Plan Review Details - Permit 07030460
Plan Review Stops For Permit 07030460
Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-05-08 Cont ID  
Sent By lursu Date 2007-05-08 Time 08:56 Rev Time 0.00
Received By lursu Date 2007-05-08 Time 08:56 Sent To  
Notes
2007-05-08 09:01:30THE UNITY OF TITLE WAS RECEIVED BY THIS DEPARTMENT. FOR
 BUILDING 3 A NEW SITE ADDRESS WILL BEISSUED AS 5830 N
 FLAGLER DR .THE APARTMENTUNITS INSIDE THE BUILDING
 WILL RECEIVE UNIQUE SITE ADDRESSES CORRESPONDED WITH
 THEIR FLOOR , FOR EXAMPLE APARTMENT 1 ON THE FIRST
 FLOOR WILL HAVE THE ADDRESS AS 5830 N FLAGLER DR # 101
 , APARTMENT 10 ON FLOOR 11 WILL HAVE THE ADDRESS OF
 5830 N FLAGLER DR # 1110 .WILL BE THE OWNER/DEVELOPER
 RESPONSIBILITY TO CREATE THE ADDRESS LIST OF ALL
 APARTMENTS INSIDE BUILDING 3 .THIS LIST MUST BE
 APPROVED BY THE MIS/GIS- ADDRESSING DEPT PRIOR OF
 ISSUING THE CO.
 ON THE REVISED SITE PLANS AND APPLICATION PLEASE
 REFLECT THE NEW SITE ADDRESS FOR BUILDING 3.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-20 Cont ID  
Sent By jwitmer Date 2008-06-20 Time 13:50 Rev Time 10.55
Received By jwitmer Date 2008-06-20 Time 13:50 Sent To  
Notes
2008-06-20 14:04:35 
 FLAGLER BEACH CLUB BUILDING# 3TOWER (15 STORY)&
 PARKING STRUCTURES
  
 BUILDING PLAN REVIEW
  
 PERMIT: 07030460
 ADD: 5818 N FLAGLER DR(HIGH RISE BUILDING# 3) CONT:
 SCOTT GROUP
 TEL: (561)346-9888
 CONTACT NAT HEALY635-6935
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 ARCHITECT: DAVID LAWRENCE
 T: (561)805-5793
 F: (561)805-5795
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2-4) COMPLIED.
  
 5) BUILDING PROVISO: FBC BUILDING 3110.1.2 / CITY OF
 WPB CODE OF ORDINANCES SECTION 94-546. STRUCTURE IS
 LOCATED IN AN "A-5" FLOOD ZONE. A FLOOD ELEVATION
 CERTIFICATE WILL BE REQUIRED. MINIMUM BASE FLOOD
 ELEVATION IS 7'-6".
  
 6) COMPLIED.
  
 7) 2ND REQUEST, .FL S S 713.13NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT.NOTE:
 713.24(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 8) 2ND REQUEST,THRESHOLD INSPECTOR:WPB AMENDMENT
 105.13.6. W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT KEN
 CONRAD MANAGER OF THE SPECIAL INSPECTOR PROGRAM AT
 (561)805-6711 FOR FURTHER INFORMATION BEFORE THE PERMIT
 MAY BE ISSUED.
  
 9-15A) COMPLIED.
  
 15B) INFORMATIONALONLY, NO COMMENT REQUIRED. 15B)
 PLANS INDICATE POOL, DECKS, FENCES, GATES AND OTHER
 SITE AMENITIES THAT WOULD BE COVERED UNDER SEPARATE
 PERMITS ALTHOUGH THERE ARE FEATURES IN THESE PLANS,
 OTHER TRADES MAY NOT COMMENT ON THESE ISSUES SINCE
 THERE ARE NO PERMITS APPLIED FOR AT THIS TIME FOR THESE
 ITEMS.
  
 16-17) COMPLIED.
  
 18A) SHEET A101A, THE SKYLIGHT DRIVE THROUGH PROVIDE
 PRODUCT APPROVAL FOR WIND AND PROVIDE WHAT TYPE SAFETY
 GLAZING WILL BE USED. 2405.2 ALLOWABLE GLAZING
 MATERIALS AND LIMITATIONS. THE RESPONCE INDICATED THIS
 WAS DELETED BUT ON SHEET A101 IS STILL INDICATED ON
 PLANS, PLEASE ADVISE, 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 18B-D) COMPLIED.
  
 18E) SEMI-COMPLIED, RESPONCE INDICATED THAT IN THE DOOR
 SCHEDULE FOUND ON A400 DOOR NUMBERS 9, 13,16,17,18 & 19
 WERE 90 MINUTE DOORS AND FRAMES, THE DOOR SCHEDULE ALSO
 INDICATES THESE DOOR FRAMES ARE TO BE ALUMINUM, PLEASE
 PROVIDE UL OR OTHER RECONIZED AGENCY REPORT. 715.3.1
 NFPA 252 OR UL 10C.
  
 19) SHEET A102
  
 19A)(1) 2ND REQUEST, SEE DETAIL B-3 SHEET A-402, THE
 SLIDING GLASS DOOR TRACK ASSEMBLY AS SHOWN DOES NOT
 MEET FAIR HOUSING GUIDELINES,FOR SECONDARY DOORS
 (SLIDING GLASS DOORS) THE GUIDELINE SPECIFY THAT THE
 THRESHOLDS AT THESE DOORS SHALL BE NO HIGHER THAN ? ?.
 THE GUIDELINES FURTHER STATE THAT CHANGES IN LEVEL AT
 THESE LOCATIONS MUST BE BEVELED WITH A SLOPE NO GREATER
 THAN 1:2.
 19A)(2) FAIR HOUSING DOOR AT CONCRETE LANDINGS THE
 MAXIMUM ALLOWABLE CHANGE IN LEVEL AT EXTERIOR SLIDING
 GLASS DOORS (SECONDARY ENTRANCE) TO BALCONY OR PATIO
 WILL BE 4 INCHES TO THE FINISH DECK.
 NOTE: INCORPORATE THE HEIGHT OF THE HIGH RISE TRACK
 INTO THE DESIGN CRITERIA.
 19A)(3) THE STRUCTURAL PLANS WILL ALSO NEED TO
 CORRELATE THEIR DETAIL SHEETS TO MEET THE REQUIREMENTS
 STATED ABOVE, FAIR HOUSING SECONDARY SLIDING GLASS
 DOORS.
 19A)(4) THE TRACK DETAIL ALSO INDICATES THAT THE TRACK
 IS TO BE SET IN LEVELING GROUT. ALL PRODUCT APPROVALS
 WILL REQUIRE MECHANICAL FASTENING OF TRACK.
 THE RESPONCE INDICATED HOW THEY WOULD MEET THE
 ALTERNATIVE METHODS UNDER THE FAIR HOUSING GUIDELINES,
 WHICH WILL NEED TO BE FILED WITH THE CLERK OF THE COURT
 BEFORE ISSUANCE OF THIS PERMIT.
  
 19B-19C) COMPLIED.
  
 19D) 2ND REQUEST, PLANS FAIL TO IDENTIFY THE WALL TYPES
 THAT SURROUND THE REFUSE SHOOT.707.13.3 REFUSE AND
 LAUNDRY CHUTE ACCESS ROOMS. ACCESS OPENINGS FOR REFUSE
 AND LAUNDRY CHUTES SHALL BE LOCATED IN ROOMS OR
 COMPARTMENTS COMPLETELY ENCLOSED BY CONSTRUCTION THAT
 HAS A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR
 AND OPENINGS INTO THE ACCESS ROOMS SHALL BE PROTECTED
 BY OPENING PROTECTIVES HAVING A FIRE PROTECTION RATING
 OF NOT LESS THAN ? HOUR AND SHALL BE SELF-CLOSING OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE.
  
 A506.2 THE GROUND FLOOR DETAIL (A) WALL TYPE 9/ 800
 PLEASE REVISE TYPO TO 9/801.
  
 19E-19G) COMPLIED.
  
  
 19H) 2ND REQUEST, PLANS INDICATE BETWEEN UNITS 2
 SEPARATE WALLS ONE WITH SOUND PROOFING THE OTHER IS A
 TWO HR RATED WALL. PLEASE PROVIDE AN ASSEMBLY HOW THE
 TWO WALLS WILL BE BUILT?
 A203 & A206 BOTH INDICATE A WALL TYPE 8 BUT THERE IS NO
 WALL DISIGNATION FOR THE SECOND WALL INDICATED ON THE
 PLAN. 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
  
 19I) PROVIDE COMPLIANCE WITH:1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 19J) NO, 2ND REQUEST, PROVIDE COMPLIANCE WITH: 1207.3
 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. NO STC RATING PROVIDED FOR DETAIL 9/A.801.
 THE COMMON AREAS WILL NEED TO SHOW COMPLIANCE, THE
 INDIVIDUAL UNITS WILL BE REVIEWED UNDER THE TENANT
 BUILDOUT, PERMITS WILL BE REQUIRED FOR FLOOR FINISHES
 OF UNITS.
  
 20-24A) COMPLIED.
  
 24B) SEMI-COMPLIED, PLANS STILL INDICATE GRILLS TO BE
 INSTALLED SEE A108, PROVIDE MANUFACTURERS SPEC. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 24C) PROVISO; SHOP DRAWINGS FOR CATWALKS TO BE REVIEWED
 BY DESIGN PROFESSIONAL BEFORE SUBMITION TO THE BUILDING
 DEPARTMENT.
  
 24D-24F) COMPLIED.
  
 24G) A107 THE PENTHOUSE UNITS DO HAVE THEIR OWN MEANS
 OF EGRESS USING THE SPIRAL STAIRS (1009.9.3) THEY ARE
 NOT ALLOWED TO USE THE DOORS BETWEEN UNITS FOR MEANS OF
 EGRESS, 1013.2 EGRESS THROUGH INTERVENING ROOMS.
  
 24H-26B)COMPLIED.
  
 26C) SEMI-COMPLIED) SHEET A201 EGRESS WINDOWS THE
 MINIMUM HEIGHT IS 24 INCHES, THE WORDING IS STILL
 TWENTY-TWO INCHES PLEASE MAKE CORRECTION, 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 26D) COMPLIED.
  
 27) SHEET A201;
  
 27A) 2ND REQUEST , PLANS INDICATE A 3'-4" MINIMUM ENTRY
 BETWWEN THE CABINETRY INTO THE KITCHEN, BUT THE FAIR
 HOUSING NOTES ON SHEET A700 NOTE 5 USABLE KITCHENS
 INDICATES THE MEASUREMENT IS TAKEN FROM THE EDGE OF
 COUNTER TOPSTO THE HANDLES OF APPLIANCES,
 REFRIGARATORS DEPHT MINIMUM IS 30 1/2 INCHES, RANGES 27
 INCHES. PLEASE ADJUST THE PLANS TO HAVE A CLEAR NET
 OPENING OF
 3'-4".
 27B) COMPLIED.
  
 27C) SEMI-COMPLIED, SEE 19A.
  
 28-32A) COMPLIED.
  
 32B) 2ND REQUEST, THE KITCHEN INDICATES A MINIMUM OF
 40" CLEAR BUT THE MEASUREMENT IS TO BE TAKEN FROM THE
 EDGE OF THE COUNTER TOP TO THE HANDLE OF THE 27" DEEP
 RANGE, SEE FAAIR HOUSING NOTE 5 LOCATED ON SHEET A700.
  
 33-41A) COMPLIED.
  
 41B) SEMI-COMPLIED, ATACHMENT DETAIL OF CURBING AS
 SHOWN ON S7.2 INDICATES THE USE OF RFB, PLANS DO NOT
 INDICATE WHO MAKES THIS ITEM? 106.1.2 ADDITIONAL
 INFORMATION.
  
 41C) 2ND REQUESTSHEET A804 PLANS MAKE REFERENCE TO
 THE SFBC, PLEASE MAKE CORRECTION.
  
 41-42) COMPLIED.
  
 43A) SEMI-COMPLIED. PILING, SHEET S-3.02 NOTE 4
 REFERENCES THE 2001 FBC
 43B) S-3.02 NOTE# 10 INDICATES THE USE OF 16 INCH PILE
 WHEREAS S-3.01 & S-3.02 BOTH INDICATE THE USE OF 18
 INCH PILE PLEASE CORRELATE PLANS, 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 44) COMPLIED.
  
 45) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE
 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) OF
 PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 ROOFING REPORT SUBMITTED IS FOR A WOOD DECK SEE A-306
  
 46) COMPLIED.
  
 47) COMPLIED.
  
 8) PLANS ARE TO SHOWCOMPLIANCE WITH:
 403.8 FIRE COMMAND .
 A FIRE COMMAND CENTER COMPLYING WITH SECTION 911 SHALL
 BE PROVIDED IN A LOCATION APPROVED BY THE FIRE
 DEPARTMENT.
  
  
  
 403.10 STANDBY POWER.
 A STANDBY POWER SYSTEM COMPLYING WITH SECTION 2702
 SHALL BE PROVIDED FOR STANDBY POWER LOADS SPECIFIED IN
 SECTION 403.10.2 .
  
 403.10.1 SPECIAL REQUIREMENTS FOR STANDBY POWER
 SYSTEMS.
 IF THE STANDBY SYSTEM IS A GENERATOR SET INSIDE A
 BUILDING, THE SYSTEM SHALL BE LOCATED IN A SEPARATE
 ROOM ENCLOSED WITH 2-HOUR FIRE-RESISTANCE-RATED FIRE
 BARRIER ASSEMBLIES. SYSTEM SUPERVISION WITH MANUAL
 START AND TRANSFER FEATURES SHALL BE PROVIDED AT THE
 FIRE COMMAND CENTER.
  
 403.10.2 STANDBY POWER LOADS.
 THE FOLLOWING ARE CLASSIFIED AS STANDBY POWER LOADS: 1.
 POWER AND LIGHTING FOR THE FIRE COMMAND CENTER REQUIRED
 BY SECTION 403.8 ;
 2.ELECTRICALLY POWERED FIRE PUMPS;
 3.VENTILATION AND AUTOMATIC FIRE DETECTION
 EQUIPMENT FOR SMOKEPROOF ENCLOSURES.
 STANDBY POWER SHALL BE PROVIDED FOR ELEVATORS IN
 ACCORDANCE WITH SECTION 3003 .
  
 403.11 EMERGENCY POWER SYSTEMS.
 AN EMERGENCY POWER SYSTEM COMPLYING WITH SECTION 2702
 SHALL BE PROVIDED FOR EMERGENCY POWER LOADS SPECIFIED
 IN SECTION 403.11.1 .
  
 403.11.1 EMERGENCY POWER LOADS.
 THE FOLLOWING ARE CLASSIFIED AS EMERGENCY POWER LOADS:
  
 1.EXIT SIGNS AND MEANS OF EGRESS ILLUMINATION
 REQUIRED BY CHAPTER 10 ;
 2.ELEVATOR CAR LIGHTING;
 3.EMERGENCY VOICE/ALARM COMMUNICATIONS SYSTEMS; 4.
 AUTOMATIC FIRE DETECTION SYSTEMS; AND
 5.FIRE ALARM SYSTEMS.
  
 403.12 STAIRWAY DOOR OPERATION.
 STAIRWAY DOORS OTHER THAN THE EXIT DISCHARGE DOORS
 SHALL BE PERMITTED TO BE LOCKED FROM
 STAIRWAY SIDE. STAIRWAY DOORS THAT ARE LOCKED FROM THE
 STAIRWAY SIDE SHALL BE CAPABLE OF BEING UNLOCKED
 SIMULTANEOUSLY WITHOUT UNLATCHING UPON A SIGNAL FROM
 THE FIRE COMMAND CENTER.
  
 403.12.1 STAIRWAY COMMUNICATIONS SYSTEM.
 A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS SYSTEM
 CONNECTED TO AN APPROVED CONSTANTLY ATTENDED STATION
 SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH FLOOR IN
 EACH REQUIRED STAIRWAY WHERE THE DOORS TO THE STAIRWAY
 ARE LOCKED.
  
 403.13 SMOKEPROOF EXIT ENCLOSURES.
 EVERY REQUIRED STAIRWAY SERVING FLOORS MORE THAN 75
 FEET (22 860 MM) ABOVE THE LOWEST LEVEL OF FIRE
 DEPARTMENT VEHICLE ACCESS SHALL COMPLY WITH SECTIONS
 909.20 AND 1019.1.8 .
  
 403.14 RESERVED.
  
 **403.15 SMOKE CONTROL SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTION 909.**
 909.16 FIRE-FIGHTER?S SMOKE CONTROL PANEL.
 A FIRE-FIGHTER?S SMOKE CONTROL PANEL FOR FIRE
 DEPARTMENT EMERGENCY RESPONSE PURPOSES ONLY SHALL BE
 PROVIDED AND SHALL INCLUDE MANUAL CONTROL OR OVERRIDE
 OF AUTOMATIC CONTROL FOR MECHANICAL SMOKE CONTROL
 SYSTEMS. THE PANEL SHALL BE LOCATED IN A FIRE COMMAND
 CENTER COMPLYING WITH SECTION 911 IN HIGH-RISE
 BUILDINGS OR BUILDINGS WITH SMOKE PROTECTED ASSEMBLY
 SEATING. IN OTHER BUILDINGS, THE FIRE-FIGHTER?S SMOKE
 CONTROL PANEL SHALL BE INSTALLED IN AN APPROVED
 LOCATION ADJACENT TO THE FIRE ALARM CONTROL PANEL. THE
 FIRE-FIGHTER?S SMOKE CONTROL PANEL SHALL COMPLY WITH
 SECTIONS 909.16.1 THROUGH 909.16.3 .
  
 909.16.1 SMOKE CONTROL SYSTEMS.
 FANS WITHIN THE BUILDING SHALL BE SHOWN ON THE
 FIRE-FIGHTER?S CONTROL PANEL. A CLEAR INDICATION OF THE
 DIRECTION OF AIRFLOW AND THE RELATIONSHIP OF COMPONENTS
 SHALL BE DISPLAYED. STATUS INDICATORS SHALL BE PROVIDED
 FOR ALL SMOKE CONTROL EQUIPMENT, ANNUNCIATED BY FAN AND
 ZONE, AND BY PILOT-LAMP-TYPE INDICATORS AS FOLLOWS:
 1.FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN
 THEIR NORMAL STATUS?WHITE.
 2.FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN
 THEIR OFF OR CLOSED STATUS?RED.
 3.FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN
 THEIR ON OR OPEN STATUS?GREEN.
 4.FANS, DAMPERS AND OTHER OPERATING EQUIPMENT IN A
 FAULT STATUS?YELLOW/AMBER.
  
 909.16.2 SMOKE CONTROL PANEL.
 THE FIRE-FIGHTER?S CONTROL PANEL SHALL PROVIDE CONTROL
 CAPABILITY OVER THE COMPLETE SMOKE-CONTROL SYSTEM
 EQUIPMENT WITHIN THE BUILDING AS FOLLOWS:
 1.ON-AUTO-OFF CONTROL OVER EACH INDIVIDUAL PIECE
 OF OPERATING SMOKE CONTROL EQUIPMENT THAT CAN ALSO BE
 CONTROLLED FROM OTHER SOURCES WITHIN THE BUILDING. THIS
 INCLUDES STAIRWAY PRESSURIZATION FANS; SMOKE EXHAUST
 FANS; SUPPLY, RETURN AND EXHAUST FANS; ELEVATOR SHAFT
 FANS AND OTHER OPERATING EQUIPMENT USED OR INTENDED FOR
 SMOKE CONTROL PURPOSES.
 2.OPEN-AUTO-CLOSE CONTROL OVER INDIVIDUAL DAMPERS
 RELATING TO SMOKE CONTROL AND THAT ARE ALSO CONTROLLED
 FROM OTHER SOURCES WITHIN THE BUILDING.
 3.ON-OFF OR OPEN-CLOSE CONTROL OVER SMOKE CONTROL
 AND OTHER CRITICAL EQUIPMENT ASSOCIATED WITH A FIRE OR
 SMOKE EMERGENCY AND THAT CAN ONLY BE CONTROLLED FROM
 THE FIRE-FIGHTER?S CONTROL PANEL.
  
  
 49)COMPLIED.
  
 50) NEW,PROVIDE INFORMATION ON THE VENTILATION OF THE
 ENCLOSED PARKING GARAGE. 406.4.2 VENTILATION. A
 MECHANICAL VENTILATION SYSTEM SHALL BE PROVIDED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL .
 NOTEFLORIDA ADMINISTRATIVE CODE RULE 9B-3.0472 EVERY
 BUILDING WHICH A PERMIT FOR NEW CONSTRUCTION IS ISSUED
 ON OR AFTER 7-1-08 AND HAVING A FOSSIL -FUEL- BURNING
 HEATER OR APPLIANCE OR AN ATTACHED GARAGE SHALL HAVE AN
 OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN 10
 FEET OF EACH ROOM USED FOR SLEEPING PURPOSES. IN
 CONSTRUCTION ALARMS SHALL RECEIVE THEIR PRIMARY POWER
 FROM
 THE BUILDING WIRING WHEN SUCH WIRING IS SERVED FROM THE
 LOCAL POWER UTUILIY SUCH ALARMS SHALL HAVE BATTERY BACK
 UP. BOMBINATION SMOKE/ CARBON MONOXIDE ALARMS SHALL BE
 LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
  
 51)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST
 BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE INFORMATION.
  
 THIS REVIEW IS MAY HAVE ADDITIONAL COMMENTS AS A RESULT
 OF THE DESIGNERS ANSWERS TO THE PLAN REVIEW OR NEW
 INFORMATION BEING ADDED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 FLAGLER BEACH CLUB TOWER 1ST REVIEW.DOC
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-25 Cont ID  
Sent By jwitmer Date 2007-04-25 Time 15:10 Rev Time 30.00
Received By jwitmer Date 2007-04-19 Time 09:56 Sent To FIRE
Notes
2007-04-19 13:38:19 
 FLAGLER BEACH CLUB BUILDING# 3 ? TOWER (15 STORY)&
 PARKING STRUCTURES
  
 BUILDING PLAN REVIEW
 PERMIT: 07030460
 ADD: 5818 N FLAGLER DR(HIGH RISE BUILDING# 3) CONT:
 SCOTT GROUP
 TEL: (561)###-####
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) ADDRESS ISSUES TO BE ADDRESSED PLEASE SEE LILI URSA
 AT 822-1239.
 THE CITY?S LIST THIS ADDRESS AS 5818 WHERE AS THE PLANS
 INDICATE 5810 N FLAGLER.
 PLEASE CORRECT.
  
 3)DAVID LAWRENCE ARCHITECTURE IS MISSING THEIR
 CERTIFICATE OF AUTHORIZATION.
 481.219 F .S. CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A CORPORATION, OR A
 PARTNERSHIP, OFFERING ARCHITECTURAL SERVICES, SHALL
 INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER.ADD
 THE NUMBER TO EACH SHEET. THIS MAY BE ADDED BY HAND.
  
 4) MISSING ARCHITECTURAL SEAL SHEETS A01.02- A809 IN
 ONE ROLL.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 5) PROJECT IS LOCATED IN AN A-5 FLOOD ZONE. PROVIDE
 FLOOD ZONE ELEVATION CERTIFICATE FOR NEW CONSTRUCTION
 WITH THE BASE FLOOD ELEVATION PLUS AN ADDITIONAL SIX
 INCHES A CITY FLOOD PLAIN REQUIREMENT. THE MINIMUM
 FINISH SLAB ELEVATION OF 7?-6?.
  
 6)FBC 1802.2.1 QUESTIONABLE SOILS,
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT
 SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 7)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 8)WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION
 SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY S. 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT
 HAROLD PISKURA MANAGER OF THE SPECIAL INSPECTOR PROGRAM
 AT (561) 805-6711 FOR FURTHER INFORMATION BEFORE THE
 PERMIT MAY BE ISSUED.
  
 9)W.P.B. AMENDMENT 105.13.4.4 ALL PLANS FOR THE
 BUILDING WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY
 THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 10)FL S. S. 553.71(7) " THRESHOLD BUILDING" MEANING
 ANY BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT
 IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS. 105.13.1 THE
 ENFORCING AGENCY SHALLREQUIRE A SPECIAL INSPECTOR TO
 PERFORM STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING
 PURSUANT TO A STRUCTURALINSPECTION PLAN PREPARED BY
 THE ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE
 OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 11) 109.3.10*IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PREFORMED IN A
 MANNERSO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED
 TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE
 FINAL INSPECTION.
  
  
 12 ) 109.3.10.1 HURRICANE PROTECTION.IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAIL TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
  
 13)SHEETS A01.02- A809 ARE SIGNED BUT NOT SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 14) SHEET A01.01:
 14A) NOTES INDICATE PLANS ARE DESIGNED TO THE 2004 FBC,
 PLEASE UPDATE TO THE 2006 FBC AMENDMENTS.
  
 14B) CODE COMPLIANCE NOTES: INDICATE THE BUILDING TYPE
 TO BE : TYPE 1A SPRINKLED
 ( UNPROTECTED), PLEASE CORRECT,SEE TABLE 601 FOR A
 TYPE 1-A BUILDING ALL STRUCTURAL MEMBERS DO HAVE FIRE-
 RESISTANCE RATINGS SEE FOOTNOTES FOR FIRE SPRINKLED
 BUILDING.
  
 15) SHEETA01.1:
 15A) PLANS INDICATE 5 HANDICAPPED PARKING SPACES UNDER
 THE COVERED PARKING IN THE LOT, THE 15 STORY BUILDING
 ALSO INDICATES 4 PARKING SPACES BUT NONE OF THESE ARE
 DESIGNED AS ACCESSIBLE PARKING SPACES. THE DESIGNER
 HADN?T CONSIDERED :
 11-2.2 EQUIVALENT FACILITATION.
 DEPARTURES FROM PARTICULAR TECHNICAL AND SCOPING
 REQUIREMENTS OF THIS CODE BY THE USE OF OTHER DESIGNS
 AND TECHNOLOGIES ARE PERMITTED WHERE THE ALTERNATIVE
 DESIGNS AND TECHNOLOGIES USED WILL PROVIDE
 SUBSTANTIALLY EQUIVALENT OR GREATER ACCESS TO AND
 USABILITY OF THE FACILITY.
 DEPARTURE FROM THE EXPLICIT TECHNICAL AND SCOPING
 REQUIREMENTS OF THIS CODE FOR ANY ELEMENT VOIDS ANY
 OTHERWISE APPLICABLE PRESUMPTION OF REBUTTABLE EVIDENCE
 THAT THE ELEMENT HAS BEEN CONSTRUCTED OR ALTERED IN
 ACCORDANCE WITH THE MINIMUM ACCESSIBILITY REQUIREMENTS
 OF THE ADA.
  
 15B) PLANS INDICATE POOL, DECKS, FENCES, GATES AND
 OTHER SITE AMENITIES THAT WOULD BE COVERED UNDER
 SEPARATE PERMITS ALTHOUGH THERE ARE FEATURES IN THESE
 PLANS, OTHER TRADES MAY NOT COMMENT ON THESE ISSUES
 SINCE THERE ARE NO PERMITS APPLIED FOR AT THIS TIME FOR
 THESE ITEMS.
  
 15C) PLANS INDICATE OPEN PARKING GARAGE WITH A SECOND
 STORY CREATING A PUTTING GREEN,
 THIS CREATES A MIXED OCCUPANCY REQUIRING OCCUPANCY
 SEPARATION. THE DETAILS OF THE ROOF AND OR AREA DRAINS
 FOUND IN DETAIL ?B? SHEET A803 DO NOT INDICATE ANY FIRE
 STOP FOR HORIZONTAL SEPARATION.712.4.1.1
 FIRE-RESISTANCE-RATED ASSEMBLIES.
 PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN
 APPROVED FIRE-RESISTANCE-RATED ASSEMBLY.
  
 712.4.1.2 THROUGH-PENETRATION FIRE STOP SYSTEM. THROUGH
 PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 THROUGH-PENETRATION FIRE STOP SYSTEM INSTALLED AND
 TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A
 MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH
 (2.49 PA) OF WATER. THE SYSTEM SHALL HAVE AN F RATING
 AND A T RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS
 THAN THE REQUIRED RATING OF THE FLOOR PENETRATED.
  
 SHEET A)1.1:
 15D)DETAIL ON THE EAST SIDE OF THE BUILDING INDICATE
 A POOL DECK STAIRS AND A LOWER DECK OR SIDEWALK WHICH
 LEADS TO THE BEACH AND BOAT DOCKS. PLANS FAIL TO
 PROVIDE VERTICAL ACCESSIBILITY TO THE LOWER WALKWAY
 ELEMENTS NO RAMP IS PROVIDED ONLY STAIRS.
  
 REQUIREMENT2. ACCESSIBLE AND USABLE PUBLIC AND COMMON
 USE AREAS.
  
 SECTION 100.205(C)(1) PROVIDES THAT COVERED MULTIFAMILY
 DWELLINGS WITH A BUILDING ENTRANCE ON AN ACCESSIBLE
 ROUTE SHALL BE DESIGNED IN SUCH A MANNER THAT THE
 PUBLIC AND COMMON USE AREAS ARE READILY ACCESSIBLE TO
 AND USABLE BY HANDICAPPED PERSONS.
  
 GUIDELINE
  
 THE FOLLOWING CHART IDENTIFIES THE PUBLIC AND COMMON
 USE AREAS THAT SHOULD BE MADE ACCESSIBLE, CITES THE
 APPROPRIATE SECTION OF THE ANSI STANDARD, AND DESCRIBES
 THE APPROPRIATE APPLICATION OF THE SPECIFICATIONS,
 INCLUDING MODIFICATIONS TO THE REFERENCED STANDARD.
 FAIR HOUSING 4.3(D).
  
 15E) THE DETAIL A,B & C / A02.0ALL INDICATE A CHANGE
 IN GRADE LESS THAN 21? WHICH WILL REQUIRE 13? TREADS ON
 ALL STAIRS. 1003.5.1. WHERE A CHANGE IN LEVEL MEANS OF
 EGRESS NOT EXCEEDING 21 INCHES (533 MM) IS ACHIEVED BY
 A STAIR, THE MINIMUM TREAD DEPTH OF SUCH STAIR SHALL BE
 13 INCHES (330 MM) AND THE PRESENCE AND LOCATION OF
 EACH STEP SHALL BE READILY APPARENT.
  
 16) SHEET A01.2
 16A) SHEET A01.2- A01.3THE HANDICAPPED LIFT SHOWN ON
 THE PLANS MUST MEET THE
 REQUIREMENTS OF: 11-4.11.2. IF PLATFORM LIFTS
 (WHEELCHAIR LIFTS) ARE USED, THEY SHALL COMPLY WITH
 SECTIONS 11-4.2.4 , 11-4.5 , 11-4.27 , AND ASME A17.1,
 SAFETY CODE FOR ELEVATORS AND ESCALATORS , SECTION XX,
 1990.
 11-4.2.4 CLEAR FLOOR OR GROUND SPACE FOR WHEELCHAIRS.
 11-4.5 GROUND AND FLOOR SURFACES.
 11-4.27 CONTROLS AND OPERATING MECHANISMS.
  
 16B) A01.2 PLANS IDENTIFY THE CHAIRLIFT AS A
 WHEEL-O-VATOR MODEL BC SHROUD OR EQUAL, PLANS ARE TO
 IDENTIFY SPECIFIC MODELS.104.2.1 W.P.B.
 ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL
 BE SPECIFIC AND THE TECHNICAL CODES "SHALL NOT BE CITED
 AS A WHOLE OR IN PART, NOR THETERM "LEGAL" OR ITS
 RQUIVALENT BE USEDAS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
  
 17)SHEET A101
 17A) THE DOORS LOCATED ON EACH SIDE OF THE DRIVE
 THROUGH (SF3 & SF10) DO NOT INDICATE ANY DETECTABLE
 WARNING ON THE SIDEWALK SURFACES.
 11-4.29.5 DETECTABLE WARNINGS AT HAZARDOUS VEHICULAR
 AREAS.
 IF A WALK CROSSES OR ADJOINS A VEHICULAR WAY, AND THE
 WALKING SURFACES ARE NOT SEPARATED BY CURBS, RAILINGS,
 OR OTHER ELEMENTS BETWEEN THE PEDESTRIAN AREAS AND
 VEHICULAR AREAS, THE BOUNDARY BETWEEN THE AREAS SHALL
 BE DEFINED BY A CONTINUOUS DETECTABLE WARNING WHICH IS
 36 INCHES (915 MM) WIDE, COMPLYING WITH SECTION
 11-4.29.2 .
  
 17B) THE GYM DOOR IS MISSING A IDENTIFICATION MARKER.
 ADDITIONAL INFORMATION REQUIRED.
 106.1.2.*
  
 17C) THE TRASH ROOM DOORIS INDICATE AS A ROLL UP DOOR
 PLEASE PROVIDE THE LISTING REPORT PROVIDING THE 1 ? HR
 FIRE RATING AS LISTED IN THE DOOR SCHEDULE.
  
 17D) THE SAUNA ROOM DOOR (6) IS IDENTIFIED WITH A 2?-8?
 DOOR, THIS WILL ONLY PROVIDE A 30?
 OPENING FAIR HOUSING WILL REQUIRE A MINIMUM OF 32?
 CLEAR WIDTH. ANSIA117.1- 404.2.3.
  
 17E) WHEN REFERRING TO THE STOREFRONT DOORS FOUND ON
 SHEET A-101 AND THE DOOR SCHEDULE ON A404, THE DOORS
 ARE NOT REFERENCED IN THE DOOR SCHEDULE? 106.1.2.
 ADDITIONAL INFORMATION REQUIRED.
  
 17F)DOORS SF 7A ARE HORIZONTAL SLIDING DOORS, PLEASE
 PROVIDE PRODUCT APPROVALS CONFORMING TO THE FOLLOWING:
  
 1008.1.3.3 HORIZONTAL SLIDING DOORS.
 IN OTHER THAN GROUP H OCCUPANCIES, HORIZONTAL SLIDING
 DOORS PERMITTED TO BE A COMPONENT OF A MEANS OF EGRESS
 IN ACCORDANCE WITH EXCEPTION 5 TO SECTION 1008.1.2
 SHALL COMPLY WITH ALL OF THE FOLLOWING CRITERIA: 1. THE
 DOORS SHALL BE POWER OPERATED AND SHALL BE CAPABLE OF
 BEING OPERATED MANUALLY IN THE EVENT OF POWER FAILURE.
 2.THE DOORS SHALL BE OPERABLE BY A SIMPLE METHOD
 FROM BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT. 3.
 THE FORCE REQUIRED TO OPERA TE THE DOOR SHALL NOT
 EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND
 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN IT TO THE
 MINIMUM REQUIRED WIDTH.
 4.THE DOOR SHALL BE OPERABLE WITH A FORCE NOT TO
 EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS
 (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR ADJACENT
 TO THE OPERATING DEVICE.
 5.THE DOOR ASSEMBLY SHALL COMPLY WITH THE
 APPLICABLE FIRE PROTECTION RATING AND, WHERE RATED,
 SHALL BE SELF-CLOSING OR AUTOMATIC-CLOSING BY SMOKE
 DETECTION, SHALL BE INSTALLED IN ACCORDANCE WITH NFPA
 80 AND SHALL COMPLY WITH SECTION 715 .
 6.THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED
 STANDBY POWER SUPPLY.
  
 SHEET A101 (17F)
  
 7.THE DOOR ASSEMBLY POWER SUPPLY SHALL BE
 ELECTRICALLY SUPERVISED.
 8.THE DOOR SHALL OPEN TO THE MINIMUM REQUIRED
 WIDTH WITHIN 10 SECONDS AFTER ACTIVATION OF THE
 OPERATING DEVICE.
 9.IN APARTMENT BUILDINGS, HOTELS AND DORMITORIES,
 HORIZONTAL SLIDING DOORS SHALL NOT BE USED ACROSS
 CORRIDORS.
  
 18) SHEET A101A) REFLECTED CEILING PLAN:
 18A)SKYLIGHT DRIVE THROUGH PROVIDE PRODUCT APPROVAL
 FOR WIND AND PROVIDE WHAT TYPE OF SAFETY GLAZING WILL
 BE USED. 2405.2 ALLOWABLE GLAZING MATERIALS AND
 LIMITATIONS.
 SLOPED GLAZING SHALL BE ANY OF THE FOLLOWING MATERIALS,
 SUBJECT TO THE LISTED LIMITATIONS.
 1.FOR MONOLITHIC GLAZING SYSTEMS, THE GLAZING
 MATERIAL OF THE SINGLE LIGHT OR LAYER SHALL BE
 LAMINATED GLASS WITH A MINIMUM 30-MIL (0.76 MM)
 POLYVINYL BUTYRAL (OR EQUIVALENT) INTERLAYER, WIRED
 GLASS, LIGHT-TRANSMITTING PLASTIC MATERIALS MEETING THE
 REQUIREMENTS OF SECTION 2607 , HEAT-STRENGTHENED GLASS
 OR FULLY TEMPERED GLASS.
 2.FOR MULTIPLE-LAYER GLAZING SYSTEMS, EACH LIGHT
 OR LAYER SHALL CONSIST OF ANY OF THE GLAZING MATERIALS
 SPECIFIED IN ITEM 1 ABOVE.
 ANNEALED GLASS IS PERMITTED TO BE USED AS SPECIFIED
 WITHIN EXCEPTIONS 2 AND 3 OF SECTION 2405.3 .
 FOR ADDITIONAL REQUIREMENTS FOR PLASTIC SKYLIGHTS, SEE
 SECTION 2610 . GLASS-BLOCK CONSTRUCTION SHALL CONFORM
 TO THE REQUIREMENTS OF SECTION 2101.2.5 .
  
 18B)LOBBY SKYLIGHT IS IN ACTUALITY AN ATRIUM PLEASE
 SEE ALL REQUIREMENTS IN 404 FOR : ATRIUM. AN OPENING
 CONNECTING TWO OR MORE STORIES OTHER THAN ENCLOSED
 STAIRWAYS, ELEVATORS, HOIST WAY, ESCALATORS, PLUMBING,
 ELECTRICAL, AIR-CONDITIONING OR OTHER EQUIPMENT, WHICH
 IS CLOSED AT THE TOP AND NOT DEFINED AS A MALL.
 STORIES, AS USED IN THIS DEFINITION, DO NOT INCLUDE
 BALCONIES WITHIN ASSEMBLY GROUPS OR MEZZANINES THAT
 COMPLY WITH SECTION 505.
  
 404.2 USE.
 THE ATRIUM FLOOR AREA IS PERMITTED TO BE USED FOR LOW
 AND ORDINARY FIRE HAZARD USES WHERE THE INDIVIDUAL
 SPACE IS PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM
 IN ACCORDANCE WITH SECTION 903.3.1.1 .
  
 404.3 AUTOMATIC SPRINKLER PROTECTION.
 AN APPROVED AUTOMATIC SPRINKLER SYSTEM SHALL BE
 INSTALLED THROUGHOUT THE ENTIRE BUILDING.
  
 404.4 SMOKE CONTROL.
 A SMOKE CONTROL SYSTEM SHALL BE INSTALLED IN ACCORDANCE
 WITH SECTION 909.
  
 404.5 ENCLOSURE OF ATRIUMS.
 ATRIUM SPACES SHALL BE SEPARATED FROM ADJACENT SPACES
 BY A 1-HOUR FIRE BARRIER WALL.
 EXCEPTIONS:
 1.A GLASS WALL FORMING A SMOKE PARTITION WHERE
 AUTOMATIC SPRINKLERS ARE SPACED 6 FEET (1829 MM) OR
 LESS ALONG BOTH SIDES OF THE SEPARATION WALL, OR ON THE
 ROOM SIDE ONLY IF THERE IS NOT A WALKWAY ON THE ATRIUM
 SIDE, AND BETWEEN 4 INCHES AND 12 INCHES (102 MM AND
 305 MM) AWAY FROM THE GLASS AND SO DESIGNED THAT THE
 ENTIRE SURFACE OF THE GLASS IS WET UPON ACTIVATION OF
 THE SPRINKLER SYSTEM. THE GLASS SHALL BE INSTALLED IN A
 GASKETED FRAME SO THAT THE FRAMING SYSTEM DEFLECTS
 WITHOUT BREAKING (LOADING) THE GLASS BEFORE THE
 SPRINKLER SYSTEM OPERATES.
 2.A GLASS-BLOCK WALL ASSEMBLY IN ACCORDANCE WITH
 SECTION 2110 AND HAVING A ?-HOUR FIRE PROTECTION
 RATING.
 3.THE ADJACENT SPACES OF ANY THREE FLOORS OF THE
 ATRIUM SHALL NOT BE REQUIRED TO BE SEPARATED FROM THE
 ATRIUM WHERE SUCH SPACES ARE INCLUDED IN COMPUTING THE
 ATRIUM VOLUME FOR THE DESIGN OF THE SMOKE CONTROL
 SYSTEM.
  
 404.6 STANDBY POWER.
 EQUIPMENT REQUIRED TO PROVIDE SMOKE CONTROL SHALL BE
 CONNECTED TO A STANDBY POWER SYSTEM IN ACCORDANCE WITH
 SECTION 909.11.
  
 404.7 INTERIOR FINISH.
 THE INTERIOR FINISH OF WALLS AND CEILINGS OF THE ATRIUM
 SHALL NOT BE LESS THAN CLASS B WITH NO REDUCTION IN
 CLASS FOR SPRINKLER PROTECTION.
  
 404.8 TRAVEL DISTANCE.
 IN OTHER THAN THE LOWEST LEVEL OF THE ATRIUM, WHERE THE
 REQUIRED MEANS OF EGRESS IS THROUGH THE ATRIUM SPACE,
 THE PORTION OF EXIT ACCESS TRAVEL DISTANCE WITHIN THE
 ATRIUM SPACE SHALL NOT EXCEED 200 FEET (60 960 MM).
  
 18C)PLANS IDENTIFY THE USE OF 5/8? WALLBOARD FOR USE
 IN CONSTRUCTING OF EXTERIOR SOFFIT IN GARAGE AREAS.
 2508.2
 GYPSUM WALLBOARD SHALL NOT BE USED WHERE THERE WILL BE
 DIRECT EXPOSURE TO WATER OR CONTINUOUS HIGH HUMIDITY
 CONDITIONS. GYPSUM SHEATHING SHALL BE INSTALLED ON
 EXTERIOR SURFACES IN ACCORDANCE WITH ASTM C 1280.
  
 18D) THE DESIGN OF THE PARKING AREA WITHIN THE TOWER IS
 S-2 ENCLOSED PARKING GARAGE,
 THE PLANS INDICATE ALL BLOCK WALLS AS 2HR WALLS, AS
 REQUIRED BY TABLE 302.3.2.
 18D) (1) PLEASE HAVE THE BLOCK MANUFACTURER PROVIDE THE
 EQUIVALENT THICKNESS OF ALL
 RATED BLOCK SEE TABLE 721.3.2.
 18D) (2) PLEASE INDICATE ON ALL THE STOREFRONT DOORS
 AND WINDOWS THE FIRE RATING; ALSO INDICATE ALL OPENINGS
 IN THE DOOR AND WINDOW SCHEDULE. TABLE 715.3.
  
 18E)DOOR # 12 IS MISSING A FIRE RATING FROM THE DOOR
 SCHEDULE. TABLE 715.3
  
 18F)PLANS QUOTE FIRE RATED CORRIDOR NOTE NFPA 101 BUT
 DO NOT MENTION THE MORE RESTRICTIVE OCCUPANCY
 SEPARATION BETWEEN THE ENCLOSED PARKING S-2 OCCUPANCY
 AND ADJACENT SPACES. THE MOST RESTRICTIVE CODE IS USED
 IN THIS CASE. 102.4*.
  
 19) SHEET A102
 19A)(1) SEE DETAIL B-3 SHEET A-402, THE SLIDING GLASS
 DOOR TRACK ASSEMBLY AS SHOWN DOES NOT MEET FAIR HOUSING
 GUIDELINES,FOR SECONDARY DOORS (SLIDING GLASS DOORS)
 THE GUIDELINE SPECIFY THAT THE THRESHOLDS AT THESE
 DOORS SHALL BE NO HIGHER THAN ? ?.THE GUIDELINES
 FURTHER STATE THAT CHANGES IN LEVEL AT THESE LOCATIONS
 MUST BE BEVELED WITH A SLOPE NO GREATER THAN 1:2.
 19A)(2) FAIR HOUSING DOOR AT CONCRETE LANDINGS THE
 MAXIMUM ALLOWABLE CHANGE IN LEVEL AT EXTERIOR SLIDING
 GLASS DOORS (SECONDARY ENTRANCE) TO BALCONY OR PATIO
 WILL BE 4 INCHES TO THE FINISH DECK.
 NOTE: INCORPORATE THE HEIGHT OF THE HIGH RISE TRACK
 INTO THE DESIGN CRITERIA.
 19A)(3) THE STRUCTURAL PLANS WILL ALSO NEED TO
 CORRELATE THEIR DETAIL SHEETS TO MEET THE REQUIREMENTS
 STATED ABOVE, FAIR HOUSING SECONDARY SLIDING GLASS
 DOORS.
 19A)(4) THE TRACK DETAIL ALSO INDICATES THAT THE TRACK
 IS TO BE SET IN LEVELING GROUT. ALL PRODUCT APPROVALS
 WILL REQUIRE MECHANICAL FASTENING OF TRACK.
  
 19B)THIS COMMENT WILL BE COMMON TO ALL FLOORS PLANS
 INDICATE A ? HR FIRE RATING PER NFPA 101 WHEREAS THE
 FBC TABLE 1016.1 FOR FIRE SPRINKLED BUILDINGS REQUIRES
 A 1 HR RATING. IF THERE IS A CONFLICT BETWEEN THE TWO
 CODES THE MOST RESTRICTIVE RULES. 1 HOUR FIRE RATED
 CORRIDORS WILL BE REQUIRED WITH 20MINUTE OPENING
 PROTECTIVE.
  
 19C) THERE ARE 3 DOORS THAT ARE NOT LABELED NOR SHOW UP
 ON THE DOOR SCHEDULE AS FOLLOWS:
 1) TRASH ROOM DOOR
 2) ANY DOOR THAT LEADS TO ANY INDIVIDUAL UNIT
 3) ELEVATOR LOBBY DOORS
  
 19D) PLANS FAIL TO IDENTIFY THE WALL TYPES THAT
 SURROUND THE REFUSE SHOOT.
 707.13.3 REFUSE AND LAUNDRY CHUTE ACCESS ROOMS. ACCESS
 OPENINGS FOR REFUSE AND LAUNDRY CHUTES SHALL BE LOCATED
 IN ROOMS OR COMPARTMENTS COMPLETELY ENCLOSED BY
 CONSTRUCTION THAT HAS A FIRE-RESISTANCE RATING OF NOT
 LESS THAN 1 HOUR AND OPENINGS INTO THE ACCESS ROOMS
 SHALL BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE
 PROTECTION RATING OF NOT LESS THAN ? HOUR AND SHALL BE
 SELF-CLOSING OR AUTOMATIC-CLOSING UPON THE DETECTION OF
 SMOKE.
  
 19E)GLASS WALL (SF14) AT ATRIUM TO BE 1 HR RATED, SEE
 404.5 EXCEPTION# 1 BELOW:
 #1) A GLASS WALL FORMING A SMOKE PARTITION WHERE
 AUTOMATIC SPRINKLERS ARE SPACED 6 FEET (1829 MM) OR
 LESS ALONG BOTH SIDES OF THE SEPARATION WALL, OR ON THE
 ROOM SIDE ONLY IF THERE IS NOT A WALKWAY ON THE ATRIUM
 SIDE, AND BETWEEN 4 INCHES AND 12 INCHES (102 MM AND
 305 MM) AWAY FROM THE GLASS AND SO DESIGNED THAT THE
 ENTIRE SURFACE OF THE GLASS IS WET UPON ACTIVATION OF
 THE SPRINKLER SYSTEM. THE GLASS SHALL BE INSTALLED IN A
 GASKETED FRAME SO THAT THE FRAMING SYSTEM DEFLECTS
 WITHOUT BREAKING (LOADING) THE GLASS BEFORE THE
 SPRINKLER SYSTEM OPERATES.
  
 19F) STAIR TOWER 1 & 2 IN BOTH CASES THE DOORS SWING
 INTO THE STAIR LANDING MORE THAN 7? SEE 1009.1.4
 EXCEPTION 2. WHEN FULLY OPEN, THE DOOR SHALL NOT
 PROJECT MORE THAN 7 INCHES (178 MM) INTO A LANDING.
  
 19G)DOOR S1 IS INDICATED TO BE A 1 ? HR FIRE RATED
 DOOR WITH A 6? WIRE GLASS VIEW PANEL
 PLEASE PROVIDE WHAT TYPE FRAME THIS ASSEMBLY WILL BE
 SECURED TO?
  
  
 19H) PLANS INDICATE BETWEEN UNITS 2 SEPARATE WALLS ONE
 WITH SOUND PROOFING THE OTHER IS A TWO HR RATED WALL.
 PLEASE PROVIDE AN ASSEMBLY HOW THE TWO WALLS WILL BE
 BUILT?
  
 19I) PROVIDE COMPLIANCE WITH:1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 19J) PROVIDE COMPLIANCE WITH: 1207.3 STRUCTURE-BORNE
 SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 20) SHEET A102A)
 20A) DETAIL D SHEET A 802 SHOULD BE INTO THE ATRIUM BUT
 IS INDICATED AS PRIVACY WALL AND PARAPET @ COVERED
 TERRACES, PLEASE CORRECT.
  
 21) SHEET A103A)
 21A)THIS SHEET INDICATES VARIOUS SOFFIT DETAILS
 PROVIDE ATTACHMENT INFORMATION, NOT SUSPENDED FROM THE
 DECK ABOVE. 106.1.2* ADD INFO.
  
 21B) THIS SHEET DETAILS THE THIRD STORY CEILINGS, JUST
 BEHIND THE 3 STORY ATRIUM THERE IS A DIMENSION OF 1?-0?
 IN DETAIL ?B? WHAT DOES THIS DIMENSION REFLECT?
 106.1.2* ADD INFO.
  
 21C) THIS SHEET REFLECTS THE CEILING MATERIAL SCHEDULE,
 APPARENTLY ONLY THE SERVICE ELEVATOR AND ELEVATOR# 1
 LOBBIES ARE GOING TO HAVE DROPPED DRYWALL CEILINGS,
 NONE IN ANY PART OF THIS FLOOR. IN THE UNITS MOST
 KITCHENS AND BATHROOMS ARE DROPPED FOR A/C DUCT WORK?
  
 22)SHEET A104:
 22A)INDICATES THE SKYLIGHT IS TO BE UNDER A SEPARATE
 PERMIT, THIS BUILDING IS DESIGNED AS AN ENCLOSED
 STRUCTURE, REQUIRING ALL PARTS OF THE ENVELOPE TO BE
 PERMITTED AS A SINGLE UNIT. THE SKYLIGHT PRODUCT
 APPROVAL INFORMATION WILL BE REQUIRED TO BE PART OF THE
 BASE BUILDING DATA SUBMITTED BEFORE A PERMIT WILL BE
 ISSUED.
  
 22B) ON THE SOUTH SIDE OF THE SKYLIGHT THERE IS A PAIR
 OF DOORS, NOT LABELED, NOT RATED?PLEASE PROVIDE WHAT
 PROPOSED USAGE THIS ROOM WILL BE USED FOR?
  
 22C)TO THE EAST & WEST SIDES OF THE SKYLIGHT THE
 PLANS INDICATE A ROOF DRAIN BUT IT DOESN?T APPEAR TO
 HAVE EMERGENCY OVERFLOW SYSTEM LOCATED ON THE EAST END
 OF THE SKYLIGHT? 1503.4.3WHEN OTHER MEANS OF DRAINAGE
 OF OVERFLOW WATER IS NOT PROVIDED, OVERFLOW SCUPPERS
 SHALL BE PLACED IN WALLS OR PARAPETS NOT LESS THAN 2
 INCHES (51 MM) NOR MORE THAN 4 INCHES (102 MM) ABOVE
 THE FINISHED ROOF COVERING AND SHALL BE LOCATED AS
 CLOSE AS PRACTICAL TO REQUIRED VERTICAL LEADERS OR
 DOWNSPOUTS OR WALL AND PARAPET SCUPPERS. AN OVERFLOW
 SCUPPER SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, PLUMBING.
  
 23) SHEET A106:
 23A) PLANS INDICATE SPIRAL STAIRS, PLEASE SUBMIT
 INFORMATION ON STAIRS: SEE 1009.9
 (1-3) SPIRAL STAIRWAYS.
  
 24) SHEET A107:
 24A) PLEASE PROVIDE ADDITIONAL INFORMATION ON WHAT
 APPEARS TO BE A WHIRLPOOL?
  
 24B) PLANS ALSO INDICATE A GRILL ON THE EXTERIOR OF
 EACH UNIT; PROVIDE MANUFACTURERS SPECS ON THESE UNITS.
 DO THESE UNITS ALSO NEED VENTS?
  
 24C) PLANS INDICATE AN ALUMINUM CATWALK SYSTEM TO BE
 COORDINATED WITH THE MECHANICAL EQUIPMENT, ADDITIONAL
 INFORMATION WILL BE NEEDED ON BOTH?
  
 24D) MACHINE ROOM# 3 THE PLANS MAY HAVE A TYPO, THERE
 ARE STAIRS INDICATED AND A DOOR DESIGNATION R-3 BUT NO
 DOOR, DOOR IS AROUND THE CORNER.106.1.2* ADD INFO
 REQUIRED.
  
 24E) IN THE CENTER OF THE BUILDING THE PLANS INDICATE
 VARIOUS ROOF DRAINS BUT NO SECONDARY
 OVERFLOW DRAINS.1503.4.3WHEN OTHER MEANS OF
 DRAINAGE OF OVERFLOW WATER IS NOT PROVIDED, OVERFLOW
 SCUPPERS SHALL BE PLACED IN WALLS OR PARAPETS NOT LESS
 THAN 2 INCHES (51 MM) NOR MORE THAN 4 INCHES (102 MM)
 ABOVE THE FINISHED ROOF COVERING AND SHALL BE LOCATED
 AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL LEADERS OR
 DOWNSPOUTS OR WALL AND PARAPET SCUPPERS. AN OVERFLOW
 SCUPPER SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, PLUMBING.
  
 24F) THE ELEVATOR MACHINE ROOM DOORS ARE LABELED (R1)
 DOORS WITH 45 MIN DOORS PLEASE CORRECT TO 1 ? HR RATED
 DOORS (SHAFTS)/ ELEVATOR MACHINE ROOMS.
  
 24G) PLANS INDICATE BETWEEN PENTHOUSE UNITS TERRACE A
 DOOR THIS WILL CROSS UNIT LINES REQUIRING A UNITY OF
 TITLE BETWEEN UNITS.
  
 24H) STAIRWELL# 1 INDICATES THAT A 6? DIA. FIRE RATED
 VIEW PANEL WILL BE IN THIS DOOR, WILL NEED TO BE TESTED
 FOR WIND PRESSURES ALSO.
  
  
 25) SHEET A108:
 25A)PLANS INDICATE ON PENTHOUSE B AND THE REVERSE
 PENTHOUSE BTHE ROOF SCUPPERS ARE DIRECTLY OVER THE
 DOORWAY!!!!!
  
 25B) ALL ROOF SCUPPERS ARE INSTALLED LEVEL WITH THE
 ROOF DECK, PLANS DO NOT INDICATE ANY EMERGENCY OVERFLOW
 SCUPPERS. 1503.4.3WHEN OTHER MEANS OF DRAINAGE OF
 OVERFLOW WATER IS NOT PROVIDED, OVERFLOW SCUPPERS SHALL
 BE PLACED IN WALLS OR PARAPETS NOT LESS THAN 2 INCHES
 (51 MM) NOR MORE THAN 4 INCHES (102 MM) ABOVE THE
 FINISHED ROOF COVERING AND SHALL BE LOCATED AS CLOSE AS
 PRACTICAL TO REQUIRED VERTICAL LEADERS OR DOWNSPOUTS OR
 WALL AND PARAPET SCUPPERS. AN OVERFLOW SCUPPER SHALL BE
 SIZED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 PLUMBING.
  
 26) SHEET A201: NOTES 26A-26C COMMON TO ALL 200 SERIES
 SHEETS.
 26A) GENERAL NOTE# 9 INDICATES APPROVAL FROM THE
 ARCHITECT AND BUILDING DEPARTMENT. PLEASE CORRECT THE
 DESIGNER OF RECORD APPROVES, THE CITY REVIEWS FOR CODE
 COMPLIANCE ONLY!!
  
 26B) FINISH NOTES COMMENT ONLY ON NFPA 101, THE 2006
 FBC803.1/ TABLE 803.5 ARE THE CODE SECTIONS THE
 BUILDING DEPARTMENT WILL REVIEW TOO.
  
 26C) EGRESS WINDOWS THE MINIMUM HEIGHT IS 24? NOT 22?
 AND THE MINIMUM OPEN VENT SIZE IS 5.7? SECOND FLORR AND
 5.0? FIRST FLOOR NOT 4.)?. SEE FBC 1025.2 BUILDING.
  
 26D) UNIT DOOR SCHEDULE INDICATES WOOD DOORS (8-9) BOTH
 INDICATE WOOD DOORS AND FRAMES FIRE RATED 60 MINUTE
 DOORS. PLEASE PROVIDE APPROVAL REPORTS FOR 1 HR FIRE
 RATING.
  
 27) SHEET A201:
 27A) PLANS INDICATE 3?-0? ENTRY BETWEEN CABINET ENTRY
 INTO THE KITCHEN, PLEASE SEE A700.
 THE TITLE INDICATES PALM BEACH COUNTY ACCESSIBILITY
 CODE PLEASE CORRECT TO THE 2004
 /2006 FBC CHAPTER 11 PARTB FAIR HOUSING ACCESSIBILITY
 GUIDELINES.
 SEE NOTE# 5 INDICATES A MINIMUM OF 40? FOR KITCHENS NOT
 THE 3?-0? DIMENSIONED IN THE PLAN. USABLE KITCHENS
 (1)(B)
  
 27B) PLANS DO NOT INDICATE THE SIZE OF THE SHOWER
 DOOR?
  
  
 27C) IMPORTANT NOTE!!!!! PLANS DO NOT INDICATE
 INFORMATION AS TO EXTERIOR SLIDERS,SEE COMMENT
 19A)(1-3), AGAIN IT IS CRITICAL THAT THE SLIDING DOOR
 TRACK BE RECESSED ENOUGH TO ALLOW NO MORE THAN ?? ABOVE
 FINISH FLOOR AND FROM THE INTERIOR FINISH FLOOR TO THE
 TOP OF THE BALCONY DECK NO MORE THAN A 4? DROP. THIS IS
 TYPICAL OF ALL EXTERIOR SLIDING GLASS DOOR UNITS!!!!
 LEGEND-CURBS TYPICAL FOR ALL UNITS, THIS COMMENT WILL
 NOT BE RESTATED!!!!!!!!!!!!!!!!
  
 28) SHEET A203:
 28A) THE PRIMARY ENTRANCE DOORS ARE A PAIR OF 30?
 DOORS, THE MINIMUM CLEAR WIDTH OF THE OPEN DOOR IS 32?
 WHEN OPEN 90DEGREES TO THE OPENING. ANSI 4.13./
 1008.1.1.
  
 28B) USABLE DOOR #14 DOES NOT MEET THE GUIDELINES, THE
 BIFOLD DOOR IS LISTED AS 1 ??
 OR 3 ?? SUBTRACTED FROM 2?-10? LEAVES A 2?-61/2?
 OPENING. THE MINIMUM CLEAR OPENING IS 2?-8? FOR USABLE
 DOORS.
  
 29) SHEET A205:
 29A) THE PRIMARY ENTRY DOOR #8 WOULD REQUIRE A CLEAR
 32? THIS WILL NOT BE POSSIBLE WITH A 30? DOOR.
 1008.1.1.
  
 30) SHEET A207: DOOR # 7 IS INDICATED AS A TYPE ?D?
 POCKET WHERE IT IS SHOWN AS A SWING DOOR.
  
 31) SHEET A209) DOOR 3 & 4 BOTH ARE BI-FOLD DOORS
 2?-10? BIFOLD ? 31/2? = 2?-61/2? THIS DOES NOT MEET THE
 32? FOR USABLE DOORS.
  
 32) SHEET A212:
 32A) ENTRY DOOR# 10, ) THE PRIMARY ENTRANCE DOORS ARE A
 PAIR OF 30? DOORS, THE MINIMUM CLEAR WIDTH OF THE OPEN
 DOOR IS 32? WHEN OPEN 90DEGREES TO THE OPENING. ANSI
 4.13./ 1008.1.1.
  
 32B)KITCHEN MISSING THE DIMENSION BETWEEN CABINETS.
 MINIMUM 40? CLEAR.
  
 32C) BIFOLD DOORS ARE BI-FOLD DOORS 2?-10? BIFOLD ?
 31/2? = 2?-61/2? THIS DOES NOT MEET THE 32? FOR USABLE
 DOORS.
  
 33) SHEET A215:
 33A)DOOR # 8 ) THE PRIMARY ENTRANCE DOORS ARE A PAIR
 OF 30? DOORS, THE MINIMUM CLEAR WIDTH OF THE OPEN DOOR
 IS 32? WHEN OPEN 90DEGREES TO THE OPENING. ANSI 4.13./
 1008.1.1.
  
 33B) DOOR# 17 IS A 2?-8? DOOR IS REQUIRED TO BE 32? AS
 BEING A USABLE DOOR AND IN CLOSETS DEEPER THAN 2?-0?.
  
 34) SHEET A402 HAS VARIOUS DETAILS INDICATING THE USE
 OF STEEL TO CREATE STRUCTURAL MULLIONS.1707.4.5.1
 MULLIONS OCCURRING BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE REQUIRED BY AN
 APPROVED TESTING LABORATORY OR BE ENGINEERED.
 1707.4.5.2 MULLIONS SHALL BE DESIGNED TO TRANSFER THE
 DESIGN PRESSURE LOADS APPLIED BY THE WINDOW OR DOOR
 ASSEMBLIES TO THE ROUGH OPENING SUBSTRATE.
  
 35) SHEET A-501 INDICATES IN DETAIL# 2 A 3? GAP BETWEEN
 THE HANDRAIL AND WALL. FAIR HOUSING ANSI A117.1, 505.5
 CLEARANCE BETWEEN THE CLEAR SPACE BETWEEN THE WALL AND
 THE HANDRAIL SHALL BE 1 ??.
  
 36) SHEET A-503:
 36A) PLANS DO NOT PROVIDE COMPLIANCE FOR THE ELEVATOR
 CARS TO ACCOMMODATE AMBULANCE STRETCHER REQUIREMENTS
 3002.4.
  
 36B) PLEASE NOTE SIGNAGE REQUIREMENT: 3002.3 EMERGENCY
 SIGNS.
 AN APPROVED PICTORIAL SIGN OF A STANDARDIZED DESIGN
 SHALL BE POSTED ADJACENT TO EACH ELEVATOR CALL STATION
 ON ALL FLOORS INSTRUCTING OCCUPANTS TO USE THE EXIT
 STAIRWAYS AND NOT TO USE THE ELEVATORS IN CASE OF FIRE.
 THE SIGN SHALL READ: IN FIRE EMERGENCY, DO NOT USE
 ELEVATOR. USE EXIT STAIRS. THE EMERGENCY SIGN SHALL NOT
 BE REQUIRED FOR ELEVATORS THAT ARE PART OF AN
 ACCESSIBLE MEANS OF EGRESS COMPLYING WITH SECTION 1007
 .
  
 3004.2 LOCATION OF VENTS.
 VENTS SHALL BE LOCATED BELOW THE FLOOR OR FLOORS AT THE
 TOP OF THE HOISTWAY, AND SHALL OPEN EITHER DIRECTLY TO
 THE OUTER AIR OR THROUGH NONCOMBUSTIBLE DUCTS TO THE
 OUTER AIR. NONCOMBUSTIBLE DUCTS SHALL BE PERMITTED TO
 PASS THROUGH THE ELEVATOR MACHINE ROOM PROVIDED THAT
 PORTIONS OF THE DUCTS LOCATED OUTSIDE THE HOISTWAY OR
 MACHINE ROOM ARE
  
 ENCLOSED BY CONSTRUCTION HAVING NOT LESS THAN THE FIRE
 PROTECTION RATING REQUIRED FOR THE HOISTWAY. HOLES IN
 THE MACHINE ROOM FLOORS FOR THE PASSAGE OF ROPES,
 CABLES OR OTHER MOVING ELEVATOR EQUIPMENT SHALL BE
 LIMITED SO AS NOT TO PROVIDE GREATER THAN 2 INCHES (51
 MM) OF CLEARANCE ON ALL SIDES.
  
 3004.3 AREA OF VENTS.
 EXCEPT AS PROVIDED FOR IN SECTION 3004.3.1 , THE AREA
 OF THE VENTS SHALL NOT BE LESS THAN 3? PERCENT OF THE
 AREA OF THE HOISTWAY NOR LESS THAN 3 SQUARE FEET (0.28
 M 2 ) FOR EACH ELEVATOR CAR, AND NOT LESS THAN 3?
 PERCENT NOR LESS THAN 0.5 SQUARE FOOT (0.047 M 2 ) FOR
 EACH DUMBWAITER CAR IN THE HOISTWAY, WHICHEVER IS
 GREATER. OF THE TOTAL REQUIRED VENT AREA, NOT LESS THAN
 ONE-THIRD SHALL BE OF THE PERMANENTLY OPEN TYPE UNLESS
 ALL VENTS ACTIVATE UPON DETECTION OF SMOKE FROM ANY OF
 THE ELEVATOR LOBBY SMOKE DETECTORS.
  
 37) SHEET A600 AND ALL 600 SHEETS:
 37A) FIRE RATING LEGEND WALLS, PLEASE SEE TABLE 601 FOR
 FIRE RATINGS OF STRUCTURAL MEMBERS AND NON RATED
 WALLS.
  
 38)SHEET A700:
 38A) PLANS INDICATE PALM BEACH COUNTY ACCESSIBILITY
 PLEASE CORRECT TO 2004/2006 FLORIDA BUILDING CODE
 CHAPTER 11 FLORIDA ACCESSIBILITY CODE.
  
 38B) NOTE 16 -01 IS ILLEGIBLE DOUBLE TYPED.
  
 38C) NOTE 16-04 PLEASE SEE FAIR HOUSING ACCESSIBILITY
 GUIDELINES UNDER PURPOSE:
 THE DESIGN TEAM IS RESPONSIBLE FOR FAIR HOUSING .!!!
 PURPOSE: THE PURPOSE OF THESE GUIDELINES IS TO PROVIDE
 TECHNICAL GUIDANCE ON DESIGNING DWELLING UNITS AS
 REQUIRED BY THE FAIR HOUSING AMENDMENTS ACT OF 1988
 (FAIR HOUSING ACT). THESE GUIDELINES ARE NOT MANDATORY,
 NOR DO THEY PRESCRIBE SPECIFIC REQUIREMENTS WHICH MUST
 BE MET, AND WHICH, IF NOT MET, WOULD CONSTITUTE
 UNLAWFUL DISCRIMINATION UNDER THE FAIR HOUSING ACT.
 BUILDERS AND DEVELOPERS MAY CHOOSE TO DEPART FROM THESE
 GUIDELINES AND SEEK ALTERNATE WAYS TO DEMONSTRATE THAT
 THEY HAVE MET THE REQUIREMENTS OF THE FAIR HOUSING ACT.
 THESE GUIDELINES ARE INTENDED TO PROVIDE A SAFE HARBOR
 FOR COMPLIANCE WITH THE ACCESSIBILITY REQUIREMENTS OF
 THE FAIR HOUSING ACT.
  
 39) SHEET A802 DETAIL ?G? IS DOESN?T INDICATE HOW THIS
 SUPPORT IS TO BE TIED DOWN TO THE ROOF DECK PLEASE
 PROVIDE A CONTINUOUS PATH OF RESISTANCE.
  
 40) SHEET A803 PLEASE PROVIDE RATING BETWEEN THE
 ASSEMBLY OCCUPANCY AND THE S-2 OCCUPANCY BELOW.
  
 41) SHEET A804:
 41A)DETAIL H PLANS INDICATE A POOL COPING DETAIL,
 WHEREAS IT IS ACTUALLY AN EXHAUST FAN DETAIL, PLEASE
 CORRECT.
  
 41B) PLANS ALSO DO NOT INDICATE ANY STRAPPING IN THIS
 DETAIL SECURING THE CURB TO THE ROOF DECK?
  
 41C) PLANS MAKEREFERENCE TO THE SFBC, CORRECT
  
 42) SHEET S703 CORRECT THE REFERENCED STANDARDS :
 REINFORCED MASONRY NOTES
 42A) ACI 530.1-99
 42B) ASCE 5-99
 42C) ASCE 6-99
 42D) TMS 402-99
  
 SHEARWALL NOTES
 42E) ACI 318-99
 42F) ACI 318R-92
  
 42G)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 43 ) S-103 PLANS INDICATE THERE WILL BE PILING BUT NO
 INFORMATION HAS BEEN SUBMITTED
 THAT THIS WILL BE PART OF THIS PERMIT. PLEASE PROVIDE
 WHAT TYPE OF PILING, DIAMETER,
 LENGTH OF PILE, REINFORCING REQUIREMENTS, ETC.
  
 44) S-901 IT APPEARS THAT RWDI HAS COMPLETED A WIND
 TUNNEL TEST. PLEASE SUBMIT 3 ORIGINAL SIGNED& SEAL
 REPORTS .
  
 45) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE
 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR) OF
 PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 A) FIXED GLASS
 B) STOREFRONT GLASS
 C) OPERABLE WINDOWS
 D) MULLIONS HORIZONTAL & VERTICAL
 E) SKYLIGHTS
 F) GLASS BLOCK
 G) LOUVERS
 H) HOLLOW METAL DOORS/ ROOF HATCHES
 I) GLASS DOORS SWING
 J) OVERHEAD DOORS/ COIL DOORS
 K) SLIDING GLASS DOORS
 L) AUTOMATIC HORIZONTAL SLIDING DOORS
 M)PANEL WALL SYSTEM: SOFFITS, EFIS
 N) ROOFING ASSEMBLIES
  
 AT THIS TIME NO APPROVALS (GLAZING) CAN BE REVIEWED!
 FOR EXAMPLE FOR STOREFRONT PGT NOA 03-0508.03 WAS
 SUBMITTED FOR LARGE AND SMALL MISSILE TESTING.
 THE FIRST ISSUE IS FOR THE LARGE MISSILE
 TEST NO ONE HAS INDICATED WHICH FASTENER TYPE WAS TO BE
 USED, SECOND WHICH STYLE LAMINATED GLAZING WAS TO BE
 INSTALLED. PLEASE HIGHLIGHT OR INDICATE THE DESIGN
 TEAM?S CHOICE.
 THE NEXT ISSUE WITH THIS PRODUCT APPROVAL
 IS THE LIMITATION ON THE HEIGHT AND WIDTH OR MAXIMUM
 DAYLIGHT OPENING ALLOWED BY THE NOA, SEE SHEET A400 &
 A401.
  
 THE NEXT ISSUE IS WITHIN THE NOA ITSELF,
 THIS PGTNOA INDICATES THAT IT IS TO BE USED FOR LARGE
 AND SMALL MISSILE IMPACT WINDOW BUT THERE IS NO
 LITERATURE FOR SMALL MISSILE IMPACT RATING INDICATED IN
 THE PRODUCT APPROVAL?
 THIS COMMENT WILL STAND FOR ALL PRODUCT
 APPROVALS IN REGARDS TO THE WIND STUDY. SINCE THERE ARE
 NUMEROUS WIND PRESSURE ZONES FOR THIS BUILDING THE
 DESIGN TEAM WILL NEED TO PROVIDE SOME MEANS OF
 IDENTIFYING WHICH PRODUCT APPROVALS WILL TIE TO THERE
 ASSOCIATED GLAZING UNIT FOR BOTH LARGE AND SMALL
 MISSILE UNITS.
  
 THIS NEXT ISSUE WILL DEAL WITH THE WIND
 REPORT SUBMITTED FROM RWDI AND THE REQUIREMENTS OF
 ASCE7-02 SECTION 6.6 METHOD 3 WIND TUNNEL TEST. UNDER
 THE HEADING OF LIMITATIONS SEE ANALYSIS FOR WIND SPEEDS
 CONFORMS TO THE REQUIREMENTS OF SECTION 6.5.4.2.
 6.5.4.2 ESTIMATION OF BASIC WIND SPEEDS FROM
 REGIONAL CLIMATIC DATA
 (2) THE DESIGN WIND SPEEDS RESULTING FROM THE STUDY
 SHALL NOT BE LESS THAN THE RESULTING
 500-YEAR RETURN PERIOD WIND SPEED DIVIDED BY SQUARE
 ROOT OF 1.5.
 THE SQUARE ROOT OF 1.5 IS 1.22. 500 DIVIDED
 BY 1.22= 154 WIND SPEED. THE RESULTING STUDY SHOULD
 HAVE BEEN COMPOSED USING 154 MPH NOT THE 145 MPH 3
 SECOND GUST.
  
 ANOTHER ISSUE WITH THE WIND STUDY PLEASE
 COMMENT ON WHY ON A SYMMETRIC BUILDING SEE FIGURE# 6
 THE WEST ELEVATION THE PRESSURES ARE SYMMETRIC BUT ON
 THE EAST SIDE OF THE BUILDING WHICH IS ALSO SYMMETRIC
 WHY THERE IS A DIFFERENCE IN CONFIGURATION IN PRESSURE
 ZONES 75/ 85 FROM THE CENTERED 65 PSF? I WOULD BELIEVE
 THE WIND WOULD BE EFFECTED THE SAME AMOUNT ON A
 SYMMETRIC BUILDING. THE SAME CONCEPT I WOULD BELIEVE
 HOLD TRUE ON THE NORTH AND SOUTH SIDES?
  
 THE SAME ISSUE WITH THE SLIDING GLASS DOOR NOA
 SUBMITTED. THE TYPE OF GLAZING
 (LAMINATION) WAS NOTHIGHLIGHTED . PROVIDE A DETAILED
 ACCOUNT WHERE EACH OF THESE TYPE UNITS ARE TO LOCATED
 ON THE BUILDING.
  
 MULLIONS:1707.4.5.1 MULLIONS OCCURRING BETWEEN
 INDIVIDUAL WINDOW AND GLASS DOOR ASSEMBLIES. TESTING
 REPORTS ARE REQUIRED BY AN APPROVED TESTING LABORATORY
 OR BE ENGINEERED.
 1707.4.5.2 MULLIONS SHALL BE DESIGNED TO TRANSFER THE
 DESIGN PRESSURE LOADS APPLIED BY THE WINDOW OR DOOR
 ASSEMBLIES TO THE ROUGH OPENING SUBSTRATE.
  
 THIS ROOF IS MISSING OR NOT IN COMPLIANCE WITH THE
 FOLLOW ITEMS:
 ___ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH. _X__
 CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE USED.
 _X__ THE SYSTEM PROVIDED HAS A LOWPRESSURE FOR ZONE
 _2&3__ .
 SINCE THE ROOFING REPORT DOESN?T HAVE THE SUBSYSTEM
 HIGHLIGHTED THE NEXT 2 ITEMS ARE HIGHLIGHTED._X__ THE
 SYSTEM PROVIDED STATESLIMITATION# 7, SHOULD THE
 FASTENERRESISTANCE BE LESS THAN THAT REQUIRED, AS
 DETERMINED BY THEBUILDING OFFICIAL, A REVISED
 FASTENERSPACING, PREPARED , SIGNED AND SEALED BY A
 FLORIDA REGISTEREDPROFESSIONAL ENGINEER,
 REGISTEREDARCHITECT OR REGISTERED ROOF CONSULTANT
 MAY BE SUBMITTED.
 _X__THE SYSTEM PROVIDED INDICATESLIMITATION#
 9, NO ENHANCEDFASTENING ALLOWED.
  
  
 46)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
 WWW.FLORIDABUILDING.ORG
  
 47) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 48) PLANS ARE TO SHOWCOMPLIANCE WITH:
 403.8 FIRE COMMAND .
 A FIRE COMMAND CENTER COMPLYING WITH SECTION 911 SHALL
 BE PROVIDED IN A LOCATION APPROVED BY THE FIRE
 DEPARTMENT.
  
 403.9 ELEVATORS.
 ELEVATOR OPERATION AND INSTALLATION SHALL BE IN
 ACCORDANCE WITH CHAPTER 30 .
  
 403.10 STANDBY POWER.
 A STANDBY POWER SYSTEM COMPLYING WITH SECTION 2702
 SHALL BE PROVIDED FOR STANDBY POWER LOADS SPECIFIED IN
 SECTION 403.10.2 .
  
 403.10.1 SPECIAL REQUIREMENTS FOR STANDBY POWER
 SYSTEMS.
 IF THE STANDBY SYSTEM IS A GENERATOR SET INSIDE A
 BUILDING, THE SYSTEM SHALL BE LOCATED IN A SEPARATE
 ROOM ENCLOSED WITH 2-HOUR FIRE-RESISTANCE-RATED FIRE
 BARRIER ASSEMBLIES. SYSTEM SUPERVISION WITH MANUAL
 START AND TRANSFER FEATURES SHALL BE PROVIDED AT THE
 FIRE COMMAND CENTER.
  
 403.10.2 STANDBY POWER LOADS.
 THE FOLLOWING ARE CLASSIFIED AS STANDBY POWER LOADS: 1.
 POWER AND LIGHTING FOR THE FIRE COMMAND CENTER REQUIRED
 BY SECTION 403.8 ;
 2.ELECTRICALLY POWERED FIRE PUMPS;
 3.VENTILATION AND AUTOMATIC FIRE DETECTION
 EQUIPMENT FOR SMOKEPROOF ENCLOSURES.
 STANDBY POWER SHALL BE PROVIDED FOR ELEVATORS IN
 ACCORDANCE WITH SECTION 3003 .
  
 403.11 EMERGENCY POWER SYSTEMS.
 AN EMERGENCY POWER SYSTEM COMPLYING WITH SECTION 2702
 SHALL BE PROVIDED FOR EMERGENCY POWER LOADS SPECIFIED
 IN SECTION 403.11.1 .
  
 403.11.1 EMERGENCY POWER LOADS.
 THE FOLLOWING ARE CLASSIFIED AS EMERGENCY POWER LOADS:
  
 1.EXIT SIGNS AND MEANS OF EGRESS ILLUMINATION
 REQUIRED BY CHAPTER 10 ;
 2.ELEVATOR CAR LIGHTING;
 3.EMERGENCY VOICE/ALARM COMMUNICATIONS SYSTEMS; 4.
 AUTOMATIC FIRE DETECTION SYSTEMS; AND
 5.FIRE ALARM SYSTEMS.
  
 403.12 STAIRWAY DOOR OPERATION.
 STAIRWAY DOORS OTHER THAN THE EXIT DISCHARGE DOORS
 SHALL BE PERMITTED TO BE LOCKED FROM
 STAIRWAY SIDE. STAIRWAY DOORS THAT ARE LOCKED FROM THE
 STAIRWAY SIDE SHALL BE CAPABLE OF BEING UNLOCKED
 SIMULTANEOUSLY WITHOUT UNLATCHING UPON A SIGNAL FROM
 THE FIRE COMMAND CENTER.
  
 403.12.1 STAIRWAY COMMUNICATIONS SYSTEM.
 A TELEPHONE OR OTHER TWO-WAY COMMUNICATIONS SYSTEM
 CONNECTED TO AN APPROVED CONSTANTLY ATTENDED STATION
 SHALL BE PROVIDED AT NOT LESS THAN EVERY FIFTH FLOOR IN
 EACH REQUIRED STAIRWAY WHERE THE DOORS TO THE STAIRWAY
 ARE LOCKED.
  
 403.13 SMOKEPROOF EXIT ENCLOSURES.
 EVERY REQUIRED STAIRWAY SERVING FLOORS MORE THAN 75
 FEET (22 860 MM) ABOVE THE LOWEST LEVEL OF FIRE
 DEPARTMENT VEHICLE ACCESS SHALL COMPLY WITH SECTIONS
 909.20 AND 1019.1.8 .
  
 403.14 RESERVED.
  
 403.15 SMOKE CONTROL SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTION 909.
  
 49)SHEET AC-01 THE VALET OFFICE INDICATES A THROUGH
 THE WALL A/C UNIT, IS THIS GOING TO DRAW FRESH AIR FROM
 THE ENCLOSED PARKING GARAGE?
  
 50)PROVIDE INFORMATION ON THE VENTILATION OF THE
 ENCLOSED PARKING GARAGE. 406.4.2 VENTILATION. A
 MECHANICAL VENTILATION SYSTEM SHALL BE PROVIDED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, MECHANICAL
 .
  
  
 51)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST
 BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE INFORMATION.
  
 THIS REVIEW IS MAY HAVE ADDITIONAL COMMENTS AS A RESULT
 OF THE DESIGNERS ANSWERS TO THE PLAN REVIEW OR NEW
 INFORMATION BEING ADDED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 FLAGLER BEACH CLUB TOWER 1ST REVIEW.DOC
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-06-24 Cont ID  
Sent By dpalmer Date 2008-06-24 Time 16:04 Rev Time 0.00
Received By dpalmer Date 2008-06-24 Time 08:00 Sent To  
Notes
2008-06-24 16:05:06** DENIED 2ND REVIEW **
  
  
 ** PLEASE SEE THERE ARE STILL COMMENTS FROM THE
 PREVIOUS REVIEW WHICH ARE IN NEED OF ADDRESSING.
 ** PLEASE SEE THERE ARE SOME NEW COMMENTS TO
 INFORMATION NOW BEING SUBMITTED WHICH WAS ON PREVIOUS
 PLANS OR SUBMITTED WITH PREVIOUS DOCUMENTS.
 ** PLEASE SEE THERE ARE ALSO SOME NEW COMMENTS.
  
 1)NOTE: PLEASE SUBMIT THREE COMPLETE SETS OF PLANS
 AND SUPPORTING DOCUMENTS. IN THE PLANS SUBMITTED, SOME
 ROLLS WERE NOT FASTENED TOGETHER, SOME WERE STAPLED
 BACKWARDS. PLEASE BE SURE ALL SETS ARE IN A NEAT AND
 ORDERLY FASHION WITH ALL SHEETS CONNECTED.
 ** PLEASE BE SURE THE SUBMITTALS ARE PLACED INTO SETS
 IN A NEAT AND ORDERLY FASHION. BINDERS OR FOLDERS OF
 SOME KIND WITH DOCUMENTS IN ORDER LABELED OR TABBED
 WITH INFORMATION WILL EXPEDITE THE REVIEW IN A MORE
 TIMELY FASHION.
 PLEASE SEE FBC ADMIN SECTION 106.1, 106.1.3, 106.5
  
 2) NOTE: PLEASE SEE MANY TITLE BLOCKS ARE MISSING THE
 REQUIRED LICENSE AND PRINTED NAME INFORMATION PER FAC
 61G1-16.004 AND FS 481.219.
 MANY OF THE SHEETS WERE REVISED WITH HAND DRAWN
 INFORMATION HOWEVER MANY WERE NOT.
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY THOSE TRADES.
  
 3) NOTE: PLEASE SEE THE SUBMITTED FLORIDA BUILDING CODE
 FOR ENERGY EFFICIENCIES FLA-COM ENERGY CALCULATIONS ARE
 NOT COMPLIANT.
 IN FACT THERE ARE NUMEROUS ITEMS ON PLANS WHICH ARE NOT
 EVEN SHOWN IN THE CALCULATIONS. THERE ARE SEVERAL ITEMS
 FOR BUILDING COMPONENTS WHICH WILL BE NOTED BY THIS
 REVIEWER AND IS REQUIRED WHETHER OR NOT THE COMMENTS
 ARE MADE BY THE OTHER TRADES.
 THE INPUT DATA REPORTWILL BE NOTED BELOW AS THE IDR
 FOR THE REMAINDER OF THIS COMMENT.
 PLEASE SEE 13-101, 13-400.3.A, 13-415.2,
 13-415.2.ABC.1.1, .1.2 AND .1.3.
  
 FOR EXAMPLE:
 PLEASE SEE THE IDR WHICH SHOWS NO EXTERIOR DOORS. HOW
 IS THIS POSSIBLE WHEN THE PLANS CLEARLY SHOW MANY
 EXTERIOR DOORS?
  
 FOR EXAMPLE:
 PLEASE SEE THE IDR WHICH SHOWS NO FLOORS IN THIS
 BUILDING. HOW IS THIS POSSIBLE WHEN THE BUILDINGS
 CLEARLY CONTAIN FLOORS?
  
 FOR EXAMPLE:
 PLEASE SEE THE IDR WHICH SHOWS NO SKYLIGHTS, YET THE
 PLANS CLEARLY SHOWS A VERY LARGE SKYLIGHT AT THE FRONT
 OF THE BUILDING!
  
 FOR EXAMPLE:
 PLEASE SEE THE JURISDICTION LISTED IN SHOWN AS PALM
 BEACH COUNTY. THIS SHOULD BE THE CITY OF WEST PALM
 BEACH, PALM BEACH COUNTY.
  
 FOR EXAMPLE;
 PLEASE SEE THE EXTERIOR LIGHTING ON THE IDR WHICH SHOWS
 ONLY 75W FIXTURES. HOW IS THIS POSSIBLE WHEN THE PLANS
 CLEARLY SHOW DOZENS OF FIXTURES WHICH ARE SIMPLY NOT
 PLACED INTO THE IDR? ALL FIXTURES SHOWN ON THE IDR FOR
 EXTERIOR LIGHTS WHICH ARE SHOWN AS 75WATTS. PLEASE SEE
 SHEET E-2: PLEASE SEE THE PLANS CLEARLY SHOW 455W,
 195W, 55W, 250W ETC. WHERE ARE ALL THESE FIXTURES?
 13-415.2, 13-415.2.ABC.1.3
  
 FOR EXAMPLE:
 PLEASE EXPLAIN HOW MANY OF THE CONTROL METHOD SHOWN IN
 THE IDR ARE SHOWN AS *MANUAL ON/OFF* WHEN T IN FACT THE
 CODE REQUIRES SOME SORT OF AUTOMATED CONTROLS ON MANY
 OF THESE ITEMS?
  
 FOR EXAMPLE:
 PLEASE SEE THERE ARE MANY LIGHTING FIXTURES ON THE
 FIXTURE LEGEND AND ON PLANS WHICH DO NOT SHOW UP IN THE
 IDR FOR INTERIOR LIGHTS.
 PLEASE LOOK AT THE WATTAGE/VA RATINGS OF FIXTURES ON
 THE LEGEND. WHERE ARE THE 2-F32T8, 3-F32T8, 4-F32T8??
 ETC. WHERE ARE THE 60W FIXTURES?
 13-415.2.ABC.1.1, .1.2
 THIS IS ONLY A FEW AS NOTED AND IS IN NO WAY ALL.
  
 *** AS NOTED, THESE ARE SOME EXAMPLES ONLY AND ARE IN
 NO WAY AN EXHAUSTED LIST OF ALL ITEMS WHICH DO NOT
 CORRELATE. THESE ARE GIVEN AS A BENEFIT ONLY.
  
 4) NOTE: PLEASE SEE 13-413.1.ABC.2.1, 13-413.1.ABC.2.2
 FOR DRAWING AND REQUIRED NOTES TO BE PLACED ON PLANS.
 PLEASE SEE THE FOLLOWING SECTIONS AND PLACE NOTES ON
 PLANS ACCORDINGLY. NOTES SHOULD REFLECT THE WORDING IN
 THE CODE.
  
 5) NOTE: PLEASE SUBMIT THE COMPLETED VOLTAGE DROP
 CALCULATIONS AS REQUIRED PER FBC 13-413.1.ABC.1.1 AND
 .1.2. THE SUBMITTED CALCULATIONS DO NOT PROVIDE THE
 WORST CASE SCENARIOS AS THESE STOP AS A DISTANCE AND DO
 NOT INCLUDE THE LONGEST RUNS TO THE LAST DEVICE/BRANCH
 CIRCUIT.
 THE CALCULATIONS SHOW LENGTH OF 100FT YET THE BUILDING
 ALONE IS TALLER THAN 100FT.
  
 6) NOTE: PLEASESEE THE PREVIOUS REVIEW REQUESTED THE
 MANUFACTURES SPECS/CUT SHEETS FOR THE FIRE PUMP AND
 FIRE PUMP CONTROLLER AMOUNT OTHERS EQUIPMENT SPECS. THE
 SUBMITTALS FOR THE FIRE PUMP AND CONTROLLER ARE NOW
 SHOWING THE FIRE PUMP AS DIESEL YET THE ELECTRICAL
 PLANS INDICATES THE FIRE PUMP AND FPC AS ELECTRICAL.
 AS THE INFORMATION IS NOT CLEAR ON PLANS WHICH ONE WILL
 BE USED IT IS UNCLEAR WHICH ONE NEEDS TO BE REVIEWED.
 PLEASE SEE FOR EXAMPLE IF A DIESEL PUMP IS USED THERE
 ARE SEVERAL REQUIREMENTS IN NFPA-20 WHICH ARE NOT THE
 SAME AS THE ELECTRICAL REQUIREMENTS SUCH AS VENTILATION
 ETC.
 THE SPRINKLER PLANS DO NOT SHOW ENOUGH INFORMATION FOR
 THE FIRE PUMP OR CONTROLLER.
 PLEASE COORDINATE ALL INFORMATION AND SUPPORTING
 DOCUMENTS.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 7) NOTE: PLEASE SEE THE CORRIDORS DO NOT INDICATE ANY
 OF THE FIXTURES FOR EMERGENCY EGRESS WITH BATTERY BACK
 UP.
 PLEASE SEE PREVIOUS NOTES AS THE BUILDING BEING
 OCCUPIED PER HOUSE BILL 7121 WILL REQUIRE THESE ON THE
 GENERATOR HOWEVERAS THE BUILDING IS NOW BECOMING
 OCCUPIED UNDER NORMAL CONDITIONS UNDER EMERGENCY POWER
 THE EMERGENCY EGRESS LIGHTS SHALL BE BATTERY BACK UP TO
 MEET THE MINIMUM 1FT CANDLE. THE STAIRS WERE REVISED
 HOVER FIXTURES D1 AND D2 WERE NOT REVISED TO INDICATE
 ANY BACK UP.
 PLEASE ALSO SEE THE PHOTO-METRICS SUBMITTED DO NOT MAKE
 SENSE. PLEASE TAKE A LOOK AT THE LIGHTING LEVELS SHOWN
 ONE SHEET E6-A. HOW CAN THE SAME LIGHT FIXTURES WHICH
 ARE SHOWN UNDER NORMAL AND UNDER EMERGENCY HAVE A
 DECREASED LIGHTING LEVEL? THESE ARE 75W MR16 BULBS
 BASED ON FIXTURE LEGEND; THESE WILL OPERATE AND PUT OUT
 THE SAME LUMEN LEVEL UNDER EITHER SOURCE OF POWER.
 THESE ARE NOT SHOWN WITH BACK UP BALLAST WHICH SOME
 TIMES MAY BE USED ON FLUORESCENT FIXTURES WITH A LOWER
 LUMEN OUTPUT.
 PLEASE SEE THE D1 FIXTURES ARE ALSO BEING INCLUDED ON
 THE LEVELS UNDER EMERGENCY. THIS IS NOT POSSIBLE BASED
 ON FIXTURES ETC.
 IF BUILDING IS OCCUPIED UNDER EMERGENCY POWER A SINGLE
 MEANS OF A OVER CURRENT PROTECTION DEVICE WOULD LEAVE
 ALL EGRESS PATHS IN TOTAL DARKNESS.
 PLEASE COMPLETE LEVELS FOR ALL WALKING SURFACES.
 FOR EXAMPLE:
 PLEASE SEE THE FRONT ENTRANCE STAIRS WHICH SHOW
 LIGHTING LEVELS ON ONE PART OF STAIRS ONLY YET THE
 STAIR WIDTH IS QUITE SUBSTANTIAL.
 PLEASE SEE NFPA-101 7.8, 7.9, 7.8.1.3, 7.9.2.2 ETC.
  
 8) NOTE: PLEASE COORDINATE ALL FIXTURES ON PLANS.
 PLEASE SEE NOTES ABOVE WITH RESPECT TO LIFE SAFETY
 LIGHTING LEVELS AND ENERGY CALCULATIONS AS FIXTURES ON
 PLANS, FIXTURE LEGEND ETC DO NOT CORRELATE.
 ** PLEASE KEEP IN MIND NEW FEDERAL LAW WHICH WAS PASSED
 WHICH WILL MAKE ALL INCANDESCENT LIGHT OBSOLETE.
  
 (9) NOTE: PLEASE SEE THE FOLLOWING LOCATIONS SHALL
 CONTAIN EMERGENCY BATTERY BACK UP LIGHTS OF SOME KIND.
  
 10) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTES WITH
 RESPECT TO HB 7121 AND MINIMUM REQUIRED FUEL BACK UP
 FOR THE GENERATOR. THIS INFORMATION WAS PROVIDED
 HOWEVER THE ITEMS WHICH ARE REQUIRED TO BE ON THE
 GENERATOR WILL BE ALL REQUIRED LIFE SAFETY SYSTEMS IF
 BUILDING IS GOING TO BE OCCUPIED. THE NORMAL OCCUPANCY
 UNDER EMERGENCY POWER WILL REQUIRE THE LIFE SAFETY
 SYSTEMS SUCH AS VENTILATION, CO SENSORS, ETC.
 ** EVEN AS SHOWN IF THE EMERGENCY GENERATOR IS RUNNING
 AND EMERGENCY PANELS ARE BEING FED FROM THE BACK UP
 SOURCE, ALL LOADS ON PANELS WOULD BE *ON*.HOW IS IT
 THAT ALL THESE OTHER LIFE SAFETY REQUIRED LOADS WOULD
 BE TURNED OFF? LOAD SHEDDING?
 HOW CAN REQUIRED LIFE SAFETY SYSTEMS BE ON ANY LOAD
 SHEDDING?
 THESE SCENARIOS ARE NOT POSSIBLE. ALL SYSTEMS ON THE
 LIFE SAFETY OR LEGALLY REQUIRED SYSTEMS SHALL BE ALL BE
 ON THE BACK UP SOURCE DURING BUILDING OCCUPANCY.
  
 11) NOTE:PLEASE SEE PREVIOUS REVIEW NOTES WITH
 RESPECT TO THE MINIMUM LEVELS REQUIRED FOR HORNS AND
 STROBES. THE RESPONSE WAS TO SEE REVISED NOTES ON PLANS
 HOWEVER THE REVISE NOTES ONLY QUOTED THE CODE SECTIONS.
 IN FACT THE WORDING ONLY STATED THE CANDELA LEVELS. IN
 EITHER CASE THE CODES OR IN THIS CASE CODES ARE NOT
 PERMITTED TO BE QUOTED IN LIEU OF ACTUALLY MINIMUM
 LEVELS REQUIRED.
 PLEASE BE SURE TO SEE THE LEVELS IN THE FBC AS NOTED
 AND PLEASE BE SURE TO GO OVER DESIGN FOR LEVELS NEEDED
 IN LOCATIONS AS WELL AS THE LOCATIONS REQUIRED FOR
 ADA.
 FBC 11-4.28.1,.2 AND .3.CANDELAS ARE .3(4).
  
 12) NOTE: PLEASE KNOW AS THE FIRE PUMP HAS NOT YET BEEN
 CLEARED UP TOP WHETHER OR NOT THE FIRE PUMP IS
 ELECTRICAL OR DIESEL THE FUEL REQUIRED ON THE GENERATOR
 CAN NOT BE CONFIRMED TO MEET NFPA-20 9.6.2.2
  
 13) NOTE: PLEASE SEE PREVIOUS NOTE WITH RESPECT TO THE
 POOL REQUIRED EQUAL-POTENTIAL BONDING GRID. THE PLANS
 DO CONTAIN A DETAIL AND SHOW ALMOST ALL REQUIRED ITEMS
 HOWEVER THEY DO NOT SHOW THE DETAIL FOR ONE OF THE
 REQUIRED METHODS UNDER THE NEW CODE.
 NO GRID, NO GROUND RING WITH FOUR BONDING LOCATIONS
 ETC.
 PLEASE SEE 680.26 OF THE 2005 NEC WITH THE FLORIDA
 BUILDING COMMISSION UPDATE FOR THE EXECUTIVE ORDER
 SENATE BILL 2836 RELEASED DATED JUNE 19, 2007.
 SEPARATELY).
  
 14) NOTE: PLEASE VERIFY WHERE THE INFORMATION IS FOR
 SITE LIGHTING POLES. PREVIOUS NOTE:
 PLEASE PROVIDE WIND LOADS AND INFORMATION FOR SITE/ROOF
 TOP POLES WHICH ARE REQUIRED TO MEET FBC 140MPH.
 THIS WILL BE REVIEWED ONCE SUBMITTED BY THE STRUCTURAL
 REVIEWER. PLEASE KNOW THE EFFECTIVE PROJECTED AREA
 (EFA) OF FIXTURE.
 FBC 106.1.2
  
 15) NOTE: PLEASE SEE FBC 3006.2 AS EACH ELEVATOR
 EQUIPMENT ROOM SHALL CONTAIN A DEDICATE AIR
 CONDITIONING SYSTEM. THIS IS A NEW NOTE HOWEVER
 REQUIRED WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADES.
  
 16) NOTE: PLEASE SEE LIGHTING CONTROLS IN SOME AREAS DO
 NOT MEET FBC 13-415.1.ABC.1.1, .1.2. NOT ALL AREAS IN
 THIS BUILDING ARE 24HRS OR REQUIRED FOR SECURITY.
 PLEASE SEE LOCATIONS SUCH AS COMMON ARE BATHROOMS,
 STORAGE ROOMS ETC.
 PLEASE BE SURE TO SEE FBC 1016.1 AND LS 101 7.8.1.2.2
 WHEN OCCUPANCY DEVICES ARE USED IN AREAS OF EGRESS THE
 DEVICES ARE REQUIRED TO BE FAIL SAFE ON.
  
 17) NOTE: PLEASE VERIFY HOW ALL EXTERIOR LIGHTS MEET
 FBC 13-415.1.ABC.1.4. IF ANY ON TIME CLOCK, PLEASE BE
 SURE TO SPECIFY THE REQUIRED ASTRONOMICAL TIME CLOCK
 WITH THE MINIMUM 10HR BATTERY BACK UP.
  
 18) NOTE: PLEASE SEE NFPA-110, NFPA-101 AS ANY
 COMMUNICATION SYSTEMS SUCH AS THE PHONE EQUIPMENT WHICH
 REQUIRE LINE VOLTAGE TO POWER SYSTEMS SHALL BE ON
 BATTERY BACK UP AND/OR ON GENERATOR CIRCUITS. ANY
 COMMUNICATION SYSTEMS USED FOR FIRE LIFE SAFETY ARE
 ALSO REQUIRED TO CONTAIN BACK UP POWER.
 SOME PHONE BOARD RECEPTACLES ARE SHOWN ON NORMAL POWER
 PANELS AT THIS TIME.
 THIS IS A NEW COMMENT.
 4.4.1 TYPICALLY, LEVEL 1 SYSTEMS ARE INTENDED TO
 AUTOMATICALLY SUPPLY ILLUMINATION OR POWER, OR BOTH, TO
 CRITICAL AREAS AND EQUIPMENT IN THE EVENT OF FAILURE OF
 THE PRIMARY SUPPLY OR IN THE EVENT OF DANGER TO
 ELEMENTS OF A SYSTEM INTENDED TO SUPPLY, DISTRIBUTE,
 AND CONTROL POWER AND ILLUMINATION ESSENTIAL FOR SAFETY
 TO HUMAN LIFE.
 LEVEL 1 SYSTEMS GENERALLY ARE INSTALLED IN PLACES OF
 ASSEMBLY WHERE ARTIFICIAL ILLUMINATION IS REQUIRED BY
 OTHER STANDARDS FOR SAFE EXITING AND FOR PANIC CONTROL
 IN BUILDINGS SUBJECT TO OCCUPANCY BY LARGE NUMBERS OF
 PEOPLE.
 EMERGENCY SYSTEMS CAN ALSO PROVIDE POWER FOR SUCH
 FUNCTIONS AS VENTILATION WHEN ESSENTIAL TO MAINTAIN THE
 FOLLOWING, AS WELL AS OTHER SIMILAR FUNCTIONS:
 (1)LIFE
 (2)FIRE DETECTION AND ALARM SYSTEMS
 (3)ELEVATORS
 (4)FIRE PUMPS
 (5)PUBLIC SAFETY COMMUNICATIONS SYSTEMS
 (6)INDUSTRIAL PROCESSES WHERE CURRENT
 INTERRUPTION WOULD PRODUCE SERIOUS LIFE SAFETY OR
 HEALTH HAZARDS
  
 19) NOTE: PLEASE SEE SOME AREAS WHICH ARE MISSING SOME
 RECEPTACLES PER 210.52. SOME ARE REDLINED ON PLANS.
 THESE COULD BE REDLINED ON PROJECT AS THEY ARE MINOR IN
 NATURE AND ONLY ONE OR SO IN UNITS D, A, PHA ARE
 MISSING ON 2FT OR MORE OF WALL IN BETWEEN KITCHEN AND
 DINING ROOM.
  
 20)NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT THE
 LIGHTING CONTROLS FOR UNITS WHICH CONTAIN UPPER
 ROOF/LEVEL SPIRAL STAIRS. PLEASE SEE SEVERAL OF THESE
 SHOWS A STANDARD SINGLE POLE SWITCH AT THE LOWER LEVEL.
 THESE APPEAR TO BE A MISPRINT AS THE SINGLE POLE SWITCH
 IN SOME AREAS WHICH CONTROL THE HALF SWITCHED
 RECEPTACLE ACTUALLY SHOWS A THREE WAY SWITCH. THE
 DESIGNATIONS SEEM TO BE REVERSED.
 PLEASE ADJUST.
 210.70, LS 101 7.8
  
 21) NOTE: PLEASE SEE THE LOADS FOR STORAGE TYPE WATER
 HEATERS ARE REQUIRED TO BE SHOWN AND FIGURED INTO
 CALCULATIONS AT 125%.
 PLEASE SEE THE PREVIOUS REVIEW COMMENTS WHICH INCLUDED
 THE TEXT WHICH WAS EXTRACTED DIRECTLY FROM THE 2005
 NEC. PLEASE READ THE LAST SENTENCE IN THE CODE
 COMMENTARY AS THIS STATES THE LOADS WILL HAVE AN AFFECT
 ON THE FEEDERS AND THE SERVICES. THUS THE CONTINUOUS
 LOADS OF 125%.
 PLEASE SEE THE FOLLOWING WHICH IS SHOWN DIRECTLY FROM
 THE NEC.
  
 *THE REVISION TO 422.13 SPECIFICALLY IDENTIFIES AN
 ELECTRIC WATER HEATER WITH A STORAGE CAPACITY OF 120
 GAL OR LESS AS A CONTINUOUS LOAD. THIS REVISION
 REQUIRES THE BRANCH CIRCUIT OVERCURRENT DEVICE AND
 CONDUCTORS TO BE SIZED BASED ON 125 PERCENT OF THE
 WATER HEATER NAMEPLATE RATING UNLESS THE OVERCURRENT
 DEVICE AND THE ASSEMBLY IT IS INSTALLED IN ARE LISTED
 TO BE USED AT 100 PERCENT OF ITS CONTINUOUS CURRENT
 RATING. IN ADDITION, FEEDERS AND SERVICES THAT SUPPLY
 WATER HEATER BRANCH CIRCUITS ARE ALSO IMPACTED BY THE
 FACT THAT THIS TYPE OF EQUIPMENT IS CONSIDERED TO BE A
 CONTINUOUS LOAD.*
  
 THE LAST SENTENCE STATES IMPACT ON FEEDERS, SERVICES.
 PLEASE SEE DEFINITIONS IN NEC 100 OF CONTINUOUS LOADS
 AND 215.3, 230.42 FOR FIGURING ADDITIONAL LOADS.
  
 22) NOTE: PLEASE CLARIFY WATER HEATERS SHOWN ON THE
 INPUT DATA REPORT OF THE ENERGY CALCULATIONS AND THOSE
 WHICH ARE SHOWN ON PLANS FOR HOUSE LOADS.
 PLEASE SEE A WH-3 IS SHOWN, WHERE ARE THE OTHERS?
 13-400.3.A, 13-412.1.ABC
  
 23) NOTE: PLEASE TALE A LOOK AT THE UNIT METER CENTER
 CALCULATIONS WHICH DO NOT LIST ANY WATER HEATERS AT
 ALL.
 NEC 220
  
 24) NOTE: PLEASE SEE NEC 700.9 AS WIRING AND POWER
 DISTRIBUTION TO EMERGENCY LOADS SHALL BE SEPARATED FROM
 OTHER LOADS FOR LEGALLY REQUIRED AND ANY OPTIONAL
 STAND-BY SYSTEMS.
 PLEASE SEE EXPLANATORY SECTION OF NEC AND NFPA-110
 THERE IS AN EXCEPTION TO EMERGENCY AND LEGALLY
 REQUIRED LOADS IN SAME PANEL HOWEVER THE PANEL AS SHOWN
 AND SUBMITTED DOES NOT INCLUDE THIS.
  
 24) NOTE: PLEASE SEE THE GENERATOR IS NOW SHOWN AT A
 SEPARATELY DERIVED SYSTEM TO ADDRESS PREVIOUS NOTE AS
 ATS WAS SHOWN AS 4-POLE, YET THE ATS IS NOW SHOWN AS
 3-POLE. HOW CAN THE GENERATOR BE SEPARATELY DERIVED
 WHEN THE ATS IS 3-POLE AND THERE IS NOT GROUNDING
 ELECTRODE SYSTEM FOR THE GENERATOR?
 PLEASE SEE 250.50, 250.20 ETC
 THE RESPONSE COMMENT REALLY DOES NOT APPLY TO THE
 PREVIOUS NOTE.
  
 25) NOTE: PLEASE SHOW THE OVER CURRENT PROTECTION ON
 THE GENERATOR FOR EACH OF THE BREAKERS AS SHOWN ON
 RISER. THE RISER NOTES DO NOT SEEM TO SHOW ANY
 INFORMATION AND UNABLE TO REVIEW SEVERAL CODE SECTIONS
 FROM CONDUCTOR SIZES, CONDUIT SIZES TO ANY MAGNETIC
 TYPE BREAKER FOR ANY ELECTRICAL FIRE PUMP.
 AS NOTED ABOVE IN NOTE #24, PLEASE PAY CLOSE ATTENTION
 TO WHETHER OR NOT THE GENERATOR WILL BE SEPARATELY
 DERIVED AS THESE BREAKERS AT THE GENERATOR MAY JUST
 BECOME THE FIRST MEANS OF DISCONNECT.
 240.4,310.16,445.13,250.24,250.6,250.24 ETC
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 26) NOTE: PLEASE KNOW AFTER THE LAST MEETING WITH
 ARCHITECT AND OWNER OF PROJECT IT WAS SAID A SEPARATE
 MEETING FOR MEP ENGINEERS AND PLANS REVIEW STAFF WAS
 GOING TO TAKE PLACE. TO DATE, AFTER THE LAST MEETING NO
 MEETING WAS EVER SCHEDULED WITH THIS REVIEWER AND NO
 PHONE CALLS WERE MADE TO GO OVER COMMENTS.
 IT IS SUGGESTED AT A MINIMUM IF THERE ARE ANY QUESTIONS
 TO AT LEAST CALL BY PHONE TO GO OVER COMMENTS. SOME
 CODE SECTIONS WERE REPEATED, SOME ARE NEW AND SOME HAVE
 YET TO BE ANSWERED.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-30 Cont ID  
Sent By dpalmer Date 2007-03-30 Time 15:44 Rev Time 0.00
Received By dpalmer Date 2007-03-24 Time 19:54 Sent To  
Notes
2007-03-30 15:45:32****** UNSAT *****
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
 ** PLEASE KNOW AS THE PLANS ARE NOT COMPLETE WITH SOME
 INFORMATION AS NEEDED FOR REVIEW, ONLY A REVIEW OF
 SUBMITTED PLANS COULD BE DONE.
  
 *** FLAGLER BEACH CLUB ***
  
 ** PLEASE KNOW THAT AS SOME INFORMATION HAS NOT BEEN
 SUBMITTED FOR REVIEW YET THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW.
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 PLEASE SEE SHEETS WHICH CONTAIN REFERENCES TO THE 2001
 FBC AND 2002 NEC.
 PLEASE SEE MANY LOCATIONS ON ELECTRICAL PLANS WHICH
 REFLECT CODES WHICH ARE FROM THE 2002 NEC ALSO. 2005
 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2003 NFPA-20
 2002 NFPA-110
 ** SOME OP THESE CODES MAY BE PRESENT ON PLANS HOWEVER
 PLEASE SEE PLANS FOR ELECTRICAL AS THERE ARE SEVERAL
 CODE SECTIONS WHICH ARE REFLECTED ON PLANS FROM THE
 PREVIOUS CODES AND ANY NEW CODE SECTIONS SHOULD BE
 REFLECTED.
  
 2) NOTE: PLEASE SEE THAT ALL SHEETS MUST CONTAIN TITLE
 BLOCKS FOR DESIGNERS OR RECORD WITH ALL INFORMATION AS
 REQUIRED PER FAC 61G15-23.002 AND 61G1-16.004. PLEASE
 SEE SHEET 358-9
  
 3) NOTE: PLEASE SEE MISSING LICENSE INFORMATION FOR
 LANDSCAPE ARCHITECT TITLE BLOCKS. FS 481.219 AND FAC
 61G1-16.004
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER, MISSING
 PRINTED NAME.
  
 4) NOTE: PLEASE SEE THE SEAL FOR THE LANDSCAPE
 ARCHITECT DOES NOT MEET THE FAC 61G1-16.002
 THE SEAL IS OF SIZE REQUIRED. 2 INCHES MINIMUM.
  
 5) NOTE: PLEASE KNOW THAT ALL PLANS SHALL CONTAIN
 ORIGINAL SIGNATURES, DATES AND RAISED SEALS FROM ALL
 DESIGN PROFESSIONALS. PLEASE SEE FS 471.025 AND
 481.221
  
  
 6) NOTE: PLEASE SEE FBC 2004 W/ 2006 FOR THE FLORIDA
 ENERGY CODE AND RELEVANT CODES FOR THIS BUILDING.
 PLEASE SEE THERE ARE AREAS WHICH DO NOT SHOW LIGHTING
 CONTROLS AS REQUIRED PER 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE SEE THAT THE ENERGY CALCULATIONS DO NOT INDICATE
 AUTOMATED CONTROLS FOR LIGHTING. SHOWS MANUAL ON/OFF
 FOR CONTROL METHODS.
 PLEASE SEE THE ELECTRICAL LIGHTING FIXTURES ON PLANS,
 LEGEND AND ENERGY CALCULATIONS DO NOT CORRELATE. PLEASE
 SEE 13-415.2 FOR PERFORMANCE OF INTERIOR LIGHTING.
 PLEASE PROVIDE INFORMATION IN DETAIL FOR THIS.
  
 PLEASE SEE THE ENTIRE REVISED CHAPTER 13 WITH THE 2006
 REVISIONS TO THE 2004 FBC ALONG WITH THE EXISTING IN
 THE 2004.
  
 7) NOTE: PLEASE CLARIFY ELEVATOR PIT/ROOM FOR GARAGE
 ELEVATOR.
 PLEASE SEE NEC 620 AS THIS COULD NOT BE FULLY LOCATED
 ON PLANS.
  
 8) NOTE: PLEASE SUBMIT THE MANUFACTURE?S SPECS/CUT
 SHEETS FOR THE FOLLOWING.FIRE PUMP, FIRE PUMP
 CONTROLLER, GENERATOR, ATS, FUEL TANK(S).
 PLEASE KNOW ANY OTHER EQUIPMENT SPECS MAY BE REQUESTED
 FROM OTHER TRADES.
 110.3, 90.7.
 FBC 106.1.2
  
 9) NOTE: PLEASE SEE THE FOLLOWING LOCATIONS SHALL
 CONTAIN EMERGENCY BATTERY BACK UP LIGHTS OF SOME KIND.
  
 GENERATOR ROOM (TO A LEVEL OF 30FT CANDLES), FIRE
 COMMAND ROOM, MAIN ELECTRICAL ROOM,ELEVATOR EQUIPMENT
 ROOM(S).
 PLEASE SEE NEXT NOTE WITH RESPECT TO STAIRS.NFPA-70
 110.26, 700.16, 700.12E, NFPA-110 7.3, NFPA-20 5.12.3,
 AND .4, NFPA-72 CHAPTER 2 FOR FCRM.
  
 10) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR
 STAIRS FOR BOTH UNDER NORMAL AND UNDER EMERGENCY
 CONDITIONS.
 PLEASE SEE THE HALLWAY EGRESS AREAS WHICH DO NOT
 INDICATE ANY BATTERY BACK UP FIXTURES.
 PLEASE KNOW AS THIS BUILDING MAY BE OCCUPIED AFTER
 POWER FAILURE DUE TO A STORM, THE SINGLE FAILURE OF A
 SINGLE OCP DEVICE WILL PLACE EGRESS HALLS IN TOTAL
 DARKNESS OR DURING AN EMERGENCY THE LIGHTING FOR COMMON
 AREAS HALLS AND FAILURE OF THESE WILL PLACE AREA IN
 DARKNESS. THIS ONLY REQUIRES MINIMUM LOCATIONS FOR
 MINIMUM LEVELS. (HALLS ARE 1FC UNDER EMERGENCY
 CONDITIONS.
 PLEASE SEE NFPA-101, 7.8., 7.9
  
 11 NOTE: PLEASE PROVIDE NOTES FOR FAIL SAFE OPERATION
 OF GATES/DOORS WHICH MAY NOT INTERFERE WITH EGRESS IN
 THE EVENT OF POWER FAILURE.
 PLEASE SEE NFPA-101 CHAPTER 7, 7.1.9,7.2.1.5.
  
 12) NOTE: PLEASE SEE DOORS ON WEST WALL WHICH SEEM TO
 SWING IN PATH OF EGRESS. PLEASE ALSO VERIFY THE MAKE UP
 AIR, AND/OR EXHAUST ALONG THIS SAME AREA OF EGRESS.
 PLEASE SEE THAT THIS MAY ALSO BE IN THE COMMENTS FROM
 OTHER TRADES.
 PLEASE VERIFY WITH ALL TRADES AND REVIEWER(S).
 FBC 106.1.2
  
 13) NOTE: PLEASE PLACE A SCHEDULE/ LIST FOR ALL
 COMPONENTS IN THE FIRE COMMAND ROOM AS REQUIRED PER
 NFPA-101 11.8.5
  
 14) NOTE: PLEASE COMPLETE ALL FIXTURE LEGENDS AS THE
 LIGHTING NEEDS TO BE DETERMINED AT THIS TIME AND TO
 CORRELATE AS NOTED IN NOTE FOR FBC CHAPTER 13. THE
 LEGEND MENTIONS TBD BY OWNER; HOWEVER THIS INFORMATION
 IS NEED TO FOR REVIEW.
 PLEASE ALSO SEE THE EXTERIOR LIGHTING IS ALSO TO BE
 DETERMINED AND COORDINATED WITH ENERGY CALCULATIONS AND
 PLANS.
 FBC CHAPTER 13-415.1.ABC.1.4, 13-415.1.ABC.2,
 13-415.2.ABC.1.3 ETC
  
 15) NOTE: PLEASE BE SURE ALL DEVICE AND LEVELS FOR
 HORNS AND STROBES MEET FBC ADA 11-4.28, .1, .2 AND
 .3(4).
 PLEASE STATE ALL LEVELS PER FBC ADA AS THE PLANS
 CURRENTLY SHOW AND NOTE SEVERAL ITEMS TO NFPA- 72 AND
 OTHER STANDARDS.
 PLEASE KNOW THAT THE MINIMUM LEVELS REQUIRED IN THE FBC
 CHAPTER 11 FOR ADA ARE SUBSTANTIALLY HIGHER.
  
 16) NOTE: PLEASE PROVIDE ELEVATIONS FOR THE EPSS SYSTEM
 WHICH MUST MEET THE ELEVATIONS AS SET-FORTH ON THE
 100YEAR STORM SURGE CHARTS OR *SLOSH* CHARTS PER
 CHAPTER 7, 7.3.1 NFPA-110.
 PLEASE SEE THE ELEVATIONS FOR THE EQUIPMENT WHICH IS
 BEING SHOWN AT THE GARAGE SEEMS TO BE OK, HOWEVER THE
 LEVELS OF EPSS EQUIPMENT, FIRE PUMP, FIRE PUMP
 CONTROLLER, AND ALL EMERGENCY EQUIPMENT AT THE MAIN
 BUILDING NEEDS TO BE SHOWN AT 6 INCHES ABOVE.
  
 17) NOTE: PLEASE PROVIDE INFORMATION ON FUEL
 CONSUMPTION ON GENERATOR FOR 100% LOAD OF THE FIRE PUMP
 AND ALL EMERGENCY SYSTEMS PER 700 AND 701.
 PLEASE SEE NFPA-110, NFPA-20 9.6.2.2
 * THIS WILL ALSO BE IN ADDITION AND ALONG WITH
 INFORMATION FOR THE NEXT COMMENT.
  
 18) NOTE: PLEASE SEE THE NEW FLORIDA STATE STATUTES
 WITH RESPECT TO THE NEW HOUSE BILL 7121 WHICH WAS
 SIGNED INTO LAW JULY OF 07.
 PLEASE SEE THERE ARE SEVERAL STATUTES WHICH WERE
 AFFECTED. PLEASE SEE THAT AN INDUSTRY BULLETIN IS BEING
 PLACED IN WITH THE REVIEW NOTES AS ADDITIONAL
 INFORMATION.
 * PLEASE SEE THE ADDITIONAL STATUTES WHICH REQUIRED
 ON-SITE FUEL FOR A SPECIFIED AMOUNT OF TIME FOR THE
 EMERGENCY LOADS AS REQUIRED.
 *ONCE THIS INFORMATION IS READ AND STATUTES REVIEWED,
 PLEASE PROVIDE ALL INFORMATION AS REQUIRED ON PLANS AND
 DOCUMENTATION FOR REVIEW.
 PLEASE KNOW THAT SOME OF THIS INFORMATION WILL ALSO BE
 NEEDED BY THE FIRE MARSHAL, STATE BOARD FOR ELEVATORS
 ETC.
  
 19) NOTE: PLEASE BE SURE THE FOLLOWING STATEMENT IS
 PLACED ON PLANS AS REQUIRED PER FBC 109.3.6.4.4 PLEASE
 SEE A STATEMENT OF SIMILAR WORDING IS ALREADY ON THE
 LIFE SAFETY PLANS.
 * TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633, FLORIDA STATUTES*
  
 20) NOTE: PLEASE PLACE AN EMERGENCY BATTERY BACK UP
 FIXTURE OF SOME KIND IN THE LARGER BATHROOMS NEAR GYM
 ON PLANS. THESE REQUIRED PER LS 101 7.8, 7.9 PLEASE BE
 SURE TO SEE CHAPTER 13 AND 700.12E FOR CIRCUITING OF
 THESE.
  
 21) NOTE: PLEASE PROVIDE THE NORMAL AND EMERGENCY
 PHOTO-METRICS FOR ALL EGRESS PATHS. PLEASE KNOW THIS
 WOULD ALSO INCLUDE POOL DECK AREAS. ETC WHICH LEAD TO
 THE PUBLIC RIGHT OF WAY.
 LS 101 7.8, 7.9
 FBC 106.1.2
  
 22) NOTE: PLEASE PROVIDE NOTE FOR POOL AREA LIGHTS:
 LIGHTING SHALL BE INSTALLED A MINIMUM OF 5FT FROM
 WATERS EDGE FOR 120V W/GFI PROTECTION AND A MINIMUM OF
 10FT FOR LOW VOLTAGE TYPE FIXTURES. (WORDS TO THIS
 AFFECT)
 680.22, 411.4B
  
 23) NOTE: PLEASE PROVIDE NOTE FOR POOL AREA AND THE
 EQUAL-POTENTIAL BONDING GRID WHICH IS REQUIRED PER
 680.26. PLEASE KNOW THE POOL PERMIT WILL BE UNDER A
 SEPARATE PERMIT, HOWEVER AS THE STRUCTURAL ELEMENTS
 MOST LIKELY WILL BE IN PLACE BEFORE PERMITTING OF POOL,
 PLEASE INCLUDE NOTE AT THIS TIME.
  
 24) NOTE: PLEASE INCLUDE NOTE FOR ANY LIGHTNING
 PROTECTION SYSTEMS SHALL MEET NFPA-780. (EVEN WHEN
 PERMITTED SEPARATELY).
  
 25) NOTE: PLEASE PROVIDE WIND LOADS AND INFORMATION FOR
 SITE/ROOF TOP POLES WHICH ARE REQUIRED TO MEET FBC
 140MPH.
 THIS WILL BE REVIEWED ONCE SUBMITTED BY THE STRUCTURAL
 REVIEWER. PLEASE KNOW THE EFFECTIVE PROJECTED AREA
 (EFA) OF FIXTURE.
 FBC 106.1.2
  
 26) NOTE: PLEASE PROVIDE NOTE FOR NO NIGHT-TIME OR DUSK
 TO DAWN SWIMMING PERMITTED UNLESS THE INTENT IS THAT
 NIGHT-TIME SWIMMING WILL BE ALLOWED. IF THIS IS THE
 CASE PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR POOL AREA
 WHICH WILL BE REQUIRED TO BE STAMPED BY THE PALM BEACH
 COUNTY HEALTH DEPARTMENT.
 FBC 106.1.2
  
 27) NOTE: PLEASE BE SURE TO PROVIDE ALL ROOM AND AREA
 DESIGNATIONS ON PLANS. PLEASE KNOW SOME AREA
 DESIGNATIONS ARE NEEDED TO DETERMINE ARE USE AND REVIEW
 FOR CIRCUITING CODE COMPLIANCE AND USE. (DINING AREAS
 ETC)
 FBC 106.1.2
  
 28) NOTE: PLEASE PROVIDE MORE INFORMATION FOR ELEVATOR
 ROOMS AND THE DEDICATED CIRCUITS REQUIRED PER 620.22,
 23 AND 24. SOME OF THESE ARE SHOWN ON PLANS, HOWEVER
 NOT ALL.
 PLEASE SEE COMMENT #9 ABOVE WITH RESPECT TO LIGHTING
 REQUIRED.
 FBC 106.1.2
  
 29) NOTE: PLEASE SEE AREA OUTSIDE ELEVATOR #1, AS THE
 PRINT SEEMS TO HAVE MISSED IN PRINT.
  
 30) NOTE: PLEASE PROVIDE VOLTAGE DROP FOR THE SAME
 FEEDERS AND BRANCH CIRCUITS. WORST CASE FOR EACH AS
 LONGEST RUNS.
 PLEASE SEE FBC 13-413.ABC.1
  
 31) NOTE: PLEASE SEE NFPA-72, FBC FOR THE DEFINITIONS
 OF SMOKE DEVICES. PLEASE DETERMINE IF THESE ARE INDEED
 DEVICES WHICH ONLY DETECT AND DO NOT SOUND.
 IF DEVICES DETECT AND ONLY PROVIDE SIGNALING TO
 HORN/SIREN DEVICES THEN THESE WOULD BE SD/ SMOKE
 DETECTORS.
 IF DEVICES ARE 120V BATTERY BACK AS SHOWN ON PLANS
 WHICH DETECT AND SOUND, THEN THESE DEVICES WOULD BE
 CONSIDERED SA/ SMOKE ALARMS.
 PLEASE ADJUST PLANS.
 NFPA-72 11.5.1.1, 11.8.3
  
 32) NOTE: PLEASE SEE WHAT APPEARS TO BE MISSING GFI
 RECEPTACLES ON SOME PENINSULAS AND KITCHEN COUNTER
 SPACES IN KITCHENS PER 210.52C1-5. PLEASE SEE LOCATION
 OF SOME DO NOT SEEM TO MEET THE DISTANCE AS REQUIRED.
 PLEASE SEE SOME AREAS WHICH SHOWS WHAT APPEARS TO BE A
 WALL SPACE AND A COUNTER SPACE, HOWEVER AREA AND USE IS
 NOT CLEAR. SEE REDLINED PLANS FOR SOME OF THESE
 LOCATIONS.
  
 33) NOTE: PLEASE SEE SOME UNITS WHICH DO NOT APPEAR TO
 SHOW ANY LIGHTING FIXTURES IN SOME AREAS WHERE ARE
 LIGHT FIXTURE OF SOME KIND WILL BE REQUIRED. PLEASE ANY
 BEDROOM OR LIVING ROOM AREAS. SOME UNITS INDICATE
 KEYLESS FIXTURES. PLEASE SEE 210.70, LS 7.8 WHICH WILL
 REQUIRE A LIGHT FIXTURE IF SOME SORT INSTALLED FOR
 FINAL.
 PLEASE SEE SOME OF THESE AREAS ARE REDLINED ON PLANS.
  
 34) NOTE:PLEASE PROVIDE THE FLOOR CURB DETAIL FOR
 BUS-DUCT PENETRATIONS. PLEASE SEE THE RISER SHOWS THIS
 4? CURB, HOWEVER THIS IS REQUIRED IN A DETAIL WHICH
 GOES ALL THE WAY AROUND THE DUCT. (MAY NOT BE UP
 AGAINST A WALL WITH ONLY THREE SIDES WITH CURB. 368.10
 (C) 2 B.
  
 35) NOTE: PLEASE INCLUDE NOTE ON PLANS FOR PLACEMENT OF
 SA/SD DEVICES PER NFPA-72 2002 11.5.1.1, 11.8.3 PLEASE
 SEE SOME OF THE UNITS SHOW A CEILING LEVEL WHICH IS
 HIGHER THAN THE SMOKE DEVICES WHICH ARE ON A LOWER
 LEVEL. IF THE CEILINGS ARE 12INCHES OR GREATER IN
 HEIGHT, THEN THESE DEVICES MUST BE MOVED TO BE LOCATED
 WITHIN 12INCHES OF THE HIGHEST POINT OF A FLAT
 CEILING.
  
 36) NOTE: PLEASE SEE ANY BUILDING REVIEW COMMENTS WITH
 RESPECT TO ANY DOOR SWINGS IN HALLWAYS WHICH MAY AFFECT
 THE BACKGROUNDS OR LAYOUTS ON ELECTRICAL PLANS. THIS
 NOTE IS ONLY MADE FOR INFORMATIONAL PURPOSE ONLY AS
 SOME DOOR SWINGS MAY CONTAIN SOME DIRECTIONAL CHANGES.
  
 37) NOTE: PLEASE SEE AREAS AT PENTHOUSE LEVELS WHICH DO
 NOT INDICATE ANY LIGHTING OR STAIRS FOR ACCESS AND
 EGRESS FROM THESE AREAS WHICH DO NOT SHOW LIGHTING OR
 CONTROL FOR LIGHTING.
 210.70 NEC.
 NFPA 101 7.8
  
 38) NOTE: PLEASE SEE THAT ARC FAULT IS REQUIRED FOR ALL
 OUTLETS INCLUDINGRECEPTACLES, LIGHTS, FANS AND SMOKE
 ALARMS. PLEASE SEE ALL CIRCUITING. IT APPEARS MOST ARE
 SHOWN.
 PLEASE SEE 210.12.
  
 39) NOTE:PLEASE SEE 2005 NEC 422.13 FOR WATER HEATERS
 AND LOADS TO BE SHOWN AT 125%.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS BEING TAKEN FROM
 THE CODE.
 *THE REVISION TO 422.13 SPECIFICALLY IDENTIFIES AN
 ELECTRIC WATER HEATER WITH A STORAGE CAPACITY OF 120
 GAL OR LESS AS A CONTINUOUS LOAD. THIS REVISION
 REQUIRES THE BRANCH CIRCUIT OVERCURRENT DEVICE AND
 CONDUCTORS TO BE SIZED BASED ON 125 PERCENT OF THE
 WATER HEATER NAMEPLATE RATING UNLESS THE OVERCURRENT
 DEVICE AND THE ASSEMBLY IT IS INSTALLED IN ARE LISTED
 TO BE USED AT 100 PERCENT OF ITS CONTINUOUS CURRENT
 RATING. IN ADDITION, FEEDERS AND SERVICES THAT SUPPLY
 WATER HEATER BRANCH CIRCUITS ARE ALSO IMPACTED BY THE
 FACT THAT THIS TYPE OF EQUIPMENT IS CONSIDERED TO BE A
 CONTINUOUS LOAD.*
  
 40) NOTE: PLEASE SEE THE PANEL SCHEDULE SHALL INDICATE
 THE SPECIFIC ROOMS AND AREAS IN WHICH THEY FEED. THE
 USE OF GENERAL LIGHTS, OR RECEPTACLES WAS REVISED IN
 408.4 OF THE 2005 NEC FOR WHICH AREAS ETC ARE TO BE
 SPECIFIC.
 PLEASE SEE THE FOLLOWING TEXT TAKEN FROM THE NEC.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
  
 41) NOTE: PLEASE SEE ANOTHER REVISION TO THE 2005 NEC
 WAS TO REQUIRE ALL 15/20 AMP RECEPTACLES 120V WITHIN
 6FT OF A SINK IN A LAUNDRY ROOM ARE REQUIRED TO BE GFI
 OR GFI PROTECTED. 210.8A7.
 THIS DOES NOT CHANGE EVEN IF THE RECEPTACLE IS A
 DEDICATED POINT OF USE SINGLE RECEPTACLES.
  
 42) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES AND OTHER CIRCUITS
 ON PLANS.
 PLEASE SEE THAT MOST OF THE CIRCUITS ARE SHOWN HOWEVER
 SOME SEEM TO MISSING.
 PLEASE SEE SOME AREAS WHICH ARE BEING SHOWN AS COMMON
 AREAS YET THEY ARE BEING SHOWN BEING FED FROM THE
 UNITS. PLEASE ALSO SEE THESE SAME COMMON AREAS ARE
 BEING SHOWN BEING FED FROM THE HOUSE POWER.
 PLEASE SEE 210.25 AS COMMON AREAS ARE NOT TO BE FED
 FROM THE TENANT PANELS OR ELECTRICAL. SOME AREAS ARE
 REDLINED ON PLANS.
 408.4, 310.16, 240.4.
 FBC 106.1.2
  
 43) NOTE: PLEASE PROVIDE NOTES ON ELECTRICAL ROOMS/FIRE
 COMMAND ROOMS SHEETS ALONG WITH THE RISER SHEETS FOR
 REQUIREMENTS FOR SIGNAGE FOR ALL SERVICES, MAINS,
 LOCATIONS.
 230.2E, 700.8, 701.9 ETC
  
 44) NOTE: PLEASE VERIFY THE SIZE OF THE OPC ON THE
 JACUZZI AS THE LOAD IS BEING SHOWN AT 12KW AND THE
 CIRCUIT SHOWS 80AMP OCP.
  
 45) NOTE: PLEASE KNOW THAT ALL *LOCK-OFF/ON* DEVICES
 SHALL BE APPROVED BY THIS AHJ. THE DEVICE SHALL BE AN
 INTEGRAL PART OF THE BREAKER SO AS NOT TO BE REMOVED.
 PLEASE KNOW THAT SNAP-ON, CLIPS ETC WHICH READILY FALL
 OFF WHEN PANEL COVER IS REMOVED SHALL NOT BE USED.
 PLEASE PLACE NOT ON PLANS FOR THE TYPE REQUIRED. 110.3,
 90.7
  
 46) NOTE: PLEASE CORRELATE ALL FEEDERS ON RISER
 DIAGRAM.
 PLEASE SEE MAIN 1 TO MAIN OF BUILDING AS SHOWN IS RATED
 AT 1520AMPS,AND THIS IS A 2000AMP DEVICE.
 PLEASE SEE 240.4
 * PLEASE SEE SOME OF THE FEEDERS ONLY APPEARED TO BE
 MIS-LABLED. PLEASE SEE THERE ARE TWO SEPARATE FEEDERS
 INDICATED ON THE SAME CONDUIT.
  
 47) NOTE: PLEASE CLARIFY MAINS 2 AND 3 AT GARAGE. IS 1B
 A 1600AMP RATED MCB?
 IS THIS EQUIPMENT MLO WITH TWO MAINS?
 PLEASE SEE THAT NO MORE THAN 6 SPACES ARE PERMITTED IN
 EQUIPMENT WITH OUT THE USE OF A MCB.
 PLEASE SEE 230.70, 230.71.
 IF THIS EQUIPMENT IS TWO *MAINS* LOCATED ON THE SAME
 EQUIPMENT, THE EQUIPMENT SHALL CONTAIN A FACTORY
 INSTALLED DEAD-FRONT INSTALLED AND SHALL BE NOTED ON
 PLANS ACCORDINGLY.
  
 48) NOTE: PLEASE SEE THAT NO PANEL SCHEDULE OR
 INFORMATION FOR PANEL XG WAS SUBMITTED OR SHOWN ON
 PLANS.
 PLEASE SEE NO VERIFICATION FOR TAPPED CONDUCTORS,
 CIRCUITS, MAINS, ETC ARE SHOWN.
 408.36, 240.21.
  
 48) NOTE: PLEASE INDICATE THE GROUNDING ELECTRODE
 SYSTEM FOR THE SEPARATELY DERIVED GENERATOR AS THE ATS
 IS BEING NOTED AS 4-POLE. PLEASE SEE 250.20, 250.30,
 250.50 ETC.
 AS THIS SYSTEM/SERVICE AS SHOWN DOES NOT REQUIRE GF
 PROTECTION IN SERVICE, THIS IS NOT REQUIRED TO HAVE A
 SD SYSTEM, ALTHOUGH THIS MOST CERTAINLY MAY BE DONE.
 PLEASE CLARIFY THIS.
  
 49) NOTE: PLEASE SEE THE TOTAL LOADS FOR THE GENERATOR
 CAN NOT BE CONFIRMED AT THIS TIME AS THE PANEL/LOAD FOR
 XG WAS NOT SUBMITTED.
 PLEASE ALSO CLARIFY THE LOADS AS BEING SHOWN FOR THE
 EMERGENCY LOADS AS LOAD SHEDDING IS NOT SHOWN OR
 INDICATED.
 PLEASE SEE OTHER SECTIONS OF NOTES PERTAINING TO THE
 MINIMUM LOADS NOW REQUIRED BY FLORIDA STATUTES WHICH
 WILL REQUIRE ADDITIONAL LOAD AND USE OF FUEL ETC.
 PLEASE SUBMIT AND COMPLETE INFORMATION.
 700, 701, NEC 220. ETC
 FBC 106.3.5.1.2
  
 50) NOTE: PLEASE KNOW THAT A DETAILED RESPONSE LETTER
 FOR ALL OF THE ABOVE NOTES WILL HELP TO EXPEDITE THE
 REVIEW PROCESS.
  
 51) NOTE: PLEASE KNOW THAT THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW, SOME ITEMS CAN NOT BE REVIEWED AT
 THIS TIME FOR CODE COMPLIANCE.
  
 52) NOTE: PLEASE SEE LOAD CALCULATIONS AND THE SECTION
 OF THE CODES IN DIFFERENT PLACES WHICH ARE FROM THE
 PREVIOUS CODE. PLEASE SEE THE 2005 NEC AND UPDATE CODE
 SECTIONS.
 FBC 106.1.2
  
 53) NOTE: PLEASE INDICATE ALL CONTINUOUS LOADS AND
 LARGEST MOTOR LOADS AT 125% ON EACH PANEL AND THEN FOR
 THE SERVICE LOADS.
 230.42, 215.3 ETC.
 PLEASE SHOW IN LOAD CALCULATIONS.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-27 19:35:272007-03-27 19:35:27
 TO CONTINUE ON 3/28
2007-03-26 07:02:362007-03-26 07:02:36
 REVIEW IN PROGRESS
2007-03-25 14:30:312007-03-25 14:30:31
 REVIEW TO CONTINUE AND COMMENCE ON 3/26
2007-03-24 19:55:072007-03-24 19:55:07
 ON ROLLIN ELEC FOR REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-06-05 Cont ID  
Sent By rchokshi Date 2008-06-05 Time 14:29 Rev Time 0.00
Received By rchokshi Date 2008-06-05 Time 14:00 Sent To  
Notes
2008-06-05 14:29:10PLEASE PROVIDE FOLLOWING INFO:
  
 1.PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 2. PLEASE PROVIDE A COPY OF SFWMD PERMIT, STORM WATER
 QUALITY CALCULATION, & GEO TECH REPORT TO 1000 45TH
 STREET ENGINEERING SERVICES(JONATHAN BRAMLEY, DIRECTOR)
 TO APPROVE THEM. ONCE1000 45TH STREET ENG DEPT
 APPROVE THEM, PLEASE SEND A COPY OF SFWMD, STORM WATER
 QUALITY CALS, & GEO-TECH REPORT TO CONSTRUCTION SERVICE
 DEPT., AT CITY HALL.
  
 3. PLEASE SHOW SOMEWHERE ON DRAWING THE SITE AREA, YOU
 ARE DEVELOPING FOR THIS PROJECT,WHAT IS TOTAL
 PERVIOUS,& IMPERVIOUS AREA FOR THIS PROJECT. PLEASE
 SHOW ON THE DRAWING.
  
 4. PLEASE SHOW SILT FENCE DETAILS FOR POLLUTION
 PREVENTION, CLOTHES USED FOR THE SILT FENCE ETC., YOUR
 PLANS SHOULD SHOW SILT FENCE AROUND THE WHOLE SITE
  
 5. WATER & SEWER PLANS MUST BE APPROVED AND STAMPED
 FROM 45TH STREET (MANNY G.), UTILITY DEPT BEFORE WE
 APPROV
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-04-13 Cont ID  
Sent By rchokshi Date 2007-04-13 Time 14:04 Rev Time 0.00
Received By rchokshi Date 2007-04-13 Time 13:54 Sent To  
Notes
2007-04-13 14:04:13PLEASE PROVIDE FOLLOWING INFO:
  
 1. PLEASE SHOW STANDARDS NOTES OF CITY OF WPB ON
 DRAWINGSFOR SIDEWALK WIDTH , ITS SLOPE, DRIVEWAY,
 PARKING, HANDICAP PARKING, PAINTPER CITY CODES ETC.,,
 MUST MEET PER ADA,,ETC.,YOU CAN GET STANDARD NOTES OF
 CITY OFWPB IN A C.D. FROM 1000 45TH STREET. WE SHOULD
 HAVE THOSE NOTES ON YOUR DRAWINGS.
 2. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
 3. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD ,
 SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA &FL
 BUILDING CODE, FIRST FLOOR ELEVATION MUST MEET THESE
 MINIMUM REQUIREMENTS.
 4. PLEASE PROVIDE A COPY OF SFWMD PERMIT,,AND SHOW
 CALCULATION FOR LENGTH OF EXFILTRATION TRENCH, & SAFETY
 YOU USED IN LENGTH.
 5.PLEASE SHOW STORM WATER CALCULATIONS, WHAT CRITERIA
 YOU ASSUMEDFOR RUNOFF CAL.,, LIKE 1" OVER ENTIRE SITE
 OR2.5"CRITERIA, ETC?
 6. WHAT IS THE SITE AREA, YOU ARE DEVELOPING FOR THIS
 PROJECT ONLY ?ALSO, WHAT IS TOTAL PERVIOUS,& IMPERVIOUS
 AREA FOR THIS PROJECT.
 7. HOW YOU CONNECT TO THE STORM WATER PIPES IN YOUR
 SITE? ITS DETAILS.PLEASE SHOW ALL STORM WATER PIPES
 AROUND YOUR SITE SO, WE CANSEE THE BEST PIPE TO
 CONNECT WITH THE STORM WATERFROM ALL OTHER STORM
 WATER PIPES. PLEASE SHOW DETAIL OF THE CONTROL
 STRUCTURES WITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC DID YOU USE EXFILTRATION TRENCH ? 8.
 POLLUTION PREVENTION DETAILS,CLOTHES USED FOR SILT
 ETC., PLANS SHOWING SILT FENCE AROUND THE SITE
 9. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH
 STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED 10.
 ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND YOUR
 SITE FOR STORM WATER DRAIN.
 10. POLLUTION PREVENTION PLANS, SILT DETAILS, SILT MUST
 BE AROUND THE SITE BOARDER.
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-07-08 Cont ID  
Sent By mcarsill Date 2008-07-08 Time 14:52 Rev Time 0.00
Received By mcarsill Date 2008-07-08 Time 14:42 Sent To  
Notes
2008-07-08 14:52:021. THE FIRE DEPARTMENT CONNECTIONS (FDC'S) ON THE SITE
 SHALL BE EQUIPPED WITH KNOX-BOX LOCKING CAPS.
  
 2. THE USE OF PROPANE AND CHARCOAL GRILLS IN
 MULTI-FAMILY BUILDINGS ARE NOT PERMITTED. ONLY LISTED
 ELECTRIC TYPE EQUIPMENT IS ALLOWED.
  
 3. ON PAGE A601 EXIT DIRECTION MARKINGS LEAD TO
 OPENINGS. THESE LARGE OPENINGS CANNOT CONTAIN GATES OT
 OTHER DEVICES WHICH WILL NOT ALLOW FOR EXITING.
  
 4. ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED ON PAGE
 E-8.
  
 5. THE PROPOSED FIRE STANDPIPE SYSTEM FOR THE DOCKS
 SHALL COMPLY WITH NFPA 303. SEPARATE PLANS AND PERMITS,
 AND FDC ARE REQUIRED.
  
 6. ON PAGE SP-1.1 THE TYPICAL FIRE CABINET SHALL BE
 EQUIPPED WITH 2 1/2 TO 1 1/2 REDUCERS. ALL STANDPIPE
 CONNECTIONS SHALL ALSO BE EQUIPPED WITH THESE DEVICES.
  
 7. ON PAGE AC-15 SMOKE CONTROL SYSTEM SEQUENCE OF
 OPERATIONS INDICATES THAT SMOKE DETECTORS WILL ACTIVATE
 A SUPERVIOSRY SIGNAL. DUCT SMOKE DETECTORS SHALL
 ACTIVATE A GENERAL ALARM AND NOT A SUPERVISORY SIGNAL.
  
 8. ALL ASSOCIATED DAMPERS SHALL BE DROP TESTED TO
 ENSURE PROPER OPERATION AFTER INSTALLATION.
  
 9. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM EQUIPMENT PLANNED FOR
 BUILDINGS 1 & 2.
  
 10. PLEASE CORRECT BUILDING CODE AND FIRE DEFICIENCIES
 AS IDENTIFIED BY THE CONSTRUCTION SERVICES PLAN
 REVIEWER.
  
 11. ALL CONSTRUCTION METHODS AND INSTALLATION METHODS
 ARE SUBJECT TO FIELD INSPECTION AND APPROVAL.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-05-08 Cont ID  
Sent By mcarsill Date 2007-05-08 Time 17:03 Rev Time 0.00
Received By mcarsill Date 2007-05-08 Time 16:23 Sent To  
Notes
2007-05-08 17:03:151. SITE PLAN DOES NOT ILLUSTRATE ANY FIRE HYDRANTS.
  
 2. BUILDING 1 AND BUILDING 2 SHALL BE BE FIRE SPRINKLER
 PROTECTED IN ACCORDANCE WITH FS 553.895 (2).
  
 3. THE DEPICTED ENTRY CONFIGURATION SHALL BE DESIGNED
 SO AS TO BE UTILIZED BY FIRE RESCUE.
  
 4. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 5. EXIT STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION.
  
 6. SUITABLE ROADS THAT CAN SUPPORT FIRE APPARATUS SHALL
 BE PROVIDED DURING CONSTRUCTION ACTIVITIES.
  
 7. TEMPORARY STANDPIPE SYSTEMS ARE REQUIRED WHEN THE
 BUILDING REACHES THREE STORIES OR THIRTY FEET IN
 HEIGHT.
  
 8. STANDPIPE SYSTEM FOR FUTURE DOCK MUST BE PERMITTED.
  
 9. DEBRIS SHALL BE REMOVED FROM THE SITE AND BUILDING
 DAILY.
  
 10. PLEASE INDICATE WHAT SAFETY PRACTICES WILL BE
 EMPLOYED WHEN THE TORCH APPLIED ROOFING MATERIALS ARE
 INSTALLED.
  
 11. PLEASE EXPLAIN STAIRS THAT ARE ABSENT OF DOORS.
  
 12. PLEASE INDICATE ON THE PLANS THAT VOID SPACES WILL
 NOT BE USED FOR ANY PURPOSE.
  
 13. ANY SECURITY FEATURES PLANNED SHALL NOT INTERFERE
 WITH ANY EXITING FROM THE BUILDING.
  
 14. PLEASE ILLUSTRATE ON THE PLANS THAT ALL EXTERIOR
 STAIRS AND RAMPS WILL BE SLIP RESISTANT.
  
 15. PLEASE EXPLAIN WHY THE PARKING AREA ON THE GROUND
 FLOOR OF BUILDING THREE ONLY HAS A ONE HOUR FIRE
 RATING.
  
 16. ELEVATOR WARNING SIGNS ARE REQUIRED.
  
 17. KNOX-BOXES WILL BE REQUIRED FOR THE BUILDING.
  
 18. ARCHITECTURAL FEATURES SUCH AS SOFFITS SHALL NOT
 INTERFERE WITH WITH THE OPERATION OF ANY FIRE SPRINKLER
 HEADS.
  
 19. SINCE BUILDING THREE WILL BE CONSIDERED A HIGH-RISE
 BUILDING, ALL OF THE REQUIREMENTS SHALL BE MET OF THE
 FLORIDA FIRE AND BUILDING CODE.
  
 20. THE LOBBY APPEARS TO BE AN ATRIUM AND THE REQUIRED
 PROTECTION FOR AN ATRIUM SHALL BE PROVIDED.
  
 21. THE NOTE FOR EGRESS WINDOWS ON PAGE A201 DOES NOT
 INDICATE A MAXIMUM SILL HEIGHT.
  
 22. ELEVATION DRAWING DOES NOT DISPLAY BUILDING
 ADDRESS. A MINIMUM OF AT LEAST 6" HIGH NUMBERS WITH 1"
 IN WIDTH SHALL BE PROVIDED.
  
 23. SERVICE ELEVATOR DOORS LOCATED NEAR STAIR # 2 SHALL
 BE MARKED "NO EXIT" SINCE IT IS IN CLOSE PROXIMITY TO
 THE STAIR # 2 EXIT DOOR.
  
 24. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR
 LOCATIONS.
  
 25. STAIRWELL IDENTIFICATION SIGNS REQUIRED. THESE
 SIGNS SHALL IDENTIFY THE STAIR IDENTITY, FLOOR LEVEL,
 AND TERMINUS TOP AND BOTTOM.
  
 26. ALL FIRE AND SMOKE DAMPERS SHALL BE DROP TESTED
 AFTER INSTALLATION TO ENSURE PROPER OPERATION.
  
 27. THE CARBON MONOXIDE DETECTORS SHOWN ON PAGE AC-01
 SHALL BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS
 INSTRUCTIONS. SPACING AND AREA TO BE COVERED SHALL NOT
 EXCEED THESE REQUIREMENTS.
  
 28. MORE DETAILS NEEDED ON THE RECIRCULATION
 RESIDENTIAL EXHAUST HOOD DISPLAYED ON PAGE AC-07.
  
 29. PLEASE PROVIDE AN ELEVATION DRAWING OF THE
 GENERATOR EXHAUST AND STAIR DISPLAYED ON PAGE AC-12.
  
 30. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 COMPLETE INSTALLATION OF THE AUTOMATIC FIRE SPRINKLER
 SYSTEMS.
  
 31. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 INSTALLATION OF THE FIRE ALARM SYSTEM.
  
 32. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A UL
 LISTED CENTRAL STATION APPROVED FOR CENTRAL STATION
 SERVICE.
  
 33. PLEASE INDICATE WHAT THE VOICE EVACUATION MESSAGE
 WILL SAY WHEN THE REQUIRED FIRE ALARM SYSTEM IS
 ACTIVATED.
  
 34. PLEASE INDICATE ON THE PLANS WHAT UL LISTINGS THAT
 THE 500 GALLON FUEL TANK WILL HAVE.
  
 35. PLEASE DECLARE ON PAGE P-15 THAT THE GAS
 INSTALLATION WILL COMPLY WITH NFPA 54.
  
 36. THE FDC SHOWN ON PAGE SP-1.1 SHOULD BE ROTATED TO
 FACE SOUTH. HOSE MAY KINK THE WAY IS IS POSITIONED.
  
 37. WHY ARE BUILDINGS 1 & 2 SHARING A FD CONNECTION.
  
 38. FIRE SPRINKLER HEADS THAT ARE LOCATED OUTSIDE SHALL
 BE WAX OR CORROSION RESISTANT.
  
 39. SOME DRAWINGS ILLUSTRATE THAT CLOSETS ARE FIRE
 SPRINKLER PROTECTED AND SOME ARE NOT. PLEASE PROVIDE
 DETAILS ON THE PLANS.
  
 40. PLEASE PROVIDE MORE DETAILS ON THE PRESSURE
 RESTRICTING AND PRESSURE REGULATING DEVICES PLANNED FOR
 USE. WILL THESE DEVICES BE FACTORYOR FIELD ADJUSTED.
  
 41. THE BACKFLOW DEVICE SHOWN ON PAGE SP-14 SHALL BE
 EQUIPPED WITH A CHAIN AND LOCK.
  
 42. PLEASE VERIFY ALL DOORS THAT NEED TO BE RATED AS TO
 THE RATING AND TYPES THAT CAN BE USED.
  
 43. ELECTRIC POWERED SMOKE DETECTORS SHALL BE PROVIDED
 ON EVERY LEVEL OF THE RESIDENTIAL UNITS.
  
 44. WET FIRE HYDRANTS ARE REQUIRED PRIOR, TO DURING,
 AND AFTER CONSTRUCTION.
  
 45. THE FLORIDA FIRE PREVENTION CODE REQUIRES THAT
 EMERGENCY INSTRUCTIONS BE PROVIDED TO THE RESIDENTS.
 PLEASE ADVISE HOW THIS WILL BE ACCOMPLISHED AND ENSURE
 THAT THIS REQUIREMENT IS PLACED ON THE PLANS.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-07-02 Cont ID  
Sent By kstevens Date 2008-07-02 Time 07:35 Rev Time 0.00
Received By kstevens Date 2008-07-02 Time 07:35 Sent To  
Notes
2008-07-02 07:37:02 
  
  
  
 PASSED/PROVISO
  
 BTU LOAD NOT SHOWN ON MANUF. SPECIFICATION SHEETS. BTU
 LOAD WILL BE VERIFIED BY FIELD INSPECTOR AT THE TIME OF
 FINAL GAS INSPECTION. BTU LOAD SHALL BE INDICATED ON
 THE BOILER.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-04-23 Cont ID  
Sent By kstevens Date 2007-04-23 Time 07:58 Rev Time 0.00
Received By kstevens Date 2007-04-23 Time 07:57 Sent To  
Notes
2008-07-01 08:06:30DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT P-15GAS PIPING RISER DIAGRAM. PLEASE SUBMIT
 THE CALCULATION FOR EQUATION 4-2.--SUBMIT
 MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND,
 AS WELL AS THE RETURN OF THE RED LINED SET OF PLANS
 FROM THE FIRST REVIEW, WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-20 Cont ID  
Sent By adarroug Date 2008-05-20 Time 08:44 Rev Time 0.00
Received By adarroug Date 2008-05-20 Time 08:44 Sent To  
Notes
2008-05-20 08:46:24TO "COMM" BD#53--PLANS ON RACK/4 ROLLS AND PAPERWORK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-05-08 Time   Rev Time 0.00
Received By adarroug Date 2007-03-13 Time 14:19 Sent To  
Notes
2007-03-19 14:21:20TO "COMM" BD#11/PLANS ON RACK, 3 ROLLS

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-06-16 Cont ID  
Sent By rregueir Date 2008-06-16 Time 08:59 Rev Time 0.00
Received By rregueir Date 2008-06-04 Time 14:57 Sent To  
Notes
2008-06-16 08:59:33REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1 THROUGH 3: OK
  
 4. NOT ALL PLENUM CLOSET DOORS HAVE BEEN CORRECTLY
 DESIGNATED AS METAL DOORS. EXAMPLE: IN MANAGER OFFICE
 A116, THE CLOSET FOR AC-7 SERVES AS A PLENUM AND HAS A
 #8 DOOR DESIGNATION ON PG A101. COMMON AREA DOOR
 SCHEDULE ON PG A400 SHOWS A #8 DOOR TO BE A WOOD DOOR.
 PLEASE CHECK AND VERIFY ALL DOORS ON PLENUM CLOSETS ARE
 CORRECTLY DESIGNATED ON PLANS TO DEMONSTRATE COMPLIANCE
 WITH FBCM 602.2.1.
  
 5 THROUGH 7: OK
  
 8. THE WRITTEN RESPONSE TO THIS COMMENT INDICATES THE
 PRESENCE OF PERMANENT OPENINGS TO BE USED IN
 CONJUNCTION WITH THE CIRCULATION FANS TO PROVIDE THE
 CONTINUOUS VENTILATION RATE OF 0.05 CFM/SF. PAGE A101
 NOW SHOWS ROLLUP DOORS AT THE LOCATION OF THE
 PREVIOUSLY PERMANENT OPENINGS. FOR THIS REASON, ANOTHER
 MEANS OF INTRODUCING OUTSIDE AIR FOR GARAGE VENTILATION
 IS REQUIRED FOR BOTH THE CONTINUOUS AND THE ELEVATED
 VENTILATION RATE IN ACCORDANCE WITH FBCM 403.2 AND FBCM
 4042.
  
 9. OK
  
 10. SEQUENCE OF OPERATIONS FOR GARAGE EXHAUST WILL BE
 AFFECTED BY COMMENT #8 ABOVE.
  
 11. SMOKE CONTROL RATIONAL ANALYSIS HAS BEEN RECEIVED.
 THE SMOKE CONTROL SYSTEM WILL BE REVIEWED AT THE END OF
 THIS REVIEW.
  
 12 AND 13: OK
  
 14. NEW SUPPLY FANS HAVE BEEN ADDED SINCE LAST REVIEW.
 SF-3, 4, 5, 6 ALL EXCEED 2000 CFM AND REQUIRE FAN
 SHUT-DOWN BY SMOKE DETECTOR IN ACCORDANCE WITH FBCM
 606.1.1. PROVIDE DUCT SMOKE DETECTORS ON THE SUPPLY
 SIDE OF THESE FANS TO DEMONSTRATE COMPLIANCE WITH THIS
 SECTION.
  
 15 THROUGH 23: OK
  
 24: IT IS THE DETERMINATION OF THE BUILDING OFFICIAL
 THAT THE REQUIREMENT FOR FAN SHUT-DOWN BY SMOKE
 DETECTOR SHALL BE DETERMINED BASED ON THE CAPACITY OF
 THE AIR HANDLING APPLIANCE. PROVIDE DOCUMENTATION FROM
 THE APPLIANCE MANUFACTURER INDICATING THAT THIS
 APPLIANCE IS NOT CAPABLE OF PRODUCING AIR VOLUMES IN
 EXCESS OF 2,000 CFM UNDER ANY CONFIGURATION. IN LIEU OF
 THIS INFORMATION, FAN SHUT-DOWN BY SMOKE DETECTOR IS
 REQUIRED.
  
 25 THROUGH 27: OK
  
 28. THE NOTES ON PAGE AC-12 RELATED TO LOUVERS FOR THE
 GENERATOR ROOM ARE CUT-OFF AND CAN NOT BE READ. PLEASE
 CORRECT AND RESUBMIT. OTHERWISE, THIS COMMENT IS
 ADEQUATELY ADDRESSED.
  
 29 THROUGH 33: OK
  
 34. SMOKE CONTROL TO BE REVIEWED AT THE END OF THESE
 COMMENTS/RESPONSES.
  
 35. OK
  
 36. SEE COMMENT #24 ABOVE.
  
 37 THROUGH 44: OK
  
 45. PART (3): HP DETAIL CALLS FOR ? INCH COPPER
 CONDENSATE DRAIN AND TRAP. THIS APPEARS TO BE A
 TYPOGRAPHICAL ERROR. PLEASE CORRECT AND RESUBMIT.
  
 46. OK
  
 47. THE ADDRESS ON THE SUMMARY FORM HAS NOT BEEN
 CORRECTED. ADDITIONALLY THE FOLLOWING ISSUES HAVE COME
 TO LIGHT REGARDING THE ENERGY CALCULATIONS:
 A) IN THE INPUT DATA REPORT (IDR) UNDER SPACES, ZONE:
 APTMS 3-14, THIS SPACE SHOULD HAVE A MULTIPLIER OF 12
 FOR A TOTAL VOLUME OF 1,192,212.0 CUBIC FEET. SEE ZONE:
 CORRIDOR FOR AN EXAMPLE.
 B) IN THE IDR THERE IS NOTHING LISTED FOR DOORS OR
 FLOORS. PLEASE CORRECT.
 C) THE PIPING SECTION IS CALLING FOR 1.5 INCH
 INSULATION ON DOMESTIC HOT WATER PIPING. WHERE CAN THIS
 INFORMATION BE FOUND ON PLANS?
 D) NO COOLING LOAD CALCULATIONS OR SYSTEM SIZING
 SUMMARY WAS FOUND ATTACHED TO THE ENERGY CALCULATIONS
 AS REQUIRED BY FBCB 13-407-1-ABC.1.
 E) THESE COMMENTS ARE BASED ON A BRIEF OVERVIEW OF THE
 ENERGY CALCULATIONS. PLEASE SEE OTHER TRADE REVIEWS FOR
 OTHER POTENTIAL COMMENTS. PLEASE VERIFY ALL INFORMATION
 IN THE IDR CORRESPONDS WITH THE INFORMATION ON THE
 PLANS PRIOR TO RESUBMITTAL.
  
 48 AND 49: OK
  
 NEW: THE FOLLOWING ARE NEW COMMENTS RELATED TO DESIGN
 CHANGES AND ADDITIONAL INFORMATION WHICH HAS BEEN
 PROVIDED SINCE FIRST REVIEW:
  
 50. AC-01 STAIR #1 CORRIDOR: DUCTS FOR AC-6 ARE SHOWN
 PENETRATING THE ENCLOSED EXIT PASSAGEWAY. PENETRATIONS
 INTO AND OPENINGS THROUGH AN EXIT PASSAGEWAY ARE
 PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT
 AND DUCTWORK NECESSARY FOR INDEPENDENT PRESSURIZATION
 IN ACCORDANCE WITH FBCB 1020.5. PAGE AC-01 SHOWS A
 2-HOUR RATED ENCLOSURE AT THE LOCATION OF THESE DUCTS
 IN THE EXIT PASSAGEWAY, BUT NO SUCH STRUCTURE IS SHOWN
 ON THE ARCHITECTURAL PAGES. PAGE A-101A SHOWS ONLY BARE
 CONCRETE CEILINGS AT THIS LOCATION. ALSO, BOTH DUCTS
 ARE SHOWN PENETRATING TWO 2-HOUR FIRE BARRIERS AT THE
 EXIT PASSAGEWAY WITHOUT PROTECTION OF THE PENETRATIONS.
 DUCT PENETRATIONS AND AIR TRANSFER OPENINGS IN FIRE
 BARRIERS SHALL BE PROTECTED WITH APPROVED FIRE DAMPERS
 INSTALLED IN ACCORDANCE WITH FBCM 607.5.2.
  
 51. AC-01 STAIR #2 CORRIDOR: DUCTS FOR AC-7 AND
 REFRIGERANT PIPING FOR AC-5 ARE SHOWN PENETRATING AN
 ENCLOSED EXIT PASSAGEWAY. PLEASE SEE COMMENT #50 ABOVE
 FOR RELEVANT CONDITIONS AND CODE SECTIONS.
  
 52. AC-01: THE EXHAUST DUCT FOR EF-2 IS SHOWN
 PENETRATING A 2-HOUR RATED FIRE BARRIER WITHOUT
 PROTECTION OF THE PENETRATION. DUCT PENETRATIONS AND
 AIR TRANSFER OPENINGS IN FIRE BARRIERS SHALL BE
 PROTECTED WITH APPROVED FIRE DAMPERS IN ACCORDANCE WITH
 FBCM 607.5.2. SHOW HOW THIS DUCT PENETRATION IS TO BE
 PROTECTED.
  
 53. AC-01: THERE ARE SEVERAL FIRE DAMPERS SHOWN ON
 FLOOR PLAN WHERE DUCTS ARE PENETRATING NON-RATED WALL
 ASSEMBLIES ACCORDING TO PAGE A101. EXAMPLES: THE 24X10
 SUPPLY TRUNK LINE FOR AC-3, THE 24X10 SUPPLY AND RETURN
 DUCTS FOR AC-2, THE 20X10 SUPPLY TRUNK LINE FOR AC-4.
 PLEASE COORDINATE MECHANICAL AND ARCHITECTURAL PLANS,
 SHOWING FIRE DAMPERS AT THE LOCATION OF RATED
 ASSEMBLIES ONLY. FIRE DAMPERS SHALL BE INSTALLED IN
 ACCORDANCE WITH THEIR LISTING (AT RATED ASSEMBLIES) PER
 FBCM 607.2.
  
 NOTE: THE FOLLOWING COMMENTS ARE RELATED TO THE
 PROPOSED SMOKE CONTROL SYSTEM. THIS IS THE FIRST REVIEW
 OF THE SMOKE CONTROL SYSTEM AS NO INFORMATION WAS
 PROVIDED REGARDING THIS SYSTEM AT TIME OF FIRST
 REVIEW.
  
 54. THE RATIONAL ANALYSIS CALLS FOR A COMBINATION OF
 MECHANICAL AN PASSIVE SYSTEMS. THE PASSIVE SYSTEMS ARE
 TO BE USED TO SEPARATE PORTIONS OF THE BUILDING INTO
 SMOKE ZONES WITH APPROVED SMOKE BARRIERS. THE LOCATIONS
 OF THE SMOKE ZONES IS NOT INDICATED ANYWHERE ON THE
 PLANS. ALSO, THERE IS NO INDICATION OF THE LOCATIONS OF
 SMOKE BARRIERS IN THE ARCHITECTURAL PLANS.
  
 55. IN CONJUNCTION WITH COMMENT #54 ABOVE, THERE IS
 ALSO NO INDICATION ON PLANS AS TO THE PRESENCE OF
 SPOT-TYPE SMOKE DETECTORS LISTED FOR RELEASING SERVICE
 IN EACH SMOKE ZONE BEING PROTECTED BY A PASSIVE SYSTEM
 IN ACCORDANCE WITH FBCB 909.12.2.2. THIS PART OF THE
 SYSTEM IS NOT COVERED IN THE FIRE ALARM RISER DIAGRAM,
 THE FIRE ALARM SEQUENCE OF OPERATIONS OR THE SMOKE
 CONTROL SEQUENCE OF OPERATIONS. PLEASE CLARIFY. THERE
 ARE SEVERAL SMOKE DAMPERS IN CORRIDOR WALLS AND
 ELEVATOR LOBBIES AS SHOWN ON FLOOR PLANS WITH NO
 INDICATION ON FIRE ALARM OR SMOKE CONTROL SEQUENCE
 SHOWING HOW THESE DAMPERS ARE TO BE CONTROLLED.
  
 56. AC-15 CALLS FOR A SMOKE CONTROL PANEL, PRESUMABLY
 LOCATED IN THE FIRE COMMAND ROOM, BUT THIS PANEL IS NOT
 SHOWN ON OTHER PLANS. A FIRE-FIGHTER?S SMOKE CONTROL
 PANEL FOR FIRE DEPARTMENT EMERGENCY RESPONSE PURPOSES
 ONLY SHALL BE PROVIDED AND SHALL INCLUDE MANUAL CONTROL
 OR OVERRIDE OF AUTOMATIC CONTROL FOR MECHANICAL SMOKE
 CONTROL SYSTEMS. THE PANEL SHALL BE LOCATED IN A FIRE
 COMMAND CENTER COMPLYING WITH SECTION 911 IN HIGH-RISE
 BUILDINGS IN ACCORDANCE WITH FBCB 909.16.
  
 57. HOW WILL PASSIVE SYSTEMS BE TESTED? SEE FBCB
 909.5.1.
  
 58. PAGE 3 OF THE RATIONAL ANALYSIS SAYS ?INJECTION
 POINTS AT TOP OF STAIR AND LEVEL 10.? MECHANICAL FLOOR
 PLANS DO NOT SHOW ANY SUPPLY FANS, DUCTWORK OR ACTUAL
 INJECTION POINTS FOR STAIR ENCLOSURES. PLEASE CLARIFY
 AND COORDINATE FLOOR PLANS WITH THE RATIONAL ANALYSIS.
  
 59.AC-14: FAN SCHEDULE SHOWS SF-3 FOR STAIR
 PRESSURIZATION BUT THE FLOOR PLAN SHOWS IT IS FOR
 ELEVATOR PRESSURIZATION. SF-7 AND SF-8 ARE ALSO
 MISLABELED ON SCHEDULE. PLEASE CLARIFY AND COORDINATE
 FLOOR PLANS WITH SCHEDULES.
  
 60. PROVIDE INFORMATION ON SPECIAL INSPECTION AGENCY TO
 BE USED WITH DOCUMENTATION/EVIDENCE OF QUALIFICATIONS
 IN ACCORDANCE WITH FBCB 909.18.8.2.
  
 61. PROVIDE THREE COPIES OF SMOKE CONTROL RATIONAL
 ANALYSIS, SIGNED AND SEALED BY THE DESIGN PROFESSIONAL.
 FBCB 909.4, FBCB 106.1.
  
 62. IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE RULE
 9B-3.0472, THIS BUILDING IS SUBJECT TO THE FOLLOWING
 REQUIREMENTS:
 (2) EVERY BUILDING FOR WHICH A PERMIT FOR NEW
 CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES.
 (3) IN NEW CONSTRUCTION, ALARMS SHALL RECEIVE THEIR
 PRIMARY POWER FROM THE BUILDING WIRING WHEN SUCH WIRING
 IS SERVED FROM THE LOCAL POWER UTILITY. SUCH ALARMS
 SHALL HAVE BATTERY BACK UP.
 (4) COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE
 LISTED OR LABELED BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-04-13 Cont ID  
Sent By rregueir Date 2007-04-13 Time 10:06 Rev Time 0.00
Received By rregueir Date 2007-04-06 Time 09:01 Sent To  
Notes
2007-04-12 14:26:47-------------------DENIED-------------------
  
 FBC 2004 CODE FAMITY W/2006 REVISIONS
 FBC CH 1 AS AMENDED BY THE CITY OF WEST PALM BEACH NFPA
 90A-02
 NFPA 110-02
  
 1. AC-01: AC-6, BOTH ROOMS ARE MARKED AS 'STORAGE'
 ROOMS BUT ALSO SERVE AS PLENUMS. PLENUMS SHALL NOT BE
 USED FOR OCCUPANCY OR STORAGE PER NFPA 90A-4.3.10.1.1.
  
 2. AC-01: AC-6 CLOSETS: CAVITIES DESIGNED FOR AIR
 TRANSPORT SUCH AS MECHANICAL CLOSETS SHALL BE LINED
 WITH AN AIR BARRIER (NON-POUROUS, NO EXPOSED BLOCK) AND
 SEALED IN ACCORDANCE WITH FBC,M 603.9 AND SHALL BE
 INSULATED IN ACCORDANCE WITH FBC TABLE
 13-410.1.ABC.2.2.
  
 3. AC-01: ELECTRICAL ROOM A133, MECHANICAL PLAN CALLS
 FOR LOUVERED DOOR FOR MAKE-UP AIR, DOOR SCHEDULE IN
 ARCHITECTURAL PLAN DOES NOT CALL FOR A LOUVERED DOOR IN
 THAT LOCATION. PLEASE COORDINATE DRAWING AND SCHEDULE.
 FBC 106.1.1.
  
 4. ALL A/C CLOSETS: SEVERAL CLOSETS CALL FOR WOOD DOORS
 ON SCHEDULE (A400 AND UNIT DOOR SCHEDULES). MATERIALS
 EXPOSED IN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL
 HAVE A FLAME SPREAD/SMOKE DEVELOPMENT INDEX OF NOT MORE
 THAN 25/50 PER FBC,M 602.2..1.
  
 5. AC-04: PLAN STATES "TYPICAL FLOOR PLAN (4-14)"BUT
 FLOORS 5 THRU 14 DO NOT HAVE AN AC-1 OR RELATED
 DUCTWORK. PLEASE CLARIFY PER FBC 106.1.1.
  
 6. AC-04: RISER DIAGRAM SHOWS 8" ROUND O/A DUCT TO
 FIRST FLOOR, BUT PG AC-01 SHOWS A 6" ROUND DUCT. PLEASE
 CLARIFY. FBC 106.1.1.
  
 7. AC-04 RISER DIAGRAM: AC-1 DUCTS ON 2ND THRU 4TH
 FLOORS AND O/A DUCT FOR AC-6 ON FIRST FLOOR ARE
 PENETRATING A SHEFT ENCLOSURE. PENETRATIONS OF SHAFT
 ENCLOSURES SHALL BE PROTECTED WITH APPROVED FIRE AND
 SMOKE DAMPERS INSTALLED IN ACCORDANCE WITH THEIR
 LISTING PER FBC,M 607.5.5.1.
  
 8. AC-01 GARAGE VENTILATION: AUTOMATIC OPERATION OF THE
 GARAGE VENTILATION SYSTEM (BY C.O. SENSORS) SHALL NOT
 REDUCE THE VENTILATION RATE BELOW 0.05 CFM PER SQ FT OF
 FLOOR AREA PER FBC,M 404.2. PLEASE SHOW HOW THIS
 CONTINUOUS VENTILATION WILL BE PROVIDED.
  
 9. AC-01: OCCUPIED SPACES ACCESSORY TO A PUBLIC GARAGE
 (VALET OFFICE) SHALL BE MAINTAIONED AT A POSITIVE
 PRESSURE AND SHALL BE PROVIDED WITH VENTILATION IN
 ACCORDANCE WITH FBC,M 403.3 AND 404.3
  
 10. AC-01 C.O. SENSORS DRAWING NOTES: NOTE #2 AND
 SEQUENCE OF OPERATION CONDITIONS DO NOT RELATE TO
 CONDITIONS IN THIS BUILDING. PLEASE CORRECT.
  
 11. AC-13 HVAC DESIGN REQUIREMENTS SCHEDULE INDICATES
 THAT SMOKE CONTROL IS NOT REQUIRED. IN HIGH-RISE
 BUILDINGS, SMOKE CONTROLS SHALL BE PROVIDED IN
 ACCORDANCE WITH FBC SEC909 PER FBC 403.15. THIS SECTION
 WAS REVISED AS OF DEC 8, 2006.
  
 12. AC-01: MATERIALS NOTE 1 ON AC-13 LIMITS LENGTH OF
 FLEX DUCT TO 8 FEET. PLEASE VERIFY THIS WITH FLEX DUCTS
 IN THE SAUNA/GYM AREA.
  
 13. AC-01: APPLIANCES (CIRCULATION FANS) LOCATED IN
 PUBLIC GARAGES OR OTHER AREAS FREQUENTED BY MOTOR
 VEHICLES SHALL BE INSTALLED A MINIMUM OF 8 FEET ABOVE
 THE FLOOR UNLESS PROTECTED FROM VEHICLE IMPACT PER
 FBC,M 304.5.
  
 14. AC-06: STAIR 2 PRESSURIZATION FAN DOES NOT SHOW A
 DUCT SMOKE DETECTOR. PLEASE SHOW COMPLIANCE WITH FBC,M
 606.2.1.
  
 15. AC-07 UNIT A: FLEX DUCT FEEDING PDR IS MISSING
 SIZE. PLEASE CORRECT. FBC 106.1.1.
  
 16. AC-07 THRU AC-11: PLAN SHOWS 5" ROUND FLEX FEEDING
 SIDEWALL GRILL IN ELEVATOR LOBBY. HOW WILL THIS BE
 ACCOMPLISHED IF BOTH SIDES OF WALL HAVE THE SAME
 CEILING HEIGHT? ALSO, PLEASE SHOW MEANS OF ACCESS TO
 THE FIRE DAMPER. FBC 106.1.1.
  
 17. AC-07 UNIT A AND A REVERSED: PLAN APPEARS TO SHOW
 DRYER EXHAUST OUTLET TO BE IN CLOSE PROXIMITY TO THE
 O.A. INTAKES FOR AC-1 AND AC-6. PLEASE SHOW COMPLIANCE
 WITH FBC,M 401.5 AND 501.2.
  
 18. AC-07 UNIT A AND A REVERSED: A/C FLOOR PLAN CALLS
 FOR 1500 AND 1550 CFM RESPECTIVELY. HEAT PUMP SCHEDULE
 ON AC-14 SHOWS AC-3.5 AS PRODUCING 1370 CFM. PLEASE
 CLARIFY AND CORRECT AS NEEDED.
  
 19. AC-08 UNIT D AND D REVERSED: A/C FLOOR PLAN CALLS
 FOR 1450 AND 1500 CFM RESPECTIVELY. HEAT PUMP SCHEDULE
 ON AC-14 SHOWS AC-3.5 PRODUCING 1370 CFM. PLEASE
 CLARIFY AND CORRECT AS NEEDED.
  
 20. AC-08 UNIT C AND D: RETURN AIR TRANSFERS DUCT FROM
 MASTER BEDROOM IS NOT DESIGNED TO MEET THE BALANCED
 RETURN EXCEPTIONS OF FBC,M 601.4 (1 1/2 TIMES THE SIZE
 OF SUPPLY). A FIELD TEST WILL BE REQUIRED TO VERIFY
 COMPLIANCE WITH 0.01" WC MAXIMUM ALLOWABME PRESSURE
 DIFFERENTIAL UNLESS RETURNS ARE DESIGNED TO MEET THE
 EXCEPTIONS OF THIS SECTION.
  
 21. AC-09 BEDRROOM 2 W.I.C DROP IS MISSING GRILL SIZE
 AND CFM. PLEASE CORRECT.
  
 22. AC-09: PLEASE SEE COMMENT #20 REGARDING BALANCED
 RETURN,
  
 23. AC-10: WILL THERE BE PROVISIONS FOR AN AIR-TIGHT
 DOOR ON AC CLOSET IN LAUNDRY ROOM AS THERE IS IN UNIT
 C?
  
 24. AC-10: AC-5.0 AS STATED ON AC-14 IS RATED FOR 2060
 CFM. FAN SHUT-DOWN BY SMOKE DETECTOR IS REQUIRED PER
 FBC,M 606.2..
  
 25. AC-11: TWO DROPS IN BEDROOM 2 MISSING CFM AND GRILL
 SIZES.
  
 26. AC-11: SEE COMMENT #20 REGARDING BALANCED RETURN -
 MASTER SUITE.
  
 27. AC-12: PLAN SHOWS GENERATOR EXHAUST DISCHARGING
 NORTH. PG P-1C SHOWS EXHAUST DISCHARGING EAST. PLEASE
 COORDINATE DRAWINGS.
  
 28. AC-12 GENERATOR ROOM: PLEASE SHOW HOW THE
 REQUIREMENTS OF NFPA 110-7.7.1 THROUGH 7.7.8 ARE BEING
 MET IN CONJUNCTION WITH MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
  
 29. AC-13 MECHANICAL EQUIPMENT NOTES #20: PROVIDE DRYER
 MANUFACTURER'S INSTALLATION INSTRUCTIONS SHOWING
 MAXIMUM ALLOWABLE DUCT LENGTH PER FBC,M 504.6.1. IF
 DRYER BOOSTER FAN IS TO BE USED, PROVIDE DOCUMENTATION
 FROM THE DRYER MANUFACTURER DEMONSTRATING COMPATIBILITY
 WITH BOOSTER FAN. WILL MANUFACTURER HONOR WARRANTY IF
 DRYER IS USED WITH A BOOSTER FAN? FBC 106.1.2.
  
 30. AC-13 GENERAL A/C NOTES #26: PLEASE SEE COMMENT #13
 REGARDING APPLIANCES LOCATED IN GARAGES.
  
 31. AC-13 MATERIALS NOTE #1: FLEX DUCT LIMITITED TO
 MAXIMUM 8'0" BY THIS NOTE. PLAN CALLLS FOR LONGER FLEX
 DUCT IN SEVERAL AREAS. PLEASE CORRELATE NOTES AND FLOOR
 PLANS PER FBC 106.1.1.
  
 32. AC-13 MATERIALS NOTE K: THE OPERATING TEMPERATURE
 OF A FUSIBLE LINK SHALL BE APPROXIMATELY 50 DEGREES (F)
 ABOVE THE NORMAL TEMPERATURE WITHIN THE DUCT SYSTEM BUT
 NOT LESS THAN 160 DEGREES PER FBC,M 607.3.1.1. WHAT IS
 THE NORMAL TEMPERATURE WITHIN THE DUCT SYSTEM TO
 REQUIRE A 265 DEGREE FUSIBLE LINK?
  
 33. AC-13 MATERIALS NOTE T: SEE COMMENT # 29 REGARDING
 BOOSTER FANS.
  
 34. AC-13 HVAC DESIGN REQUIREMENTS: SEE COMMENT #11
 REGARDING SMOKE CONTROL.
  
 35. AC-14 HEAT PUMP SCHEDULE: UNIT B IS LISTED UNDER
 BOTH AC-3.5 AND AC-4.0. UNIT D IS MISSING FROM THE
 SCHEDULE. PLEASE CORRECT.
  
 36. AC-14 HEAT PUMP SCHEDULE: AC-5.0 IN PH-B REQUIRES
 FAN SHUT-DOWN BY SMOKE DETECTOR PER FBC,M 606.2.1.
  
 37. AC-14 SPLIT SYSTEM SCHEDULE SHOWS AHU 2 AND CU 2
 SERVING STORAGE ROOMS. PG AC-01 SHOWS IT SERVING MAIN
 TELEPHONE ROOM. PLEASE CORRECT.
  
 38. AC-14 FAN SSCHEDULE: EF 1,2,3,4 CALL FOR WALL CAPS
 ON SOME FLOOR PLANS BUT WALL CAPS ARE NOT CALLED FOR ON
 SCHEDULE AS AN ACCESSORY. PLEASE PROVIDE DETAIL FOR
 WALL CAP EXHAUST TERMINATIONS FOR EFS AND DRYER
 EXHAUST. FBC 106.1.1.
  
 39. AC-15: CW RISER 4: PH-C IS SHOWN ON RISER AS AC-5.0
 BUT ON HP SCHEDULE AND FLOOR PLAN IT IS SHOWN AS
 AC-4.0. PLEASE CORRECT AND VERIFY ALL HEAT PUMPS AS
 CORRECTLY CORRESPONDING WITH THE AREA BEING SERVED.
  
 40. AC-15 CW1 AND CW2, PLEASE MARK ALL HPS FOR SIZE AND
 AREA BEING SERVED.
  
 41. AC-16: SHAFT ENCLOSURES THAT ARE PERMITTED TO BE
 PENETRATED BY DUCTS AND AIR TRANSFER OPENINGS SHALL BE
 PROTECTED WITH APPROVED FIRE AND SMOKE DAMPERS IN
 ACCORDANCE WITH THEIR LISTING PER FBC,M 607.5.5.1.
 PLEASE NOTE THAT THE USE OF A SUBDUCT UNDER EXCEPTION 1
 OF THIS SECTION PROVIDES AN EXCEPTION FOR THE FIRE
 DAMPER ONLY WHILE LEAVING IN PLACE THE REQUIREMENT FOR
 THE SMOKE DAMPER. IF A SHAFT IS TO BE USED FOR THE
 BATHROOM EXHAUST, A SMOKE DAMPER WILL BE REQUIRED AT
 EACH DUCT PENETRATION. AN ALTERNATE LOCATION FOR DRYER
 EXHAUST TERMINATION MAY BE NEEDED AS THE USE OF A SMOKE
 DAMPER ON DRYER EXHAUST DUCTS IS PROHIBITED PER FBC,M
 504.2.
  
 42. AC-16 EXHAUST FAN ON STAND ROOFTOP DETAIL:
 1) PLEASE REFERENCE FBC 2004, NOT 2001
 2) PRE-ENGINEERED ROOF STANDS ARE STRUCTURAL ELEMENTS
 AS DEFINED BY FAC 9B-72. AS SUCH, PRODUCT APPROVAL IS
 REQUIRED UNDER FS 553.842.
 3) BOTTOM NOTE ON DETAIL POINTS TO WHAT APPEARS TO BE A
 PITCH PAN, BUT STATES THAT STEEL PLATES ARE TO BE
 WELDED TO THE LEGS OF THE ALUMINUM STAND(?). PLEASE
 CLARIFY THIS DETAIL.
 4) PRE-ENGINEERED ROOF STANDS ARE TO BE INSTALLED PER
 THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
  
 43. SOME DETAILS ON THIS PAGE DIFFER FROM STRUCTURAL
 DETAILS PROVIDED WHICH ARE RELATED TO ROOFTOP
 INSTALLATION OF DUCTS, PIPES AND EQUIPMENT. PLEASE
 COORDINATE DRAWINGS/DETAILS SO AS TO NOT BE IN CONFLICT
 WITH STRUCTURAL PLANS. THE STRUCTURAL DETAILS FOR
 OUTDOOR EQUIPMENT SHOULD PREVAIL PER FBC,M 301.13 AND
 FBC CH 15 & 16.
  
 44. AC-17 SUPPLY FAN ROOF DETAIL: SMOKE DETECTOR IS TO
 BE INSTALLED IN THE SUPPLY AIR DUCT PER FBC,M 606.2.1.
  
 45. AC-17: HEAT PUMP UNIT DETAIL:
 1) PLEASE REFERENCE FBC,M 2004, NOT 2001.
 2) PLEASE INDICATE MEANS OF SECONDARY/AUXILIARY DRAIN
 PROTECTION TO BE USED PER FBC,M 307.2.3. MOST HEAT
 PUMPS DO NOT HAVE A SECONDARY DRAIN OUTLET AND AS SUCH,
 THE METHOD SHOWN MAY NOT BE AN AVAILABLE OPTION FOR
 COMPLIANCE WITH THIS SECTION.
 3) PLEASE SPECIFY TYPE OF PIPE MATERIAL TO BE USED FOR
 CONDENSATE DISPOSAL, SHOWING COMPLIANCE WITH FBC,M
 606.2.2.1 (MATERIALS EXPOSED IN PLENUM) AND FBC,M
 307.2.2 (MIN. 3/4" I.D.).
  
 46. AC-19: PLEASE SEE COMMENT #43 REGARDING ROOFTOP
 EQUIPMENT DETAILS.
  
 47. PLEASE CORRECT ADDRESS ON ENERGY CALCULATIONS AND
 PLAN TO MATCH THAT ON PERMIT APPLICATION.
  
 48. PLEASE VERIFY MAX. TONNAGE AS STATED ON ENERGY
 CALCULATIONS. PLANS INDICATE >350 TONS.
  
 49. STAIR AND ELEVATOR SHAFT VENTS SHALL BE EQUIPPED
 WITH MOTORIZED DAMPERS THAT ARE CAPABLE OF BEING
 AUTOMATICALLY CLOSED DURING NORMAL BUILDING OPERIATION
 AND ARE INTERLOCKED TO OPEN AS REQUIRED BY FIRE AND
 SMOKE DETECTION SYSTEMS PER FBC 13-409.1.ABC.3.1.
  
 PLEASE NOTE: WHILE EVERY EFORT WAS MADE TO PERFORM A
 COMPLETE REVIEW, ADDITIONAL COMMENTS ARE POSSIBLE AFTER
 RESUBMITTAL, ESPECIALLY RELATED TO ANY CHANGES/NEW
 PAGES WHICH MAY BE SUBMITTED IN RESPONSE TO REVIEW
 COMMENTS FROM ALL TRADES.
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-07-01 Cont ID  
Sent By kstevens Date 2008-07-01 Time 08:04 Rev Time 0.00
Received By kstevens Date 2008-07-01 Time 08:04 Sent To  
Notes
2008-07-01 08:04:37DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 MUNICIPAL CODE WPB
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHT 358-9 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET. IF
 PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS, THEY SHALL ALSO INDICATE THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET.FAC
 61G15-23.002(1)(2) & FS 471.025.
 ****RESPONSE NOTED, NOW SHEET 1 OF 1 HAS BEEN DELETED
 BUT THE INDEX ON SHEETS A01.02 & 1 OF 6A STILL SHOWS
 SHEET 358.9. PLEASE CORRELATE.
  
 3. OK
  
 4. SHT A01.3 SECONDARY ROOF DRAINS REQUIRED FOR THE
 AREA NEAR STAIR G1, PUMP ROOM, LAWN EQUIP. ETC.
 SECTIONS 1107.1 & 1107.2.
 ****RESPONSE NOTED, BUT SECONDARY ROOF DRAINS ARE NOT
 LOCATED ON SHT P-1B.
  
 5. SHT A01.3 THERE IS NO PRIMARY OR SECONDARY ROOF
 DRAINS INDICATED IN THE AREA OF STAIR G2, EMERGENCY
 GENERATOR ROOM AND LIFT AS REQUIRED IN SECTIONS 1101.2,
 1107.1 & 1107.2.
 ****RESPONSE NOTED, BUT THERE ARE NO PRIMARY OR
 SECONDARY ROOF DRAINS SHOWN ON SHT P-1B. SHEET A01.3
 SHOWS THE PRIMARY ROOF DRAIN BUT NO SECONDARY ROOF
 DRAIN.
  
 6. OK
  
 7. SHT A01.3ROOF DRAINS ARE SHOWN IN AREAS INDICATED
 AS MULCH AREAS.MORE INFORMATION IS REQUIRED. PLEASE
 INDICATE HOW THE MULCH WILL BE KEPT FROM DRAINING INTO
 THE ROOF DRAINS AND OR CLOGING THE ROOF DRAINS AND
 PREVENTING THEM FROM DRAINING PROPERLY.PLEASE SUBMIT
 A DETAIL FOR THE DRAINS IN THESE AREAS. SECTION 104.6.
 ****RESPONSE NOTED, BUT THE DETAIL D/A01.6 SHOWS ROCK
 AROUND THE DRAIN THEN MULCH, WHERE AS THE ROOF DECK
 PLAN SHOW ONLY GRAVEL. PLEASE CORRELATE. ALSO THE CODE
 REQUIRES THAT THE ROOF DRAIN STRAINERS SHALL HAVE AN
 AVAILABLE INLET AREA, ABOVE THE ROOF, OF NOT LESS THAN
 ONE AND ONE-HALF TIMES THE AREA OF THE CONDUCTOR OR
 LEADER TO WHICH THE DRAIN IS CONNECTED. PLEASE INDICATE
 HOW THE STAINLESS STEEL MESH WILL PROVIDE THE REQUIRED
 AVAILABLE INLET AREA. SECTION 1105.1.
  
 8. SHT A01.3ROOF DRAINAGE INDICATES DETAILS A/A803 &
 D/A803. SECTION 1105.1 STATES ROOF DRAINS SHALL HAVE
 STRAINERS EXTENDING NOT LESS THAN 4 INCHES ABOVE THE
 SURFACE OF THE ROOF IMMEDIATELY ADJACENT TO THE ROOF
 DRAINS. STRAINER SHALL HAVE AN AVAILABLE INLET AREA,
 ABOVE THE ROOF, OF NOT LESS THAN ONE AND ONE-HALF TIMES
 THE AREA OF THE CONDUCTOR OR LEADER TO WHICH THE DRAIN
 IS CONNECTED. PLEASE INDICATE HOW THIS AND THE FACT
 THAT THE ROOF DRAIN WILL BE COVERED WITH ROCKS WILL
 MEET THIS CODE REQUIREMENT. THERE IS A CONCERN THAT THE
 GRASS CLIPPINGS, DIRT, MOSS BUILD UP ETC WILL
 EVENTUALLY KEEP THE DRAIN FROM DRAINING AS INTENDED.
 PLEASE SUBMIT INFORMATION ON HOW THIS WILL BE
 ADDRESSED. SECTION 104.6.
 ****RESPONSE NOTED, BUT THE INTENT OF THE CODE IS NOT
 ADDRESSED. THE REQUIRED STRAINER IS NOT SHOWN AND THE
 AVAILABLE INLET AREA IS IN QUESTION AS THERE IS
 DRAINAGE ROCKS OVER THE ROOF DRAINS. SECTION 1105.1.
 ALSO THE CONCERN THAT THE STAINLESS STEEL MESH WILL
 FURTHER DIMINISH THE INLET AREA HAS TO BE ADDRESSED.
  
 9. SHT A01.3 OVERFLOW DRAINS DETAILS B/A803 & C/A803 DO
 NOT MEET THE INTENT OF THE CODE TO BE USED ONLY IN CASE
 OF BLOCKAGE OF THE PRIMARY ROOF DRAINS. THESE DETAILS
 INDICATE THAT THE DRAINS ARE FLUSH WITH THE ROOF AND
 WILL DRAIN WHEN THE PRIMARY ROOF DRAINS DRAIN AND NOT
 AFTER THE BUILDUP OF A BLOCKED PRIMARY DRAIN. DRAINS
 INDICATED IN DETAIL C/A803 ARE SHOWN TO BE NEXT TO AN
 AREA THAT HAS MULCH IN IT. PLEASE CLARIFY AND INDICATE
 HOW THE MULCH WILL NOT BLOCK THE DRAINS. SECTION
 1107.1.
 ****RESPONSE NOTED, BUTTHE COMMENT WAS FOR THE
 OVERFLOW DRAINS AT THE PUTTING GREEN/CHIPPING GREEN
 AREA. ADDING THE NOTE DOES NOT CHANGE THE FACT THAT THE
 DRAINS ARE STILL SHOWN LEVEL WITH THE GREEN SURFACE.
 ALSO THE PLANTER DRAINS ARE INDICATED AS DRAINING INTO
 THE OVERFLOW DRAINS IN DETAIL "B". THIS WILL ALLOW
 STORM WATER TO DRAIN INTO THE OVERFLOW DRAINS AND WILL
 HAVE STORM WATER DRAINING EVERY TIME IT RAINS AND WILL
 NOT INDICATE THAT THERE IS A BLOCKAGE IN THE PRIMARY
 ROOF DRAIN SYSTEM AS INTENDED. SECTION 1107.
  
 10. OK
  
 11. SHT A01.3 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES. SHOW THE SQUARE FOOTAGE OF EACH
 DRAIN AND INCLUDE 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS AND SHOW ANY ROOF AREA THAT
 CONTRIBUTES TO THE SQUARE FOOTAGE OF ANY DRAIN FROM
 ROOF AREAS ABOVE.
 ****RESPONSE NOTED, BUT NO CALCULATION FOR THE AREAS BY
 THE STAIRS AND WATER FEATURE AND THE STAIRS AND THE
 GENERATOR ROOM WERE SUBMITTED.
  
 12. OK
 13. OK
  
 14. SHT A101 SHOW THE CLEAR FLOOR SPACE FOR ALL
 ACCESSIBLE FIXTURES IN ALL TOILET ROOMS. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTIONS 11-4.16,
 11-4.17, 11-4.18, 11-4.19 AND 11-4.22 WITH ALL
 SUBSECTIONS.
 ****RESPONSE NOTED, BUT COMMENT DID NOT ADDRESS THE
 COMMON TOILET ROOMS. THE RESPONSE ADDRESSED FHA-98
 REQUIREMENTS FOR THE UNITS.
  
 15. OK
 16. OK
 17. OK
  
 18. SHT A201 UNITS A & A REV. INDICATE THE BACKING FOR
 THE TUB IN THE MASTER BATH PER PAGE 6.10.--THE WING
 WALL NEXT TO THE W/C IN THE MASTER BATH TO BE A MAXIMUM
 2'0" PER PAGE 7.44.--LAVS SHALL BE CENTERED ON THE
 48" DIMENSION OF THE CLEAR FLOOR SPACE PER PAGE 7.48 OR
 FORWARD APPROACH WITH REMOVABLE BASE CABINET SHALL BE
 INDICATED.--SHOW THE CLEAR FLOOR SPACE FOR THE
 W/C'S. PAGE 7.43.--RANGE SHALL BE CENTERED ON THE
 48" DIMENSION OF THE CLEAR FLOOR SPACE PER PAGES 7.4 &
 7.9. --THE OPENING FOR THE W/C'S IN BATH 2 SHALL BE
 33" AND MUST SHOW 18" OFF THE TUB OR LAV TO THE CENTER
 OF THE FIXTURE AND 15" MIN. OFF THE OTHER FIXTURE.
 PAGES 7.43, 7.44 & 7.45.--MINIMUM CLEARANCES
 BETWEEN ALL COUNTERS, APPLIANCES, BASE CABINETS AND
 WALLS SHALL BE 40". PAGES 7.8, 7.11, 7.22 & 7.23. 36"
 IS SHOWN. PLEASE SHOW COMPLIANCE.
 ****RESPONSE NOTED, BUT RESPONSE ONLY SHOWS STANDARD
 TUB BACKING REQUIREMENTS. THE BACKING FOR LARGER TUBS
 WITH DECKS HAS NOT BEEN ADDRESSED. SEE PAGES 6.10 &
 6.11.
  
 19. SHT A203 UNITS B & B REV. INDICATE THE BACKING FOR
 THE TUB IN THE MASTER BATH PER PAGE 6.10.--SHOW THE
 CLEAR FLOOR SPACE FOR THE W/C IN THE MASTER BATH PER
 PAGE 7.43.--THE W/C IN THE MASTER BATH SHALL BE 18"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE PER PAGE
 6.5.--LAVS SHALL BE CENTERED ON THE 48" DIMENSION
 OF THE CLEAR FLOOR SPACE PER PAGE 7.48 OR FORWARD
 APPROACH WITH REMOVABLE BASE CABINET SHALL BE
 INDICATED.--BATH #2 OPENING FOR THE W/C SHALL BE
 MINIMUM 33". INDICATE MEASURMENT FROM THE CENTERLINE OF
 THE W/C TO THE SIDE OF THE VANITY PER PAGES 7.43, 7.44
 & 7.45.--MINIMUM CLEARANCES BETWEEN ALL COUNTERS,
 APPLIANCES, BASE CABINETS AND WALLS SHALL BE 40".
 (SHOWN AS 36"). PAGES 7.8, 7.11, 7.22 & 7.23. 36".
 PLEASE SHOW COMPLIANCE.
 ****RESPONSE NOTED, BUT RESPONSE ONLY SHOWS STANDARD
 TUB BACKING REQUIREMENTS. THE BACKING FOR LARGER TUBS
 WITH DECKS HAS NOT BEEN ADDRESSED. SEE PAGES 6.10 &
 6.11.--OPENING FOR W/C NOT SHOWN ON SHT A204 FOR
 SECOND BATHROOM. ALSO SHOW BACKING FOR GRAB BARS IN
 SECOND BATHROOM. REQUIREMENT 6.
  
 20. SHT A205 UNIT C. INDICATE THE BACKING FOR THE TUB
 IN THE MASTER BATH PER PAGE 6.10.-- SHOW THE CLEAR
 FLOOR SPACE FOR THEUSABLE W/C PER PAGE 7.43.-- SHOW
 THE CLEAR FLOOR SPACE FOR THE TUBS OR SHOWERS PER PAGES
 7.53 THRU 7.56.--W/C'S SHALL BE 1'6" OFF THE WALL
 TO THE CENTERLINE OF THE FIXTURE PER PAGE 6.5.
 ****RESPONSE NOTED, BUT RESPONSE ONLY SHOWS STANDARD
 TUB BACKING REQUIREMENTS. THE BACKING FOR LARGER TUBS
 WITH DECKS HAS NOT BEEN ADDRESSED. SEE PAGES 6.10 &
 6.11.--SHOW THE BACKING FOR THE GRAB BARS IN M/B &
 BATHROOM 3. REQUIREMENT 6.
  
 21. SHT A207 UNITS D & D REV.INDICATE THE BACKING FOR
 THE TUB IN THE MASTER BATH PER PAGE 6.10.--SHOW THE
 CLEAR FLOOR SPACE FOR THE USABLE W/C PER PAGE 7.43.--
 SHOW THE OPENING FOR THE W/C IN BATH #2 TO BE A MINIMUM
 OF 33". THE W/C SHALL BE 1'6" OFF ONE FIXTURE TO THE
 CENTERLINE OF THE FIXTURE AND 15" MINIMUM OFF THE OTHER
 FIXTURE OR VANITY CABINET PER PAGES 7.43 THRU 7.45.--
 MINIMUM CLEARANCES BETWEEN ALL COUNTERS, APPLIANCES,
 BASE CABINETS & WALLS SHALL BE 40". PAGES 7.8, 7.11,
 7.22 & 7.23. 36" IS SHOWN. PLEASE SHOW COMPLIANCE.
 ****RESPONSE NOTED, BUT RESPONSE ONLY SHOWS STANDARD
 TUB BACKING REQUIREMENTS. THE BACKING FOR LARGER TUBS
 WITH DECKS HAS NOT BEEN ADDRESSED. SEE PAGES 6.10 &
 6.11.--SHOW THE BACKING FOR THE GRAB BARS IN
 BATHROOM 2. REQUIREMENT 6.
  
 22. SHT A209 UNITS PHA & PHA REV. INDICATE THE BACKING
 FOR THE TUB IN THE MASTER BATH PER PAGE 6.10.--SHOW
 THE CLEAR FLOOR SPACE FOR THE W/C IN THE MASTER BATH
 PER PAGE 7.43.--THE WING WALL NEXT TO THE W/C IN
 THE MASTER BATH SHALL BE A MAXIMUM OF 2'0" PER PAGE
 7.44.--THE LAVS SHALL BE CENTERED ON THE 48"
 DIMENSION OF THE CLEAR FLOOR SPACE PER PAGE 7.48 OR
 FORWARD APPROACH.--A MINIMUM 33" OPENING IS
 REQUIRED FOR THE W/C IN BATH #2. SHOW THE W/C TO BE
 1'6" OFF ONE FIXTURE TO THE CENTERLINE OF THE FIXTURE,
 AND A MINIMUM OF 15" OFF THE OTHER FIXTURE OR VANITY
 CABINET.--MINIMUM CLEARANCES BETWEEN ALL COUNTERS,
 APPLIANCES, BASE CABINETS & WALLS SHALL BE 40". PAGES
 7.8, 7.11, 7.22 & 7.23. 36" IS SHOWN. PLEASE SHOW
 COMPLIANCE.
 ****RESPONSE NOTED, BUT RESPONSE ONLY SHOWS STANDARD
 TUB BACKING REQUIREMENTS. THE BACKING FOR LARGER TUBS
 WITH DECKS HAS NOT BEEN ADDRESSED. SEE PAGES 6.10 &
 6.11.--SHOW THE BACKING FOR THE GRAB BARS IN
 BATHROOM 2. REQUIREMENT 6.
  
 23. SHT A212 UNITS PHB & PHB REV. INDICATE THE BACKING
 FOR THE TUB IN THE MASTER BATH PER PAGE 6.10.--SHOW
 THE CLEAR FLOOR SPACE FOR THE USABLE W/C IN THE MASTER
 BATH PER PAGE 7.43.--THE W/C IN THE MASTER BATH
 SHALL BE 18" OFF THE WALL TO THE CENTERLINE OF THE
 FIXTURE PER PAGE 6.5.--THE LAVS SHALL BE CENTERED
 ON THE 48" DIMENSION OF THE CLEAR FLOOR SPACE PER PAGE
 7.48 OR FORWARD APPROACH.--A MINIMUM 33" OPENING IS
 REQUIRED FOR THE W/C IN BATH #2. SHOW THE W/C TO BE
 1'6" OFF ONE FIXTURE TO THE CENTERLINE OF THE FIXTURE,
 AND A MINIMUM OF 15" OFF THE OTHER FIXTURE OR VANITY
 CABINET.--MINIMUM CLEARANCES BETWEEN ALL COUNTERS,
 APPLIANCES, BASE CABINETS & WALLS SHALL BE 40". PAGES
 7.8, 7.11, 7.22 & 7.23. 36" IS SHOWN. PLEASE SHOW
 COMPLIANCE.
 ****RESPONSE NOTED, BUT RESPONSE ONLY SHOWS STANDARD
 TUB BACKING REQUIREMENTS. THE BACKING FOR LARGER TUBS
 WITH DECKS HAS NOT BEEN ADDRESSED. SEE PAGES 6.10 &
 6.11.--SHOW THE BACKING FOR THE GRAB BARS IN
 BATHROOM 2. REQUIREMENT 6.
  
 24. OK
  
 25. SHT A215 INDICATE THE BACKING FOR THE TUB IN BOTH
 BATHS PER PAGE 6.10.--SHOW THE CLEAR FLOOR SPACE
 FOR THE W/C IN BOTH BATHS PER PAGE 7.43.--THE W/C
 IN BOTH BATHS SHALL BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE PER PAGE 6.5.--THE LAVS
 IN THE MASTER BATH SHALL BE CENTERED ON THE 48"
 DIMENSION OF THE CLEAR FLOOR SPACE PER PAGE 7.48 OR
 FORWARD APPROACH. PLEASE SHOW COMPLIANCE. ****RESPONSE
 NOTED, BUT RESPONSE ONLY SHOWS STANDARD TUB BACKING
 REQUIREMENTS. THE BACKING FOR LARGER TUBS WITH DECKS
 HAS NOT BEEN ADDRESSED. SEE PAGES 6.10 & 6.11.--
 SHOW THE BACKING FOR THE GRAB BARS IN M/B & BATHROOM 3.
 REQUIREMENT 6.
  
 26. OK
  
 27. SHT A404 SHOW COMPLIANCE WITH THE FOLLOWING: __FOR
 W/C'S:
 A. 11-4.16.5 FLUSH CONTROLS
 ****RESPONSE NOTED, BUT THE FLUSH CONTROLS SHALL BE
 LOCATED ON THE WIDE SIDE OF THE TANK. THIS IS NOT
 INDICATED.
 B. OK
 __FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 ****RESPONSE NOTED, BUT THE KNEE CLEARANCE, (29"), IS
 NOT NOTED ON PLANS.
 B. OK
  
 28. SHT A405 SHOW COMPLIANCE WITH THE FOLLOWING: __FOR
 W/C'S:
 A. OK
 B. OK
 C. 11-4.16.5 FLUSH CONTROLS
 ****RESPONSE NOTED, BUT THE FLUSH CONTROLS SHALL BE
 LOCATED ON THE WIDE SIDE OF THE TANK. THIS IS NOT
 INDICATED.
 __STALLS:
 A. OK
 __LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 ****RESPONSE NOTED, BUT THE KNEE CLEARANCE, (29"), IS
 NOT NOTED ON PLANS.
 B. OK
 C. OK
 __FOR THE SHOWER:
 A. OK
 B. OK
  
 29. OK
 30. OK
 31. OK
 32. OK
  
 33.SHT A805 DETAIL A INDICATES A TRENCH DRAIN. PLEASE
 INDICATE WHERE THIS CAN BE FOUND ON THE FLOOR PLAN.
 SECTION 106.1.1.
 ****RESPONSE NOTED, BUT TRENCH DRAIN DETAIL STILL
 SHOWN.
  
 34. SHT A806 THE SQUARE FOOTAGE FOR ALL EXTERIOR
 PLANTERS SHALL INDICATE 1/2 THE AREA OF ALL VERTICAL
 WALLS. IN THE CASE OF PLANTERS AGAINST THE BUILDING
 THIS WILL INCLUDE THE 1/2 THE AREA OF THE BUILDING UP
 TO THE PARAPETS OF THE ROOF. PLEASE SUBMIT THE
 CALCULATIONS FOR THESE PLANTER DRAINS PER TABLE
 1106.3.
 ****RESPONSE NOTED, BUT CLARIFICTION REQUIRED AS NO
 PLANTER CALCULATIONS WERE SUBMITTED.
  
 35. OK
 36. OK
 37. OK
 38. OK
 39. OK
  
 40. SHT P-1B PLAN INDICATED ON SHEET INDEX HAS NOT BEEN
 SUBMITTED. SUBMIT A 2ND FLOOR/ROOF PLAN FOR THE GARAGE.
 SHOW ALL ROOF DRAINS, SECONDARY ROOF DRAINS, WATER
 SUPPLY & BACKFLOW FOR THE WATERFALL ETC. SECTION
 106.1.2.
 ****RESPONSE NOTED, BUT NO SECONDARY ROOF DRAINS WERE
 SHOWN FOR AREAS 2, 3, 5, 16, 17 & 19.
  
 41. OK
 42. OK
 43. OK
 44. OK
 45. OK
 46. OK
 47. OK
  
 48. SHT P-3 SHOWS 4 PLANTER DRAINS BUT ONLY SHOWS
 PIPING AND SQUARE FOOTAGE TO 2 PLANTER DRAINS. PLEASE
 SHOW THE PIPING & SF TO ALL PLANTER DRAINS. SECTION
 1101.2.
 ****RESPONSE NOTED, BUT THE INDOOR PLANTER ON THE SOUTH
 SIDE OF THE LOBBY SHALL CONNECT TO THE STORM, NOT THE
 SECONDARY DRAIN.
  
 49. SHT P-3 RWL SHOWS 1730SF, BUT SAME RWL IS INDICATED
 AS DRAINING 2010SF ON THE LEVELS ABOVE AND BELOW.
 PLEASE CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE SHEET NOW SHOWS 2010SF,
 WHILE THE LEVELS ABOVE AND BELOW INDICATE 1849SF.
 PLEASE CORRELATE.
  
 50. OK
 51. OK
  
 52. SHT P-7 SINKS FOR 3 UNITS ARE NOT SHOWN DRAINING TO
 ANY RISER DIAGRAMS. PLEASE INDICATE WHERE THESE SINKS
 ARE DRAINING TO AND SHOW THE CONNECTION ON THE RISER
 DIAGRAM WHEN INDICATING WHERE THE SINKS ARE DRAINING
 TO. SECTION 106.1.1. INDICATE TOTAL FIXTURE UNITS FOR
 STACK WHEN ADDING THE SINK. TABLE710.1(2). ****RESPONSE
 NOTED, BUT SHT P-7 SHOWS THE SINK IN AREA #3 CONNECTING
 TO RISER #8 AND THE SINK IN AREA #16 CONNECTING TO
 RISER #25. PLEASE CORRELATE.
  
 53. OK
 54. OK
 55. OK
 56. OK
 57. OK
 58. OK
 59. OK
 60. OK
  
 61. SHT P-12 PH UNIT "C" & PH UNIT "B" SUBMIT WATER
 RISER DIAGRAMS. SECTION 106.3.5.1.3(3)(10)(13).
 ****RESPONSE NOTED, BUT NO WATER SUPPLY SHOWN TO MASTER
 BATH WATER CLOSET ON THE RISER DIAGRAM.
  
 62. OK
 63. OK
 64. OK
 65. OK
 66. OK
 67. OK
 68. OK
 69. OK
  
 70. SHT P-13 RISER 11 THE PIPING FOR THE SECOND FLOOR
 FIXTURES IS NOT SHOWN ON THE FLOOR PLAN. SECTION
 106.1.1.
 ****RESPONSE NOTED, COMMENT ADDRESSED. (NEW) THE WASH
 MACHINE SHALL CONNECT BELOW THE LAUNDRY SINK. SECTION
 901.2.
  
 71. OK
 72. OK
 73. OK
 74. OK
 75. OK
 76. OK
  
 77. SHT P-15GAS PIPING RISER DIAGRAM. PLEASE SUBMIT
 THE CALCULATION FOR EQUATION 4-2.--SUBMIT
 MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BTU LOAD FOR THE BOILER IS NOT
 INDICATED ON MANUFACTURE SHEETS. I WILL PROVISO THAT
 THE BTU LOAD WILL BE VERIFIED AT TIME OF GAS FINAL. BTU
 LOAD SHALL BE SHOWN ON THE BOILER TO BE APPROVED.
  
 78. OK
 79. OK
 80. OK
 81. OK
 82. OK
 83. OK
 84. OK
 85. OK
 86. OK
 87. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND,
 AS WELL AS THE RETURN OF THE RED LINED SET OF PLANS
 FROM THE FIRST REVIEW, WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-23 Cont ID  
Sent By kstevens Date 2007-04-23 Time 16:37 Rev Time 0.00
Received By kstevens Date 2007-04-16 Time 18:56 Sent To  
Notes
2007-04-23 19:03:51DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 MUNICIPAL CODE WPB
  
 1. SHT 2 OF 6A BACKFLOWS FOR THE DOMESTIC WATER SERVICE
 SHALL BE AT LEAST THE SAME SIZE AS THE LINE IN WHICH
 THER ARE INSTALLED.4" BACKFLOWS ARE REQUIRED. 4"
 WATER SERVICE SHOWN. TABLE 603.1(D).
  
 2. SHT 358-9 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME, ADDRESS, AND LICENSE NUMBER ON EACH SHEET. IF
 PRACTICING THROUGH A DULY AUTHORIZED ENGINEERING
 BUSINESS, THEY SHALL ALSO INDICATE THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET.FAC
 61G15-23.002(1)(2) & FS 471.025.
  
 3. SHT A01.2 SUBMIT THE MANUF. SPECIFICATION SHEETS FOR
 THE LIFT STATION. SECTIONS 106.1.2 & 303.2 303.4.
  
 4. SHT A01.3 SECONDARY ROOF DRAINS REQUIRED FOR THE
 AREA NEAR STAIR G1, PUMP ROOM, LAWN EQUIP. ETC.
 SECTIONS 1107.1 & 1107.2.
  
 5. SHT A01.3 THERE IS NO PRIMARY OR SECONDARY ROOF
 DRAINS INDICATED IN THE AREA OF STAIR G2, EMERGENCY
 GENERATOR ROOM AND LIFT AS REQUIRED IN SECTIONS 1101.2,
 1107.1 & 1107.2.
  
 6. SHT A01.3 ROOF DRAINS LOCATED AT THE WALLS STATES 4"
 RD (TYP) SEE PLUMBING DRAWINGS & DETAIL. PLEASE
 INDICATE WHERE IN THE PLUMBING PLANS THESE CAN BE
 FOUND. SECTION 106.1.1.
  
 7. SHT A01.3ROOF DRAINS ARE SHOWN IN AREAS INDICATED
 AS MULCH AREAS.MORE INFORMATION IS REQUIRED. PLEASE
 INDICATE HOW THE MULCH WILL BE KEPT FROM DRAINING INTO
 THE ROOF DRAINS AND OR CLOGING THE ROOF DRAINS AND
 PREVENTING THEM FROM DRAINING PROPERLY.PLEASE SUBMIT
 A DETAIL FOR THE DRAINS IN THESE AREAS. SECTION 104.6.
  
 8. SHT A01.3ROOF DRAINAGE INDICATES DETAILS A/A803 &
 D/A803. SECTION 1105.1 STATES ROOF DRAINS SHALL HAVE
 STRAINERS EXTENDING NOT LESS THAN 4 INCHES ABOVE THE
 SURFACE OF THE ROOF IMMEDIATELY ADJACENT TO THE ROOF
 DRAINS. STRAINER SHALL HAVE AN AVAILABLE INLET AREA,
 ABOVE THE ROOF, OF NOT LESS THAN ONE AND ONE-HALF TIMES
 THE AREA OF THE CONDUCTOR OR LEADER TO WHICH THE DRAIN
 IS CONNECTED. PLEASE INDICATE HOW THIS AND THE FACT
 THAT THE ROOF DRAIN WILL BE COVERED WITH ROCKS WILL
 MEET THIS CODE REQUIREMENT. THERE IS A CONCERN THAT THE
 GRASS CLIPPINGS, DIRT, MOSS BUILD UP ETC WILL
 EVENTUALLY KEEP THE DRAIN FROM DRAINING AS INTENDED.
 PLEASE SUBMIT INFORMATION ON HOW THIS WILL BE
 ADDRESSED. SECTION 104.6.
  
 9. SHT A01.3 OVERFLOW DRAINS DETAILS B/A803 & C/A803 DO
 NOT MEET THE INTENT OF THE CODE TO BE USED ONLY IN CASE
 OF BLOCKAGE OF THE PRIMARY ROOF DRAINS. THESE DETAILS
 INDICATE THAT THE DRAINS ARE FLUSH WITH THE ROOF AND
 WILL DRAIN WHEN THE PRIMARY ROOF DRAINS DRAIN AND NOT
 AFTER THE BUILDUP OF A BLOCKED PRIMARY DRAIN. DRAINS
 INDICATED IN DETAIL C/A803 ARE SHOWN TO BE NEXT TO AN
 AREA THAT HAS MULCH IN IT. PLEASE CLARIFY AND INDICATE
 HOW THE MULCH WILL NOT BLOCK THE DRAINS. SECTION
 1107.1
  
 10. SHT A01.3 SHOWS 4" RD'S IN PLANTERS. PLEASE
 CLARIFY. PLEASE SUBMIT A DETAIL. SECTION 106.1.1.
  
 11. SHT A01.3 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES. SHOW THE SQUARE FOOTAGE OF EACH
 DRAIN AND INCLUDE 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS AND SHOW ANY ROOF AREA THAT
 CONTRIBUTES TO THE SQUARE FOOTAGE OF ANY DRAIN FROM
 ROOF AREAS ABOVE.
  
 12. SHT A01.3 UPPER ROOF PLANS. PER SECTION 1107.1
 SECONDARY ROOF DRAINS OR SCUPPERS SHALL BE PROVIDED
 WHERE THE ROOF PERIMETER CONSTRUCTION EXTENDS ABOVE THE
 ROOF. PER SECTION 1107.2 SEPARATE SYSTEMS ARE REQUIRED.
 PLEASE SHOW THE SECONDARY ROOF DRAINS/SCUPPERS.
  
 13. SHT A01.3 INDICATE IF THE WATERFALL WILL HAVE A
 SEPARATE WATER SUPPLY. IF SO INDICATE THE REQUIRED
 METHOD OF BACKFLOW PREVENTION. SECTION 608. ALSO
 INDICATE IF THERE WILL BE A DRAIN FOR THE WATERFALL.
 SECTION 106.1.1.
  
 14. SHT A101 SHOW THE CLEAR FLOOR SPACE FOR ALL
 ACCESSIBLE FIXTURES IN ALL TOILET ROOMS. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTIONS 11-4.16,
 11-4.17, 11-4.18, 11-4.19 AND 11-4.22 WITH ALL
 SUBSECTIONS.
  
 15. SHT A104 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES. SHOW THE SQUARE FOOTAGE OF EACH
 DRAIN AND INCLUDE 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS AND SHOW ANY ROOF AREA THAT
 CONTRIBUTES TO THE SQUARE FOOTAGE OF ANY DRAIN FROM
 ROOF AREAS ABOVE.
  
 16. SHT A107 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES. SHOW THE SQUARE FOOTAGE OF EACH
 DRAIN AND INCLUDE 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS AND SHOW ANY ROOF AREA THAT
 CONTRIBUTES TO THE SQUARE FOOTAGE OF ANY DRAIN FROM
 ROOF AREAS ABOVE.--NO SECONDARY ROOF DRAINS ARE
 INDICATED FOR THE INTERIOR ROOF DRAIN AREAS AS REQUIRED
 IN SECTIONS 11-7.1 & 1107.2. PLEASE SHOW THE LOCATION
 OF THE REQUIRED SECONDARY DRAINS.--SCUPPERS
 INDICATED AS 4"X8"ALUM. TRANSFER SCUPPERS AS
 REFERENCED AS DETAIL C/802 ARE NOT APPROVED. PER
 SECTION 1503.4.3. OVERFLOW SCUPPERS SHALL BE PLACED IN
 THE WALL NOT LESS THAN 2" NOR MORE THAN 4" ABOVE THE
 ROOF.
  
 17. SHTS A201, A203, A205, A207 & A209. INDICATE
 SPECIFICATION "A" OR "B" FOR ALL UNITS AS REQUIRED PER
 PAGES 7.34 & 7.35.
  
 18. SHT A201 UNITS A & A REV. INDICATE THE BACKING FOR
 THE TUB IN THE MASTER BATH PER PAGE 6.10.--THE WING
 WALL NEXT TO THE W/C IN THE MASTER BATH TO BE A MAXIMUM
 2'0" PER PAGE 7.44.--LAVS SHALL BE CENTERED ON THE
 48" DIMENSION OF THE CLEAR FLOOR SPACE PER PAGE 7.48 OR
 FORWARD APPROACH WITH REMOVABLE BASE CABINET SHALL BE
 INDICATED.--SHOW THE CLEAR FLOOR SPACE FOR THE
 W/C'S. PAGE 7.43.--RANGE SHALL BE CENTERED ON THE
 48" DIMENSION OF THE CLEAR FLOOR SPACE PER PAGES 7.4 &
 7.9. --THE OPENING FOR THE W/C'S IN BATH 2 SHALL BE
 33" AND MUST SHOW 18" OFF THE TUB OR LAV TO THE CENTER
 OF THE FIXTURE AND 15" MIN. OFF THE OTHER FIXTURE.
 PAGES 7.43, 7.44 & 7.45.--MINIMUM CLEARANCES
 BETWEEN ALL COUNTERS, APPLIANCES, BASE CABINETS AND
 WALLS SHALL BE 40". PAGES 7.8, 7.11, 7.22 & 7.23. 36"
 IS SHOWN. PLEASE SHOW COMPLIANCE.
  
 19. SHT A203 UNITS B & B REV. INDICATE THE BACKING FOR
 THE TUB IN THE MASTER BATH PER PAGE 6.10.--SHOW THE
 CLEAR FLOOR SPACE FOR THE W/C IN THE MASTER BATH PER
 PAGE 7.43.--THE W/C IN THE MASTER BATH SHALL BE 18"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE PER PAGE
 6.5.--LAVS SHALL BE CENTERED ON THE 48" DIMENSION
 OF THE CLEAR FLOOR SPACE PER PAGE 7.48 OR FORWARD
 APPROACH WITH REMOVABLE BASE CABINET SHALL BE
 INDICATED.--BATH #2 OPENING FOR THE W/C SHALL BE
 MINIMUM 33". INDICATE MEASURMENT FROM THE CENTERLINE OF
 THE W/C TO THE SIDE OF THE VANITY PER PAGES 7.43, 7.44
 & 7.45.--MINIMUM CLEARANCES BETWEEN ALL COUNTERS,
 APPLIANCES, BASE CABINETS AND WALLS SHALL BE 40".
 (SHOWN AS 36"). PAGES 7.8, 7.11, 7.22 & 7.23. 36".
 PLEASE SHOW COMPLIANCE.
  
 20. SHT A205 UNIT C. INDICATE THE BACKING FOR THE TUB
 IN THE MASTER BATH PER PAGE 6.10.-- SHOW THE CLEAR
 FLOOR SPACE FOR THEUSABLE W/C PER PAGE 7.43.-- SHOW
 THE CLEAR FLOOR SPACE FOR THE TUBS OR SHOWERS PER PAGES
 7.53 THRU 7.56.--W/C'S SHALL BE 1'6" OFF THE WALL
 TO THE CENTERLINE OF THE FIXTURE PER PAGE 6.5. --
  
 21. SHT A207 UNITS D & D REV.INDICATE THE BACKING FOR
 THE TUB IN THE MASTER BATH PER PAGE 6.10.--SHOW THE
 CLEAR FLOOR SPACE FOR THE USABLE W/C PER PAGE 7.43.--
 SHOW THE OPENING FOR THE W/C IN BATH #2 TO BE A MINIMUM
 OF 33". THE W/C SHALL BE 1'6" OFF ONE FIXTURE TO THE
 CENTERLINE OF THE FIXTURE AND 15" MINIMUM OFF THE OTHER
 FIXTURE OR VANITY CABINET PER PAGES 7.43 THRU 7.45.--
 MINIMUM CLEARANCES BETWEEN ALL COUNTERS, APPLIANCES,
 BASE CABINETS & WALLS SHALL BE 40". PAGES 7.8, 7.11,
 7.22 & 7.23. 36" IS SHOWN. PLEASE SHOW COMPLIANCE.
  
 22. SHT A209 UNITS PHA & PHA REV. INDICATE THE BACKING
 FOR THE TUB IN THE MASTER BATH PER PAGE 6.10.--SHOW
 THE CLEAR FLOOR SPACE FOR THE W/C IN THE MASTER BATH
 PER PAGE 7.43.--THE WING WALL NEXT TO THE W/C IN
 THE MASTER BATH SHALL BE A MAXIMUM OF 2'0" PER PAGE
 7.44.--THE LAVS SHALL BE CENTERED ON THE 48"
 DIMENSION OF THE CLEAR FLOOR SPACE PER PAGE 7.48 OR
 FORWARD APPROACH.--A MINIMUM 33" OPENING IS
 REQUIRED FOR THE W/C IN BATH #2. SHOW THE W/C TO BE
 1'6" OFF ONE FIXTURE TO THE CENTERLINE OF THE FIXTURE,
 AND A MINIMUM OF 15" OFF THE OTHER FIXTURE OR VANITY
 CABINET.--MINIMUM CLEARANCES BETWEEN ALL COUNTERS,
 APPLIANCES, BASE CABINETS & WALLS SHALL BE 40". PAGES
 7.8, 7.11, 7.22 & 7.23. 36" IS SHOWN. PLEASE SHOW
 COMPLIANCE.
  
 23. SHT A212 UNITS PHB & PHB REV. INDICATE THE BACKING
 FOR THE TUB IN THE MASTER BATH PER PAGE 6.10.--SHOW
 THE CLEAR FLOOR SPACE FOR THE USABLE W/C IN THE MASTER
 BATH PER PAGE 7.43.--THE W/C IN THE MASTER BATH
 SHALL BE 18" OFF THE WALL TO THE CENTERLINE OF THE
 FIXTURE PER PAGE 6.5.--THE LAVS SHALL BE CENTERED
 ON THE 48" DIMENSION OF THE CLEAR FLOOR SPACE PER PAGE
 7.48 OR FORWARD APPROACH.--A MINIMUM 33" OPENING IS
 REQUIRED FOR THE W/C IN BATH #2. SHOW THE W/C TO BE
 1'6" OFF ONE FIXTURE TO THE CENTERLINE OF THE FIXTURE,
 AND A MINIMUM OF 15" OFF THE OTHER FIXTURE OR VANITY
 CABINET.--MINIMUM CLEARANCES BETWEEN ALL COUNTERS,
 APPLIANCES, BASE CABINETS & WALLS SHALL BE 40". PAGES
 7.8, 7.11, 7.22 & 7.23. 36" IS SHOWN. PLEASE SHOW
 COMPLIANCE.
  
 24. SHT A214 INDICATES DETAIL B/A802 BUT NO SCUPPER IS
 SHOWN. PLEASE CLARIFY. SECTION 106.1.1.
  
 25. SHT A215 INDICATE THE BACKING FOR THE TUB IN BOTH
 BATHS PER PAGE 6.10.--SHOW THE CLEAR FLOOR SPACE
 FOR THE W/C IN BOTH BATHS PER PAGE 7.43.--THE W/C
 IN BOTH BATHS SHALL BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE PER PAGE 6.5.--THE LAVS
 IN THE MASTER BATH SHALL BE CENTERED ON THE 48"
 DIMENSION OF THE CLEAR FLOOR SPACE PER PAGE 7.48 OR
 FORWARD APPROACH. PLEASE SHOW COMPLIANCE.
  
 26. SHT A400 GROUND FLOOR AND COMMON AREA FINISH
 SCHEDULE. ROOMS 106, 107 & 108 SHOW WALLBOARD FOR THE
 FINISH. PER SECTION 1210.2 WALLS WITHIN 2 FEET OF A W/C
 OR URINAL SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE TO A HEIGHT OF 4' ABOVE THE FLOOR. WALLBOARD
 DOES NOT COMPLY WITH THIS REQUIREMENT. PLEASE INDICATE
 METHOD OF COMPLIANCE.
  
 27. SHT A404 SHOW COMPLIANCE WITH THE FOLLOWING: __FOR
 W/C'S:
 A. 11-4.16.5 FLUSH CONTROLS
 B. 11-4.16.6 DISPENSERS
 __FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.5 FAUCETS
  
 28. SHT A405 SHOW COMPLIANCE WITH THE FOLLOWING: __FOR
 W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.4 GRAB BARS (1-1/2" BETWEEN THE WALL &
 GB)
 C. 11-4.16.5 FLUSH CONTROLS
 __STALLS:
 A. SEE FIG. 30E
 __LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.5 FAUCETS
 __FOR THE SHOWER:
 A. 11-4.21.3 SEAT HEIGHT
 B. 11-4.21.5 CONTROL HEIGHT
  
 29. SHT A700 INDICATES PALM BEACH COUNTY ACCESSIBILITY
 NOTES. THE CODE REFERENCE SHALL BE FBC-2004 CHAPTER 11
 AND/OR FHA-98 DESIGN MANUAL. PLEASE CHANGE REFERENCE.
  
 30. SHT A7.00 NOTE 04) D) INDICATESLAVATORIES TO BE
 15"FROM THE WALL TO THE CENTERLINE OF THE FIXTURE.
 PER PAGE 7.48 THE LAV SHALL BE A MINIMUM OF 24" TO THE
 CENTERLINE OF THE FIXTURE OFF THE WALL OR CENTERED ON
 THE 48" DIMENSION OF THE CLEAR FLOOR SPACE, OR IF
 FORWARD APPROACH INDICATE REMOVABLE BASE CABINETS.
  
 31. SHT A700 NOTE AFTER 16) REFERENCES PALM BEACH
 COUNTY AND MOST OF THE NOTE IS NOT LEGIBLE. PLEASE
 CORRECT THE JURISDICATION OF AUTHORITY AND MAKE SURE
 THE NOTE IS OF SUFFICIENT CLARITY TO INDICATE
 INFORMATION SUBMITTED. SECTION 106.1.1.
  
 32. SHT A700 THE FINAL NOTE IN THE NOTE SECTION (04)
 SHALL BE DELETED. PER FHA-98 DESIGN MANUAL, THE
 RESPONSIBILITY FOR COMPLYING WITH THE LAW RESTS WITH
 ANY AND ALL PERSONS INVOLVED IN THE DESIGN AND
 CONSTRUCTION OF COVERED MULTIFAMILY DWELLINGS. THIS
 DOES NOT INCLUDE LOCAL OR STATE GOVERNMENTS, AND TO TRY
 TO RELIEVE ONE SELF FROM LIBILITY WITH A NOTE WILL NOT
 BE APPROVED. PAGE 22 FHA-98 DESIGN MANUAL.
  
 33.SHT A805 DETAIL A INDICATES A TRENCH DRAIN. PLEASE
 INDICATE WHERE THIS CAN BE FOUND ON THE FLOOR PLAN.
 SECTION 106.1.1.
  
 34. SHT A806 THE SQUARE FOOTAGE FOR ALL EXTERIOR
 PLANTERS SHALL INDICATE 1/2 THE AREA OF ALL VERTICAL
 WALLS. IN THE CASE OF PLANTERS AGAINST THE BUILDING
 THIS WILL INCLUDE THE 1/2 THE AREA OF THE BUILDING UP
 TO THE PARAPETS OF THE ROOF. PLEASE SUBMIT THE
 CALCULATIONS FOR THESE PLANTER DRAINS PER TABLE
 1106.3.
  
 35. SHTS LP-1, LP-2, MP-1 & IR-1. THE LICENSE FOR THE
 LANDSCAPE ARCHITECT IS NULL & VOID AS OF 11-30-1995. --
 THE CERTIFICATE OF AUTHORIZATION NUMBER, (BUSINESS
 LICENSE), IS NOT ISSUED AS THE STATUS IS FOR AN
 APPLICANT.--THE ADDRESS FOR MAJESTIC VIEWS
 LANDSCAPE ARCHITECTS INC SHOWN ON THE TITLE BLOCK DOES
 NOT REFLECT THE ADDRESS OF RECORD ON THE FLORIDA STATE
 DBPR WEBSITE. (SEE ATTACHED SHEETS). THIS INFORMATION
 SHALL BE REQUIRED AND APPROVED PRIOR TO ISSUING THE
 PERMIT.
  
 36. SHT P-1A 4" 2050SF NOT APPROVED. MINIMUM 5"
 REQUIRED OR INDICATE SLOPE OF PIPE PER TABLE 1106.3.
  
 37. SHT P-1A 4" SECONDARY DRAIN BY THE FPL VAULT
 REQUIRED TO BE 5" MINIMUM OR INDICATE THE SLOPE OF PIPE
 PER TABLE 1106.3.
  
 38. SHT P-1A INDICATE THE SQUARE FOOTAGE BEING DRAIN
 FOR EACH SECONDARY ROOF DRAIN. TABLE 1106.3.
  
 39. SHT P-1A 4" DD 400SF NOT ADDED TO HORIZONTAL
 UNDERGROUND TOTAL SQUARE FOOTAGE.
  
 40. SHT P-1B PLAN INDICATED ON SHEET INDEX HAS NOT BEEN
 SUBMITTED. SUBMIT A 2ND FLOOR/ROOF PLAN FOR THE GARAGE.
 SHOW ALL ROOF DRAINS, SECONDARY ROOF DRAINS, WATER
 SUPPLY & BACKFLOW FOR THE WATERFALL ETC. SECTION
 106.1.2.
  
 41. SHT P-1C THE GENERATOR & GENERATOR FUEL INFORMATION
 IS FOR MECHANICAL PLAN REVIEW. PLEASE MOVE THE
 INFORMATION TO THE MECHANICAL SHEETS.
  
 42. SHT P-2 THE W/C & LAV BY COL. LINE H/6 DOES NOT
 CONNECT TO THE BRANCH LINE. PLEASE CLARIFY. SECTION
 106.1.1.
  
 43. SHT P-2 SHOWS 2 3" SPK DRAIN LINES CONNECTING TO
 THE STORM SYSTEM. THIS IS NOT APPROVED PER CITY CODE
 SECTION 90-203(A). CONNECT THE DRAIN LINES TO THE
 SANITARY SYSTEM.
  
 44. SHT P-2 RELIEF VENTS ARE REQUIRED FOR THE AAV'S
 SERVING THE FLOOR DRAINS IN THE PUMP ROOMS. SECTION
 917.3.2.
  
 45. SHT P-2 THE HOSE BIBB IN THE TRASH ROOM DOES NOT
 CONNECT TO THE WATER SUPPLY MAIN. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 46. SHT P-2 THE FITTING CONNECTING THE HORIZONTAL
 BRANCH LINE FOR THE RWL IN "CART" ROOM GUIDES THE STORM
 WATER AGAINST THE FLOW. SECTIONS 706.3 & 1101.6.
  
 47. SHT P-3 SHOW THE PIPING TO EACH FIXTURE IN EACH
 UNIT AT THE BASE OF EACH STACK ON THE FLOOR PLAN.
 SECTION 106.1.2.
  
 48. SHT P-3 SHOWS 4 PLANTER DRAINS BUT ONLY SHOWS
 PIPING AND SQUARE FOOTAGE TO 2 PLANTER DRAINS. PLEASE
 SHOW THE PIPING & SF TO ALL PLANTER DRAINS. SECTION
 1101.2.
  
 49. SHT P-3 RWL SHOWS 1730SF, BUT SAME RWL IS INDICATED
 AS DRAINING 2010SF ON THE LEVELS ABOVE AND BELOW.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 50. SHTS P-4 & P-5 THE RISER DESIGNATION FORRISER
 S/14 IS NOT INDICATED. PLEASE SHOW RISER DESIGNATION.
 SECTION 106.1.2.
  
 51. SHT P-5 THE TYPICAL FLOOR PLAN (4-14) SHOWS AREAS 1
 & 2 WITH ROOF DRAINS. IS THIS TYPICAL FOR ALL FLOORS
 (4-14)? PLEASE CLARIFY. SECTION 106.1.1.
  
 52. SHT P-7 SINKS FOR 3 UNITS ARE NOT SHOWN DRAINING TO
 ANY RISER DIAGRAMS. PLEASE INDICATE WHERE THESE SINKS
 ARE DRAINING TO AND SHOW THE CONNECTION ON THE RISER
 DIAGRAM WHEN INDICATING WHERE THE SINKS ARE DRAINING
 TO. SECTION 106.1.1. INDICATE TOTAL FIXTURE UNITS FOR
 STACK WHEN ADDING THE SINK. TABLE710.1(2).
  
 53. SHT P-7 THE COOLING TOWER OVERLFOW SHALL BE
 INDIRECTLY DRAINED TO THE STORM SYSTEM, AND THE COOLING
 TOWER DRAIN SHALL BE INDIRECTLY DRAINED TO THE SANITARY
 SYSTEM.PLEASE INDICATE ON THE PLANS AND SHOW ON THE
 RISER DIAGRAMS. SECTION 106.1.1.
  
 54. SHT P-7 THE VENT THRU THE ROOF FOR STACK S-7 IS NOT
 INDICATED ON THE ROOF PLAN. PLEASE SHOW VTR ON PLANS.
 SECTION 903.3.
  
 55. SHT P-8 UNIT "A" WATER RISER DIAGRAM. A FULL OPEN
 VALVE IS REQUIRED ON THE SUPPLY LINE TO THE WATER
 HEATER. SECTION 606.1(7).
  
 56. SHT P-8 UNIT "B" WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN AT THE REF. & AT THE PDR ROOM.
 --THE SHOWER IS INDICATED AS A TUB IN THE M/B BY THE
 W/C.-- THE WATER SUPPLY TO THE REF. IS NOT INDICATED
 ON THE FLOOR PLAN.PLEASE CORRECT THE WATER RISER
 DIAGRAM & FLOOR PLAN. SECTION 106.1.1.
  
 57. SHT P-9 UNIT "D"FLOOR PLAN DOES NOT SHOW THE
 WATER SUPPLY CONNECTION FROM THE REF. TO THE WATER
 MAIN.--THE WATER RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLANAT THE REF. PLEASE SHOW PIPING ON THE
 FLOOR PLAN AND SHOW PIPING ON THE RISER DIAGRAM THAT
 REFLECT THE FLOOR PLAN. SECTION 106.1.1.
  
 58. SHT P-9 UNIT "C"THE WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN AT THE SINK, D/W, W/M & AT THE
 CONNECTION FROM THE W/H TO THE WATER MAIN OVERHEAD.
 PLEASE CORRELATE INFORMATION. SECTION 106.1.1.
  
 59. SHT P-10 PH UNIT "A" FLOOR PLAN. INDICATE WHERE THE
 REF. WATER SUPPLY CONNECTS TO THE WATER MAIN. SECTION
 106.1.1.--SUBMIT A UNIT "A" WATER RISER DIAGRAM
 THAT REFLECTS THE FLOOR PLAN. SECTION
 106.3.5.1.3(3)(10)(13).
  
 60. SHT P-11 PH UNIT "B" FLOOR PLAN. INDICATE WHERE THE
 REF. WATER SUPPLY CONNECTS TO THE WATER MAIN. SECTION
 106.1.1.--SUBMIT A UNIT "A" WATER RISER DIAGRAM
 THAT REFLECTS THE FLOOR PLAN. SECTION
 106.3.5.1.3(3)(10)(13).
  
 61. SHT P-12 PH UNIT "C" & PH UNIT "B" SUBMIT WATER
 RISER DIAGRAMS. SECTION 106.3.5.1.3(3)(10)(13).
  
 62. SHT P-13 RISERS 1 & 18 DO NOT REFLECT THE FLOOR
 PLAN. 1ST & 2ND FLOORS INDICATE SHOWERS, BUT THE FLOOR
 PLAN INDICATES TUBS.-- THE PIPING FOR THE SECOND
 FLOOR FIXTURES IS NOT SHOWN ON THE FLOOR PLAN. PLEASE
 CORRELATE INFORMATION. SECTION 106.1.1.
  
 63. SHT P-13 RISERS 2, 10, 14, 20 & 27 DO NOT REFLECT
 THE FLOOR PLAN. ALL RISERS SHOW OFFSETS, BUT OFFSETS
 FOR RISERS 2 & 20 ARE DIFFERENT FROM THE OTHER RISERS.
 PLEASE CLARIFY & CORRELATE THE INFORMATION FROM THE
 RISERS & FLOOR PLANS. SECTION 106.1.1.
  
 64. SHT P-13 RISERS 3 & 21 THE PIPING FOR THE SECOND
 FLOOR FIXTURES IS NOT SHOWN ON THE FLOOR PLAN.-- THE
 VENT DOES NOT SHOW THE OFFSET INDICATED ON THE FLOOR
 PLAN. SECTION 106.1.1.
  
 65. SHT P-13 RISERS 4 & 19 THE PIPING FOR THE SECOND
 FLOOR FIXTURES IS NOT SHOWN ON THE FLOOR PLAN.--
 RECHECK THE TOTAL FU COUNT. ADDS UP TO 110FU.-- SHOW
 THE SIZE OF THE PIPING TO THE W/M'S AT THE 2ND & 3RD
 FLOORS. SECTIONS 106.1.1 & 406.3 & TABLE 709.1.
  
 66. SHT P-13 RISERS 5 & 22 THE PIPING FOR THE SECOND
 FLOOR FIXTURES IS NOT SHOWN ON THE FLOOR PLAN. SECTION
 106.1.1.
  
 67. SHT P-13 RISERS 6 & 23 SHOW ALL PIPE SIZES FROM THE
 STACK THRU TO THE LAVS.--RECHECK THE TOTAL FU
 COUNT. ADDS UP TO 112FU. TABLES 709.1 & 710.1(2).
  
 68. SHT P-13 RISERS 8 & 25THE PIPING FOR THE SECOND
 FLOOR FIXTURES IS NOT SHOWN ON THE FLOOR PLAN.-- VENT
 OFFSETS ARE NOT SHOWN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 69. SHT P-13 RISER 9 THE PIPING FOR THE SECOND FLOOR
 FIXTURES IS NOT SHOWN ON THE FLOOR PLAN.--VENT
 OFFSET IS NOT SHOWN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 70. SHT P-13 RISER 11 THE PIPING FOR THE SECOND FLOOR
 FIXTURES IS NOT SHOWN ON THE FLOOR PLAN. SECTION
 106.1.1.
  
 71. SHT P-13 RISER 12 THE PIPING FOR THE SECOND FLOOR
 FIXTURES IS NOT SHOWN ON THE FLOOR PLAN.--SHOW ALL
 PIPE SIZES ON RISER. SECTION 106.1.1 & TABLE 710.1(2).
  
 72. SHT P-13 RISER 13 THE PIPING FOR THE SECOND FLOOR
 FIXTURES IS NOT SHOWN ON THE FLOOR PLAN. SECTION
 106.1.1.
  
 73. SHT P-13 RISER 15 THE PIPING FOR THE SECOND FLOOR
 FIXTURES IS NOT SHOWN ON THE FLOOR PLAN.--VENT
 OFFSET IS NOT SHOWN. SHOW THE CONNECTION FROM RISER
 S/14. SECTION 106.1.1.
  
 74. SHT P-13 RISER 16 THE PIPING FOR THE SECOND FLOOR
 FIXTURES IS NOT SHOWN ON THE FLOOR PLAN.--VENT
 OFFSET IS NOT SHOWN.--SINK CONNECTION FROM THE
 ROOF NOT SHOWN.--RECHECK THE TOTAL FIXTURE COUNT.
 ADDS UP TO 56. SECTION 106.1.1 & TABLE 710.1(2).
  
 75. SHT P-13 RISER 17 SHOW ALL PIPE SIZES.--THE
 VENT OFFSET IS NOT SHOWN.--RECHECK THE TOTAL
 FIXTURE COUNT. ADDS UP TO 98. SECTION 106.1.1 & TABLE
 710.1(2).
  
 76. SHT P-14 BACKFLOW PROTECTION IS REQUIRED FOR THE
 SUPPLY LINE TO THE TRASH CHUTE FLUSH RING. PLEASE
 INDICATE THE METHOD TO BE USED. (AN N-36 VACUUM BREAKER
 AT THE TOP OF THE SUPPLY LINE IS AN ACCEPTABLE METHOD).
 SECTION 608.--THE PAN DRAIN LINE IS MISLABELED AS
 "CD" RISER DIAGRAM. SECTION 106.1.1.
  
 77. SHT P-15GAS PIPING RISER DIAGRAM. PLEASE SUBMIT
 THE CALCULATION FOR EQUATION 4-2.--SUBMIT
 MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 78. SHT P-15HORIZONTAL WATER ISOMETRIC RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN. OFFSETS IN 1" WATER
 MAIN PRIOR TO THE W/H AND TOILET ROOMS IS NOT SHOWN. --
 NO TRAPPED SECTIONS ALLOWED IN THE T/P DISCHARGE LINE.
 --MANUF. SPECIFICATION SHEET REQUIRED FOR THE IN-LINE
 EXPANSION TANK. SHOW MODEL NUMBER. SECTIONS 106.1.1,
 303.2, 303.4 & 504.6.1.
  
 79. SUBMIT A WATER RISER DIAGRAM FOR THE COOLING TOWER
 WATER. SECTION 106.3.5.1.3(3)(10)(13).
  
 80. SHT P-16 HORIZONTAL SANITARY ISOMETRIC DIAGRAM.
 RECHECK THE DFU'S FOR THE RISERS AND TOTAL AS IT
 ACCUMULATES IN THE SYSTEM.--PIPING DOES NOT REFLECT
 THE FLOOR PLAN AT THE W/C'S, LAV ETC BY THE SHOWERS &
 RISER 27.--THE NOTE FOR REVENT INDICATES CONNTECION
 TO RISER #25. RISER #25 DOES NOT SHOW THE VENT
 CONECTION.--RELIEF VENTS ARE REQUIRED FOR THE AAV'S
 FOR THE FLOOR DRAINS IN THE PUMP ROOMS.TABLE
 710.1(2), SECTIONS 106.1.1 & 917.3.2.
  
 81. SHT P-17 RISER DOES NOT REFLECT THE FLOOR PLAN. THE
 PIPING FOR THE 4" GD'S, 3" SPA DRAINS, PIPING AROUND 6"
 3106SF, 3" RWL BRANCH LINE ARE NOT SHOWN.SECTION
 106.1.1.
  
 82. SHT P-17 THE SIZE OF THE DRAINAGE PIPE SHALL NOT BE
 REDUCED IN SIZE IN THE DIRECTION OF FLOW. (6" RWL
 REDUCES TO 4"). SECTION 704.2.
  
 83. SHT P-17 OFFSETS ARE NOT SHOWN ON THE RISERS TO
 REFLECT THOSE SHOWN ON THE FLOOR PLAN FOR THREE RISERS.
 CORRELATE INFORMATION . SECTION 106.1.1.
  
 84. SHT P-17 4" RWL 1480SF IS INDICATED AS 1340SF AT
 THE ROOF DRAIN. PLEASE CORRELATE INFORMATION. SECTION
 106.1.1.
  
 85. SHT P-18 HORIZONTAL CONDENSATE ISOMETRIC DIAGRAM.
 SHOW ALL PIPE SIZES ON RISER DIAGRAM. SECTION 106.1.1.
  
 86. SHT P-19. GARAGE ROOF STORM DRAINAGE ISOMETRIC
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN AT DD 400SF. --
 SHOW THE PIPING & PIPE SIZE OF PIPE BETWEEN THE
 STRUCTURES.--2 SECONDARY DRAIN SHOWN AS 4" ARE
 REQUIRED TO BE A MINIMUM OF 5". INDICATE PIPE SIZE OR
 SLOPE OF PIPE. TABLE 1106.3 & SECTION 106.1.1.
  
 87. SHT P-20 FIXTURE CONNECTION SCHEDULE. INDICATE THE
 HOT & COLD WATER CONNECTION SIZES TO REFLECT THOSE
 SHOWN ON THE WATER RISER DIAGRAM FOR THE WATER HEATER.
 SECTION 106.1.1 & TABLE 604.5.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND,
 AS WELL AS THE RETURN OF THE RED LINED SET OF PLANS
 FROM THE FIRST REVIEW, WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop X PERMIT EXTENSION
Rev No 1 Status P Date 2009-01-14 Cont ID  
Sent By amckenzi Date 2009-01-14 Time 08:15 Rev Time 0.00
Received By amckenzi Date 2009-01-14 Time 08:15 Sent To  
Notes
2009-01-14 08:16:54EXTEND PERMIT APPLICATION UNTIL APRIL 4, 2009 PER
 RR/AMM

Review Stop Z ZONING
Rev No 2 Status F Date 2008-06-02 Cont ID  
Sent By eschneid Date 2008-06-02 Time 14:51 Rev Time 0.00
Received By eschneid Date 2008-06-02 Time 14:51 Sent To  
Notes
2008-06-02 14:51:52FAILED
  
 1) REPEAT COMMENT - ORDINANCE NO. 3856-05 REQUIRES THE
 SUBMITTAL OF A PHOTOMETRIC PLAN PRIOR TO BUILDING
 PERMIT APPROVAL.
  
 2) REPEAT COMMENT - AN APPROVED TREE ALTERATION PERMIT
 IS REQUIRED.NOTE THAT THE TREE MITIGATION PLAN SHOWS
 TREES REMAINING IN PLACE THAT ARE NOT DEPICTED ON THE
 LANDSCAPE PLAN (EX. #20 & 21 ALONG NORTH PROPERTY LINE,
 ETC).IT APPEARS THAT REMAINING TREE #72 IS IN A PAVED
 AREA.ADDITIONALLY, THE NUMBER OF RELOCATED TREES IS
 NOT ACCURATE BETWEEN THE MITIGATION PLAN AND THE
 LANDSCAPE PLAN.PLEASE CONTACT BOB KUSSNER, LANDSCAPE
 PLANNER, @ (561) 822-1435 FOR AN APPLICATION.
  
 3) THE PARKING SPACE DETAIL ON SHEET A01.1 SHALL SHOW
 THE STANDARD PARKING SPACE AS A MINIMUM OF 18 FEET IN
 DEPTH.SHOWN AT 17 FEET 10 INCHES.
  
 4) WHEN NORTHERNMOST HANDICAP PARKING SPACE WAS
 RELOCATED, THE NUMBER OF SPACES PROVIDED WAS NOT
 UPDATED TO STATE "6 SPACES" - SHEET A01.1.
  
 5) THE LANDSCAPE PLAN WAS NOT UPDATED TO REFLECT THE
 INSTALLATION OF THE HYDRANT IN AN ISLAND ALONG THE
 NORTH PROPERTY LINE.THE PROPOSED TREE AND LANDSCAPE
 WILL CONFLICT WITH THE HYDRANT.PLEASE NOTE THAT THE
 FIRE LINE INSTALLED UNDERGROUND ALONG THE NORTHERN
 PROPERTY LINE WILL CONFLICT WITH THE NORTHERN LANDSCAPE
 BUFFER.THE FIRE LINE SHOULD RUN UNDER THE PAVING TO
 AVOID THESE CONFLICTS.
  
 6) PROVIDE THE PLANNING AND ZONING DEPARTMENT WITH NEW
 CORRECTED SHEETS A01.1, A101, A302, A303 AND LP1 SO
 THAT THE PLANS APPROVED BY THE MINOR AMENDMENT MAY BE
 REVISED TO REFLECT THE BUILDING PLANS.
  
 7) THE INFORMATION SUBMITTED WITH THE PERMIT HAD
 GENERATOR SPECS.WHERE IS THE GENERATOR LOCATED?
  
 8) PROVIDE EVIDENCE THAT THE FPL UTILITY EASEMENT HAS
 BEEN ABANDONED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-27 Cont ID  
Sent By eschneid Date 2007-03-27 Time 09:57 Rev Time 0.00
Received By eschneid Date 2007-03-27 Time 09:57 Sent To  
Notes
2007-03-27 10:04:19FAILED
  
 1) INDICATE THE LIMITS OF WORK, TO INCLUDE DRIVE AISLES
 AND LANDSCAPE, INCLUDED AS PART OF THIS PERMIT.
  
 2) ORDINANCE NO. 3856-05 REQUIRES THE SUBMITTAL OF A
 PHOTOMETRIC PLAN PRIOR TO BUILDING PERMIT APPROVAL.
  
 3) A UNITY OF TITLE IS REQUIRED.
  
 4) PLEASE NOTE THAT ORDINANCE NO. 3856-05 PROHIBITS THE
 USE OF REFLECTIVE GLASS AND REQUIRES THE USE OF AUGER
 CAST PILINGS.
  
 5) THE PARALLEL PARKING SPACES LOCATED IN THE MIDDLE OF
 THE SITE DO NOT CONFORM TO CITY PARKING STANDARDS.
  
 A. PARALLEL SPACES ARE REQUIRED TO BE 8 FEET 6 INCHES
 WIDE.
 B. PARALLEL SPACES ARE REQUIRED TO BE 22 FEET LONG.
 THE SUPPORT COLUMNS LOCATED AT THE OUTSIDE EDGE OF THE
 PARKING SPACES ENCROACH INTO EACH PARKING SPACE,
 CREATING AN OPENING OF 21 FEET, WHICH IS INSUFFICIENT
 FOR A STANDARD PARKING SPACE.
  
 6) THE PARKING SPACE DETAIL ON SHEET A01.1 SHALL SHOW
 THE STANDARD PARKING SPACE AS A MINIMUM OF 18 FEET IN
 DEPTH.THE STANDARD PARKING STALL DETAIL ON SCHORAH
 SHEET 5 IS LISTED AT 19 FEET DEEP BY 9 FEET WIDE, BUT
 NONE OF THE PARKING STALLS ARE THIS SIZE ON THE PLANS
 AND THE PARALLEL PARKING STALL DETAIL DOES NOT REFLECT
 CONDITIONS ON THE SITE.
  
 7) THE SOUTHERN ROW OF PARKING SPACES IS DEPICTED WITH
 A DEPTH OF 15 FEET 10 INCHES WITH A 2 FOOT OVERHANG.
 THIS IS LESS THAN THE REQUIRED 18 FOOT STANDARD PARKING
 STALL DEPTH.
  
 8)THE NORTHERN LANDSCAPE BUFFER IS LISTED ON THE
 PLANS AS BEING 5 FEET WIDE ?OPEN TO ABOVE,? YET IS
 MEASURES AS 4 FEET WIDE TO THE GARAGE ROOF LINE.
  
 9) THE NORTH AND SOUTH CARPORT ROOF DETAILS SHOWN ON
 SHEET A01.5 DO NOT MATCH THE CARPORTS SHOWN ON THE
 CIVIL, ARCHITECTURAL SITE PLANS AND LANDSCAPE PLANS.
  
 10) THE PLANTERS SHOWN ON THE CARPORT ROOFS ARE NOT
 REFLECTED ON THE LANDSCAPE PLANS.
  
 11) NO ADA WALKWAY IS PROVIDED ACROSS THE PARKING AISLE
 FOR THE NORTHERNMOST HANDICAP PARKING SPACE.
  
 12) FENCES AND COLUMNS MAY NOT EXCEED 6 FEET IN THE
 REQUIRED SIDE AND REAR SETBACKS.THIS IS EXCEEDED ON
 THE NORTH SIDE OF BUILDING 2 AND THE SOUTH SIDE OF
 BUILDING 1.THE RETAINING WALL PLUS PICKET FENCE ON
 THE NORTH PROPERTY LINE MAY NOT EXCEED 6 FEET IN HEIGHT
 WHEN MEASURED FROM THE OUTSIDE OF THE PROPERTY (NOT 11
 FEET AS SHOWN).THE CMU PRIVACY WALL SHOWN ADJACENT TO
 THE SOUTH PROPERTY LINE MAY ONLY BE 6 FEET IN HEIGHT,
 NOT THE 8 FOOT HIGH AS SHOWN.SPECIFIC DETAILS OF THIS
 WALL WERE NOT PROVIDED.
  
 13) THE LANDSCAPE PLANS DO NOT MATCH THOSE APPROVED BY
 ORDINANCE NO. 3856-05.MINOR AMENDMENT IS REQUIRED.
  
 14) THE ROOF CANOPY (OVER CENTRAL PARKING) NEEDS
 APPROVAL FOR A MINOR AMENDMENT FOR LANDSCAPE AND
 DESIGN.
  
 15) REMOVE THE BOAT SLIPS FROM THE PROJECT FACT SHEET.
  
 16) THE PROJECT FACT SHEET SHALL BE UPDATED TO REFLECT
 THE SETBACKS APPROVED BY THE ORDINANCE NO. 3856-05 SITE
 PLAN.
  
 17) THE FOOTPRINT AND ELEVATIONS FOR BUILDING 3 IS
 DIFFERENT FROM THE ONE APPROVED BY ORDINANCE NO.
 3856-05.A MINOR AMENDMENT IS REQUIRED.
  
 18) ORDINANCE NO. 3856-05 APPROVED A MAXIMUM BUILDING
 HEIGHT OF 150 FEET.THE PLANS SHOW AIR CONDITIONED
 SPACE (AN EXTRA FLOOR) ABOVE 150 FEET - STAIRS AND
 LANDING - AND JACUZZIS, WHICH ARE NOT COVERED UNDER THE
 HEIGHT EXEMPTIONS.
  
 19) THE USE OF THE PRIVATE GARBAGE PICK-UP REQUIRES
 SIGN-OFF FROM THE CITY?S ENGINEERING SERVICES
 DEPARTMENT.
  
 20) AN ABSTRACTED SURVEY, SHOWING ALL EASEMENTS, IS
 REQUIRED.
  
 21) AN APPROVED TREE RELOCATION PERMIT IS REQUIRED.
 NOTE THAT THE TREE MITIGATION PLAN APPEARS TO CALL OUT
 TREES INCORRECTLY AS TO SPECIES AND SHOWS TREES
 REMAINING IN PLACE IN PAVED AREAS.ADDITIONALLY, THE
 RELOCATED AND PRESERVED TREES DO NOT MATCH THE
 LANDSCAPE PLAN.
  
 22) PROVIDE RESPONSES TO COMMENTS IN WRITTING WITH
 PERMIT RESUBMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.