Plan Review Details - Permit 07030491
Plan Review Stops For Permit 07030491
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-07-25 Cont ID  
Sent By jwitmer Date 2008-07-25 Time 08:15 Rev Time 3.33
Received By jwitmer Date 2008-07-25 Time 08:15 Sent To PC
Notes
2008-07-25 08:16:41BILCO HATCH APPROVAL FOR A S-20 ROOF HATCH

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-05-12 Cont ID  
Sent By jwitmer Date 2008-05-12 Time 15:57 Rev Time 0.77
Received By jwitmer Date 2008-05-12 Time 15:57 Sent To  
Notes
2008-05-12 15:58:05REV# 2 REVISED CONDENSING UNIT CURB

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-11-19 Cont ID  
Sent By jwitmer Date 2007-11-19 Time 16:41 Rev Time 2.22
Received By jwitmer Date 2007-11-19 Time 16:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-21 Cont ID  
Sent By jwitmer Date 2007-09-21 Time 17:07 Rev Time 3.33
Received By jwitmer Date 2007-09-21 Time 17:07 Sent To  
Notes
2007-09-21 17:10:06WALGREENS STORE # 7265
  
 BUILDING PLAN REVIEW
 PERMIT: 07030491
 ADD: 9921 OKEECHOBEE BLVD
 CONT: ROCKWELL DEVELOPMENT
 TEL: (561)278-3100
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2) SECOND REQUEST FOR A NOTICE OF COMMENCEMENT,
 RESPONSE INDICATED A NOC WAS SUBMITTED, ONLY DOCUMENT
 SIMILAR IN FORM FOUND WAS A WARRANTY DEED. FL S S
 713.13NOTICE OF COMMENCEMENT, TO BE FILED WITH THE
 CLERK OF THE COURT.NOTE: 713.13(2) IF THE WORK
 DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3-18) COMPLIED
  
 19A) THIRD REQUEST,, NO PERMIT SHALL BE ISSUED WITHOUT
 COMPLYING WITH THESE PROVISIONS, PROVIDE FIRE SPRINKLER
 PLANS, 903.2.6 GROUP M.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED
 THROUGHOUT BUILDINGS CONTAINING A GROUP M OCCUPANCY
 WHERE ONE OF THE FOLLOWING CONDITIONS EXISTS:
 1.WHERE A GROUP M FIRE AREA EXCEEDS 12,000 SQUARE
 FEET (1115 M 2 ).
 TABLE 503 AND 504.2.
  
 19B) 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS(5) FIRE SUPRESSION SYSTEMS SHALL INCLUDE
 PREENGINEERED SYSTEMS , FIRE SPRINKLER SYSTEMS.
  
 19C) NOTE!!! SEE ATTACHED FL S S 553.80(2)(B) LOCAL
 GOVERNMENT SHALL IMPOSE EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION A
 FEE OF FOUR TIMES THE AMOUNT OF THE PORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLAN REVIEW.
  
 20)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
 EL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-29 Cont ID  
Sent By jwitmer Date 2007-06-29 Time 10:57 Rev Time 4.00
Received By jwitmer Date 2007-06-29 Time 10:57 Sent To  
Notes
2007-06-29 10:59:04WALGREENS STORE # 7265
  
 BUILDING PLAN REVIEW
 PERMIT: 07030491
 ADD: 9921 OKEECHOBEE BLVD
 CONT: ROCKWELL DEVELOPMENT
 TEL: (561)278-3100
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2) SECOND REQUEST FOR A NOTICE OF COMMENCEMENT,
 RESPONSE INDICATED A NOC WAS SUBMITTED, ONLY DOCUMENT
 SIMILAR IN FORM FOUND WAS A WARRANTY DEED. FL S S
 713.13NOTICE OF COMMENCEMENT, TO BE FILED WITH THE
 CLERK OF THE COURT.NOTE: 713.13(2) IF THE WORK
 DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SECOND REQUEST, IS FOR SOILS REPORT, SUBMITTED IS
 COPIESNOT ORIGINAL SIGNED AND SEALED DOCUMENTS. SHEET
 S5.1 SITE WORK# 2 ALSO REQUIRES A SOILS INVESTIGATIVE
 REPORT BY A LICENSED GEOTECHNICAL ENGINEER.1802.2.1
 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 4) COMPLIED.
  
 5) BUILDING PROVISO: 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL
 BE PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT
 THE CONDITION OF ADJACENTPROPERTY, UNLESS SUCH
 ACTIVITY IS PERMITTED TO AFFECT SAID PROPERTY PURSUANT
 TO A CONSENT BY THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL
 OF DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND
 THE STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED
 TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE
 FINAL INSPECTION.
  
 6) BUILDING PROVISO:109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS EQUIPMENT AND
 DEBRIS TO REMAIN LOOSE OR OTHERWISE UNSECURED AT A
 CONSTRUCTION SITE FROM 24 HRS. AFTER A HURRICANE WATCH
 HAS BEEN ISSUED UNTIL THE HURRICANE WATCH OR WARNING
 HAS BEEN LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED FROM THE
 CONSTRUCTION SITE OR SECURED IN SUCH A MANNER AS TO
 MINIMIZE THE DANGER OF SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS CAUSING DAMAGE TO PERSONS OR
 PROPERTY FROM HIGH WINDS. ANY PERSONS WHO FAILS TO
 COMPLY TO REMOVE OR SECURE THE CONSTRUCTION MATERIALS
 EQUIPMENT AND DEBRIS WITHIN 24 HRS AFTER A HURRICANE
 WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00. IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE SUBJECT
 TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 7-10 COMPLIED.
  
 11) SECOND REQUEST, IT APPEARS THAT THE CONTRACTOR IS
 TRYING TO COMPLY WITH THIS REQUEST FOR PRODUCT
 APPROVALS REQUIRED BY RULE 9B-72, THE CONTRACTOR DID
 SUPPLY THE FLORIDA COVER SHEETS THAT INDICATE TESTING
 WAS COMPLETED AND COMPLIES WITH THE STANDARD. WE ALSO
 NEED THE TEST REPORTS WITH THE TECHNICAL DRAWINGS (NOT
 SHOP DRAWINGS) THAT WERE ALSO SUBMITTED TO THE STATE
 FOR APPROVAL. THE PRODUCT APPROVALS WILL PROVIDE TO
 WHAT PRESSURES THE COMPONENTS WERE TESTED TO, WHAT
 LIMITATIONS ARE IMPOSED, AND THE CALCULATIONS WILL
 DETERMINE TO WHICH CODE THE TEST WAS COMPLETED TO.
 PLEASE SUBMIT THE TEST REPORTS, MOST WILL BE A
 MIAMI-DADE APPROVAL BUT NOT NECESSARILY SO. AS LONG AS
 YOU TAKE THE ATTACHED PDF FILE FROM THE FLORIDA
 WEBSITE!!!! FLORIDABUILDING.ORG.
 FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES (3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS ,MISSING REPORTS
 ARE AS FOLLOWS:
 A) EXTERIOR HOLLOW METAL SWING DOORS
 B) OVERHEAD COIL DOORS
 C) AUTOMATIC SLIDING DOORS
 D) ROOF HATCHES
 E) WINDOWS- STOREFRONT
 F) WINDOWS- PASS THROUGH
 G) ROOF ASSEMBLIES: FLAT ROOF AND SLOPED TILE ROOF H)
 PRE-MANUFACTURED A/C STANDS
 ***SHEET A4.5 STILL INDICATES SLEEPERS, SEE 1509.7
 & TABLE 1509.7***
 I ) WOOD OR TRUSS TIE DOWN ANCHORS
  
 12) SECOND REQUEST,ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 13) SEMI- COMPLIED, THE CONTRACTOR HAS MEET THIS
 REQUIREMENT BUT NEEDS TO SUPPLY THE BACK UP
 DOCUMENTATION.
  
 14)2ND REQUEST,) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH.
  
 _XX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE
 USED.
  
 _XX__ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2&3__ .
  
 _XX__ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE BUILDING OFFICIAL, A
 REVISED FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED PROFESSIONAL
 ENGINEER, REGISTERED ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 15) COMPLIED.
  
 16) COMPLIED.
  
 17) SHEET A2.4 HAS BEEN REVISED FOR THE CANOPY CEILING
 INSTALLATION TO SHOW THE USE OF WIRE LATH,
 TYPE OF WIRE LATH IS NOT SPECIFIED, PLEASE SEE 2510.3
 INSTALLATION FOR STUCCO REFERS TO ASTM C 1063. ASTM C
 1063 TABLE 3 PROVIDES TYPES OF LATH, THE WEIGHT OF
 LATH, VERTICAL AND HORIZONTAL
 APPLICATIONS AND THE SPACING OF SUPPORTS. THE STANDARD
 ALSO PROVIDES THE LENGTH OF FASTENER REQUIREMENTS
 PLEASE PROVIDE.
  
 18) 2ND REQUEST, THE REQUIREMENT FOR ATTIC VENTILATION
 STILL REMAINS,1203.2 ATTIC SPACES.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 FRAMING MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH
 SEPARATE SPACE BY VENTILATING OPENINGS PROTECTED
 AGAINST THE ENTRANCE OF RAIN. BLOCKING AND BRIDGING
 SHALL BE ARRANGED SO AS NOT TO INTERFERE WITH THE
 MOVEMENT OF AIR. A MINIMUM OF 1 INCH (25 MM) OF
 AIRSPACE SHALL BE PROVIDED BETWEEN THE INSULATION AND
 THE ROOF SHEATHING. THE NET FREE VENTILATING AREA SHALL
 NOT BE LESS THAN 1 / 150 OF THE AREA OF THE SPACE
 VENTILATED, WITH 50 PERCENT OF THE REQUIRED VENTILATING
 AREA PROVIDED BY VENTILATORS LOCATED IN THE UPPER
 PORTION OF THE SPACE TO BE VENTILATED AT LEAST 3 FEET
 (914 MM) ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE
 OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE
 VENTS.
  
 19) SECOND REQUEST, PROVIDE FIRE SPRINKLER PLANS,
 903.2.6 GROUP M.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED
 THROUGHOUT BUILDINGS CONTAINING A GROUP M OCCUPANCY
 WHERE ONE OF THE FOLLOWING CONDITIONS EXISTS:
 1.WHERE A GROUP M FIRE AREA EXCEEDS 12,000 SQUARE
 FEET (1115 M 2 ).
 TABLE 503 AND 504.2.
  
 20)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
 EL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-13 Cont ID  
Sent By jwitmer Date 2007-04-13 Time 15:22 Rev Time 12.55
Received By jwitmer Date 2007-04-13 Time 15:22 Sent To FIRE
Notes
2007-04-13 15:26:25BUILDING PLAN REVIEW
 PERMIT: 07030491
 ADD: 9921 OKEECHOBEE BLVD
 CONT: ROCKWELL DEVELOPMENT
 TEL: (561)278-3100
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT
 IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)THE
 POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) FBC 1802.2.1 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL IS
 IN DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE
 IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE THAT
 THE NECESSARY INVESTIGATION BE
 MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 4)106.1.2 * ADDITIONAL INFORMATION REQUIRED, PLANS
 FAIL TO PROVIDE AN INDEX INDICATING
 ON WHICH SHEET ANY CERTAIN DOCUMENT WILL BE FOUND. THIS
 WOULD GREATLY INCREASE PRODUCTIVITY
 IN THE AMOUNT OF TIME IT TAKES TO DO A REVIEW OF YOUR
 PROJECT!!!!
  
 5) 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 6) 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 7)SHEET A0.1 INDICATES THE PLANS WERE DESINED TO THE
 2004 FBC. PLANAS SUBMITTED AFTER DEC.8, 2006 ARE TO BE
 DESIGNED TO THE 2004FBC WITH THE 2006 AMENDMENTS.
  
 8)SHEET A0.2 SITE PLAN INDICATES WHAT APPEARS TO BE A
 PROPERTY LINE AROUND THE NEW PROPOSED STORE, BUT THERE
 ALSO APPEARS TO BE A SECOND PROPERTY LINE AT THE FRONT
 OF THE STORE? WHAT AREA IS THE LEASABLE AREA OR
 PROPERTY LINE ? IS THERE ONLY 38 PARKING SPACES IN THIS
 PROJECT OR IS THERE 87 PARKING SPACES? IF THERE ARE 87
 PARKING SPACES THEN 11-4.1.2(5)(A)INDICATES THERE
 SHOULD BE (4) SPACES FOR THE PHYSICLLY DISABLED .
  
 9) SURVEY BY CRAIG S. PUSEY IS A RAISED SEAL BUT PHOT
 COPIED SIGNATURE.
  
 10)) SHEET A0.2 ALSO SHOULD SHOW THE ACCESSABLE ROUTE
 TO THE PUBLIC WAY. 11-4.1.2(1) .
  
 11)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS FOLLOWS:A)
 EXTERIOR HOLLOW METAL SWING DOORS
 B)OVERHEAD COIL DOORS
 C) AUTOMATIC SLIDING DOORS
 D) ROOF HATCHES
 E) WINDOWS- STOREFRONT
 F) WINDOWS PASS THROUGH
 G) ROOF ASSEMBLIES, BASE SHEETS, TILE AND FASTENER
 TYPES
 H) PRE-MANUFACTURED A/C STANDSSHEET A4.5INDICATES
 SLEEPERS, 1509.7/ TABLE 1509.7.
 I) WOOD TRUSS TIE DOWN ANCHORS
  
 12)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG.
  
  
 13) PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 14) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
 ROOF TILE :
 _X__ CONTRACTOR DID NOT PROVIDE THE MEAN
  
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 _X__ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 __X_ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE _2&3__ .
  
 __X_ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 _X__THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 __X__- PROVIDE TYPE OF RIDGE AND HIP BOARD TO BE USED
 AND TYPE OF ATACHMENT.
 CONCRETE TILE / CLAY TILEATTACHMENTSHALL BE
 FASTENED IN ACCORDANCE WITH 1609 OR IN ACCORDANCE WITH
 FRSA/TRI 07320-04 INSTALLATION MANUAL.
  
 15) SHEET S2.1 TRUSS TIE DOWNANCHORS, THE DESIGNER OF
 RECORD HASN,T GIVEN THE VALUES REQUIRED FOR THE HOLD
 DOWN FASTENERS.PLEASE PROVIDE GRAVITY LOADS, LATERAL
 LOADS & UPLIFT LOADS TO BE RESISTED.THE ANCHORS ARE
 PART OF THE MAIN FORCE RESISTING SYSTEM1609.1.1. PLEASE
 PROVIDE VALUES TO BE RESISTED.T1 & T2 ARE NOT LOCATED
 ON PLAN.
  
 16)FRONT ENTRY HORIZONTAL SLIDING DOORS: 1008.1.3.3
 HORIZONTAL SLIDING DOORS.
 IN OTHER THAN GROUP H OCCUPANCIES, HORIZONTAL SLIDING
 DOORS PERMITTED TO BE A COMPONENT OF A MEANS OF EGRESS
 IN ACCORDANCE WITH EXCEPTION 5 TO SECTION 1008.1.2
 SHALL COMPLY WITH ALL OF THE FOLLOWING CRITERIA: 1.
 THE DOORS SHALL BE POWER OPERATED AND SHALL BE CAPABLE
 OF BEING OPERATED MANUALLY IN THE EVENT OF POWER
 FAILURE.
 2.THE DOORS SHALL BE OPENABLE BY A SIMPLE METHOD
 FROM BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT. 3.
 THE FORCE REQUIRED TO OPERA TE THE DOOR SHALL NOT
 EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND
 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN IT TO THE
 MINIMUM REQUIRED WIDTH.
 4.THE DOOR SHALL BE OPENABLE WITH A FORCE NOT TO
 EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS
 (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR ADJACENT
 TO THE OPERATING DEVICE.
 5.THE DOOR ASSEMBLY SHALL COMPLY WITH THE
 APPLICABLE FIRE PROTECTION RATING AND, WHERE RATED,
 SHALL BE SELF-CLOSING OR AUTOMATIC-CLOSING BY SMOKE
 DETECTION, SHALL BE INSTALLED IN ACCORDANCE WITH NFPA
 80 AND SHALL COMPLY WITH SECTION 715 .
 6.THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED
 STANDBY POWER SUPPLY.
 7.THE DOOR ASSEMBLY POWER SUPPLY SHALL BE
 ELECTRICALLY SUPERVISED.
 8.THE DOOR SHALL OPEN TO THE MINIMUM REQUIRED
 WIDTH WITHIN 10 SECONDS AFTER ACTIVATION OF THE
 OPERATING DEVICE.
 9.IN APARTMENT BUILDINGS, HOTELS AND DORMITORIES,
 HORIZONTAL SLIDING DOORS SHALL NOT BE USED ACROSS
 CORRIDORS.
  
 17)A2.4 INDICATES THE USE OF HI-RIB LATH ON THE UNDER
 SIDE (HORIZONTAL FRAMING MEMBERS) OF THE CANOPY, PLEASE
 PROVIDE THE NAILING REQUIREMENTS FOR LATH. TABLE
 2511.1/ ASTM
 C-1063. 2504.2.2 INSTALLATION OF EXTERIOR
 LATHING AND FRAMING SHALL COMPLY WITH
 ASTM C-1063.
  
 18)SHEET A2.4 INDICATES THE USE OF EAVE ANDTHE
 MONIER LIFETILE ATTIC VENT, PLEAS PROVIDE THE
 CALCULATIONS AS PER 1203.2, PLEASE ALSO PROVIDE THE
 PRODUCT APPROVAL
 FOR THE LIFETILE ATTIC VENT, RULE 9-B-72.
  
 19)PLEASE PROVIDE THE FIRE SPRINKLER PLANS SHEET A0.1
 PROJECT INFORMATION INDICATES TAKING AREA INCREASES FOR
 A FIRE SPRINKLERED BUILDING, PLEASE PROVIDETHE
 REQUIREDAUTOMATIC SPRINKLER PLANS PER, TABLE 503,
 504.2 & 903.1.1
  
 20)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-09-11 Cont ID  
Sent By dpalmer Date 2007-09-11 Time 17:29 Rev Time 0.00
Received By dpalmer Date 2007-09-11 Time 17:29 Sent To  
Notes
2007-09-11 17:30:072007-09-11 17:30:07
  
 ELEC OK, STAMPED PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-22 Cont ID  
Sent By dpalmer Date 2007-06-22 Time 14:16 Rev Time 0.00
Received By dpalmer Date 2007-06-22 Time 09:31 Sent To  
Notes
2007-06-22 14:16:15*** UNSAT2ND REVIEW ***
  
 ** PLEASE SEE THERE ARE STILL SOME NOTES FROM PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
  
  
 * PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 WILL BE FROM THE ADMINISTRATIVE SECTION OF THE CODE AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE:SAME NOTE FROM PREVIOUS REVIEW. THE RESPONSE
 LETTER FROM ARCHITECT MENTIONS THIS WILL BE ADDRESSED
 BY THE CONTRACTOR HOWEVER THIS IS NOT THE
 RESPONSIBILITY OF THE CONTRACTOR. IT IS THE
 RESPONSIBILITY OF THE DESIGNER OR FIRM AS NOTED.
 PLEASE ALSO SEE SOME *L* SHEETS IN SETS WHICH ARE NOTE
 SIGNED, DATED OR SEALED.
 PLEASE SEE MISSING LICENSE NUMBER FOR THE LANDSCAPE
 FIRM AS LISTED ON THE TITLE BLOCKS FOR *L* SHEETS. THIS
 IS ALSO KNOWN AS THE CERTIFICATE OF AUTHORIZATION
 NUMBER.
 PLEASE SEE 481.219, FAC 61G1-16.004
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 2) NOTE:SAME NOTE AS PREVIOUS REVIEW. THE RESPONSE
 LETTER FROM ARCHITECT MENTIONS THIS WILL BE ADDRESSED
 BY THE CONTRACTOR HOWEVER THIS IS NOT THE
 RESPONSIBILITY OF THE CONTRACTOR. IT IS THE
 RESPONSIBILITY OF THE DESIGNER OR FIRM AS NOTED PLEASE
 SEE THE MISSING LICENSE NUMBER FOR THE SURVEY FIRM AS
 REQUIRED PER FS 472.021. 61G17
 ALSO KNOWN AS THE CERTIFICATE OF AUTHORIZATION NUMBER.
  
 3) NOTE:PLEASE SEE THIS COMMENT REMAINS AS THE PLANS
 NOW INDICATE A 2005 NFPA-72 WHICH IS NOT YET ADOPTED BY
 THE STATE OF FLORIDA. PLEASE SEE THE PREVIOUS REVIEW
 NOTES BELOW WHICH GIVE THE CODES TO BE ON PLANS. PLEASE
 SEE THERE ARE STILL LOCATIONS ON PLANS ON SHEETS WHICH
 WERE NOTE CHANGED OUT WHICH REFLECT THE *STANDARD
 BUILDING CODE*.
 ** PREVIOUS REVIEW NOTE*
 PLEASE SEE THAT ALL OF THE CODES WHICH PLANS ARE UNDER
 DESIGN AND RECORD SHALL BE STATED ON PLANS AS FOLLOWS.
 PLEASE SEE THAT THERE ARE SEVERAL LOCATIONS WHICH CODES
 FROM OLDER ADOPTED CODES ARE STATED ON PLANS. PLEASE
 ALSO SEE THAT THE PLANS ALSO CONTAIN STATEMENTS IN
 DIFFERENT LOCATIONS FOR THE *STANDARD BUILDING *.
 PLEASE KNOW THAT THE STANDARD BUILDING CODE WAS NO
 LONGER IN AFFECT AS OF MARCH 1ST, 2002 WHEN THE STATE
 OF FLORIDA ADOPTED THE 2001 FBC.
 PLEASE KNOW THAT AS OF DECEMBER 8TH, 2006 THE FOLLOWING
 CODE(S) WERE ADOPTED. PLEASE LIST THE FOLLOWING AT A
 MINIMUM FOR THIS REVIEWER.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** THESE ARE REQUIRED FOR THIS REVIEWER AT A MINIMUM
 AND OTHER CODES WILL BE REQUIRED FOR OTHER TRADES.
  
 4) NOTE: PLEASE SEE THE ADDRESS FOR THIS PROJECT IS
 9921 OKEECHOBEE BLVD. PLEASE INCLUDE THIS INFORMATION
 AS REQUIRED ON TITLE BLOCKS. PLEASE SEE NUMEROUS SHEETS
 FROM PREVIOUS REVIEW NOT ONLY FOR ELECTRICAL BUT FOR
 OTHER TRADE SHEETS AS WELL DO NOT SHOW THE ADDRESS. THE
 LOCATION AS NOTED TO THE NEAREST MAIN INTERSECTION IS
 NOT ACCEPTABLE.
 THIS IS TO BE CORRECTED ON ALL SHEETS EVEN IF COMMENT
 IS NOT MADE BY OTHER TRADE(S). PLEASE KNOW THAT SHEETS
 WHICH MAY ALREADY CONTAIN STAMPS FROM REVIEWERS MAY
 HAVE THE CORRECT ADDRESS PLACED ON SHEETS BY PERMANENT
 MEANS. (PRINTED, STAMPED ETC)
 FAC 61G1-16.004, FAC 61G15-23.002
  
 5) NOTE: PLEASE SEE 2004 FBC W/2006 REVISIONS FOR
 CHAPTER 13. PLEASE SEE RESPONSE MENTIONS TO SEE TIMES
 FOR OVER RIDE DEVICES ON SHEETS AND 4.1 YET THESE TIMES
 FOR OCCUPANCY TYPE DEVICE COULD NOT BE LOCATED ON
 PLANS.
 PLEASE SEE THE ENERGY CALCULATION AS SUBMITTED STILL DO
 NOT CORRELATE WITH THE FIXTURE LEGEND AND FIXTURE NOTES
 ON THE SAME SHEET AS FIXTURE LEGEND. PLEASE SEE THE
 NUMBER OF FIXTURE, TYPES AND WATTAGES NEED TO
 COORDINATE WITH THE ENERGY CALCULATIONS.
 KEYED NOTE #4 ON LIGHTING SHEETS MENTIONS TO SEE NOTE
 #111 ON E4.1, HOWEVER THE NOTE ON E4.1 DOES NOT
 ELABORATE ON DEVICE TIMES?
 LIGHTING CASES?
 13-415.1.ABC1.1, .1.2, .1.3.
 ** PLEASE SEE THAT THE OWNER AGENT IS NOT SIGNED ON
 ENERGY CALCULATIONS.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.PLEASE SEE
 SOME LOCATIONS WHICH DO NOT INDICATE ANY LIGHTING
 CONTROLS UNDER AN AUTOMATED MEANS. PLEASE SEE THAT
 THESE DEVICES NEED TO BE SHOWN AS SOME OF THE DEVICES
 SHOWN SEEM TO BE NORMAL CONTROL SWITCHES AND SOME AREAS
 DO NOT SEEM TO INDICATE OCCUPANCY TYPE DEVICES. PLEASE
 SEE THE COOLER, FREEZER, DRIVE THRU SWITCH, TOWER
 SWITCH, PHOTO-LAB ETC. PLEASE VERIFY ALL LOCATIONS.
 PLEASE INDICATE THE MAXIMUM OVER RIDE TIMES, AND TIMES
 FOR ALL DEVICES. THE PLANS DO CONTAIN SOME NOTES WHICH
 STATE 2HRS HOWEVER NOT FOR ALL.
 PLEASE SEE OUTSIDE LIGHTING IS REQUIRED TO BE ON AN
 ASTRONOMICAL TIME CLOCK WITH CONTROLS TO SHUT LIGHTING
 OFF WHEN SUFFICIENT DAY LIGHT IS PRESENT.
 PLEASE SEE 13-415.1.ABC.3 FOR TANDEM WIRING. PLEASE SEE
 THE LIGHTING FIXTURE LEGEND DOES NOT CORRELATE WITH THE
 ENERGY CALCULATIONS SUBMITTED. PLEASE ALSO SEE THE
 TOTAL WATTAGE AND MAXIMUM LIGHTING POWER DENSITIES AS
 SHOWN CAN NOT BE VERIFIED. PLEASE SEE THAT THE LIGHTING
 ENERGY CALCULATIONS DO NOT INDICATE THE EXTERNAL AND
 EXTERIOR LIGHTING AS SHOWN ON PLANS.
 PLEASE SEE THAT THE ENERGY CALCULATIONS SUBMITTED
 INDICATES *MANUAL ON/OFF* FOR ALL LIGHTING? PLEASE SEE
 THAT THIS IS NOT POSSIBLE WHEN THE LIGHTING IS
 AUTOMATED.
 PLEASE SEE THE SHEET #3 NEEDS TO CONTAIN THE
 INFORMATION AS NEEDED FOR PRINTED INFORMATION FOR THE
 DESIGNER OF RECORD, SIGNED, DATED AND SEAL.PLEASE BE
 SURE ALL TO SEE 13-103.1.1.1
  
 6) NOTE:PLEASE SEE THE RESPONSE TO THIS COMMENT
 MENTIONS TO SEE SHEETS E1.1 AND E2.1A HOWEVER PLEASE
 CLARIFY AND SHOW AS NOTED ON PREVIOUS REVIEW WHERE
 THESE ARE FIGURED INTO THE LOAD CALCULATIONS PER NEC
 SECTIONS AS GIVEN.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING SHOW WINDOW/DISPLAY WINDOW AREAS
 WHICH WILL REQUIRE RECEPTACLES LOCATED ABOVE THE WINDOW
 AREAS AND PORTIONS THEREOF.PLEASE SEE THE LOADS FOR
 THE SHOW WINDOWS SHALL COMPLY WITH 220.43A FOR FEEDER
 CALCULATIONS. THE CALCULATION OF 200 VOLT-AMPERES FOR
 EACH LINEAR FOOT OF A SHOW WINDOW IS REQUIRED TO
 DETERMINE THE FEEDER LOAD. SEE THE COMMENTARY FOLLOWING
 220.14(G) FOR LOAD CALCULATIONS FOR BRANCH CIRCUITS IN
 SHOW WINDOWS.
 AS NO LOAD CALCULATIONS WERE SUBMITTED, REVIEW OF THIS
 FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME.
  
 7) NOTE:PLEASE SEE THE PREVIOUS NOTE REQUESTED A
 SIGNED, DATED, SEALED AND NOTARIZED LETTER FROM THE
 DESIGNER O RECORD FOR SIGNATURE. PLEASE SEE A LETTER
 WAS SUBMITTED HOWEVER PLEASE SEE THIS LETTER IS NOT
 ORIGINAL, AND IT WAS NOT SEALED.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS APPEAR TO BE SIGNED WITH INITIALS, IF
 THIS IS INDEED THE LEGAL SIGNATURE PLEASE SUBMIT A
 SIGNED, DATED AND SEALED NOTARIZED LETTER. FS 471.025
 THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR ANY
 FUTURE REFERENCE.
 PLEASE ALSO BE SURE THE LETTER IS ORIGINAL AND IS
 PROPERLY NOTARIZED PER FS 117.05.
  
 8) NOTE: PLEASE SEE NO INFORMATION WAS SUBMITTED FOR
 THE MINIMUM COMPLIANCE FOR ADA PER FBC AS PREVIOUSLY
 STATED. RESPONSE MENTIONS THIS WILL BE COMPLIED WITH,
 HOWEVER COULD NOT LOCATE THIS AND RESPONSE IS UNCLEAR.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT PLANS MENTIONS FIRE ALARM SYSTEM AND
 SECURITY ALARM SYSTEM.
 PLEASE KNOW BASED ON THIS BUILDING AND IT BEING
 SPRINKLED AND FIRE ALARM PROTECTED, PLEASE SEE FIRE
 REVIEW COMMENTS WHICH WILL REQUIRED FIRE SPRINKLER
 LAYOUT AND PLEASE SHOW FA DEVICES ON BASED BUILDING
 PLANS. PLEASE KNOW THAT EVEN THOUGH ANY FIRE ALARM AND
 FIRE SPRINKLER WORK WILL BE DONE UNDER A SEPARATE
 PERMIT, THE BASE PLANS ARE REQUIRED TO SHOW
 PROTECTION.
 PLEASE BE SURE ALL DEVICES AS REQUIRED IN FBC
 11-4.28.1, .2 AND .3(4) AS SHOWN WITH MINIMUM LEVELS
 FOR ADA COMPLIANCE.
 FBC 106.1.2, 106.3.5.1.2
  
 9) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE UPS SYSTEM EQUIPMENT.
 110.3, 90.7
  
 10) NOTE: PLEASE DO NOT ATTACH ALL OF THE RESPONSES,
 LETTERS REPORTS, PRODUCT APPROVALS, AND OTHER
 SUPPORTING DOCUMENTS DOWN THE LEFT SIDE OF PLANS. THIS
 SHOULD BE ATTACHED, MADE INTO TWO SEPARATE SETS OF
 SUPPORTING DOCUMENTS. (FOLDERS, SPIRAL BOUND, TABBED
 ETC.
 THESE DOCUMENTS WERE REMOVED FROM ONE SET FOR EASE OF
 REVIEW.
 FBC ADMIN SECTION 106.3
  
 11) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS. THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-20 Cont ID  
Sent By dpalmer Date 2007-03-20 Time 18:30 Rev Time 0.00
Received By dpalmer Date 2007-03-19 Time 19:55 Sent To  
Notes
2007-03-20 18:31:26** UNSAT **
  
 * PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 WILL BE FROM THE ADMINISTRATIVE SECTION OF THE CODE AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE SEE MISSING LICENSE NUMBER FOR THE
 LANDSCAPE FIRM AS LISTED ON THE TITLE BLOCKS FOR *L*
 SHEETS. THIS IS ALSO KNOWN AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
 PLEASE SEE 481.219, FAC 61G1-16.004
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 2) NOTE: PLEASE SEE THE MISSING LICENSE NUMBER FOR THE
 SURVEY FIRM AS REQUIRED PER FS 472.021. 61G17
 ALSO KNOWN AS THE CERTIFICATE OF AUTHORIZATION NUMBER.
  
 PLEASE ALSO SEE THAT THE SIGNATURE MUST BE ORIGINAL AS
 REQUIRED PER FS 472.025
 PLEASE SEE THE PLANS EVEN CONTAIN THE STATEMENT THIS IS
 REQUIRED, HOWEVER PLANS CONTAIN A RAISED SEAL OVER A
 *PHOTO-COPIED SIGNATURE*.
 THIS COMMENT IS REQUIRED WHETHER OR NOT COMMENT IS MADE
 BY OTHER TRADES.
  
 3) NOTE: PLEASE SEE THAT ALL OF THE CODES WHICH PLANS
 ARE UNDER DESIGN AND RECORD SHALL BE STATED ON PLANS AS
 FOLLOWS. PLEASE SEE THAT THERE ARE SEVERAL LOCATIONS
 WHICH CODES FROM OLDER ADOPTED CODES ARE STATED ON
 PLANS. PLEASE ALSO SEE THAT THE PLANS ALSO CONTAIN
 STATEMENTS IN DIFFERENT LOCATIONS FOR THE *STANDARD
 BUILDING *.
 PLEASE KNOW THAT THE STANDARD BUILDING CODE WAS NO
 LONGER IN AFFECT AS OF MARCH 1ST, 2002 WHEN THE STATE
 OF FLORIDA ADOPTED THE 2001 FBC.
 PLEASE KNOW THAT AS OF DECEMBER 8TH, 2006 THE FOLLOWING
 CODE(S) WERE ADOPTED. PLEASE LIST THE FOLLOWING AT A
 MINIMUM FOR THIS REVIEWER.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 ** THESE ARE REQUIRED FOR THIS REVIEWER AT A MINIMUM
 AND OTHER CODES WILL BE REQUIRED FOR OTHER TRADES.
  
 4) NOTE: ALL SIGNS, FIRE ALARM, FIRE SPRINKLER,
 BURGLAR/SECURITY PERMITS WILL BE UNDER SEPARATE PERMITS
 WITH SEPARATE PLANS AND PERMIT FEES.
  
 5) NOTE: PLEASE SEE THE VALUE SHALL INCLUDE ALL LABOR
 AND MATERIALS EVEN IF ANY EQUIPMENT OR MATERIALS ARE
 OWNER SUPPLIED.PLEASE SEE THE TOTAL VALUE IS TO
 INCLUDE ALL LIGHTING, EQUIPMENT, LOW VOLTAGE ETC. THIS
 WILL BE VERIFIED FOR BASE BUILDING AND BASE PME FROM
 THE TABLES AS SET-FORTH IN THE FBC.
 FBC ADMIN SECTION 108.3
  
 6) NOTE: PLEASE SEE THAT PLANS E0.1 AND E0.1A INDICATE
 TWO DIFFERENT TYPES OF SITE LIGHTING POLES EVEN FOR THE
 SAME SYMBOL. EACH OF THESE SHEETS ARE DONE BY A
 DIFFERENT DESIGNER. PLEASE CORRELATE.
 PLEASE SEE ONE SHEET WHICH MENTIONS WIND LOAD RATINGS
 TO BE 150MPH AND BELOW. IT CAN BE UNDERSTOOD IF THIS
 STATEMENT SAID 150 OR ABOVE, HOWEVER HOW COULD THIS BE
 BELOW?
 PLEASE SEE THE NEXT LEVEL DOWN STATES 120MPH AND BELOW
 AND SO ON. PLEASE KNOW THAT ALL LIGHTING SHALL MEET
 THIS AREA FOR WIND LOADSAT 140MPH.
 PLEASE SUBMIT THE ENGINEERING ON POLES WITH LIGHTING
 FIXTURES WHICH INDICATES THE EFFECTIVE PROJECTED AREA
 OF FIXTURES ETC. THE ACTUAL CALCULATIONS WILL BE
 REVIEWED BY THE BUILDING REVIEWER ONCE SUBMITTED.
 PLEASE SEE THAT THE SITE PLANS INDICATE LIGHTING POLES
 LOCATED OFF SITE AND NOT ON THIS PROPERTY/LEGAL
 ADDRESS. PLEASE KNOW THAT THESE WILL BE REQUIRED UNDER
 A SEPARATE PERMIT AND MAY NOT BE INCLUDED ON THESE
 PLANS.
  
 7) NOTE: PLEASE SEE THE ADDRESS FOR THIS PROJECT IS
 9921 OKEECHOBEE BLVD. PLEASE INCLUDE THIS INFORMATION
 AS REQUIRED ON TITLE BLOCKS.
 FAC 61G1-16.004, FAC 61G15-23.002
  
 8) NOTE: PLEASE SEE THAT A VOLTAGE DROP SUMMARY WAS
 SUBMITTED FOR PANELS AND SOME ITEMS HOWEVER NOT
 SUBMITTED FOR SITE LIGHTING AND OTHER WORST CASE
 SCENARIOS PER FBC 13-413.1ABC.1
  
 9) NOTE: PLEASE SEE THE LOCATION OF THE MAIN SERVICE
 MEANS OF DISCONNECT IS NOT APPROVED AT THIS TIME PER
 THIS AHJ.
 PLEASE SEE THAT THE LOCATION SHALL BE READILY
 ACCESSIBLE AT THE NEAREST POINT OF ENTRANCE INTO THE
 BUILDING IF THE MAIN IS GOING TO BE LOCATED INSIDE THE
 BUILDING. AS SHOWN ON PLANS, THIS MAIN IS ONLY OBTAINED
 IN THE CASE OF AN EMERGENCY BY FIRE DEPARTMENT
 PERSONNEL BY TRAVERSING THROUGH AT LEAST FOUR LOCKED
 DOORS AND A SUBSTANTIAL NOT RATED PATH OF TRAVEL INTO
 THE BUILDING.
 PLEASE KNOW THAT THIS HAS BEEN GONE OVER WITH THE FIRE
 MARSHAL CHIEF AND LOCATION IS ALSO NOT ACCEPTED. **
 PLEASE CALL TO GO OVER OTHER LOCALS IF NEED BE. (LOCATE
 MAIN OUTSIDE, DOOR FROM OUTSIDE INTO THE MAIN
 ELECTRICAL FIRE RATED (1HR MINIMUM) ROOM? ETC) 230.70,
 230.71, 90.4 NEC.
 FBC ADMIN SECTION 104.6
  
 10) NOTE: PLEASE SEE PLANS APPEAR TO INDICATE SOME SORT
 OF *OUTLET* TAPPED FROM THE WATER HEATER SHOWN ON
 PLANS? PLEASE CLARIFY THIS.
 FBC 106.1.2.
  
 11) NOTE: PLEASE KNOW THAT ANY (LOCK ON/LOCK OFF
 DEVICES WHICH ARE BEING INSTALLED ONLY IN THE ATTEMPT
 TO BE USED AS THE DISCONNECTING MEANS OF EQUIPMENT OR
 APPLIANCES SHALL HAVE THE DEVICE PERMANENTLY AFFIXED TO
 BREAKER SO THAT THE DEVICE CAN NOT BE READILY REMOVED
 UNLESS THE BREAKER IS REMOVED.
 PLEASE KNOW IF NONE OF THE DEVICES AS NOTED ON PLANS
 ARE FOR THIS PURPOSE AND ONLY BEING USED FOR LOCKING ON
 THE CIRCUITS THEN PLEASE STATE DEVICE(S).
 PLEASE KNOW THAT A NOTE WILL BE REQUIRED ON PLANS IN
 ADDITION TO THE *LOCK-OFF* NOTE WHICH STATES THAT THE
 DEVICE MUST BE AN INTEGRAL PART OF THE BREAKER OR WORDS
 TO THAT AFFECT.
 110.3, 90.4.
  
 12) NOTE: PLEASE SEE 2004 FBC W/2006 REVISIONS FOR
 CHAPTER 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.PLEASE SEE
 SOME LOCATIONS WHICH DO NOT INDICATE ANY LIGHTING
 CONTROLS UNDER AN AUTOMATED MEANS. PLEASE SEE THAT
 THESE DEVICES NEED TO BE SHOWN AS SOME OF THE DEVICES
 SHOWN SEEM TO BE NORMAL CONTROL SWITCHES AND SOME AREAS
 DO NOT SEEM TO INDICATE OCCUPANCY TYPE DEVICES. PLEASE
 SEE THE COOLER, FREEZER, DRIVE THRU SWITCH, TOWER
 SWITCH, PHOTO-LAB ETC. PLEASE VERIFY ALL LOCATIONS.
 PLEASE INDICATE THE MAXIMUM OVER RIDE TIMES, AND TIMES
 FOR ALL DEVICES. THE PLANS DO CONTAIN SOME NOTES WHICH
 STATE 2HRS HOWEVER NOT FOR ALL.
 PLEASE SEE OUTSIDE LIGHTING IS REQUIRED TO BE ON AN
 ASTRONOMICAL TIME CLOCK WITH CONTROLS TO SHUT LIGHTING
 OFF WHEN SUFFICIENT DAY LIGHT IS PRESENT.
 PLEASE SEE 13-415.1.ABC.3 FOR TANDEM WIRING. PLEASE SEE
 THE LIGHTING FIXTURE LEGEND DOES NOT CORRELATE WITH THE
 ENERGY CALCULATIONS SUBMITTED. PLEASE ALSO SEE THE
 TOTAL WATTAGE AND MAXIMUM LIGHTING POWER DENSITIES AS
 SHOWN CAN NOT BE VERIFIED. PLEASE SEE THAT THE LIGHTING
 ENERGY CALCULATIONS DO NOT INDICATE THE EXTERNAL AND
 EXTERIOR LIGHTING AS SHOWN ON PLANS.
 PLEASE SEE THAT THE ENERGY CALCULATIONS SUBMITTED
 INDICATES *MANUAL ON/OFF* FOR ALL LIGHTING? PLEASE SEE
 THAT THIS IS NOT POSSIBLE WHEN THE LIGHTING IS
 AUTOMATED.
 PLEASE SEE THE SHEET #3 NEEDS TO CONTAIN THE
 INFORMATION AS NEEDED FOR PRINTED INFORMATION FOR THE
 DESIGNER OF RECORD, SIGNED, DATED AND SEAL.PLEASE BE
 SURE ALL TO SEE 13-103.1.1.1
  
 13) NOTE: PLEASE SEE SOME OF THE DEVICES AS NOTED FOR
 OCCUPANCY DEVICES ARE ONLY 180 DEGREE DEVICES, WHICH
 WHEN AN OCCUPANT IS LOCATED IN SOME AREAS ON THE PLANS
 THIS DEVICE AND THE DIRECTION AS NOTED WOULD NOT PICK
 UP ON THE OCCUPANT AND THERE FORE TURNING LIGHTING OFF
 AND MAY CREATE A HAZARD.
 PLEASE SEE SOME REDLINED AREAS ON PLANS WHICH ARE OF
 CONCERN. IF THESE DEVICES ARE COMBO DEVICES WHICH
 PROVIDE ULTRASONIC SENSING THEN THIS MAY NOT BE AN
 ISSUE. PLEASE VERIFY ALL LOCATIONS AND TYPES OF DEVICES
 FOR FULL COVERAGE.
 LS 101 7.8, 7.9
  
 14) NOTE: PLEASE SEE MISSING SHOW WINDOW/DISPLAY WINDOW
 AREAS WHICH WILL REQUIRE RECEPTACLES LOCATED ABOVE THE
 WINDOW AREAS AND PORTIONS THEREOF.PLEASE SEE THE
 LOADS FOR THE SHOW WINDOWS SHALL COMPLY WITH 220.43A
 FOR FEEDER CALCULATIONS. THE CALCULATION OF 200
 VOLT-AMPERES FOR EACH LINEAR FOOT OF A SHOW WINDOW IS
 REQUIRED TO DETERMINE THE FEEDER LOAD. SEE THE
 COMMENTARY FOLLOWING 220.14(G) FOR LOAD CALCULATIONS
 FOR BRANCH CIRCUITS IN SHOW WINDOWS.
 AS NO LOAD CALCULATIONS WERE SUBMITTED, REVIEW OF THIS
 FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS TIME.
  
 15) NOTE: PLEASE SEE MISSING SIGN CIRCUIT ON PLANS AND
 PANEL SCHEDULE FOR THE MINIMUM LOADS AS INDICATED IN
 THE NEC. THIS CIRCUIT IS TO BE LOCATED AT A MINIMUM AT
 THE LOCATION OF THE FRONT ENTRANCE AS REQUIRED PER
 600.5.
  
 16) NOTE: PLEASE SEE PLANS APPEAR TO BE SIGNED WITH
 INITIALS, IF THIS IS INDEED THE LEGAL SIGNATURE PLEASE
 SUBMIT A SIGNED, DATED AND SEALED NOTARIZED LETTER. FS
 471.025
 THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR ANY
 FUTURE REFERENCE.
 PLEASE ALSO BE SURE THE LETTER IS ORIGINAL AND IS
 PROPERLY NOTARIZED PER FS 117.05.
  
 17) NOTE: PLEASE SEE THAT PLANS MENTIONS FIRE ALARM
 SYSTEM AND SECURITY ALARM SYSTEM.
 PLEASE KNOW BASED ON THIS BUILDING AND IT BEING
 SPRINKLED AND FIRE ALARM PROTECTED, PLEASE SEE FIRE
 REVIEW COMMENTS WHICH WILL REQUIRED FIRE SPRINKLER
 LAYOUT AND PLEASE SHOW FA DEVICES ON BASED BUILDING
 PLANS. PLEASE KNOW THAT EVEN THOUGH ANY FIRE ALARM AND
 FIRE SPRINKLER WORK WILL BE DONE UNDER A SEPARATE
 PERMIT, THE BASE PLANS ARE REQUIRED TO SHOW
 PROTECTION.
 PLEASE BE SURE ALL DEVICES AS REQUIRED IN FBC
 11-4.28.1, .2 AND .3(4) AS SHOWN WITH MINIMUM LEVELS
 FOR ADA COMPLIANCE.
 FBC 106.1.2, 106.3.5.1.2
  
 18) NOTE: PLEASE SEE AS NOTED ABOVE FOR CODES; PLEASE
 SEE THAT THE LOAD CALCULATIONS INDICATE SECTIONS OF THE
 CODE WHICH ARE FROM PREVIOUS CODES NO LONGER IN
 EFFECT.
 220.11, 220.13.
  
 19) NOTE: PLEASE CLARIFY AND SHOW THE BRANCH CIRCUITS
 CONDUCTOR SIZES FOR ALL. CAN BE DONE IN A TYPICAL
 DIAGRAM IF THIS IS INDEED THAT CASE, HOWEVER PLEASE SEE
 AREAS WITH VOLTAGE DROP WHICH MAY BE AFFECTED TO SHOW A
 LARGER CONDUCTOR ON A BRANCH CIRCUIT WITH SMALLER OCP.
 240.4, 310.16
  
 20) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE UPS SYSTEM EQUIPMENT.
 110.3, 90.7
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-20 07:02:062007-03-20 07:02:06
 REVIEW IN PROGRESS
2007-03-19 20:08:582007-03-19 20:08:58
 IN ELEC FOR REVIEW, NOTES TO FOLLOW ONCE REVIEW IS
 COMPLETE.

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2007-11-09 Cont ID  
Sent By rchokshi Date 2007-11-09 Time 13:50 Rev Time 0.00
Received By rchokshi Date 2007-11-09 Time 13:45 Sent To  
Notes
2007-11-09 13:50:13PASSED BASED ON THE FOLLOWING BASES:
  
 1.RECEIVED STORM WATER APPROVAL E-MAIL FROM DANIEL
 ROBERAGE ON 10/19/07.
  
 2. RECEIVED WATER/SEWER APPROVAL E-MAIL FROM MANNY
 GONZALEZ ON 11/08/07.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2007-10-03 Cont ID  
Sent By rchokshi Date 2007-10-03 Time 13:38 Rev Time 0.00
Received By rchokshi Date 2007-10-03 Time 13:13 Sent To  
Notes
2007-10-03 13:38:28****FAILED****
  
 1. CIVIL DWG SHEET 2 OF 10 NOT SEALED & SIGNED
 2. WATER QUALITY CALS MUST BE APPROVED FROM 100045TH
 STREET, ENGINEERING SERVICES DEPT.MR. BRAMLEY
 3. WATER & SEWER MUST BE APPROVED FROM MANNY OR EMRERY
 100045TH STREET. ENGINEERING
  
 ONCE YOU MEET ABOVE INFO, PLEASE RESUBMIT ALL YOU
 SUBMITTED THIS TIME FOR OUR STAMP & APPROVAL.
  
 RASIKCHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2007-07-05 Cont ID  
Sent By rchokshi Date 2007-07-05 Time 14:02 Rev Time 0.00
Received By rchokshi Date 2007-07-05 Time 13:19 Sent To  
Notes
2007-07-05 14:02:11**FAILED** FOR FOLLOWING REASONS:
  
 1. SHEETS 2 OF 9, & 5 OF 9 OF SIMMON & WHITE, HAVE
 RUBBER STAMP PE BY MR. BOLEN AND METAL SEAL BY
 DIFFERENT PE, THAT IS NOT ALLOWED BY FBPE
 2. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI) FROM
 FDEP. YOU NEED TO APPLY AT FDEP FOR NOI.
 3. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTING DETAILS FOR PARKING
 PER CITY CODES ETC.,, MUST MEET PER ADA,,ETC.,YOU CAN
 GET STANDARD NOTES OF CITY OFWPB IN A C.D. FROM 1000
 45TH STREET. ENG DEPT.WE SHOULD HAVE THOSE NOTES ON
 YOUR DRAWINGS.
 4. DO YOU HAVE DUMPSTER? IF YOU DO, PLEASE SHOW ON
 DRAWINGSDUMPSTER & ITS ENCLOSURE DETAILS PER CITY OF
 WPB, &LOCATION ON DWG, LOCATION MUST BE ACCESSIBLE
 FOR PICKUP TRUCK.
 5. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10,
 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST
 FLOOR ELEVATION, MUST MEET MINIMUM REQUIREMENTS, PLEASE
 SHOW IN THE CALCULATION.
 6.PLEASE SHOW STORM WATER QUALITY CALCULATIONS, WHAT
 CRITERIA YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER
 ENTIRE SITE OR2.5"CRITERIA, ETC, ? PLEASE SHOW IN
 THE CALCULATIONS.
 7. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR
 SITE SO, WE CANSEE THE BEST PIPE TO CONNECT WITH THE
 STORM WATER FROM ALL OTHER STORM WATER PIPES.
 8. PLEASE SHOW POLLUTION PREVENTION DETAILS,CLOTHES
 USED FOR SILT ETC., PLANS SHOWING SILT FENCE AROUND THE
 SITE & CATCH BASINS.HEIGHT OF FENCE SHOULD BE HIGH
 ENOUGH PER FDEP TO STOP DUST & PARTICLES.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-03-22 Cont ID  
Sent By rchokshi Date 2007-03-22 Time 13:47 Rev Time 0.00
Received By rchokshi Date 2007-03-22 Time 13:43 Sent To  
Notes
2007-03-22 13:47:11PLEASE SUBMIT THE CIVIL DRAWINGS, STORM WATER
 CALCULATIONS,PERVIOUS, IMPERVIOUS AREA,GEOTECH
 REPORT, , A COPY OF SFWMD PERMIT,ETC. FOR REVIEW.
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-12-03 Cont ID  
Sent By mawillia Date 2007-12-03 Time 17:22 Rev Time 0.00
Received By mawillia Date 2007-12-03 Time 16:45 Sent To  
Notes
2007-12-03 17:14:31*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEETS A2.1, A3.1, E1.1, E1.6,
 LS.1 AND THE (3) FP-3 WERE STAMPED, INITIALED, AND
 DATED.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-10-12 Cont ID  
Sent By mawillia Date 2007-10-12 Time 14:30 Rev Time 0.00
Received By mawillia Date 2007-10-12 Time 13:18 Sent To  
Notes
2007-10-12 13:20:09*****DENIED*****
  
 *THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
 04.ON THE APPROPIATE EXTERIOR ELEVATION ON A2.1,
 DISPLAY THE NUMERICAL ADDREESS ON THE BUILDING TO BE
 VISIBLE FROM OKEECHOBEE BOULEVARD. SHOW ACTUAL
 ADDRESS NUMBER ON APPROPIATE EXTERIOR ELEVATION
  
 05.INTERIOR WALL AND CEILING FINISH MATERIAL SHALL BE
 CLASS A OR CLASS B.PLEASE BE ADVISED THAT THE
 RESPONSE ON SHEET A3.1 REFERS TO NFPA 2001.THIS
 SHOULD BE NFPA 2003
  
 12. THIS STRUCTURE WILL HAVE A FIRE ALARM SYSTEM.
 PROVIDE A LAYOUT OF THE FIRE ALARM SYSTEM SIGNED,
 SEALED, AND DATED.
  
 13.IT IS INDICATED THAT THE STRUCTURE IS TO BE 100%
 SPRINKLERED.PROVIDE A LAYOUT OF THE FIRE SPRINKLER
 SYSTEM SIGNED, SEALED, AND DATED.
  
 *NEW COMMENT
  
 AA.ON SHEET LS.1 UNDER CODE REQUIREMENTS,AMEND NOTE
 TO REFLECT FLORIDA FIRE PREVENTION CODE 2004 EDITION
 AND NFPA 101 - 2003 EDITION.
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH ITEM
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-06-26 Cont ID  
Sent By mawillia Date 2007-06-26 Time 10:26 Rev Time 0.00
Received By mawillia Date 2007-06-25 Time 16:40 Sent To  
Notes
2007-06-25 18:09:38*****DENIED*****
  
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS RESPONSE TO
 THE SAID PROPERTY OR VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 03.ACCUMULATIONS OF COMBUSTIBLE WASTE MATERIAL, DUST,
 AND DEBRIS SHALL BE REMOVED FROM THE SITE AT THE END OF
 EACH SHIFT OR MORE FREQUENTLY AS NECESSARY FOR SAFE
 OPERATION.
  
 04.ON THE APPROPIATE EXTERIOR ELEVATION ON A2.1,
 DISPLAY THE NUMERICAL ADDREESS ON THE BUILDING TO BE
 VISIBLE FROM OKEECHOBEE BOULEVARD.PLEASE NOTE THAT
 THE ADDRESS IS TO VISIBLE EVEN IF SECURITY AND/OR
 HURRICANE SHUTTERS ARE INSTALLED.
  
 05.INTERIOR WALL AND CEILING FINISH MATERIAL SHALL BE
 CLASS A OR CLASS B.BE SPECIFIC
  
 06.INTERIOR FLOOR FINISHSHALL BE CLASS I OR CLASS II.
 BE SPECIFIC
  
 07.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 08.PROVIDE TRAVEL DISTANCE TO EXITS AS IN ACCORDANCE
 7.6.1 OF NFPA 101 I.E. LIFE SAFETY PLAN.
  
 09.ADDITIONAL EXIT SIGNS MAY BE REQUIRED WHEN RACKS,
 SHELVES, AND OTHER EQUIPMENT OBSCURE VISIBILITY OF THE
 NOW PROPOSED EXIT MARKINGS.
  
 10.CHECKOUT STANDS OR ASSOCIATED RAILINGS OR BARRIERS
 SHALL NOT OBSTRUCT EXITS, REQURED AISLES, OR APPROACHES
 THERETO.
  
 11.AISLES LEADING TO EACH EXIT SHALL BE REQUIRED AND
 THE AGGREGATE WIDTH SHALL NOT BE LESS THAN THE REQUIRED
 WIDTH OF THE EXIT.OTHER AISLES SHALL NOT BE LESS THAN
 36" IN CLEAR WIDTH.
  
 12.WILL THIS STRUCTURE HAVE A FIRE ALARM SYSTEM?IF
 SO, PROVIDE A LAYOUT OF THE FIRE ALARM SYSTEM.
  
 13.IT IS INDICATED THAT THE STRUCTURE IS TO BE 100%
 SPRINKLERED.PROVIDE A LAYOUT OF THE FIRE SPRINKLER
 SYSTEM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH ITEM
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2007-06-25 Cont ID  
Sent By mawillia Date 2007-06-25 Time 16:40 Rev Time 0.00
Received By mawillia Date 2007-06-25 Time 16:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-07-11 Cont ID  
Sent By adarroug Date 2008-07-11 Time 11:00 Rev Time 0.00
Received By adarroug Date 2008-07-11 Time 11:00 Sent To B
Notes
2008-07-11 11:01:05TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-04-30 Cont ID  
Sent By adarroug Date 2008-04-30 Time 08:46 Rev Time 0.00
Received By adarroug Date 2008-04-30 Time 08:46 Sent To  
Notes
2008-04-30 08:50:03TO "COMM" BD#20

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-04 Cont ID  
Sent By adarroug Date 2008-01-04 Time 16:21 Rev Time 0.00
Received By adarroug Date 2008-01-04 Time 16:21 Sent To P
Notes
2008-01-04 16:22:28TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-10-30 Cont ID  
Sent By adarroug Date 2007-10-30 Time 12:24 Rev Time 0.00
Received By adarroug Date 2007-10-30 Time 12:24 Sent To  
Notes
2007-11-13 09:54:23TO "COMM" BD#40
2007-10-30 12:25:04WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-22 Cont ID  
Sent By adarroug Date 2007-08-22 Time 09:25 Rev Time 0.00
Received By adarroug Date 2007-08-22 Time 09:25 Sent To  
Notes
2007-09-11 08:44:59TO "COMM" BD#53
2007-08-22 09:25:50WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-21 Cont ID  
Sent By shill Date 2007-05-21 Time 15:12 Rev Time 0.00
Received By shill Date 2007-05-21 Time 15:11 Sent To  
Notes
2007-06-21 14:20:17TO "COMM" BD#40
2007-05-21 15:12:28WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-07-05 Cont ID  
Sent By lmartine Date 2007-04-13 Time   Rev Time 0.00
Received By lmartine Date 2007-03-16 Time 09:31 Sent To  
Notes
2007-03-16 16:53:57TO "COMM" BD#40
2007-03-16 09:31:27WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-05-14 Cont ID  
Sent By rregueir Date 2008-05-14 Time 14:12 Rev Time 0.00
Received By rregueir Date 2008-05-14 Time 14:11 Sent To PC
Notes
2008-05-14 14:12:24REVISED PG A4.5 CONDENSER STANDS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-06-23 Cont ID  
Sent By rregueir Date 2007-06-23 Time 09:43 Rev Time 0.00
Received By rregueir Date 2007-06-23 Time 09:40 Sent To  
Notes
2007-06-23 09:43:15CONDITIONS OF PROVISO HAVE BEEN SATISFIED ON PAGES M2.1
 AND M2.2 REV. 1 DATED 5/8/07.
 PG ME1.1 ALSO REVIEWED.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-04-05 Cont ID  
Sent By rregueir Date 2007-04-05 Time 19:01 Rev Time 0.00
Received By rregueir Date 2007-04-05 Time 17:30 Sent To  
Notes
2007-04-05 19:01:18***************PROVISO****************
 1. AUXILIARY OR SECONDARY DRAIN PROTECTION IS REQUIRED
 PER FBC,M 307.2.3
  
 2. CONDENSATE DRAINS SHALL BE TRAPPED AS REQUIRED BY
 EQUIPMENTMANUFACTURER PER FBC,M 307.2.4. IF AN
 ALTERNATE METHOD IS TO BE USED, SIGNED AND SEALED
 APPROVAL BY THE EQUIPMENT MANUFACTURER'S ENGINEER IS
 REQUIRED.
  
 ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-01-17 Cont ID  
Sent By kstevens Date 2008-01-17 Time 14:37 Rev Time 0.00
Received By kstevens Date 2008-01-17 Time 14:37 Sent To  
Notes
2008-01-17 14:38:24REVISION OK - SHT P2.2 STORM RISER

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-12-05 Cont ID  
Sent By kstevens Date 2007-12-05 Time 10:50 Rev Time 0.00
Received By kstevens Date 2007-12-05 Time 10:50 Sent To  
Notes
2007-12-05 10:51:41 
  
  
 PASSED/PROVISO'S:
  
 1. ALL LAV FAUCETS SHALL COMPLY WITH 11-4.19.5.
  
 2. THE EMPLOYEE SINK FAUCET SHALL COMPLY WITH SECTION
 11-4.24.7.
  
 3. THE EMPLOYEE SINK SHALL COMPLY WITH SECTION
 11-4.24.4.
  
 4. AN RPZV BACKFLOW IS REQUIRED ON THE WATER
 SERVICE.
  
 5. SUBMIT A STORM RISER DIAGRAM FOR THE ROOF DRAINS
 PIPING FOR ROOF DRAINS AT COL. LINE 3 & COL. LINE 4.
 SHOW ALL PIPE SIZES AND INDICATE SQUARE FOOTAGE BEING
 DRAINED. SECTION 106.3.5.1.3(7)(13). (SUBMIT PRIOR TO
 FIRST ROUGH INSPECTION OF U/G STORM).
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-10-12 Cont ID  
Sent By kstevens Date 2007-10-12 Time 08:30 Rev Time 0.00
Received By kstevens Date 2007-10-12 Time 08:30 Sent To  
Notes
2007-10-12 08:48:02DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SUBMIT A STORM RISER DIAGRAM FOR THE ROOF DRAINS
 PIPING FOR ROOF DRAINS AT COL. LINE 3 & COL. LINE 4.
 SHOW ALL PIPE SIZES AND INDICATE SQUARE FOOTAGE BEING
 DRAINED. SECTION 106.3.5.1.3(7)(13).
  
 2. SEE PROVISO'S FROM REVIEW DATED 7-11-7. PLEASE SHOW
 COMPLIANCE FOR ALL ITEMS IN PROVISO.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-12-05 Cont ID  
Sent By kstevens Date 2007-07-11 Time 15:01 Rev Time 0.00
Received By kstevens Date 2007-07-11 Time 14:59 Sent To  
Notes
2007-07-11 15:05:00 
  
  
 PASSED/PROVISO
  
 ALL LAV FAUCETS SHALL COMPLY WITH 11-4.19.5
 THE EMPLOYEE SINK FAUCET SHALL COMPLY WITH SECTION
 11-4.24.7
 THE EMPLOYEE SINK SHALL COMPLY WITH SECTION 11-4.24.4
 AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE
  
  
 *********REVIEW STATUS CHANGED FROM PASSED/PROVISO TO
 FAILED BECAUSE OF PLAN DEVELOPMENT CAUSED PLANS TO FAIL
 REVIEW 10-12-07
  
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-06 Cont ID  
Sent By kstevens Date 2007-04-06 Time 17:30 Rev Time 0.00
Received By kstevens Date 2007-04-06 Time 17:30 Sent To  
Notes
2007-04-06 17:45:48DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT A1.1 ROOM FINISH SCHEDULE. SUBMIT MANUF.
 SPECIFICATIONS SHEETS FOR THE FIBERGLASS POLYESTER
 PANELS. PLANELS SHALL COMPLY WITH THE REQUIREMENTS TO
 BE "SMOOTH, HARD, NONABSORBENT" MATERIALS AS REQUIRED
 IN SECTION 1210.2.
  
 2. SHT A1.3 ROOF DRAINAGE CALCULATIONS INDICATE 4 6"
 ROOF DRAINS AND 3 8"X24" OVERFLOW SCUPPERS. SHT P2.2
 ROOF LEADER RISER SHOWS A 8"X16" PRIMARY SCUPPER AND
 8"X16" OVERFLOW SCUPPERS. PLEASE CORRELATE ROOF
 DRAINAGE INFORMATION. TABLE 1106.3 & SECTION 106.1.1.
  
 3. SHT A4.2 SHOW COMPLIANCE FOR THE FOLLOWING:
 A. 11-4.18.4 FLUSH CONTROLS
 B. 11-4.19.5 FAUCETS
  
 4. SUBMIT A DETAIL FOR THE EMPLOYEE ROOM SINK. SHOW
 COMPLIANCE WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
  
 5. SHTS P1.1 & P2.2 ITEM 10. ALL INDIRECT WASTE SHALL
 BE DRAINED TO EITHER A FLOOR SINK OR A HUB DRAIN. A
 FLOOR DRAIN IS NOT AN APPROVED INDIRECT WASTE RECEPTOR.
 SECTIONS 802.3 & 802.3.2.
  
 6. SHT P2.1 DETAIL #3 WATER HEATER DETAIL. DIELECTRIC
 UNIION ARE NOT APPROVED FOR USE IN THE WATER SYSTEM.
 DIELECTRIC COUPLINGS ARE APPROVED. PLEASE CHANGE
 REFERENCE.
  
 7. SHT P2.1 DETAIL 1 AND SHT P2.2 DOMESTIC WATER RISER
 DIAGRAM. THE WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURES, IN AN "EFFECTIVE RANGE", NOT IN THE
 CEILING AS SHOWN. PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
  
 8. ALL PLUMBING SHEETS. THE SIGNATURE OF THE ENGINEER
 SIGNING & SEALING THE DOCUMENTS IS REQUIRED. IT APPEARS
 THAT INITIALS ARE USED. IF INDEED THIS IS THE LEGAL
 SIGNATURE OF THE ENGINEER OF RECORD, THEN A SIGNED,
 SEALED, NOTORIZED LETTER INDICATING THE LEGAL SIGNATURE
 WILL BE SUBMITTED FOR OUR FILES. FAC 61G15-23.002(2)
 AND FS 471.025.
  
 9. AN RPZV BACKFLOW IS REQUIRED ON THE WATER SERVICE TO
 THE BUILDING. THIS SHALL BE AS CLOSE TO THE METER AS
 POSSIBLE AND ON PRIVATE PROPERTY. PLEASE INDICATE ON
 THE PLANS. SECTION 608.13.2.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2007-09-25 Cont ID  
Sent By jroach Date 2007-09-25 Time 20:33 Rev Time 0.00
Received By jroach Date 2007-09-25 Time 20:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-06-18 Cont ID  
Sent By jroach Date 2007-06-18 Time 18:55 Rev Time 0.00
Received By jroach Date 2007-06-18 Time 18:55 Sent To I
Notes
2007-06-18 19:03:25***FAILED***
  
 1) IN ADDITION TO STRIPING ON THE SITE PLAN, REGULAR
 AND HANDICAP PARKING STRIPING DETAILS SHALL BE
 PROVIDED, INDICATING DIMENSIONS OF STRIPING, COLOR,
 ETC.
  
 2) STRIPING SHALL BE SHOWN ON THE SITE PLAN FOR THE SIX
 (6) PARELLEL PARKING SPACES THAT ARE TO BE LOCATED EAST
 OF THE BY-PASS LANE.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-26 Cont ID  
Sent By adavila Date 2007-03-26 Time 08:48 Rev Time 0.00
Received By adavila Date 2007-03-23 Time 11:28 Sent To  
Notes
2007-03-23 11:34:07PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.SATELLITE DISH DETAILS MEETING SECTION 94-304(F)(2)
 OF THE ZONING AND LAND DEVELOPMENT REGULATIONS SHALL BE
 PROVIDED.
  
 2.REGULAR PARKING AND HANDICAP PARKING STALL DETAILS
 SHALL BE PROVIDED.
 A.PLEASE NOTE THAT HANDICAP SYMBOL SHALL FACE RIGHT.
 B.HANDICAP SYMBOL SHALL BE TWO (2) FEET FROM THE OPEN
 END OF THE PARKING SPACE.
 C.HANDICAP SYMBOL SHALL BE 3 FEET OR 5 FEET IN HEIGHT
 AND PAINTED IN WHITE.
 D.HANDICAP PARKING SPACES SHALL BE OUTLINED IN BLUE.
  
 3.PLEASE NOTE THAT A SEPARATE PERMIT SHALL BE
 PROVIDED FOR ALL SIGNS (TEMPORARY, WALL MOUNTED, FREE
 STANDING, ETC.).
  
 4.PLEASE NOTE THAT FOOTERS SHALL BE IN PLACED PRIOR
 TO SITE PLAN APPROVAL EXPIRATION.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR JOHN
 ROACH, SENIOR PLANNER, AT 822-1435.