Plan Review Details - Permit 07030445
Plan Review Stops For Permit 07030445
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-16 Cont ID  
Sent By amorse Date 2007-06-16 Time 07:07 Rev Time 0.00
Received By amorse Date 2007-06-16 Time 07:07 Sent To PC
Notes
2007-06-16 07:09:21 
  
 DENIED
  
 1)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*. FEES ARE DUE IN THE AMOUNT OF $ 982.43
 FOR THE INCREASED VALUE AND ARE REQUIRED TO BE PAID
 BEFORE FURTHER PLAN REVIEW.
  
 2)THE PERMIT APPLICATION SHALL INCLUDE TWO
 COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THE FOLLOWING ARE REQUIRED AT
 MINIMUM, SHINGLES AND TRUSS/BUILDING CONNECTORS. IF
 DOORS AND WINDOWS ARE DAMAGED AND REQUIRE REPLACEMENT
 THEY WILL ALSO REQUIRE PRODUCT APPROVALS. THE CONNECTOR
 FLORIDA STATEWIDE PRODUCT APPROVAL (FL#) CAN BE LISTED
 ON THE CONNECTOR SCHEDULE IN LIEU OF SUBMITTING THE
 PRODUCT APPROVAL SHEETS.
  
 3)THE CITY OF WEST PALM BEACH REQUIRES THE
 FLORIDA STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 4)WORK ON EXISTING BUILDINGS IS COVERED UNDER THE FBC
 (EXISTING) AS SUCH A DESIGN PROFESSIONAL OR OWNERMUST
 ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION PER
 301.5 FBC (EXISTING)
  
 5)THE JURISDICTION ON DRAWINGS IS INCORRECT
  
 6)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD
  
 7)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 8)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
 6)

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-14 Cont ID  
Sent By kconrad Date 2007-03-14 Time 18:02 Rev Time 0.00
Received By kconrad Date 2007-03-14 Time 18:02 Sent To I
Notes
2007-03-14 18:04:43REQUIRE PLANS TO BE SUBMITTED FOR REVIEW. ALSO MUST
 PROVIDE CONTRACT VALUE VERIFICATION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-05-25 Cont ID  
Sent By btrobaug Date 2007-05-25 Time 16:04 Rev Time 0.50
Received By btrobaug Date 2007-05-25 Time 15:48 Sent To M
Notes
2007-05-25 16:04:52 
  
 DENIED/INCOMPLETE INFORMATION
  
 1} SUBMIT A PANEL SCHEDULE PER408.4 CIRCUIT DIRECTORY
 OR CIRCUIT IDENTIFICATION
 EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY
 IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC
 PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-06-16 Time   Rev Time 0.00
Received By adarroug Date 2007-05-21 Time 09:20 Sent To  
Notes
2007-05-21 09:22:03TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-05-25 Cont ID  
Sent By tgordon Date 2007-05-25 Time 16:16 Rev Time 0.25
Received By tgordon Date 2007-05-25 Time 16:16 Sent To P
Notes
2007-05-25 16:21:07*** DENIED ***
 1) PLEASE SUBMIT MECHANICAL PLANS (A/C) SHOWING ALL
 DUCT WORK TO BE REPLACED AND ANY A/C EQUIPMENT TO BE
 REPLACEDPER 2004 FBC CITY OF WPB AMEND. 106.3.5.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-06-11 Cont ID  
Sent By mperson Date 2007-06-11 Time 11:11 Rev Time 0.45
Received By mperson Date 2007-06-11 Time 11:11 Sent To B
Notes
2007-06-11 11:33:13DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. MORE INFORMATION IS REQUIRED ON THE DRAWINGS DUE TO
 THE FIRE DAMAGE.
 A} IF PLUMBING LAYOUT IS THE SAME
 WITH NO CHANGES AND FIRE DAMAGE, PLEASE INDICATE THIS
 ON
 THE DRAWING.
 B} IF PLUMBING LAYOUT IS THE
 SAME AND THE PLUMBING FIXTURES ARE TO BE
 CHANGED DUE TO FIRE DAMAGE, PLEASE INDICATE THIS ON THE
 DRAWING.
 "EXACT FIXTURE CHANGE OUT ONLY."
 C} IF PLUMBING (SANITARY) PIPE WAS DAMAGED BY THE FIRE
 AND NEEDS TO BE REPLACED PLEASE FOLLOW WHAT IS REQUIRED
 IN COMMENT #2.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4
 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A
 PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING
 ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT
 LOCATIONS.
  
 3. NOTE: PER FBC-2004 PLUMBING, TABLE 403.1 THAT ONE
 (1) AUTOMATIC CLOTHES WASHER CONNECTOR PER DWELLING
 UNIT REQUIRED AND NEEDS TO BE INDICATED ON THE
 RESUBMITTED DRAWINGS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***