| Plan Review Stops For Permit 07030457 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2008-06-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-06-02 |
Time |
16:24 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-06-02 |
Time |
16:24 |
Sent To |
PC |
|
| Notes |
| 2008-06-02 16:25:35 | REVISION ADDENDUM#2 PAGE 1 DATED 5-19-08 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2008-01-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-01-22 |
Time |
14:29 |
Rev Time |
1.55 |
| Received By |
jwitmer |
Date |
2008-01-22 |
Time |
14:29 |
Sent To |
PC |
|
| Notes |
| 2008-01-22 14:30:31 | REVISI9ON DATED 1-04-08 STAIRWAY |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2007-12-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-12-21 |
Time |
14:43 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2007-12-21 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2007-12-21 14:43:59 | REVISION"F" OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2007-11-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-11-30 |
Time |
11:40 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2007-11-30 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2007-11-30 15:05:15 | BUILDING PLAN REVIEW | | | PERMIT: 07030457 | | | ADD: 221 CLEMATIS ST | | | CONT:CASTLE FLORIDA BUILDING CORP | | | TEL: (561)756-2491 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISIONREVIEW "E" | | | ACTION: DENIED | | | | | | 1) PLEASE PROVIDE ADDITIONAL INFORMATION FOR DETAIL #4 | | | A-1. EITHER THERE IS A DESCREPANCY IN THE PLANS OR THE | | | DETAIL MAY BE TRYING TO ILLUSTRATE TO AREAS OF | | | RENOVATION WITH ONE DETAIL BUT DIFFERENT WALL | | | CONFIGURATIONS. AT THE BOTTOM OF THE PLAN BOTH THE BEAM | | | AND COLUMN ARE INDICATED AS 4" THICK WHERE ASTHE | | | INFORMATION TO THE RIGHT OF THE DRAWING INDICATE A 8" | | | BEAM AND COLUMN. | | | THIS SAME DETAIL IS NOT INDICATED ON THE FLOOR PLAN FOR | | | LOCATION OR DELTA INDICATING REVISION "E". 106.1.2 | | | ADDITIONAL INFORMATION REQUIRED. | | | | | | 2) SHEETA-2 DETAIL # 1, THE NEW 2HR WALLDEPICTED | | | FAILS TO CONTINUETHE 2HR RATING ON THE TOP TRACK. THE | | | SECOND ISSUE IS THE CEILING DEPICTED IS A ACTUAL WALL | | | ASSEMBLY UL DESIGN (U413)NOT A CEILING ASSEMBLY RATED | | | FOR 2 HRS.NEITHER THE WALL OR CEILING ASSEMBLY SHOWN | | | PROVIDE THE ACTUAL UL REPORT ON THE PLAN, THE INSPECTOR | | | WILL NEED THIS TO COMPLETE THERE INSPECTIONS. 106.1.2. | | | | | | 3) SHEET A-2 DETAIL # 2 PLEASE PROVIDE THE SIZE AND | | | TYPE OF WELD REQUIRED FOR THE HOOPED STEEL PLATE WELDED | | | TO THE STEEL COLUMN. 106.1.2. ADDITIONAL INFORMATION | | | REQUIRED. NOTE THIS FIELD WELD WILL NEED TO BE | | | COMPLETED BY A CERTIFIED WELDER. | | | | | | | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-11-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-11-09 |
Time |
16:42 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2007-11-09 |
Time |
16:42 |
Sent To |
FIRE |
|
| Notes |
| 2007-11-09 16:43:08 | REVISION "C-D" |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2007-05-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-05-03 |
Time |
15:36 |
Rev Time |
0.33 |
| Received By |
jwitmer |
Date |
2007-05-03 |
Time |
15:27 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2007-04-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-04-19 |
Time |
08:31 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2007-04-19 |
Time |
08:31 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-03-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-03-16 |
Time |
07:40 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2007-03-16 |
Time |
07:09 |
Sent To |
|
|
| Notes |
| 2007-03-16 07:43:27 | BUILDING PLAN REVIEW | | | PERMIT: 07030457 | | | ADD: 221 CLEMATIS ST | | | CONT: CASTLE FLORIDA | | | TEL: (561)756-2491 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | | THE COURT. | | | NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | | NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE | | | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: | | | 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT | | | THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) 110.2* W. P. B. ADMINISTRATIVE | | | CODE, INFORMATION THAT IS REQUIRED FOR | | | RECORD KEEPING & FOR CERTIFICATE OF | | | OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH | | | THE PERMIT WAS ISSUED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3. | | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601. | | | D) THE OCCUPANT LOAD, SEE 1004. | | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | | IS REQUIRED. | | | F) ANY SPECIAL STIPULATIONS & CONDITIONS | | | OF THE BUILDING PERMIT. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2007-04-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-04-14 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-04-14 |
Time |
09:37 |
Sent To |
|
|
| Notes |
| 2007-04-14 09:40:06 | *** PROVISO ** | | | *PLANS REDLINED* | | | | | | 1) NOTE: THE DEVICES IN STAIRS MUST MEET NFPA-101 AS | | | STATED ON PREVIOUS REVIEW. | | | PLEASE SEE THAT EACH LEVEL MUST CONTAIN A MINIMUM OF | | | TWO CONTROL DEVICES. THE FAILURE OF A SINGLE CONTROL | | | DEVICE MAY NOT LEAVE ANY ONE EGRESS AREA IN TOTAL | | | DARKNESS. PLEASE SEE 7.9.2.2 | | | | | | 2) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1 AS THE MAXIMUM | | | TIMES FOR(PC) OCCUPANCY TYPE DEVICES SHALL BE 30MINS | | | MAX. | | | | | | ** PLANS TO BE REVISED BEFORE FINAL SHOWING TWO DEVICES | | | ON EACH LEVEL. ALONG WIHT ANY OTHER REVISIONS DURING | | | CONSTRUCTION. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-03-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-03-14 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-03-14 |
Time |
15:44 |
Sent To |
|
|
| Notes |
| 2007-03-14 16:45:23 | ** UNSAT ** | | | | | | | | | 1) NOTE: PLEASE SEE THE STAIR AND EGRESS PATHS MUST | | | CONTAIN THE EMERGENCY BACK UP LIGHTING TO THE RIGHT OF | | | WAY; THIS WOULD INCLUDE ANY "VESTIBULE/LANDING" AREAS | | | DIRECTLY OUTSIDE THE DOORWAY. | | | PLEASE SEE THAT THE PLANS SHOW SWITCHING ON THE STAIR | | | AND EGRESS LIGHTING. PLEASE SEE 7.8 AND 7.9 OF THE 2003 | | | NFPA-101. PLEASE KNOW THAT THE SWITCHING OF A SINGLE | | | DEVICE SHALL NOT LEAVE ANY ONE AREA IN TOTAL DARKNESS. | | | IF AN OCCUPANT IN ALREADY IN THE DIRECTION OF TRAVEL IN | | | AN EMERGENCY OR EVEN UNDER NORMAL CONDITIONS AND A | | | SWITCH IS TURNED OFF, THIS WOULD CREATE A LIFE SAFETY | | | ISSUE AND LEAVE AN OCCUPANT IN THE AREA IN DARKNESS. | | | PLEASE KNOW THAT AUTOMATED SWITCHING BY THE USE OF MORE | | | THAN ONE OCCUPANCY SENSOR IS PERMITTED HOWEVER | | | SWITCHING AS SHOWN IS NOT. | | | PLEASE ADJUST PLANS. | | | * PLEASE ALSO CLARIFY IF THESE FIXTURES CONTAIN A THIRD | | | WIRE TO BE CONNECTED AHEAD OF ANY SWITCHING DEVICES SO | | | THAT THE TURNING OFF OF A SWITCH AS SHOWN OR AN | | | OCCUPANCY SENSOR TYPE DEVICE DOES NOT CREATE THE | | | TURNING "ON" OF A FIXTURE ON THE SWITCH LEG. 700.12E | | | NEC. | | | | | | 2) NOTE: PLEASE SEE MISSING PHOTO-METRIC LEVELS AT ALL | | | EGRESS AREAS INCLUDING WHAT ARE TO BE HALLWAYS AND | | | OTHER AREAS OF EXIT EGRESS. | | | NFPA-101 7.8, 7.9 | | | PLEASE SEE THERE SEEMS TO BE S DIFFERENCE OF THE NUMBER | | | OF LIGHTING FIXTURES SHOWN ON THE PHOTO-METRIC SHEETS | | | COMPARED TO THE NUMBER OF LIGHTING FIXTURES ON THE | | | LIGHTING PLANS. PLEASE VERIFY THIS. (SEE WHAT APPEARS | | | TO BE A AND D FIXTURES TOGETHER). | | | | | | 3) NOTE: PLEASE SEE ANY FIXTURES LOCATED OUTSIDE SHALL | | | BE LISTED FOR LOCATIONS AS EITHER WET OR DAMP | | | LOCATIONS. | | | 110.3 | | | | | | ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY | | | AFFECT THE ELECTRICAL SHEETS/PLANS. | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
7 |
Status |
P |
Date |
2008-05-27 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-05-27 |
Time |
13:05 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-05-27 |
Time |
12:49 |
Sent To |
|
|
| Notes |
| 2008-05-27 13:09:13 | *****REVISION, APPROVED***** | | | | | | THE REVISION OF INTERIOR WALL FRAMING REVIEWED;NO | | | FIRE-STAMPING NEEDED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2007-12-27 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-12-27 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-12-27 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2007-12-27 10:31:17 | *****REVISION APPROVED***** | | | | | | | | | REVISED PLAN SHEETS A1 AND A2 STAMPED, INITIALED, AND | | | DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
F |
Date |
2007-12-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-12-03 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-12-03 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2007-12-03 11:42:48 | *****PROVISO***** | | | | | | | | | THE REVISED PLAN SHEETS (A1 AND/OR A2) TO BE | | | FIRE-STAMPED WHEN THE BUILDING REVIEW COMMENTS HAVE | | | BEEN SATISFIED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2007-11-13 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-11-13 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-11-13 |
Time |
13:39 |
Sent To |
|
|
| Notes |
| 2007-11-13 14:06:12 | *****APPROVED***** | | | | | | | | | REVIEWED REVISED PLAN SHEES A-1 AND A-2;SHEET A-2 | | | STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-05-07 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-05-07 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-05-07 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2007-05-07 11:23:22 | *****APPROVED***** | | | | | | | | | ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | | BEEN ADDRESSED;PLAN SHEETS A-1 AND E-1 WERE STAMPED, | | | INITIALED, AND DATED. | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-05-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-05-07 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2007-04-18 |
Time |
12:33 |
Sent To |
|
|
| Notes |
| 2007-04-18 12:42:25 | ***DENIED*** | | | | | | 1) IT DOES NOT APPEAR THAT THE FIRST FIRE REVIEW HAS | | | BEEN ADDRESSED. | | | | | | 2) PLEASE NOTE THAT NO RESPONSE WAS SUBMITTED ANSWERING | | | THE FIRST FIRE REVIEW COMMENTS. PLEASE REFER TO THE | | | FIRST REVIEW AND PROVIDE A RESPONSE AS WAS REQUESTED AT | | | THAT TIME. | | | | | | 3) NEW FIRE DAMPER INSTALLATIONS TO BE TESTED FOR | | | CLOSURE PRIOR TO FINAL INSPECTION IN ACCORDANCE WITH UL | | | 555. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 805-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-03-27 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-03-27 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-03-27 |
Time |
09:52 |
Sent To |
|
|
| Notes |
| 2007-03-27 10:34:11 | *****DENIED***** | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.DOOR(S) LEADING DIRECTLY TO A CORRIDOR SHALL BE AN | | | APPROVED, LISTED, AND LABELED FIRE DOOR AND ASSEMBLY IN | | | ACCORDANCE WITH NFPA 80. | | | | | | 3.PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT | | | ENCLOSURE ASSEMBLY SHALL BE LIMITED AS PER NFPA 101 - | | | 7.1.3.2.1 (6) | | | | | | 4.PROVIDE EMERGENCY LIGHTING FOR THE EXIT STAIR | | | ENCLOSURES. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESSWHEN RESUBMITTING, | | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | | COMMENT WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2008-05-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-20 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-20 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2008-05-20 11:50:01 | TO "BOB"#17 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2008-01-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-01-08 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-01-08 |
Time |
11:44 |
Sent To |
B |
|
| Notes |
| 2008-01-08 11:44:37 | TO "JWITMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2007-12-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-10 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-10 |
Time |
13:17 |
Sent To |
|
|
| Notes |
| 2007-12-12 10:50:53 | TO "BOB"#5 | | 2007-12-10 13:17:42 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-11-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-11-26 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-11-26 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2007-11-26 14:27:40 | TO "BOB"#17 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-10-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-26 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-26 |
Time |
16:25 |
Sent To |
|
|
| Notes |
| 2007-10-30 15:00:18 | TO "BOB"#17 | | 2007-10-26 16:25:45 | WAITING FOR "BOB" |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-04-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-25 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-25 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2007-04-25 16:04:00 | TO "BOB"#5 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-04-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-04-12 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-04-12 |
Time |
16:48 |
Sent To |
|
|
| Notes |
| 2007-04-13 16:32:36 | TO "BOB"#7 | | 2007-04-12 16:48:49 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-03-27 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-03-27 |
Time |
10:34 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-03-14 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2007-03-14 11:49:57 | TO "BOB"#11 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2007-03-19 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-03-19 |
Time |
09:06 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-03-19 |
Time |
09:06 |
Sent To |
|
|
| Notes |
| 2007-03-19 09:10:00 | *** PROVISO *** | | | 1) FIRE DAMPERS TO BE INSTALLED PER MANUFACTURER'S | | | INSTALLATION INSTRUCTIONS, SEE 2004 FBC/M 607.2. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|