Plan Review Details - Permit 07030410
Plan Review Stops For Permit 07030410
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-08-30 Cont ID  
Sent By lmartine Date 2007-08-30 Time 09:11 Rev Time 0.00
Received By lmartine Date 2007-08-30 Time 09:11 Sent To  
Notes
2007-08-30 09:12:45REVISION APPROVED

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-05-29 Cont ID  
Sent By lmartine Date 2007-05-29 Time 16:15 Rev Time 0.00
Received By lmartine Date 2007-05-29 Time 16:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-05-07 Cont ID  
Sent By lmartine Date 2007-05-07 Time 11:24 Rev Time 0.00
Received By lmartine Date 2007-05-07 Time 11:24 Sent To  
Notes
2007-05-07 11:25:04PROVIDE SECOND SET OF DRAWINGS.
  
  
  
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-06-05 Cont ID  
Sent By btrobaug Date 2007-06-05 Time 08:04 Rev Time 0.50
Received By btrobaug Date 2007-06-05 Time 07:47 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-05-24 Cont ID  
Sent By btrobaug Date 2007-05-24 Time 09:23 Rev Time 0.50
Received By btrobaug Date 2007-05-24 Time 08:30 Sent To B
Notes
2007-05-24 09:23:18 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 ALL PLANS.
  
 2} CRCUITS 24,26 & 28 ON THE PANEL SCHEDULE HAVE #14
 CONDUCTORS ON 20 AMP BREAKERS, IN VIOLATION OF 310.16.
 PLEASE VERIFY AND CORRECT. NOTE 210.11(C)(3) REGARDING
 20 AMP BATHROOM REQUIREMENTS.
  
 3} A RECEPTACLE IS REQUIRED WITHIN 2' OF THE SINK
 (ABOVE THE DISHWASHER) PER 210.52(C)(1). NEC. ALSO SEE
 210.8 FOR GFCI REQUIREMENTS.
  
 4} A SMOKE ALARM IS REQUIRED OUTSIDE THE "GREAT ROOM"
 AS IT MEETS THE DEFINITION OF BEDROOM IN THE FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-15 Cont ID  
Sent By btrobaug Date 2007-03-15 Time 14:36 Rev Time 0.50
Received By btrobaug Date 2007-03-15 Time 12:52 Sent To B
Notes
2007-03-15 14:36:06 
  
 DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 THE SCOPE OF ELECTRICAL WORK IN THE DESCRIPTION ON THE
 APPLICATION IS NOT CLEAR, NOR DOES THE PLAN INDICATE IF
 THE SERVICE IS NEW OR EXISTING.
  
 1} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS, LOAD CALCULATIONS,
 PANEL SCHEDULES, SERVICE EQUIPMENT AND PANEL LOCATIONS
 PER 106.3.5.4 FBC. THE NOTE ON THE RISER INDICAES #2
 AWG CONDUCTORS, TOO SMALL FOR 200 AMPS PER
 310.15(B)(6), THE GROUNDING ELECTRODE DOES NOT INDICATE
 THE CONNECTIONS TO COMPLETE THE SYSTEM PER 250.50, THE
 CONDUTORS IN THE RISER CONDUIT ARE NOT SIZED.
  
 2} GIVE PANEL SPECIFICATIONS, NUMBER OF SPACES, VOLTAGE
 AND AMPERE RATING, MAIN LUG OR MAIN BREAKER. INDICATE
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC
 AS AMENDED.
  
 3} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS."
  
 4} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 5} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW PER 106.1 FBC AS AMENDED.
  
 6} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-28 Cont ID  
Sent By adarroug Date 2007-07-28 Time 11:59 Rev Time 0.00
Received By adarroug Date 2007-07-28 Time 11:59 Sent To B
Notes
2007-07-28 12:00:02TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-01 Cont ID  
Sent By adarroug Date 2007-06-01 Time 10:16 Rev Time 0.00
Received By adarroug Date 2007-06-01 Time 10:16 Sent To B
Notes
2007-06-01 10:16:50TO "LMARTINEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-15 Cont ID  
Sent By adarroug Date 2007-05-15 Time 14:28 Rev Time 0.00
Received By adarroug Date 2007-05-15 Time 14:27 Sent To E
Notes
2007-05-15 14:28:23TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-05-07 Cont ID  
Sent By lmartine Date 2007-05-07 Time 11:25 Rev Time 0.00
Received By lmartine Date 2007-03-12 Time 13:29 Sent To  
Notes
2007-03-12 13:30:05TO "E" BOX