| 2007-03-12 11:08:27 | |
| | |
| | DENIED/INCOMPLETE INFORMATION |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} INDICATE THE CONDUCTOR AND CONDUIT SIZE AND TYPE |
| | FEEDING THE "NEW METER & SWITCH", SO IT CAN BE |
| | DETERMINED IF COMPLIANCE WITH 310.16 AND 250.122 ARE |
| | MET. |
| | |
| | 2} INDICATE THE CONDUIT TYPE FROM THE DISCONNECT AT THE |
| | METER TO THE NEW GUTTER. 106.3.5.1.2 FBC. FROM THE |
| | GUTTER TO THE DISCONNECTS, SEE 430.28, 2005 NEC. |
| | |
| | 3} INDICATE THE CONDUIT AND CONDUCTOR SIZES TOALL |
| | EQUIPMENT, ON THE RISER AND THE PLAN. INSTALL AN |
| | EQUIPMENT GROUND IF REQUIRED. |
| | |
| | 4} VERIFY THE PANEL DESIGNATION ( HP1) FOR THE ROOF |
| | RECEPTACLEREQUIRED BY 210.63,THE NUMBER OF |
| | CONDUCTORS AND CONDUIT SIZE AND TYPE. |
| | |
| | 5} PROVIDE A LEGEND FORTHE DESIGNATIONS USED FOR THE |
| | DISCONNECTS ON THE PLAN. IG: IT APPEARS THE DISCONNECT |
| | FOR THE 15 HP PUMPS IS A 60 AMP, FUSED AT 40 WP?AND THE |
| | RATED AMPERAGE IS 48.3. THE 7.5 HP. FAN AT 75 W. THE |
| | PLAN BELOW THE RISER HAS THAT SAME FAN ON A 40 AMP FUSE |
| | OR BREAKER. PLEASE CORRELATE. |
| | |
| | 6}INDICATE WHETHER THIS IS NEW OR REPLACEMENT |
| | EQUIPMENT. IF IT IS NEW OR LARGER REPLACEMENT |
| | EQUIPMENT, WATTAGE WISE, A LOAD CALCULATION FOR THE |
| | SERVICE MUST BE SUBMITTED. |
| | |
| | 7} THE ENGINEER OF RECORD SHALL INDICATE THE |
| | CERTIFICATE OF AUTHORIZATIONNUMBER ALONG WITH OTHER |
| | INFORMATION REQUIRED BY 61G15-23.002FLORIDA |
| | ADMINISTRATIVE CODE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |