Plan Review Details - Permit 07030368
Plan Review Stops For Permit 07030368
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-07-30 Cont ID  
Sent By jwitmer Date 2007-07-30 Time 16:37 Rev Time 1.55
Received By jwitmer Date 2007-07-30 Time 16:37 Sent To PC
Notes
2007-07-30 16:51:22BUILDING PLAN REVIEW
 PERMIT: 07030368
 ADD: 1001 OKEECHOBEE BLVD.
 CONT: SIEMENS BUILDING TECH
 TEL: (954)931-4956
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) SHEETS M4.1 NOTE 5 INDICATE A NEW OPENING, A 92"X52"
 ACCESS ROOF HATCH. THIS WILL REQUIRE A PRODUCT TESTING
 REPORT THAT COMPLIES WITH RULE 9B-72.PRODUCT
 APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED
 TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A
 COVER SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE
 APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM
 PER RULE 9B-72. SEE WWW.FLORIDABUILDING.ORG
 CURRENTLY THERE ARE NO ROOF HATCHES THAT MEET
 THE STATE APPROVALS. PLEASE VISIT THE WEBSITE LISTED
 ABOVE TO SEE THE 10 REQUIREMENTS FOR STATE APPROVAL.
 FOR A LOCAL JUPRODUCT APPROVAL THE CITY OF WEST PALM
 BEACH HAS THE SAME 10 REQUIREMENTS. NOTE THE
 REQUIREMENT FOR A THIRD PARTY QUALITY ASSURANCE PROGRAM
 BE IN AFFECT. THIS AGENCY DOES HAVE TO BE LISTED WITH
 THE STATE.
  
 3)) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-07-03 Cont ID  
Sent By dpalmer Date 2007-07-03 Time 19:02 Rev Time 0.00
Received By dpalmer Date 2007-07-03 Time 18:57 Sent To I
Notes
2007-07-03 19:05:432007-07-03 19:05:43
 *** NOTES***
  
  
 1) NOTE: PLANS ONLY SUBMITTED FOR PLAN REVIEW AND HAVE
 NOT BEEN SUBMITTED FOR PERMIT.
 PLEASE SUBMIT ELECTRICAL PLANS FOR SCOPE OF WORK WHICH
 WILL BE AFFECTED.
 FBC 106.3.5.1.2
 NEC 2005
  
 2) NOTE: PLEASE SEE M SHEETS FOR SIGNATURE WHICH IS
 DIFFERENT THAN PREVIOUS PLANS AND SIGNATURE ON FILE.
 PLEASE SEE MECH REVIEW COMMENTS. FS 471.025
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-03 19:02:422007-07-03 19:02:42
 PLANS REMOVED FROM INCOMING FOR REVIEW, TO BE RETURNED
 TO INCOMING WAITING FOR COMM BOARD ONCE ELECTRICAL
 REVIEW IS DONE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-07-26 Cont ID  
Sent By mawillia Date 2007-07-26 Time 19:31 Rev Time 0.00
Received By mawillia Date 2007-07-26 Time 19:15 Sent To  
Notes
2007-07-26 19:28:27*****DENIED*****
  
  
 1.THE ADDRESS LISTED IN THE TITLE BLOCK OF THE
 SUBMITTED MECHANICAL PLAN SHEETS IS INCORRECT.SEE
 STRUCTURAL SHEETS.
  
 2.IF THE REPLACEMENT OF THE EXISTING DUCT SMOKE
 DETECTORS ARE WARRANTED AS INDICATED IN MECHANICAL NOTE
 15 ON SHEET M0.1,IN ADDITION TO SHUTTING DOWN
 EQUIPMENT, DUCT DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM AS PER LOCAL REQUIREMENTS.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-06-22 Cont ID  
Sent By dpalmer Date 2007-07-03 Time 19:06 Rev Time 0.00
Received By adarroug Date 2007-06-22 Time 13:24 Sent To  
Notes
2007-07-09 14:45:13TO "COMM" BD#31
2007-06-22 13:25:08WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-07-19 Cont ID  
Sent By rregueir Date 2007-07-19 Time 10:51 Rev Time 0.00
Received By rregueir Date 2007-07-18 Time 16:58 Sent To  
Notes
2007-07-19 10:51:39----------------DENIED------------------
  
 FBC 2004 CODE FAMILY W/ 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS PLAN REVIEW COMMENTS AND SUBMITTED RESPONSES
 FOR THE SAKE OF CONTINUITY. ADDITIONAL INFORMATION OR
 CONDITIONS MAY FOLLOW.
  
 1. OK
  
 2. OK EXCEPT, NOTE 8 ON PG M4.1 STATES THAT NEW DUCT
 SMOKE DETECTORS SHALL BE POVIDED. PLEASE COORDINATE
 NOTES.
  
 3. REGARDING LETTER FROM TRANE; THIS LETTER IS
 ACCEPTABLE. HOWEVER, PRIOR TO PERMIT ISSUANCE, TWO
 COPIES OF THIS LETTER WITH ORIGINAL SIGNATURE AND SEAL
 OF THE TRANE ENGINEER IS REQUIRED. ALSO, APPROVAL OF
 THE CLEARANCES WILL BE CONDITIONAL PENDING SATISFACTORY
 DEMONSTRATION TO THE FIELD INSPECTOR THAT THE COILS ARE
 IN FACT ABLE TO BE REPLACED AND THE EQUIPMENT IS IN
 FACT ABLE TO BE FULLY SERVICED UNDER ACTUAL FIELD
 CONDITIONS. THIS WILL BE A PROVISO IF AND WHEN PERMIT
 IS APPLIED FOR AND ISSUED.
  
 4. THIS IS ACCEPTABLE. HOWEVER, PLEASE CHECK WITH
 BUILDING PLAN REVIEW FOR STRUCTURAL, WIND LOAD AND/OR
 PRODUCT APPROVAL REQUIREMENTS RELATED TO THE PROPOSED
 ACCESS HATCH.
  
 5. SEE COMMENT #3 ABOVE.
  
 6. OK
  
 7. PER THE DISCUSSION IN THE FIELD WITH KAMM, SIEMENS
 AMD HAROLD MOSER, PLEASE ADD NOTE TO FIRE DAMPER DETAIL
 STATING THAT WALLS PENETRATED BY FIRE DAMPERS ARE TO BE
 REPAIRED OR REPLACED TO THEIR PREVIOUS FIRE RESISTANCE
 RATING IN CONJUNCTION WITH THE REPLACEMENT OF THE
 EQUIPMENT AND DUCTWORK. THIS WORK SHOULD BE DONE UNDER
 THE SCOPE OF A BUILDING PERMIT.
  
 8. OK PENDING BUILDING PLAN REVIEW.
  
 9. OK PENDING GAS REVIEW.
  
 10. OK
  
 NEW: PLEASE SEE ELCTRICAL PLAN REVIEW NOTES REGARDING
 THE ENGINEER'S ORIGINAL SIGNATURE ON PLANS. PLEASE
 CORRECT THIS ISSUE PRIOR TO RESUBMITTAL FOR PERMIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date 2007-03-24 Cont ID  
Sent By rregueir Date 2007-03-24 Time 16:56 Rev Time 0.00
Received By rregueir Date 2007-03-24 Time 13:29 Sent To  
Notes
2007-03-24 15:37:23------------------------DENIED-------------------------
 --
  
 FBC 2004 W/ 2006 REVISIONS
 FBC,M 2004 W/ 2006 REVISIONS
 FBC 2004 CHAPTER 1 AS AMENDED BY THE CITY OF WEST PALM
 BEACH
  
 1. M0.1 MECHANICAL NOTES : PLEASE REFERENCE FBC 2004 W/
 2006 REVISIONS. ALSO, PLEASE UPDATE ALL REFERENCED
 STANDARDS TO THOSE LISTED IN FBC 2004.
  
 2. M0.1 MECHANICAL NOTE #5: WHAT IS THE MEANS TO BE
 USED FOR CERTIFICATION OF EXISTING DUCT MOUNTED SMOKE
 DETECTORS?
  
 3. M4.1 PLEASE SEE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR MINIMUM REQUIREMENTS FOR SERVICE
 ACCESS PER FBC.M 304.1,304.2. EXAMPLE: AHU 3, AHU 12
 BOTH REQUIRE MIN. 71" ON COIL CONNECTION SIDE OF UNIT
 AND 24" MIN. ON OPPOSITE SIDE. PLAN SHOWS APPROX. 48"
 ON COIL SIDE AND 12" ON OPPOSITE SIDE FOR AHU 12. THIS
 UNIT, ONCE IN PLACE, WOULD NOT BE SERVICABLE. MINIMUM
 SERVICE CLEARANCE FROM ELEMENTS OF PERMANENT
 CONSTRUCTION, INCLUDING OTHER INSTALLED EQUIPMENT, IS
 REQUIRED PER FBC,M 306.1.
  
 4. M2.2 GENERAL NOTE #5: ELIMINATING THE OPENING USED
 FOR INSTALLATION OF EQUIPMENT WITH ELEMENTS OF
 PERMANENT CONSTRUCTION, IF IT IS THE ONLY MEANS OF
 ACCESS FOR REPLACEMENT, IS NOT PERMITTED PER FBC,M
 306.1.
  
 5. M2.2 AHU 11: CHECK FOR CLEARANCE FOR SERVICE AND
 MAINTENANCE. SEE COMMENT #3.
  
 6. M4.1 VAV 2 DOES NOT APPEAR TO HAVE THE MINIMUM
 REQUIRED CLEARANCE.
  
 7. M6.1 FIRE DAMPER DETAIL: (A) FIRE DAMPERS TO BE
 INSTALLED PER THEIR LISTING AND MANUFACTURER'S
 INSTALLATION INSTRUCTIONS FBC,M 607.2.(B)FIRE DAMPER
 ACTUATING DEVICE OPERATING TEMPERATURE TO BE
 APPROXIMATELY 50 DEG.F ABOVE THE NORMAL TEMPERATURE
 WITHIN THE DUCT SYSTEM, BUT NOT LESS THAN 160 DEG.F PER
 FBC,M 607.3.1.1. WHAT WILL BE THE NORMAL TEMPERATURE BE
 WITHIN THE DUCT SYSTEM?
  
 8. M6.1. PLEASE PROVIDE DETAILED DRAWINGS FROM A
 STRUCTURAL ENGINEER SHOWING WIND LOAD CALCULATIONS,
 VERIFYING EQUIPMENT AND CURB CONNECTIONS TO BE IN
 COMPLIANCE WITH FBC CH 16. ALSO, SHOW STRUCTURAL
 ELEMENTS INVOLVED IN CREATING NEW PENETRATIONS/LOAD
 BEARING FOR NEW EQUIPMENT ON ROOF FOR BUILDING PLAN
 REVIEW.
  
 9. PLEASE PROVIDE MANUFACTURER'S SUBMITTAL DATA FOR
 OARTU-1. A SEPARATE GAS PERMIT WILL BE REQUIRED FOR
 OARTU-1 GAS PIPING.
  
 10. PLEASE SHOW MEANS OF AUXILIARY OR SECONDARY DRAIN
 PROTECTION FOR ALL NEW AHUS AND OARTU-1 PER FBC,M
 307.2.3.
  
 PLEASE CONTACT ME IF YOU HAVE ANY QUESTIONS.
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-07-17 Cont ID  
Sent By kstevens Date 2007-07-17 Time 10:47 Rev Time 0.00
Received By kstevens Date 2007-07-17 Time 10:47 Sent To  
Notes
2007-07-17 10:48:35NO PLUMBING WORK SHOWN ON PLANS--NO PLUMBING
 CONTRACTOR SIGNED ON APPLICATION

Review Stop Z ZONING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By astelly Date 2007-07-24 Time 09:25 Sent To  
Notes
2007-07-24 09:30:40AMY STELLY
 URBAN DESIGN
 822-1440
  
 PLEASE PROVIDE PHOTOS WHICH SHOW ANY EXISTING SCREENING
 OF THE ROOFTOP MECHANICAL EQUIPMENT; OR PROVIDE
 DRAWINGS SHOWING ANY PROPOSED SCREENING.