| 2007-03-10 15:54:29 | ** UNSAT ** |
| | |
| | ** PLAN REVIEW ONLY* |
| | COLEMAN PARK PROJECT |
| | PLANS SUBMITTED FOR A NEW MASTER PLAN. |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE KNOW THAT ANY REFERENCES TO THE 2002 NEC |
| | SHOULD BE CHANGED TO THE 2005 NEC. |
| | |
| | 2) NOTE: PLEASE KNOW THAT THE PLANS NEED TO CORRELATE |
| | WITH ALL CIRCUIT DESIGNATIONS ON PLANS FOR ROOMS AND |
| | AREAS. PLEASE SEE TEXT WHICH IS TAKEN FROM COMMENTARY |
| | IN THE CODE WHICH STATES THE USE OF *GEN LT* ETC IS NOT |
| | ACCEPTABLE. (CIRCUITS 1-5) |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.1.2 |
| | |
| | 3) NOTE: PLEASE SEE PLANS AND PANEL SCHEDULES INDICATE |
| | SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS THESE AS |
| | SMOKE DETECTORS ALONG WITH NOTES ON PLANS. |
| | PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN |
| | SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY |
| | INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS |
| | ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN |
| | THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS |
| | OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE |
| | ALARMS. |
| | THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE |
| | OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. |
| | BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| | SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS |
| | SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS |
| | FOR OTHER NEW HOMES. |
| | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| | RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE*. |
| | PLEASE SEE NFPA-72 11.5.1.1, 11.8.3 |
| | |
| | 4) NOTE: PLEASE SEE THE PLANS SHOULD INDICATE THE |
| | DEVICE FOR THE DISHWASHER DISPOSAL. ? SWITCHED ETC? |
| | PLEASE ALSO SEE 210.4B AS A 2-POLE BREAKER IS REQUIRED |
| | IF THESE ARE BEING FED FROM THE SAME DEVICE/YOKE. |
| | PLEASE REVISE PANEL SCHEDULE. |
| | PLEASE ALSO CLARIFY LOCATION OF THE SWITCH FOR THE |
| | DISPOSAL, THIS IS NOT A CODE ISSUE, ONLY SEEMS THE |
| | SWITCH BEING LOCATED ON THE OTHER SIDE OF THE ROOM MAY |
| | BE PLACED CLOSER TO THE SINK/UNIT AREA? |
| | |
| | 5) NOTE: PLEASE CLARIFY THE DINING ROOM/AREA BEING ON |
| | ONE OR MORE OF THE SMALL APPLIANCE CIRCUITS AS REQUIRED |
| | PER 210.52B1, 210.11C1, 220.52. |
| | * PLEASE REVISE PANEL SCHEDULE TO INDICATE. |
| | |
| | 6) NOTE: PLEASE INDICATE THE 3FOR THE 3WAY SWITCHES IN |
| | HALLWAY BY BEDROOM #1. |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 7) NOTE: PLEASE INDICATE HOW CONDUIT FROM METER TO MAIN |
| | BREAKER PANEL IS BEING ROUTED. PLEASE KNOW THAT AS PER |
| | 230.70 NO MORE THAN 8FT OF UNPROTECTED CONDUCTORS IS |
| | PERMITTED INSIDE DWELLING. PLEASE KNOW THIS INCLUDES |
| | ROUTING OVERHEAD, OR IN WALLS. THIS IS BASED ON TOTAL |
| | LENGTH. IS THIS IN THE SLAB OR NOTE/CLARIFY THE 8FT. |
| | |
| | 8) NOTE: PLEASE PLACE TYPE OF RECESSED LIGHTING FIXTURE |
| | ON PLANS/FIXTURE LEGEND AS REQUIRED UNDER FBC CHAPTER |
| | 13, 13-606.1.ABC.1.2.4. |
| | |
| | 9) NOTE: PLEASE SEE BUILDING REVIEW NOTES ALSO, AS EACH |
| | PERMIT WILL REQUIRE ENERGY CALCULATIONS PER 2004 FBC W/ |
| | 2006 REVISIONS AND SHALL BE SIGNED, DATED AND SEALED BY |
| | THE DESIGNER OF RECORD AS REQUIRED IN 13-103.1.1.1 |
| | |
| | 10) NOTE: PLEASE SEE THE WATER HEATER IS BEING SHOWN |
| | WITH A 220V OUTLET. THIS IS REQUIRED TO BE HARDWIRED. |
| | PLEASE SHOW J-BOX IF THE BREAKER IN PANEL WILL BE USED |
| | FOR DISCONNECTING MEANS, OR SHOW DISCONNECT AS REQUIRED |
| | PER 422.30, 422.31. |
| | PLEASE KNOW THIS CAN BE A 2-POLE/240V RATED TOGGLE |
| | SWITCH. |
| | |
| | 11) NOTE: PLEASE INDICATE THE DISCONNECTING MEANS FOR |
| | THE AHU. PLEASE SEE THIS IS ALSO SHOWN AS A 220V OUTLET |
| | WHERE DISCONNECT IS REQUIRED. 440.11 |
| | PLEASE KNOW THIS MUST ALSO BE HARDWIRED. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |