Plan Review Details - Permit 07030297
Plan Review Stops For Permit 07030297
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-06-07 Cont ID  
Sent By mperson Date 2007-06-07 Time 11:42 Rev Time 0.33
Received By mperson Date 2007-06-07 Time 11:42 Sent To PC
Notes
2007-06-07 11:44:37REVISION: LONGEST LENGTH AND PIPE SIZING CHANGED.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2007-05-08 Cont ID  
Sent By mperson Date 2007-05-08 Time 11:20 Rev Time 0.33
Received By mperson Date 2007-05-08 Time 11:20 Sent To PC
Notes
2007-05-08 11:52:28****************PROVISO****************
 A} PER FBC-2004 FUEL GAS SECTION 408.4 A SEDIMENT
 TRAP SHALL BE INSTALLED DOWNSTREAM OF THE EQUIPMENT
 SHUTOFF VALVE AS CLOSE TO THE INLET OF THE EQUIPMENT AS
 PRACTICAL.
  
 B} PER FBC-2004 FUEL GAS, SECTION 404.13.3AN
 INSULATED COPPER TRACER WIRE SHALL BE INSTALLED
 ADJACENT TO UNDERGROUND NONMETALLIC GAS PIPING. THE
 TRACER WIRE SIZE SHALL NOT BE LESS THAN 18 AWG AND THE
 INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL.
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-03-22 Cont ID  
Sent By mperson Date 2007-03-22 Time 08:05 Rev Time 0.45
Received By mperson Date 2007-03-22 Time 08:05 Sent To PC
Notes
2007-03-22 08:23:14DENIED
 REFERENCE: FBC-2004 FUEL GAS; FBC-2004 CHAPTER 1, THE
 CITY OF WEST PALM BEACH AMENDMENTS; THE CITH OF WET
 PALM BEACH GAS PERMIT APPLICATION REQUIREMENTS;
  
 THE FOLLOWING CORRECTION/INFORMATION ARE REQUIRED ON AN
 ISOMETRIC GAS RISER DIAGRAM FOR GAS PLAN REVIEW TO MEET
 CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC AND
 DOES NOT CLEARLY SHOW ALL CUT SECTIONS AND
 CORRESPONDING LENGTHS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: THE SUBMITTED DRAWING IS INDICATING 1" GALVANIZED
 PIPE FROM METER TO WATER HEATER BUT DOES NOT CLEARLY
 INDICATE IF PIPING IS ABOVE OR BELOW GROUND. IF
 GALVANIZED PIPING IS BELOW GROUND IT IS UNACCEPTABLE
 PER FBC-2004 FUEL GAS SECTION 404.8. PLEASE CLEARIFY ON
 THE RESUBMITTED ISOMETRIC.
  
 3. TYPE OF GAS, (LP OR NATURAL)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-22 Cont ID  
Sent By adarroug Date 2007-05-22 Time 10:00 Rev Time 0.00
Received By adarroug Date 2007-05-22 Time 10:00 Sent To G
Notes
2007-05-22 10:01:04TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-03 Cont ID  
Sent By adarroug Date 2007-05-03 Time 16:13 Rev Time 0.00
Received By adarroug Date 2007-05-03 Time 16:13 Sent To G
Notes
2007-05-03 16:13:31TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-22 Cont ID  
Sent By mperson Date 2007-03-22 Time 08:23 Rev Time 0.00
Received By mperson Date 2007-03-09 Time 16:21 Sent To  
Notes
2007-03-09 16:21:38TO "G" BOX