| 2007-03-23 13:00:18 | ***APPROVED*** | | | | | | 1) PULL STATIONS SHALL BE LOCATED AT EXIT DOORS NOT TO | | | EXCEED 200'. IT WOULD APPEAR THAT EXTRA PULL STATIONS | | | HAVE BEEN PROVIDED. | | | | | | 2) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE | | | ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS IF | | | COMPATIBLE WITH EXISTING FIRE ALARM SYSTEM. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION(561) 804-4756 |
|
|