Plan Review Details - Permit 07030489
Plan Review Stops For Permit 07030489
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-05-04 Cont ID  
Sent By shill Date 2007-05-04 Time 16:14 Rev Time 0.00
Received By shill Date 2007-05-04 Time 16:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-04-18 Cont ID  
Sent By shill Date 2007-04-18 Time 16:06 Rev Time 0.00
Received By shill Date 2007-04-18 Time 16:06 Sent To  
Notes
2007-04-18 16:15:02****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)THE SHUTTER PRODUCT APPROVALS ARE ILLEGIBLE.
  
 2.)I WAS UNABLE TO REVIEW THE SHUTTER INSTALLATION
 SCHEDULE AS I COULD NOT READ THE INFORMATION ON THE
 PRODUCT APPROVAL.
  
 3.)INDICATE WHICH MULLION PRODUCT YOU ARE USING
 (MULLION LOAD CHART).
  
 4.)YOUR APPLICATION STATES THAT YOU ARE GOING TO
 STUCCO THE EXTERIOR.WHAT IS THE SUBSTRATE?PROVIDE A
 DETAIL IF NECESSARY.
  
 THE RESPONSE LETTER ADDRESSES THE QUESTION.ALL
 RESPONSES SHOULD BE INCORPORATED INTO THE PLAN. PROVIDE
 A DETAIL OR SPECIFICATION, INCLUDING SHEATHING
 NAILING.
  
 5.)THE PLANS STATE THAT DESIGN CRITERIA IS FBC 1605,
 PLEASE CLARIFY WHAT LOAD COMBINATIONS ARE USED IN THIS
 PROJECT.ALSO REFERS TO 1606, INCORRECT CODE
 REFERENCE.
  
 6.)IT IS NOT CLEAR WHY AN ENGINEER HAS STAMPED THE
 PRODUCT APPROVALS BUT DID NOT DRAW THE PLAN.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-03-31 Cont ID  
Sent By shill Date 2007-03-31 Time 11:25 Rev Time 0.00
Received By shill Date 2007-03-31 Time 11:25 Sent To  
Notes
2007-03-31 11:45:18****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PRODUCT APPROVALS ARE FOR INSWING DOORS, OUTSWING
 SHOWN ON THE PLAN.
  
 2.)SEE ATTACHED SHUTTER INSTALLATION SCHEDULE. EITHER
 COMPLETE THIS FORM OR PROVIDE ALL INFORMATION REQUIRED
 TO DETERMINE CODE COMPLIANCE IN ANOTHER FORMAT.
  
 3.)MULLION PRODUCT APPROVAL REQUIRED.
  
 4.)YOUR APPLICATION STATES THAT YOU ARE GOING TO
 STUCCO THE EXTERIOR.WHAT IS THE SUBSTRATE?PROVIDE A
 DETAIL IF NECESSARY.
  
 5.)THE PLANS STATE THAT DESIGN CRITERIA IS 1606.2,
 INCORRECT CODE REFERENCE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-14 Cont ID  
Sent By kconrad Date 2007-03-14 Time 18:21 Rev Time 0.00
Received By kconrad Date 2007-03-14 Time 18:21 Sent To I
Notes
2007-03-14 18:24:03MET WITH HOMEOWNER AND ADVISED HIM THAT HE WILL NEED TO
 SUBMIT PRODUCT APPROVALS FOR NEW WINDOWS AND DOORS /
 SHUTTERS. THE STUCCO PERMIT IS DENIED UNTIL THE WINDOWS
 AND DOORS ARE PERMITTED AND INSPECTED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-26 Cont ID  
Sent By adarroug Date 2007-04-26 Time 16:09 Rev Time 0.00
Received By adarroug Date 2007-04-26 Time 16:09 Sent To B
Notes
2007-04-26 16:13:12TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-17 Cont ID  
Sent By adarroug Date 2007-04-17 Time 14:31 Rev Time 0.00
Received By adarroug Date 2007-04-17 Time 14:31 Sent To B
Notes
2007-04-17 14:32:13TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-31 Cont ID  
Sent By shill Date 2007-03-31 Time 11:48 Rev Time 0.00
Received By shill Date 2007-03-25 Time 12:42 Sent To  
Notes
2007-03-25 12:42:46TO "MISC" BOX#1--1ST REV