE. ADOPTED
 CODE IS THE FBC-2004 PLUMBING CODE. PLEASE CHANGE
 REFERENCE. SECTION 106.1.1.
  
 14. SHT P-3.2 THE HOT & COLD WATER SUPPLIES TO FIXTURE
 13A ARE REVERSED. HOT IS SHOWN ON THE RIGHT AND COLD IS
 SHOWN ON THE LEFT. PLEASE CORRECT. SECTION 607.4.--
 THE WATER RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN
 IN THE WOMEN'S TOILET ROOM. THE FLOOR PLAN INDICATES
 W/C P-1 ON THE FLOOR PLAN BUT IS INDICATED AS P-3 ON
 THE RISER DIAGRAM. THE TRAP PRIMER LINE IS SHOWN BY P-1
 ON THE FLOOR PLAN, BUT THE LINE IS SHOWN BY P-3 ON THE
 RISER DIAGRAM. PLEASE CORRELATE THE INFORMATION. --NO
 COLD WATER SUPPLY AND HOT WATER LINES TO THE HEATERS
 ARE INDICATED.--THE STORAGE WATER HEATER REQUIRES A
 FULL OPEN VALVE ON THE SUPPLY LINE.--A VACUUM
 RELIEF VALVE IS REQUIRED ON THE BOTTOM FED WATER
 HEATER. SECTIONS 106.1.1., 606.1(6) & 504.2.
  
 15. SHT P-3.2 THE FOLLOWING GAS REQUIREMENTS SHALL BE
 SUBMITTED:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. THIS SHALL BE SHOWN FROM THE METER TO
 THE MOST REMOTE APPLIANCE.
  
 B. TYPE OF GAS, (LP OR NATURAL).
  
 C. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES. MATERIAL IS INDICATED AS
 EITHER THREADED OR WELDED ON SHT P-3.1. IS THE PIPING
 WILL BE WELDED, THE WELDING CERTIFICATION AND WELDING
 PROCEDURE WILL BE REQUIRED AT THE TIME OF GAS PERMIT
 APPLICATION.
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - THIS IS INDICATED AS 90
 FEET ON THE PLANS, BUT CAN NOT BE VERIFIED UNTIL ALL
 CUT SECTION MEASURMENTS ARE SUBMITTED. (SEE GAS COMMENT
 A).
  
 E. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - PLANS INDICATE
 7"WC. THE PRESSURE WILL BE EITHER 2PSI OR 1/2PSI.
 PLEASE INDICATE ON THE PLANS.
  
 F. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 G. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 H. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 16. SUBMIT THE MANUF. SPECIFICATIONS FOR THE WATER
 FILTER. THE FILTER SHALL MEET THE REQUIREMENTS OF
 NSF-42. SECTION 611.1
  
 17. SUBMIT THE MANUF. SPECIFICATIONS FOR THE TEMPERING
 VALVE. SECTION 106.1.2.
  
 18. SHT P-4.1 THE 10 GALLON HOT WATER STORAGE TANK
 REQUIRES A RELIEF VALVE PER SECTION 504.4 AND SHALL BE
 INSTALLED PER 504.4.1. THE RELIEF LINE SHALL DISCHARGE
 PER SECTION 504.6.1. SUBMIT A DETAIL INDICATING
 COMPLIANCE. IF THE STORAGE TANK IS INSTALLED ABOVE THE
 GROUND FLOOR SPACE, IT SHALL BE INSTALLED IN A PAN AND
 SHALL HAVE A PAN DRAIN LINE. SECTIONS 504.7, 504.7.1 &
 504.7.2. PLEASE CLARIFY AND SUBMIT DETAILS IF
 REQUIRED.
  
 19. SHT P-4.1 THE WATER HEATER SCHEMATIC SHALL SHOW ALL
 PIPE SIZES FOR THE WATER LINES AND THE GAS LINES.--
 SCHEMATIC SHOWS 2" GAS HEADER, THIS SHALL REFLECT THE
 GAS RISER DIAGRAM.
  
 20. SHT P-4.1 THE 4 POD WATER FILTER DETAIL SHOWS A
 RESIN TANK & A BRINE TANK THAT IS NOT SHOWN ON THE
 FLOOR PLAN. PLEASE CLARIFY AND CORRELATE THE
 INFORMATION. THE SYSTEM ALSO SHOWS A 1" LINE THAT
 STATES "TO DRAIN". PLEASE INDICATE WHERE IT WILL DRAIN
 TO.SECTIONS 106.1.1 802.1.5.
  
 21. THE GREASE LINE SHALL DRAIN TO A GREASE
 INTERCEPTOR. THE INTERCEPTOR SHALL BE SIZED BY THE
 ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE CONTACT RODNEY
 COMPO AT (561) 822-2272 OR CALVIN WILLIAMS AT (561)
 822-2284. THEIR FAX NUMBER IS (561) 822-2287 OR THEY
 CAN BE REACHED BY E-MAIL [email protected] OR
 [email protected]. CITY CODE 90-124(7).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status N Date 2007-08-06 Cont ID  
Sent By eschneid Date 2007-08-06 Time 18:07 Rev Time 0.00
Received By eschneid Date 2007-08-06 Time 18:07 Sent To  
Notes
2007-08-06 18:08:10PROVISO WAS ADDRESSED.

Review Stop Z ZONING
Rev No 1 Status P Date 2007-03-29 Cont ID  
Sent By eschneid Date 2007-03-29 Time 11:40 Rev Time 0.00
Received By eschneid Date 2007-03-29 Time 11:40 Sent To  
Notes
2007-03-29 11:45:54PASS W/PROVISO
  
 PROVISO - SHEETS EC5.1 AND EC5.2 SHALL BE REVISED TO
 STATE THE CORRECT ELEVATIONS.NORTH ELEVATION IS
 LISTED AS EAST ELEVATION AND WEST ELEVATION IS LISTED
 AS NORTH ELEVATION.
  
 PLEASE BE ADVISED THAT IF THE OUTDOOR SEATING EXTENDS
 INTO THE HIBISCUS STREET RIGHT-OF-WAY, A SIDEWALK CAFE
 PERMIT WILL BE REQUIRED.
  
 SIGNS AND AWNINGS SHALL BE SUBMITTED UNDER A SEPERATE
 PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.