| 2007-04-12 16:39:58 | BUILDING PLAN REVIEW |
| | PERMIT: 07030430 |
| | ADD: 2101 45TH ST |
| | CONT: JC'S AUTO BODY SERVICES, INC |
| | TEL: (863)287-4171 |
| | |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| | THE COURT. |
| | NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS |
| | NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE |
| | RECORDING THEREOF, |
| | SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)THE |
| | POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | 3) THE PERMIT VALUEFOR THE WORK TO BE COMPLETED |
| | UNDERTHIS PERMIT IS ALOW VALUE. 108.3*BUILDING PERMIT |
| | VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED.FOR PERMITTINGPURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BYTHE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 4)ENGINEER OF RECORD IS MISSING TITLEBLOCK |
| | INFORMATION. |
| | 61G15-23.002(2)FL. ADMIN. CODE. |
| | PLANS SIGNED & SEALED BY A PROFESSIONAL |
| | ENGINEER SHALL INCLUDE EITHER THE NAME, |
| | ADDRESS AND LICENSE NUMBER OF THE |
| | ENGINEER OR, THE NAME AND LICENSE NUMBER |
| | OF THE ENGINEER AND THE NAME, ADDRESS |
| | AND CERTIFICATE OF AUTHORIZATION NUMBER |
| | OF THE ENGINEERING BUSINESS THROUGH |
| | WHICH THE ENGINEER IS PRACTICING |
| | (471.025 F.S. AND 471.023 F.S.). |
| | |
| | 5) 110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PROJECT WAS DESIGNED. 2004 FBC W/ 2006 |
| | AMENDMENTS. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | |
| | 6)2004 FL. BLD CODE 1603.1.4 THE |
| | FOLLOWING INFORMATION RELATED TO WIND |
| | SHALL BE SHOWN ON THE CONSTRUCTION |
| | DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 7)THE PRIMARY CONTRACTOR BEING A CMC IS WORKING OUT |
| | OF SCOPE OF LICENSE, WILL REQUIREA CGC OR BC FOR THE |
| | CONCRETE WORK. |
| | FL S S 489. |
| | |
| | 8) MISSING INFORMATION ON THE SPRAY BOOTH, PLEASE |
| | PROVIDE : |
| | 416.2 SPRAY ROOMS. |
| | SPRAY ROOMS SHALL BE ENCLOSED WITH FIRE BARRIER WALLS |
| | AND HORIZONTAL ASSEMBLIES OR BOTH WITH NOT LESS THAN A |
| | 1-HOUR FIRE-RESISTANCE RATING. FLOORS SHALL BE |
| | WATERPROOFED AND DRAINED IN AN APPROVED MANNER. |
| | |
| | 416.2.1 SURFACES. |
| | THE INTERIOR SURFACES OF SPRAY ROOMS SHALL BE SMOOTH |
| | AND SHALL BE SO CONSTRUCTED TO PERMIT THE FREE PASSAGE |
| | OF EXHAUST AIR FROM ALL PARTS OF THE INTERIOR AND TO |
| | FACILITATE WASHING AND CLEANING, AND SHALL BE SO |
| | DESIGNED TO CONFINE RESIDUES WITHIN THE ROOM. ALUMINUM |
| | SHALL NOT BE USED. |
| | SPRAYING |
| | 416.3 SPRAYING SPACES. |
| | SPRAYING SPACES SHALL BE VENTILATED WITH AN EXHAUST |
| | SYSTEM TO PREVENT THE ACCUMULATION OF FLAMMABLE MIST OR |
| | VAPORS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, |
| | MECHANICAL . WHERE SUCH SPACES ARE NOT SEPARATELY |
| | ENCLOSED, NONCOMBUSTIBLE SPRAY CURTAINS SHALL BE |
| | PROVIDED TO RESTRICT THE SPREAD OF FLAMMABLE VAPORS. |
| | |
| | 416.3.1 SURFACES. |
| | THE INTERIOR SURFACES OF SPRAYING SPACES SHALL BE |
| | SMOOTH AND CONTINUOUS WITHOUT EDGES, AND SHALL BE SO |
| | CONSTRUCTED TO PERMIT THE FREE PASSAGE OF EXHAUST AIR |
| | FROM ALL PARTS OF THE INTERIOR AND TO FACILITATE |
| | WASHING AND CLEANING, AND SHALL BE SO DESIGNED TO |
| | CONFINE RESIDUES WITHIN THE SPRAYING SPACE. ALUMINUM |
| | SHALL NOT BE USED. |
| | |
| | 416.4 FIRE PROTECTION. |
| | AN AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL BE |
| | PROVIDED IN ALL SPRAY , DIP AND IMMERSING SPACES AND |
| | STORAGE ROOMS, AND SHALL BE INSTALLED IN ACCORDANCE |
| | WITH CHAPTER 9 . |
| | |
| | 9) FLOOR PLAN IS NOT CLEAR WHERE THE FLOOR CUT OUT IS |
| | IN RELATION TO THE EXTERIOR WALL, PLEASE PROVIDE A |
| | CLEARERLAYOUT OF THE CONCRETE WORK. |
| | 1803.1 EXCAVATIONS NEAR FOOTINGS OR FOUNDATIONS. |
| | EXCAVATIONS FOR ANY PURPOSE SHALL NOT REMOVE LATERAL |
| | SUPPORT FROM ANY FOOTING OR FOUNDATION WITHOUT FIRST |
| | UNDERPINNING OR PROTECTING THE FOOTING OR FOUNDATION |
| | AGAINST SETTLEMENT OR LATERAL TRANSLATION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |