Plan Review Details - Permit 07030457
Plan Review Stops For Permit 07030457
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2008-06-02 Cont ID  
Sent By jwitmer Date 2008-06-02 Time 16:24 Rev Time 0.77
Received By jwitmer Date 2008-06-02 Time 16:24 Sent To PC
Notes
2008-06-02 16:25:35REVISION ADDENDUM#2 PAGE 1 DATED 5-19-08

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-01-22 Cont ID  
Sent By jwitmer Date 2008-01-22 Time 14:29 Rev Time 1.55
Received By jwitmer Date 2008-01-22 Time 14:29 Sent To PC
Notes
2008-01-22 14:30:31REVISI9ON DATED 1-04-08 STAIRWAY

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-12-21 Cont ID  
Sent By jwitmer Date 2007-12-21 Time 14:43 Rev Time 0.77
Received By jwitmer Date 2007-12-21 Time 14:43 Sent To  
Notes
2007-12-21 14:43:59REVISION"F" OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2007-11-30 Cont ID  
Sent By jwitmer Date 2007-11-30 Time 11:40 Rev Time 2.22
Received By jwitmer Date 2007-11-30 Time 11:40 Sent To  
Notes
2007-11-30 15:05:15BUILDING PLAN REVIEW
 PERMIT: 07030457
 ADD: 221 CLEMATIS ST
 CONT:CASTLE FLORIDA BUILDING CORP
 TEL: (561)756-2491
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW "E"
 ACTION: DENIED
  
 1) PLEASE PROVIDE ADDITIONAL INFORMATION FOR DETAIL #4
 A-1. EITHER THERE IS A DESCREPANCY IN THE PLANS OR THE
 DETAIL MAY BE TRYING TO ILLUSTRATE TO AREAS OF
 RENOVATION WITH ONE DETAIL BUT DIFFERENT WALL
 CONFIGURATIONS. AT THE BOTTOM OF THE PLAN BOTH THE BEAM
 AND COLUMN ARE INDICATED AS 4" THICK WHERE ASTHE
 INFORMATION TO THE RIGHT OF THE DRAWING INDICATE A 8"
 BEAM AND COLUMN.
 THIS SAME DETAIL IS NOT INDICATED ON THE FLOOR PLAN FOR
 LOCATION OR DELTA INDICATING REVISION "E". 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 2) SHEETA-2 DETAIL # 1, THE NEW 2HR WALLDEPICTED
 FAILS TO CONTINUETHE 2HR RATING ON THE TOP TRACK. THE
 SECOND ISSUE IS THE CEILING DEPICTED IS A ACTUAL WALL
 ASSEMBLY UL DESIGN (U413)NOT A CEILING ASSEMBLY RATED
 FOR 2 HRS.NEITHER THE WALL OR CEILING ASSEMBLY SHOWN
 PROVIDE THE ACTUAL UL REPORT ON THE PLAN, THE INSPECTOR
 WILL NEED THIS TO COMPLETE THERE INSPECTIONS. 106.1.2.
  
 3) SHEET A-2 DETAIL # 2 PLEASE PROVIDE THE SIZE AND
 TYPE OF WELD REQUIRED FOR THE HOOPED STEEL PLATE WELDED
 TO THE STEEL COLUMN. 106.1.2. ADDITIONAL INFORMATION
 REQUIRED. NOTE THIS FIELD WELD WILL NEED TO BE
 COMPLETED BY A CERTIFIED WELDER.
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-11-09 Cont ID  
Sent By jwitmer Date 2007-11-09 Time 16:42 Rev Time 0.77
Received By jwitmer Date 2007-11-09 Time 16:42 Sent To FIRE
Notes
2007-11-09 16:43:08REVISION "C-D"

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-05-07 Cont ID  
Sent By jwitmer Date 2007-05-03 Time 15:36 Rev Time 0.33
Received By jwitmer Date 2007-05-03 Time 15:27 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-04-19 Cont ID  
Sent By jwitmer Date 2007-04-19 Time 08:31 Rev Time 1.22
Received By jwitmer Date 2007-04-19 Time 08:31 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-16 Cont ID  
Sent By jwitmer Date 2007-03-16 Time 07:40 Rev Time 2.22
Received By jwitmer Date 2007-03-16 Time 07:09 Sent To  
Notes
2007-03-16 07:43:27BUILDING PLAN REVIEW
 PERMIT: 07030457
 ADD: 221 CLEMATIS ST
 CONT: CASTLE FLORIDA
 TEL: (561)756-2491
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-04-14 Cont ID  
Sent By dpalmer Date 2007-04-14 Time 09:37 Rev Time 0.00
Received By dpalmer Date 2007-04-14 Time 09:37 Sent To  
Notes
2007-04-14 09:40:06*** PROVISO **
 *PLANS REDLINED*
  
 1) NOTE: THE DEVICES IN STAIRS MUST MEET NFPA-101 AS
 STATED ON PREVIOUS REVIEW.
 PLEASE SEE THAT EACH LEVEL MUST CONTAIN A MINIMUM OF
 TWO CONTROL DEVICES. THE FAILURE OF A SINGLE CONTROL
 DEVICE MAY NOT LEAVE ANY ONE EGRESS AREA IN TOTAL
 DARKNESS. PLEASE SEE 7.9.2.2
  
 2) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1 AS THE MAXIMUM
 TIMES FOR(PC) OCCUPANCY TYPE DEVICES SHALL BE 30MINS
 MAX.
  
 ** PLANS TO BE REVISED BEFORE FINAL SHOWING TWO DEVICES
 ON EACH LEVEL. ALONG WIHT ANY OTHER REVISIONS DURING
 CONSTRUCTION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-14 Cont ID  
Sent By dpalmer Date 2007-03-14 Time 16:44 Rev Time 0.00
Received By dpalmer Date 2007-03-14 Time 15:44 Sent To  
Notes
2007-03-14 16:45:23** UNSAT **
  
  
 1) NOTE: PLEASE SEE THE STAIR AND EGRESS PATHS MUST
 CONTAIN THE EMERGENCY BACK UP LIGHTING TO THE RIGHT OF
 WAY; THIS WOULD INCLUDE ANY "VESTIBULE/LANDING" AREAS
 DIRECTLY OUTSIDE THE DOORWAY.
 PLEASE SEE THAT THE PLANS SHOW SWITCHING ON THE STAIR
 AND EGRESS LIGHTING. PLEASE SEE 7.8 AND 7.9 OF THE 2003
 NFPA-101. PLEASE KNOW THAT THE SWITCHING OF A SINGLE
 DEVICE SHALL NOT LEAVE ANY ONE AREA IN TOTAL DARKNESS.
 IF AN OCCUPANT IN ALREADY IN THE DIRECTION OF TRAVEL IN
 AN EMERGENCY OR EVEN UNDER NORMAL CONDITIONS AND A
 SWITCH IS TURNED OFF, THIS WOULD CREATE A LIFE SAFETY
 ISSUE AND LEAVE AN OCCUPANT IN THE AREA IN DARKNESS.
 PLEASE KNOW THAT AUTOMATED SWITCHING BY THE USE OF MORE
 THAN ONE OCCUPANCY SENSOR IS PERMITTED HOWEVER
 SWITCHING AS SHOWN IS NOT.
 PLEASE ADJUST PLANS.
 * PLEASE ALSO CLARIFY IF THESE FIXTURES CONTAIN A THIRD
 WIRE TO BE CONNECTED AHEAD OF ANY SWITCHING DEVICES SO
 THAT THE TURNING OFF OF A SWITCH AS SHOWN OR AN
 OCCUPANCY SENSOR TYPE DEVICE DOES NOT CREATE THE
 TURNING "ON" OF A FIXTURE ON THE SWITCH LEG. 700.12E
 NEC.
  
 2) NOTE: PLEASE SEE MISSING PHOTO-METRIC LEVELS AT ALL
 EGRESS AREAS INCLUDING WHAT ARE TO BE HALLWAYS AND
 OTHER AREAS OF EXIT EGRESS.
 NFPA-101 7.8, 7.9
 PLEASE SEE THERE SEEMS TO BE S DIFFERENCE OF THE NUMBER
 OF LIGHTING FIXTURES SHOWN ON THE PHOTO-METRIC SHEETS
 COMPARED TO THE NUMBER OF LIGHTING FIXTURES ON THE
 LIGHTING PLANS. PLEASE VERIFY THIS. (SEE WHAT APPEARS
 TO BE A AND D FIXTURES TOGETHER).
  
 3) NOTE: PLEASE SEE ANY FIXTURES LOCATED OUTSIDE SHALL
 BE LISTED FOR LOCATIONS AS EITHER WET OR DAMP
 LOCATIONS.
 110.3
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT THE ELECTRICAL SHEETS/PLANS.
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2008-05-27 Cont ID  
Sent By mawillia Date 2008-05-27 Time 13:05 Rev Time 0.00
Received By mawillia Date 2008-05-27 Time 12:49 Sent To  
Notes
2008-05-27 13:09:13*****REVISION, APPROVED*****
  
 THE REVISION OF INTERIOR WALL FRAMING REVIEWED;NO
 FIRE-STAMPING NEEDED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2007-12-27 Cont ID  
Sent By mawillia Date 2007-12-27 Time 10:35 Rev Time 0.00
Received By mawillia Date 2007-12-27 Time 10:19 Sent To  
Notes
2007-12-27 10:31:17*****REVISION APPROVED*****
  
  
 REVISED PLAN SHEETS A1 AND A2 STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status F Date 2007-12-03 Cont ID  
Sent By mawillia Date 2007-12-03 Time 11:42 Rev Time 0.00
Received By mawillia Date 2007-12-03 Time 11:26 Sent To  
Notes
2007-12-03 11:42:48*****PROVISO*****
  
  
 THE REVISED PLAN SHEETS (A1 AND/OR A2) TO BE
 FIRE-STAMPED WHEN THE BUILDING REVIEW COMMENTS HAVE
 BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-11-13 Cont ID  
Sent By mawillia Date 2007-11-13 Time 14:06 Rev Time 0.00
Received By mawillia Date 2007-11-13 Time 13:39 Sent To  
Notes
2007-11-13 14:06:12*****APPROVED*****
  
  
 REVIEWED REVISED PLAN SHEES A-1 AND A-2;SHEET A-2
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-05-07 Cont ID  
Sent By mawillia Date 2007-05-07 Time 11:24 Rev Time 0.00
Received By mawillia Date 2007-05-07 Time 11:10 Sent To  
Notes
2007-05-07 11:23:22*****APPROVED*****
  
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEETS A-1 AND E-1 WERE STAMPED,
 INITIALED, AND DATED.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-05-07 Cont ID  
Sent By jwitmer Date 2007-05-07 Time 08:16 Rev Time 0.00
Received By jwitmer Date 2007-04-18 Time 12:33 Sent To  
Notes
2007-04-18 12:42:25***DENIED***
  
 1) IT DOES NOT APPEAR THAT THE FIRST FIRE REVIEW HAS
 BEEN ADDRESSED.
  
 2) PLEASE NOTE THAT NO RESPONSE WAS SUBMITTED ANSWERING
 THE FIRST FIRE REVIEW COMMENTS. PLEASE REFER TO THE
 FIRST REVIEW AND PROVIDE A RESPONSE AS WAS REQUESTED AT
 THAT TIME.
  
 3) NEW FIRE DAMPER INSTALLATIONS TO BE TESTED FOR
 CLOSURE PRIOR TO FINAL INSPECTION IN ACCORDANCE WITH UL
 555.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 805-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-27 Cont ID  
Sent By mawillia Date 2007-03-27 Time 10:34 Rev Time 0.00
Received By mawillia Date 2007-03-27 Time 09:52 Sent To  
Notes
2007-03-27 10:34:11*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.DOOR(S) LEADING DIRECTLY TO A CORRIDOR SHALL BE AN
 APPROVED, LISTED, AND LABELED FIRE DOOR AND ASSEMBLY IN
 ACCORDANCE WITH NFPA 80.
  
 3.PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT
 ENCLOSURE ASSEMBLY SHALL BE LIMITED AS PER NFPA 101 -
 7.1.3.2.1 (6)
  
 4.PROVIDE EMERGENCY LIGHTING FOR THE EXIT STAIR
 ENCLOSURES.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESSWHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 COMMENT WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-05-20 Cont ID  
Sent By adarroug Date 2008-05-20 Time 11:49 Rev Time 0.00
Received By adarroug Date 2008-05-20 Time 11:49 Sent To  
Notes
2008-05-20 11:50:01TO "BOB"#17

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-01-08 Cont ID  
Sent By shill Date 2008-01-08 Time 11:44 Rev Time 0.00
Received By shill Date 2008-01-08 Time 11:44 Sent To B
Notes
2008-01-08 11:44:37TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-12-10 Cont ID  
Sent By adarroug Date 2007-12-10 Time 13:17 Rev Time 0.00
Received By adarroug Date 2007-12-10 Time 13:17 Sent To  
Notes
2007-12-12 10:50:53TO "BOB"#5
2007-12-10 13:17:42WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-11-26 Cont ID  
Sent By adarroug Date 2007-11-26 Time 14:25 Rev Time 0.00
Received By adarroug Date 2007-11-26 Time 14:25 Sent To  
Notes
2007-11-26 14:27:40TO "BOB"#17

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-10-26 Cont ID  
Sent By adarroug Date 2007-10-26 Time 16:25 Rev Time 0.00
Received By adarroug Date 2007-10-26 Time 16:25 Sent To  
Notes
2007-10-30 15:00:18TO "BOB"#17
2007-10-26 16:25:45WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-25 Cont ID  
Sent By adarroug Date 2007-04-25 Time 16:01 Rev Time 0.00
Received By adarroug Date 2007-04-25 Time 16:01 Sent To  
Notes
2007-04-25 16:04:00TO "BOB"#5

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-12 Cont ID  
Sent By adarroug Date 2007-04-12 Time 16:48 Rev Time 0.00
Received By adarroug Date 2007-04-12 Time 16:48 Sent To  
Notes
2007-04-13 16:32:36TO "BOB"#7
2007-04-12 16:48:49WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-27 Cont ID  
Sent By mawillia Date 2007-03-27 Time 10:34 Rev Time 0.00
Received By mawillia Date 2007-03-14 Time 11:48 Sent To  
Notes
2007-03-14 11:49:57TO "BOB"#11

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-03-19 Cont ID  
Sent By tgordon Date 2007-03-19 Time 09:06 Rev Time 0.20
Received By tgordon Date 2007-03-19 Time 09:06 Sent To  
Notes
2007-03-19 09:10:00*** PROVISO ***
 1) FIRE DAMPERS TO BE INSTALLED PER MANUFACTURER'S
 INSTALLATION INSTRUCTIONS, SEE 2004 FBC/M 607.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.