Plan Review Details - Permit 07030303
Plan Review Stops For Permit 07030303
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-03-23 Cont ID  
Sent By mwennerg Date 2007-03-23 Time 12:51 Rev Time 0.00
Received By mwennerg Date 2007-03-23 Time 12:51 Sent To  
Notes
2007-03-23 13:00:18***APPROVED***
  
 1) PULL STATIONS SHALL BE LOCATED AT EXIT DOORS NOT TO
 EXCEED 200'. IT WOULD APPEAR THAT EXTRA PULL STATIONS
 HAVE BEEN PROVIDED.
  
 2) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS IF
 COMPATIBLE WITH EXISTING FIRE ALARM SYSTEM.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION(561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-23 Cont ID  
Sent By mwennerg Date 2007-03-23 Time 13:02 Rev Time 0.00
Received By mwennerg Date 2007-03-10 Time 11:57 Sent To  
Notes
2007-03-10 11:57:31TO "F" BOX