Plan Review Details - Permit 07030347
Plan Review Stops For Permit 07030347
Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status N Date 2008-06-03 Cont ID  
Sent By mawillia Date 2008-06-03 Time 12:10 Rev Time 0.00
Received By mawillia Date 2008-06-03 Time 10:36 Sent To  
Notes
2008-06-03 12:10:14*****NOT APPLICABLE*****
  
  
 THE AS BUILT FIRE ALARM PLANS FOR THE CARLTON FIELDS
 TENANT BUILD-OUT SHOULD HAVE BEEN SUBMITTED UNDER
 PERMIT NUMBER 07120619 INSTEAD.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722 (OFFICE)
 561-644-7326 (CELLULAR)

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-04-22 Cont ID  
Sent By mwennerg Date 2008-04-22 Time 13:32 Rev Time 0.00
Received By mwennerg Date 2008-04-22 Time 13:32 Sent To  
Notes
2008-04-22 13:33:39FIRE ALARM SHEETS FA-1- FA-23 SUBMITTED FOR REVISION

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-12-18 Cont ID  
Sent By mawillia Date 2007-12-18 Time 13:42 Rev Time 0.00
Received By mawillia Date 2007-12-18 Time 11:41 Sent To  
Notes
2007-12-18 13:42:53****REVISIONS APPROVED*****
  
 REVISED PLAN SHEETS FA-00 THRU FA-23 WERE STAMPED,
 INITIALED, AND DATED;READY FOR PERMIT ISSUANCE.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-07-17 Cont ID  
Sent By mawillia Date 2007-07-17 Time 18:07 Rev Time 0.00
Received By mawillia Date 2007-07-17 Time 17:07 Sent To  
Notes
2007-07-17 17:13:52*****APPROVED*****
  
  
 ALL COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED.PLAN SHEETS FA-01 THRU FA-11 WERE STAMPED,
 INITIALED, AND DATED;READY FOR PERMIT ISSUANCE.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-04-23 Cont ID  
Sent By mawillia Date 2007-04-23 Time 11:29 Rev Time 0.00
Received By mawillia Date 2007-04-23 Time 10:43 Sent To  
Notes
2007-04-23 11:17:18*****DENIED*****
  
  
 1.THE NUMERICAL ADDRESS OF WHERE THE SCOPE OF WORK IS
 CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
  
 2.AS PER WEST PALM BEACH FIRE PREVENTION, DUCT SMOKE
 DETECTORS SHALL INTIATE A GENERAL FIRE ALARM.PLEASE
 SEE SHEET FA-14, FIRE ALARM SYSTEM-SEQUENCE OF
 OPERATION, UNDER DUCT DETECTORS NOTE C3.
  
 3.UL CERTIFICATE FOR CENTRAL STATION SERVICE TO BE AT
 THE FACP AND A COPY SUBMITTED TO WPB FIRE PREVENTION BY
 FINAL FIRE ALARM INSPECTION.
  
 4.WATERFLOW TO ACTIVATE A GENERAL FIRE ALARM WITHIN
 45 TO 60 SECONDS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-05-21 Cont ID  
Sent By adarroug Date 2008-05-21 Time 10:21 Rev Time 0.00
Received By adarroug Date 2008-05-21 Time 10:21 Sent To FIRE
Notes
2008-05-21 10:22:53TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-02 Cont ID  
Sent By adarroug Date 2008-04-02 Time 09:05 Rev Time 0.00
Received By adarroug Date 2008-04-02 Time 09:05 Sent To FIRE
Notes
2008-04-02 09:05:43TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-13 Cont ID  
Sent By adarroug Date 2007-12-13 Time 14:53 Rev Time 0.00
Received By adarroug Date 2007-12-13 Time 14:53 Sent To FIRE
Notes
2007-12-13 14:54:10TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-07-05 Cont ID  
Sent By adarroug Date 2007-07-05 Time 11:03 Rev Time 0.00
Received By adarroug Date 2007-07-05 Time 11:03 Sent To FIRE
Notes
2007-07-05 11:03:17TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-23 Cont ID  
Sent By mawillia Date 2007-04-23 Time 10:43 Rev Time 0.00
Received By mawillia Date 2007-03-12 Time 11:22 Sent To  
Notes
2007-03-12 11:23:14TO "F" BOX