Plan Review Details - Permit 07030430
Plan Review Stops For Permit 07030430
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-12 Cont ID  
Sent By jwitmer Date 2007-04-12 Time 15:56 Rev Time 1.55
Received By jwitmer Date 2007-04-12 Time 15:56 Sent To  
Notes
2007-04-12 16:39:58BUILDING PLAN REVIEW
 PERMIT: 07030430
 ADD: 2101 45TH ST
 CONT: JC'S AUTO BODY SERVICES, INC
 TEL: (863)287-4171
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)THE
 POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3) THE PERMIT VALUEFOR THE WORK TO BE COMPLETED
 UNDERTHIS PERMIT IS ALOW VALUE. 108.3*BUILDING PERMIT
 VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED.FOR PERMITTINGPURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BYTHE INTERNATIONAL CODE
 CONGRESS.
  
 4)ENGINEER OF RECORD IS MISSING TITLEBLOCK
 INFORMATION.
 61G15-23.002(2)FL. ADMIN. CODE.
 PLANS SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE NAME,
 ADDRESS AND LICENSE NUMBER OF THE
 ENGINEER OR, THE NAME AND LICENSE NUMBER
 OF THE ENGINEER AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH
 WHICH THE ENGINEER IS PRACTICING
 (471.025 F.S. AND 471.023 F.S.).
  
 5) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PROJECT WAS DESIGNED. 2004 FBC W/ 2006
 AMENDMENTS.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
  
 6)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 7)THE PRIMARY CONTRACTOR BEING A CMC IS WORKING OUT
 OF SCOPE OF LICENSE, WILL REQUIREA CGC OR BC FOR THE
 CONCRETE WORK.
 FL S S 489.
  
 8) MISSING INFORMATION ON THE SPRAY BOOTH, PLEASE
 PROVIDE :
 416.2 SPRAY ROOMS.
 SPRAY ROOMS SHALL BE ENCLOSED WITH FIRE BARRIER WALLS
 AND HORIZONTAL ASSEMBLIES OR BOTH WITH NOT LESS THAN A
 1-HOUR FIRE-RESISTANCE RATING. FLOORS SHALL BE
 WATERPROOFED AND DRAINED IN AN APPROVED MANNER.
  
 416.2.1 SURFACES.
 THE INTERIOR SURFACES OF SPRAY ROOMS SHALL BE SMOOTH
 AND SHALL BE SO CONSTRUCTED TO PERMIT THE FREE PASSAGE
 OF EXHAUST AIR FROM ALL PARTS OF THE INTERIOR AND TO
 FACILITATE WASHING AND CLEANING, AND SHALL BE SO
 DESIGNED TO CONFINE RESIDUES WITHIN THE ROOM. ALUMINUM
 SHALL NOT BE USED.
 SPRAYING
 416.3 SPRAYING SPACES.
 SPRAYING SPACES SHALL BE VENTILATED WITH AN EXHAUST
 SYSTEM TO PREVENT THE ACCUMULATION OF FLAMMABLE MIST OR
 VAPORS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL . WHERE SUCH SPACES ARE NOT SEPARATELY
 ENCLOSED, NONCOMBUSTIBLE SPRAY CURTAINS SHALL BE
 PROVIDED TO RESTRICT THE SPREAD OF FLAMMABLE VAPORS.
  
 416.3.1 SURFACES.
 THE INTERIOR SURFACES OF SPRAYING SPACES SHALL BE
 SMOOTH AND CONTINUOUS WITHOUT EDGES, AND SHALL BE SO
 CONSTRUCTED TO PERMIT THE FREE PASSAGE OF EXHAUST AIR
 FROM ALL PARTS OF THE INTERIOR AND TO FACILITATE
 WASHING AND CLEANING, AND SHALL BE SO DESIGNED TO
 CONFINE RESIDUES WITHIN THE SPRAYING SPACE. ALUMINUM
 SHALL NOT BE USED.
  
 416.4 FIRE PROTECTION.
 AN AUTOMATIC FIRE-EXTINGUISHING SYSTEM SHALL BE
 PROVIDED IN ALL SPRAY , DIP AND IMMERSING SPACES AND
 STORAGE ROOMS, AND SHALL BE INSTALLED IN ACCORDANCE
 WITH CHAPTER 9 .
  
 9) FLOOR PLAN IS NOT CLEAR WHERE THE FLOOR CUT OUT IS
 IN RELATION TO THE EXTERIOR WALL, PLEASE PROVIDE A
 CLEARERLAYOUT OF THE CONCRETE WORK.
 1803.1 EXCAVATIONS NEAR FOOTINGS OR FOUNDATIONS.
 EXCAVATIONS FOR ANY PURPOSE SHALL NOT REMOVE LATERAL
 SUPPORT FROM ANY FOOTING OR FOUNDATION WITHOUT FIRST
 UNDERPINNING OR PROTECTING THE FOOTING OR FOUNDATION
 AGAINST SETTLEMENT OR LATERAL TRANSLATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-23 Cont ID  
Sent By dpalmer Date 2007-03-23 Time 07:27 Rev Time 0.00
Received By dpalmer Date 2007-03-22 Time 19:55 Sent To  
Notes
2007-03-23 07:29:36 
  
 ****** UNSAT ******
  
 ** PLEASE KNOW THAT AS SOME INFORMATION HAS NOT BEEN
 SUBMITTED FOR REVIEW YET THERE MAY VERY WELL BE NEW
 COMMENTS ON THE NEXT REVIEW.
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2003 NFPA-33
 2003 NFPA-86
 ** SOME OF THESE CODES MAY BE PRESENT ON PLANS HOWEVER
 PLEASE VERIFY THE CODES AND SEE COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT THIS NOTE.
  
 2) NOTE: PLEASE SEE PLANS ARE MISSING TITLE BLOCKS AS
 REQUIRED PER FAC 61G15-23.002. PLEASE ALSO SEE FS
 471.023 AND INCLUDE INFORMATION WHERE APPLICABLE.
  
 3) NOTE: PLEASE SEE THAT ALL CLEARANCES ARE REQUIRED TO
 BE SHOWN AND LAYOUT OF UNIT AND SURROUNDING CLASS
 LOCATIONS ON PLANS.
 PLEASE SEE NFPA-70 516
  
 4) NOTE: PLEASE SUBMIT A COMPLETE ELECTRICAL RISER
 SHOWING HOW ALL NEW ELECTRICAL IS BEING FED, FROM WHERE
 AND HOW.
 PLEASE INCLUDE COMPLETE LOAD CALCULATIONS FOR NEW LOADS
 ON EXISTING EQUIPMENT ALONG WITH THE LOAD ON THE
 EQUIPMENT SERVICE EQUIPMENT.
 PLEASE SEE THAT NO INFORMATION WAS SUBMITTED EXCEPT FOR
 WHAT THE NEW ELECTRICAL ITEMS WILL BE. PLEASE KNOW THAT
 A REVIEW FOR MANY ITEMS OF CODE COMPLIANCE CAN NOT BE
 DONE AT THIS TIME.
 NEC 220, 215.5, 240.4, 310.16, ETC
 FBC 106.1.2, 106.3.5.1.2
  
 5) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS AS THE
 SCOPE OF CONSTRUCTION/BUILDING WHICH SEEMS TO FALL
 UNDER A GC MAY REQUIRE A GC TO APPLY FOR PERMIT.
 PLEASE SEE THAT THE PERMIT APPLICATION WAS SUBMITTED
 UNDER A MECHANICAL CONTRACTOR'S LICENSE.
 THE STRUCTURAL SCOPE OF WORK AS SHOWN IS NOT INCIDENTAL
 TO THE SCOPE APPLIED.
 PLEASE ALSO SEE BUIDLING REVIEW NOTES AS STATING THE
 EQUIPMENT WILL MEET WIND LOADS IN LIEU OF SHOWING
 SPECIFIC DETAILS IS NOT PERMITTED.
 FS 489, CILB, AND PBCLB.
  
 6) NOTE: PLEASE SUBMIT THE MANUFACTURE'S SPECS/CUT
 SHEETS FOR ANY LISTED EQUIPMENT WHICH IS PART OF THIS
 LISTED ASSEMBLY.
 110.3, 90.7.
 FBC 106.1.2
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-22 20:02:472007-03-22 20:02:47
 NOTES TO FOLLOW ONCE REVIEW IS COMPLETE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-04-17 Cont ID  
Sent By mawillia Date 2007-04-17 Time 16:00 Rev Time 0.00
Received By mawillia Date 2007-04-17 Time 15:04 Sent To  
Notes
2007-04-17 16:00:10*****DENIED*****
  
  
 1.IN ADDITION TO NPPA 101 (2003 EDITION),THE 2003
 EDITION OF NFPA 33 SHALL BE REFERENCED.
  
 2.PROVIDE A SITE PLAN INDICATING THE LOCATION OF THE
 PAINT BOOTH IN RELATION TO OR IN THE BUILDING.
  
 3.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE SUPPRESSION SYSTEM.
  
  
 PLEASE BE ADVISED THAT POSITIVE RESPONSES TO THE OTHER
 PLAN REVIEW COMMENTS WILL PROVIDE THE NECESSARY
 INFORMATION NEEDED TO FURTHER CONDUCT THE FIRE PORTION
 OF THEPLAN REVIEW PROCESS.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-17 Cont ID  
Sent By mawillia Date 2007-04-17 Time 15:05 Rev Time 0.00
Received By mawillia Date 2007-03-13 Time 16:18 Sent To  
Notes
2007-03-13 16:18:24TO "COMM" BD#46

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-14 Cont ID  
Sent By tgordon Date 2007-03-14 Time 16:26 Rev Time 0.30
Received By tgordon Date 2007-03-14 Time 16:26 Sent To  
Notes
2007-03-14 16:36:00*** DENIED ***
 1) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR PAINT
 BOOTH.
  
 2) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR
 HEATER.
  
 3) SHOW ON PLANS SUPPLY AIR AND EXHAUST AIR DUCT
 LAY-OUT.
  
 4) SHOW A ROOF TOP VIEW OF EXHAUST AND SUPPLY DUCT
 TERMINATION.
  
 5) SHOW HEIGHT OF EXHAUST TERMINATION TO ROOF TOP.
  
 6) PROVIDE SITE PLAN SHOWING LOCATION OF EXHAUST
 TERMINATION AND PROPERTY LINE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-04-09 Cont ID  
Sent By jbabcock Date 2007-04-09 Time 13:07 Rev Time 0.00
Received By jbabcock Date 2007-04-09 Time 13:07 Sent To I
Notes
2007-04-09 13:09:01THIS PERMIT CAN NOT BE PASSED BY ZONING UNTIL THE FINAL
 ORDER FOR CASE NO. 3172A IS MADE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved