Plan Review Details - Permit 07030341
Plan Review Stops For Permit 07030341
Review Stop G GAS REVIEW
Rev No 5 Status P Date 2007-07-25 Cont ID  
Sent By mperson Date 2007-07-25 Time 08:29 Rev Time 0.45
Received By mperson Date 2007-07-25 Time 08:14 Sent To  
Notes
2007-07-25 08:34:54REVISION: CHANGE TYPE OF WATER HEATER AND LOCATION.
  
 ****************PROVISO****************
 A} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2007-06-28 Cont ID  
Sent By mperson Date 2007-06-28 Time 13:11 Rev Time 0.45
Received By mperson Date 2007-06-28 Time 13:11 Sent To PC
Notes
2007-06-28 13:15:34REVISION: CHANGED LAYOUT
  
 ****************PROVISO****************
 PER FBC-2004 FUEL GAS, SECTION 409.4: A LISTED SHUTOFF
 VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF EACH MP
 REGULATOR.
  
 IF DRYER ROOM IS A CONFINED SPACE, OPENINGSREQUIRED
 PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 5,000 CUBIC FEET REQUIRED.

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-06-04 Cont ID  
Sent By mperson Date 2007-06-04 Time 10:35 Rev Time 0.45
Received By mperson Date 2007-06-04 Time 10:35 Sent To PC
Notes
2007-06-04 11:00:12DENIED REVISION
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW ON THE REVISION TO MEET CODE
 COMPLIANCE:
 NOTE: THE PLAN REVISION FORM ADDRESS OF JOB WAS
 INCORRECTLY INDICATED AS THE ADDRESS OF CONTRACTOR,
 PLEASE SEE RED LINE CORRECTIONS OF THIS AND PLEASE
 SUBMIT THE CORRECT ADDRESS OF JOB ON FUTURE REVISIONS.
 ALSO NOTE THAT REVISION FEES ARE OWED FOR THIS REVISION
 OF $60.00 AND REVISION FEES WILL BE REQUIRED FOR THE
 CORRECTED REVISION SUBMITTAL.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE SUBMITTED REVISION IS NOT INDICATING ALL
 CORRESPONING LENGTHS ON ALL CUT SECTIONS OF PIPE TO
 VERIFY THE NEW INDICATED LONGEST RUN OF 75'. PLEASE
 CLEARLY INDICATE THE GAS METER ON THE NEXT RESUBMITTED
 REVISION. PLEASE CORRECT.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: THE SUBMITTED REVISION IS NOT INDICATING ALL
 PIPING MATERIALS BEING USED ON ALL CUT SECTIONS.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THIS GOES ALONG WITH COMMENT NUMBER ONE.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS REVIEWER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-04-17 Cont ID  
Sent By mperson Date 2007-04-17 Time 13:50 Rev Time 0.45
Received By mperson Date 2007-04-17 Time 13:50 Sent To PC
Notes
2007-04-17 13:57:07****************PROVISO****************
 PER FBC-2004 FUEL GAS, SECTION 409.4: A LISTED SHUTOFF
 VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF EACH MP
 REGULATOR.
  
 IF DRYER ROOM IS A CONFINED SPACE, OPENINGSREQUIRED
 PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 5,000 CUBIC FEET REQUIRED.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-03-22 Cont ID  
Sent By mperson Date 2007-03-22 Time 16:29 Rev Time 0.55
Received By mperson Date 2007-03-22 Time 16:29 Sent To PC
Notes
2007-03-22 16:38:02DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
  
 THE FOLLOWING CORRECTIONS/INFORMATION IS REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004, CHAPTER 1, SECTION
 108.3, BUILDING PERMIT VALUATION: IF IN
 THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF THE BUILDING,
 ALTERATION, STRUCTURE, ELECTRICAL, GAS
 MECHANICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION,
 THE PERMIT SHALL BE DENIED. FOR
 PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, NORMAL SITE WORK (EXCAVATION AND
 BACKFILL FOR BUILDINGS), ARCHITECTURAL
 AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND
 VALUE. VALUATION REFERENCES MAY INCLUDE
 THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS ECT.) WITH
 REGIONAL ADJUSTMENTS FOR LOCATION AS
 PUBLISHED BY INTERNATIONAL CODE
 CONGRESS.
 NOTE: THERE IS NOT AN APPROVED POOL HEATER ON THE POOL
 PERMIT # 07010034. EITHER THE GAS PERMIT OR THE POOL
 PERMIT WITH A REVISION MUST REFLECT THE COST AND
 INSTALLATION OF THE POOL HEATER. REFERENCE THE PERMIT
 PLAN REVIEW COMMENTS ATTACHED TO THE GAS COMMENTS
 REFLECTING THIS.
  
 2. FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
  
 3. FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-16 Cont ID  
Sent By adarroug Date 2007-07-16 Time 08:18 Rev Time 0.00
Received By adarroug Date 2007-07-16 Time 08:18 Sent To G
Notes
2007-07-16 08:18:52TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-06-25 Cont ID  
Sent By adarroug Date 2007-06-25 Time 16:40 Rev Time 0.00
Received By adarroug Date 2007-06-25 Time 16:39 Sent To G
Notes
2007-06-25 16:40:19TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-03 Cont ID  
Sent By spalmer Date 2007-04-03 Time 17:07 Rev Time 0.00
Received By spalmer Date 2007-04-03 Time 17:07 Sent To G
Notes
2007-04-03 17:08:09TO MIKE PERSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-22 Cont ID  
Sent By mperson Date 2007-03-22 Time 16:38 Rev Time 0.00
Received By mperson Date 2007-03-12 Time 10:55 Sent To  
Notes
2007-03-12 10:55:24TO "G" BOX