Plan Review Details - Permit 07030448
Plan Review Stops For Permit 07030448
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-03-13 Cont ID  
Sent By rmcdouga Date 2007-03-13 Time 15:36 Rev Time 0.00
Received By rmcdouga Date 2007-03-13 Time 15:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-13 Cont ID  
Sent By rmcdouga Date 2007-03-13 Time 10:44 Rev Time 0.00
Received By rmcdouga Date 2007-03-13 Time 10:44 Sent To  
Notes
2007-03-13 11:04:05DENIED BY BUILDING
  
 1) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE ON THE
 PERMIT APPLICATION.
  
 2) INDICATE WHICH ONE OF THE FASTENING OPTIONS AND
 MAXIMUM DESIGN PRESSURE LISTED ON PAGES 9 AND 10 OF THE
 NOA WILL BE USED. CIRCLE THE APPROPRIATE ONE.
  
 3) SEE 2004 FBC TABLE 1609.6.2.1(2) FOR THE REQUIRED
 PRESSURES. ENHANCED FASTENER SPACING WILL BE REQUIRED
 IN ORDER TO MEET THE UPLIFT REQUIREMENTS OF THE CORNER
 AND POSSIBLY THE PERIMETER AREAS. SEE LIMIATION NUMBER
 7 ON THE PAGE 32 OF THE NOA AND SUBMIT RAS 117
 CALCULATIONS.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-03-12 Cont ID  
Sent By swurafti Date 2007-03-12 Time 16:15 Rev Time 0.00
Received By swurafti Date 2007-03-12 Time 16:15 Sent To  
Notes
2007-03-12 16:16:14HISTORIC APPROVED BY GJUDGE