Plan Review Details - Permit 07030281
Plan Review Stops For Permit 07030281
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2008-02-26 Cont ID  
Sent By lursu Date 2008-02-26 Time 08:19 Rev Time 0.00
Received By lursu Date 2008-02-26 Time 08:19 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 2 Status P Date 2007-11-06 Cont ID  
Sent By jwitmer Date 2007-11-06 Time 07:19 Rev Time 1.33
Received By jwitmer Date 2007-11-06 Time 07:19 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2007-03-19 Cont ID  
Sent By lursu Date 2007-03-19 Time 13:01 Rev Time 0.00
Received By lursu Date 2007-03-19 Time 13:00 Sent To  
Notes
2007-03-19 13:02:10PERMIT ASSIGNEDTO THE UNIT 1200 AS SPECIFIED ON THE
 SITE PLANS AND APPLICATION.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-06-03 Cont ID  
Sent By jwitmer Date 2008-06-03 Time 13:35 Rev Time 0.77
Received By jwitmer Date 2008-06-03 Time 13:35 Sent To B
Notes
2008-06-03 13:40:20REV ADDITION OF W21X14 BEAM

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-05-23 Cont ID  
Sent By hpiskura Date 2008-05-23 Time 10:03 Rev Time 0.00
Received By hpiskura Date 2008-05-23 Time 10:03 Sent To  
Notes
2008-05-23 10:04:41ONM&J LETTERS DATED 5/21/08 CERTIFYING INSPECTION OF
 XFRMR REINFORCING STEEL ,RETURNED TWO COPIES TO
 CONTRACTOR WITH TCO CERTIFICATE.HHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2008-05-20 Cont ID  
Sent By lmartine Date 2008-05-20 Time 14:27 Rev Time 0.00
Received By lmartine Date 2008-05-20 Time 14:27 Sent To  
Notes
2008-05-20 15:34:23REVISION COMMENTS FOR THE TRANSFORMER CHANGE OF
 LOCATION.
  
  
 ENGINEER OF RECORD FOR THE BASE BUILDING SHALL SUBMIT
 STRUCTURAL CALCULATIONS FOR REVIEW.
 PROVIDE COMPLETE INSTALLATION DETAIL INCLUDING ALL
 MATERIALS AND HARDWARE.
 EXPLAIN REFERENCE TO W21, THE 12TH FLOOR FRAMING PLAN
 CALLS FOR W24, 30, AND 36.
 ALL SUBMITTALS SHALL BE SIGNED AND SEALED.
  
  
  
  
  
 LUIS MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-11-06 Cont ID  
Sent By jwitmer Date 2007-11-06 Time 11:59 Rev Time 1.11
Received By jwitmer Date 2007-11-06 Time 11:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-09-18 Cont ID  
Sent By jwitmer Date 2007-09-18 Time 19:06 Rev Time 0.77
Received By jwitmer Date 2007-09-18 Time 19:06 Sent To  
Notes
2007-09-18 19:40:57CARLTON FIELDS
 CITY PLACE OFFICE TOWER
 SEPT 18, 2007
  
  
 BUILDING PLAN REVIEW
 PERMIT: 07030281
 ADD: 525 OKEECHOBEE BLVD/SUITE 1200
 CONT: CENTEX CONSTRUCTION
 TEL: (954)214-9415
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)IT APPEARS THE ARCHITECTURAL SHEETS ARE CODE
 COMPLIANT, THE STRUCTURAL SHEET S00-01 INDICATES
 TESTING AND INSPECTIONS ARE TO BE MADE BY AN APPROVED
 TESTING LABORATORY SELECTED BY AND PAID BY THE OWNER.
 THIS IS WHERE DOCUMENTS FOR A THRESHOLD INSPECTOR ARE
 TO SIGNED AND SUBMITTED TO HAROLD PISKURA BEFORE A
 PERMIT WILL BE ISSUED. WPB AMENDMENT 105.13.6.
 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561) 805-6711 FOR FURTHER INFORMATION AND
 APPOINTMENT BEFORE THE PERMIT MAY BE ISSUED.
  
 3A)105.13.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A "STRUCTURAL
 INSPECTION PLAN"
 PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 3B) THE SHELL BUILDING HAS NOT ACHIEVED A CERTIFICATE
 OF COMPLETION, THE STRUCTURAL PLANS FOR THIS TENANT
 SPACE SHALL BE REVIEWED BY THE ENGINEER OF RECORD FOR
 THE " BASE BUILDING"
 AND BE STAMPED WITH THEIR SHOP DRAWING STAMP THEY ARE
 APPROVING THE PLANS AND WORK TO BE COMPLETED UNDER THIS
 PERMIT BEFORE THEIR CERTIFICATE OF COMPLETION HAS BEEN
 ISSUED.
  
 3C) THE SAME HOLDS TRUE FOR THE ARCHITECTURAL SHEETS,
 THE DESIGNER OF RECORD FOR THE BUILDING SHALL REVIEW
 AND AFFIX THEIR SHOP DRAWING STAMP TO THESE PLANS WITH
 THEIR APPROVAL.
  
 3D) SINCE THERE WILL NEED TO BE A THRESHOLD INSPECTOR
 ON SITE, A THIRD SET OF PLANS, SUBMITTALS AND OR OTHER
 DOCUMENTS WILL NEED TO BE SUBMITTED BEFORE ISSUANCE OF
 THIS PERMIT.
  
 3E) SINCE THE STEEL BEAMS ARE NEW ELEMENTS AND NEED TO
 INDICATE FIRE PROOFING AS TO TABLE 601 FLOOR AND BEAM 3
 HR RATING SEE FOOTNOTE "G" 1 HR REDUCTION FOR FIRE
 SPRINKLED BUILDINGS.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-07-30 Cont ID  
Sent By jwitmer Date 2007-07-30 Time 14:45 Rev Time 2.22
Received By jwitmer Date 2007-07-30 Time 14:45 Sent To  
Notes
2007-07-30 15:47:20BUILDING PLAN REVIEW
 PERMIT: 07030281
 ADD: 525 OKEECHOBEE BLVD/SUITE 1200
 CONT: CENTEX CONSTRUCTION
 TEL: (954)214-9415
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3-4) COMPLIED.
  
 5) PARTIALLY COMPLIED. SHEET A14.01 DETAILS 10 & 11 NOW
 SHOW SOLID BACKING BUT THE PLAN DOES NOT INDICATE THAT
 THE PLYWOOD WILL BE FIRE RETARDANT TREATED PLYWOOD,
 ONLY THE RESPONSE.
  
 6) COMPLIED.
  
 7) 2ND REQUEST, DEALS WITH THE NEW FLOOR FRAMING, THAT
 WILLREQUIRE A THRESHOLD
 INSPECTOR FOR THE FLOOR FRAMING.WPB AMENDMENT
 105.13.6. W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY S. 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT
 HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)805-6711 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 8-10) COMPLIED.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-04 Cont ID  
Sent By jwitmer Date 2007-04-04 Time 14:11 Rev Time 4.44
Received By jwitmer Date 2007-04-04 Time 11:34 Sent To  
Notes
2007-04-04 16:54:42BUILDING PLAN REVIEW
 PERMIT: 07030281
 ADD: 525 OKEECHOBEE BLVD/SUITE 1200
 CONT: CENTEX CONSTRUCTION
 TEL: (954)214-9415
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET A00-00
 3A)ARCHITECTS JOVA/ DANIELS/ BUSBY ARCHITECTURAL FIRM
 IS MISSING THEIR CERTIFICATE OF AUTHORIZATION: 481.219
 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE BLOCK
 FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT PRACTICING UNDER
 A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION NUMBER.ADD THE
 NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 3B)ARCHITECTS SEAL IS A RUBBER SEAL NOT A EMBOSSED
 RAISED SEAL.FL S S 481.221
  
 3C) PROJECT INFORMATION INDICATES THIS TO BE A 20 STORY
 BUILDING PLEASE CORRECT.
  
 3D) PLANS SUBMITTED AFTER DEC.8 2006 WILL BE REVIEWED
 UNDER THE 2004 FBC BUILDING WITH THE 2006 AMENDMENTS
 (REVISIONS).
  
 3E) TITLE BLOCK:MISSING THE LOCATION OF THE
 PROJECT.
 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
 SPECIFIC AUTHORITY 481.2055 FS. LAW IMPLEMENTED
 481.203(6), 481.203(8), 481.2131(1),
 481.219(3),(4),(5), 481.221, 481.225(1)(E),(G),
 481.2251(1)(H) FS. HISTORY?NEW 9-7-00.
  
 4) SHEET A03.12 THIS SHEET INDICATES VARIOUS BREAKROOMS
 WITH SINKS, SEE CABINET ELEVATION SHEET A13.01: SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL
 BE MOUNTED WITH THE COUNTER NO HIGHER
 THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH
 SECTION 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK
 TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES
 (485 MM) UNDERNEATH THE SINK.
  
 5)SHEET A14.01DETAILS 10& 11 BOTH INDICATE A WOOD
 FINISH ON WALLS, UNDETERMINED WHAT IF THERE IS A BACKER
 BOARD?
 803.4.2 SET-OUT CONSTRUCTION.
 WHERE WALLS AND CEILINGS ARE REQUIRED TO BE OF
 FIRE-RESISTANCE-RATED OR NONCOMBUSTIBLE CONSTRUCTION
 AND WALLS ARE SET OUT OR CEILINGS ARE DROPPED DISTANCES
 GREATER THAN SPECIFIED IN SECTION 803.4.1 , CLASS A
 FINISH MATERIALS SHALL BE USED EXCEPT WHERE INTERIOR
 FINISH MATERIALS ARE PROTECTED ON BOTH SIDES BY AN
 AUTOMATIC SPRINKLER SYSTEM OR ATTACHED TO
 NONCOMBUSTIBLE BACKING OR FURRING STRIPS INSTALLED AS
 SPECIFIED IN SECTION 803.4.1 . THE HANGERS AND ASSEMBLY
 MEMBERS OF SUCH DROPPED CEILINGS THAT ARE BELOW THE
 MAIN CEILING LINE SHALL BE OF NONCOMBUSTIBLE MATERIALS,
 EXCEPT THAT IN TYPE III AND V CONSTRUCTION,
 FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED. THE
 CONSTRUCTION OF EACH SET-OUT WALL SHALL BE OF
 FIRE-RESISTANCE-RATED CONSTRUCTION AS REQUIRED
 ELSEWHERE IN THIS CODE.
  
 6)SHEET A0.12 & S00-01 BOTH INDICATE HEAVY LOADS
 (DENSE FILING) IN THE TWO FILE ROOMS. NEITHER SHEET
 INDICATES WHAT LIVE LOADS SEE TABLE 1607.1 PROVIDE
 MINIMUM CONCENTRATED LIVE LOADS.
  
 7) NOTE; COMMENT# 6 REQUIRES A THRESHOLD INSPECTOR ON
 SITE SINCE THIS IS A THRESHOLD BUILDING.
 WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 8) FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE
 CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURL INSPECTION
 PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE
 BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 9)W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 10) SINCE WORK ON THE STRUCTURAL FRAME (FLOOR FRAMING)
 MAKES THIS BUILDING A
 THRESHOLD BUILDING, (3) SETS OF ALL DOCUMENTS, PLANS
 SUBMITTALS AND OR REPORTS WILL BE REQUIRED.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 11 Status F Date 2008-07-15 Cont ID  
Sent By dpalmer Date 2008-07-15 Time 15:46 Rev Time 0.00
Received By dpalmer Date 2008-07-15 Time 15:46 Sent To PC
Notes
2008-07-15 15:49:54** DENIEDREVISIONS **
  
  
 1) NOTE:PLEASE SEE REVISION LABELED 7, 8 AND 9 ON
 DP11 LOAD SUMMARY DO NOT ACTUALLY REVISE THE LOADS.
 THESE ARE THE SAME AS SUBMITTED ON REVISIONS DATED
 3/27/08. THE LOADS HAVE NOT CHANGED.
 PLEASE BE SURE THE DP11 SCHEDULE REFLECT M411 NOT M412.
 THIS WAS CORRECTED ON THE RISER SEVERAL REVISIONS AGO
 HOWEVER NOT REVISED ON SCHEDULE.
 PLEASE EXPLAIN WHY THE LOAD ON M411 HAS NOW INCREASED
 BUT THE LOADS SHOWN ON DP11 ARE THE SAME AS PREVIOUS
 REVISIONS IN WHICH LOAD ON M411 WERE LOWER.
 NEC 220.
  
 FBC 106.1.1, 106.1.2, 106.5 FOR CLARITY, ADDITIONAL
 INFORMATION AND RECORD COORDINATION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2008-06-16 Cont ID  
Sent By dpalmer Date 2008-06-16 Time 13:27 Rev Time 0.00
Received By dpalmer Date 2008-06-16 Time 13:27 Sent To PC
Notes
2008-06-16 13:27:26REV E2.1

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2008-06-13 Cont ID  
Sent By dpalmer Date 2008-06-13 Time 16:53 Rev Time 0.00
Received By dpalmer Date 2008-06-13 Time 16:53 Sent To PC
Notes
2008-06-13 16:53:17** DENIEDREVISION**
  
 1) NOTE: ALL PLANS ARE REQUIRED TO CONTAIN STAMP AND
 SIGNATURE BY THE BASE BUILDING ELECTRICAL ENGINEER OF
 RECORD.
 PLEASE OBTAIN SHEETS.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2008-05-19 Cont ID  
Sent By dpalmer Date 2008-05-19 Time 13:21 Rev Time 0.00
Received By dpalmer Date 2008-05-19 Time 13:21 Sent To B
Notes
2008-05-19 13:23:39STRUCTURAL DETAIL REVISION/SUBMITTAL FOR TRANSFORMER
 SENT TO BUILDIGN FOR REVIEW. CLEARANCES SHALL MEET
 110.26 AND OTHER APPLICABLES SECTIONS UNDER CLEARANCES
 FOR TRANSFORMERS IN ARTICAL 450 OF THE NEC.
 PROVIDE A LAYOUT OF ROOM/AREA IN WHICH PROPOSED UNIT
 WILL BE LOCATED. PLEASE BE SURE TO SEE ANY
 MANUFACTURE'S SPECIFICATIONS FOR INSTALLATION.

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-04-09 Cont ID  
Sent By dpalmer Date 2008-04-09 Time 11:53 Rev Time 0.00
Received By dpalmer Date 2008-04-09 Time 11:53 Sent To  
Notes
2008-04-09 12:22:21REV # 5 SHEETS E-0.4 AND E-2.1

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-12-03 Cont ID  
Sent By dpalmer Date 2007-12-03 Time 10:29 Rev Time 0.00
Received By dpalmer Date 2007-12-03 Time 10:29 Sent To PC
Notes
2007-12-03 10:29:56REV # 5

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-11-21 Cont ID  
Sent By dpalmer Date 2007-11-21 Time 09:17 Rev Time 0.00
Received By dpalmer Date 2007-11-20 Time 15:51 Sent To PC
Notes
2007-11-21 09:18:1111/21 PERMIT APPLICATION AND SUPPORTING DOCUMENTS
 SUBMITTED
2007-11-20 17:13:29*** ELECTRICAL IS OK.
  
 PROCESSING OF PLANS AND DOCUMENTS ARE PENDING PERMIT
 APPLICATION AND ALL SUPPORTING DOCUMENTS TO BE BROUGHT
 BACK IN. THESE WERE NOT RESUBMITTED IN PACKAGE WITH
 PLANS.
 SPOKE TO DAN FROM RELATED.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-11-03 Cont ID  
Sent By dpalmer Date 2007-11-03 Time 14:54 Rev Time 0.00
Received By dpalmer Date 2007-11-03 Time 12:02 Sent To  
Notes
2007-11-03 14:54:142007-11-03 14:54:14
  
 ** DENIED 4TH REVIEW **
  
 1) NOTE: PLEASE SEE FAC 61G15-23.002 AS GIVEN ON
 PREVIOUS REVIEWS. PLEASE SEE THE TITLE BLOCKS ARE STILL
 MISSING THE PRINTED NAME OF THE ENGINEER.
 IF THIS WERE THE ONLY COMMENT, THE OWNER REPRESENTATIVE
 COULD PRINT ON ALLS SHEETS.
  
 2) NOTE: NEED TO VERIFY ON LIGHTING CALCULATIONS SHEET
 THE ADDITIONAL WATTAGE BEING SHOWN WHICH EXCEEDS THE
 TABLE ALLOWANCES. IF THERE IS ADDITIONAL WATTAGE IS
 BEING FIGURED FROM THE CODE PLEASE EXPLAIN AND INDICATE
 ON TABLE WHICH LOCATIONS/ROOMS ARE USING THE ADDITIONAL
 WATTAGE WHICH MAY BE PERMITTED UNDER 13-415.2.B.2. ONLY
 ROOMS WHICH CONTAIN THE LIGHTING FOR DECORATIVE
 PURPOSES ARE PERMITTED TO USE THE ADDITIONAL WATTAGE OF
 1.0 PER SQ FT. IF ROOM ONLY CONTAINS GENERAL LIGHTING,
 THEN THE TABLE AS SPECIFIED IN 13-415.2.B MAY ONLY BE
 USED.
 PLEASE EXPLAIN HOW OFFICE/CONFERENCE ROOM HAS LPD AT
 2.4?
 THIS CAN BE DONE WITH A ** NEXT TO THE ROOM DESIGNATION
 ON LIGHTING TABLES.
  
 3) NOTE: PLEASE SEE THE ACCENT/TASK LIGHTING REQUIRES
 ADDITIONAL CONTROLS PER 13-415.1.ABC.1.3. THE RESPONSE
 MENTIONS THESE WILL BE DONE BY A MANUAL ON/OFF SWITCH.
 THESE LIGHTING FIXTURES ARE REQUIRED TO CONTAIN SOME
 SORT OF AUTOMATED CONTROL SO THAT THESE FIXTURES ARE
 NOT INADVERTENTLY LEFT ON. THE INTENT OF CHAPTER
 13-415.41 IS TO AUTOMATICALLY TURN OFF AS MANY LIGHTS A
 POSSIBLE.
 PLEASE SEE ONE AREA IN QUESTION WHERE THE OCCUPANT IS
 REQUIRED TO SEE THE LIGHTING WHICH IS BEING OVER
 RIDDEN. PLEASE SEE ZONE 10 FOR EXAMPLE WHICH IS BEING
 CONTROLLED FROM BOTH THE SOUTH AND NORTH SIDE OF THE
 FLOOR. THIS IS OK, HOWEVER A PILOT/INDICATOR LIGHT OF
 SOME TYPE WILL BE REQUIRED SO THE OCCUPANT CAN TELL
 WHICH SPECIFIC LIGHTS ARE BEING
 CONTROLLED.13-415.1.ABC.1.2 **EXCEPTION?*
 PLEASE SEE WHAT APPEARS TO BE A ROOM DIRECTLY ACROSS
 FROM ELECTRICAL ROOM 1296. DOES THIS AREA CONTAIN FLOOR
 TO CEILING HEIGHT PARTITIONS? THIS AREA DOES SHOW A
 DOOR.
 PLEASE SEE NOTE BELOW WITH MISSING FIXTURE *K* FROM
 AREA 1256 AND CONTROL?
  
 4) NOTE: PLEASE SEE FBC 13-415.2 AS LIGHTING
 PERFORMANCE CALCULATIONS NEED TO BE ADDRESSED. THE
 FOLLOWING ARE SOME EXAMPLES OF REMAINING OUTSTANDING
 ISSUES. THESE ARE IN NO PART ALL POSSIBLE SCENARIOS.
  
 PLEASE CLARIFY WHY SOME ROOMS WHICH ARE SHOWN ON PLANS
 IN WHAT WOULD BE THE SOUTHEAST PORTION OF THE BUILDING
 WHEN THESE ARE LOCATED ON THE NORTHEAST TABLE. *EXAMPLE
 1215. THIS IS NOT AN ISSUE AS LONG AS ALL FIXTURE
 WATTAGE USAGE IS BEING CONSIDERED AND TAKEN INTO
 ACCOUNT HOWEVER COORDINATION IN REVIEW OF TABLES
 COMPARED TO PLANS SHOULD BE CONSIDERED.
  
 PLEASE CLARIFY HOW THE DENSE FILING ROOM 1289 CAN BE
 SHOWN AS A CONFERENCE MEETING ROOM. THIS ROOM DOES NOT
 FALL CLOSEST TO CONFERENCE MEETING ROOM WHICH ALLOWS
 1.3, THIS MAY BE CONSIDERED ACTIVE STORAGE AT 0.8. OR
 POSSIBLY OFFICE AT 1.1. PLEASE VERIFY IF A PERMANENT
 WORK STATION IS IN ROOM.
  
 PLEASE KNOW BASED ON THE LIGHTING POWER TABLES
 SUBMITTED THE DESIGN IS BEING SHOWN AT 13.99 WATTS
 BELOW MAXIMUM ALLOWANCE. PLEASE SEE HOWEVER THERE ARE
 FIXTURE(S) ON PLANS WHICH ARE NOT FIGURED INTO THE
 CALCULATIONS. IF THESE ARE THEN THE TOTAL ALLOWANCE
 WOULD BE EXCEEDED.
  
 N.E. AREA: PLEASE SEE FOR EXAMPLE ROOM 1288 AS THE
 TABLE SHOWS 3-FIXTURES TOTAL, YET PLANS SHOW 4.
  
 S.E. AREA: PLEASE SEE FOR EXAMPLE THE LOBBY/RECEPTION
 AREA 1200 AS TABLE COUNT FOR FIXTURE *D* DOES NOT MATCH
 WITH PLANS. PLEASE ALSO CLARIFY WHERE THE ADDITIONAL
 *E* FIXTURES ARE AS THE FOUR OF THESE FIXTURE *E* ARE
 IN ELEVATOR LOBBY ARE LISTED ON 1293.
  
 S.W. AREA: PLEASE SEE FOR EXAMPLE ROOM/AREA 1277 AS
 THIS AREA IS TAKING INTO ACCOUNT *S* FIXTURES. THIS
 AREA IS INDICATING A TOTAL OF 20 FIXTURES YET TABLE
 INDICATES 19.THERE IS QUESTION ON S FIXTURE DIRECTLY
 ACROSS FROM ELECTRICAL ROOM 1296 AS THIS SEEMS TO BE A
 SEPARATE ROOM HOWEVER AS NO OTHER DESIGNATION IS
 PRESENT THEREFORE THIS IS ASSUMED IN THIS ZONE/AREA
 1277.
  
 N.W. AREA: PLEASE SEE FOR EXAMPLE CORRIDOR 1256 WHICH
 *K* FIXTURE WATTAGE LISTED ON FIXTURE SCHEDULE IS
 HIGHER THAN ON TABLE. THE OTHER QUESTION IS THE FIXTURE
 *K* COULD NOT BE LOCATED IN THE 1256 AREA? CONTROL ETC
 WILL BE NOTED ABOVE.
  
 ** THE ABOVE EXAMPLES ARE SOME ITEMS FROM EACH SECTION
 OF THE FLOOR BEING NOTED ON PLANS AS NE, SE, SW, NW AND
 CORE.
 AS STATED ON PREVIOUS PLAN REVIEWS. PLEASE COORDINATE
 ALL LIGHTING FIXTURES ON PLANS WITH THE *MAXIMUM*
 ALLOWANCE CALCULATIONS. PLEASE COORDINATE TABLES WITH
 THE FIXTURES AND WATTAGES AS INDICATED ON FIXTURE
 LEGEND.
  
 5) NOTE: PLEASE BE SURE WHEN SUBMITTING PLANS TO ATTACH
 COMPLETE SETS TOGETHER WITH STAPLES WHICH GO ALL THE
 WAY THROUGH THE PLANS.
  
 6) NOTE: PLEASE KNOW THAT ONE COMPLETE COPY OF
 ELECTRICAL PLANS IS BEING RETAINED BY THIS OFFICE.
 PLEASE SEE FS 553.80(2)(B). PLEASE KNOW AS THE CODE
 SECTIONS WERE GIVEN FOR THE SAME SECTION OF 13-415.2
 FOR COORDINATION OF LIGHTING ON PLANS WITH CALCULATIONS
 FOR FOUR REVIEWS NOW, THE FEE AS REQUIRED PER FLORIDA
 STATUTE IS ONCE AGAIN ASSESSED.
 PLEASE SEE THAT SPECIFICALLY THE NOTES HAVE STATED ON
 FOUR REVIEWS TO BE SURE AND CORRELATE ALL LIGHTING
 FIXTURES ON PLANS, ALL WATTAGES ON PLANS WITH THE
 CALCULATIONS. THIS INCLUDES THE INPUT DATA AS
 PREVIOUSLY SUBMITTED AS WELL AS THE INPUT DATA TABLES
 NOW ON SHEET E-0.6.
 THE FEE IS REQUIRED BEFORE RESUBMISSION OF PLANS.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-09-15 Cont ID  
Sent By dpalmer Date 2007-09-15 Time 16:57 Rev Time 0.00
Received By dpalmer Date 2007-09-15 Time 13:03 Sent To  
Notes
2007-09-15 17:05:02NOTE ADDED:
  
 PLEASE BE SURE TO PROVIDE THE CORRECT PERMIT
 APPLICATION AS THE APPLICATION SUBMITTED IN THE PERMIT
 PACKAGE IS FOR CENTEX CONSTRUCTION. A CHANGE OF
 CONTRACTOR WAS DONE AND IS NOW BALFOUR/BEATLY. THIS
 APPLICATION SHOULD BE IN PACKAGE.
 PLEASE ALSO SEE THE RESUB COVER SHEET WAS FILLED OUT
 AND STILL INDICATES CENTEX CONSTRUCTION. THIS WAS
 CORRECTED ON RESUB COVER SHEET.
2007-09-15 16:57:302007-09-15 16:57:30
  
 *** DENIED 3RD REVIEW ***
  
 ** PLEASE SEE THERE ARE NOTES FROM PREVIOUS TWO REVIEWS
 WHICH ARE STILL IN NEED OF ADDRESSING.
 ** PLEASE ALSO SEE THERE SOME NEW COMMENTS BASED ON
 CHANGES AND REVISIONS TO PLANS.
  
  
 1) NOTE: PLEASE SEE SOME OF THE FLORIDA ADMINISTRATIVE
 CODE AND FLORIDA STATUTES COMMENTS BELOW WILL REMAIN AS
 SOME OF THE UPDATED REVISED SHEETS IN THE NEW SETS ARE
 STILL IN NEED OF ADDRESSING.
  
 2) NOTE:PLEASE SEE NOT ALL TITLE BLOCKS ON SHEETS FOR
 THE ARCHITECTURAL FIRM CONTAIN THE PRINTED CERTIFICATE
 OF AUTHORIZATION NUMBER/LICENSE INFORMATION. PLEASE SEE
 THE REVISED MEP SHEETS ARE STILL MISSING THIS
 INFORMATION AS THE TITLE BLOCK FOR THE ARCHITECTURAL
 FIRM IS LISTED. ** PLEASE KNOW ON ANY SHEETS WHICH MAY
 NOT HAVE TO BE REVISED THIS CAN BE PRINTED ON BY HAND.
 PLEASE SEE PREVIOUS COMMENTS AS THIS IS REQUIRED ON ALL
 SHEETS WHICH CONTAIN THE TITLE BLOCK FOR SAID FIRM. FAC
 61G1-16.004, FS481.219
 ** THIS IS REQUIRED FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 3) NOTE: PLEASE SEE PREVIOUS NOTE #3, WITH RESPECT TO
 SIGNATURE OF THE ENGINEER ON ELECTRICAL SHEETS. PLEASE
 SEE THE LETTER SUBMITTED WAS NOT SEALED WITH THE RAISED
 SEAL AS PREVIOUSLY REQUESTED.
 AS THIS OFFICE HOLDS SHEETS WHICH SEEM TO CONTAIN
 DIFFERENT SIGNATURES WE CAN ONLY VERIFY THIS BASED ON
 THE DOCUMENTED LETTER WHICH WILL PLACE IN FILE FOR
 FUTURE REFERENCE.
 PLEASE BE SURE ALL PLANS SUBMITTED FOR THIS PROJECT AND
 ALL PROJECTS ARE SIGNED WITH THE SAME SIGNATURE/MANOR
 TO ALLEVIATE ANY CONFUSION.
 PLEASE SEE THE FAC 61G15-23.002 AND FS 471.025 AS THE
 ENGINEER OF RECORD SHALL BE THE ONLY ONE TO SIGN
 PLANS.
  
 4) NOTE: PLEASE SEE THE DESIGNATIONS ON THE PLANS FOR
 PANELS ON RISER AND PANEL SCHEDULES HAVE BEEN UPDATED.
 PLEASE SEE PANEL DP-11 ON E-.04 WHICH INDICATES FEED TO
 A T7A TRANSFORMER AND THE RISER INDICATES T6A AS BEING
 THE TRANSFORMER.
 PLEASE KNOW DEPENDING ON WHICH TRANSFORMER IS BEING
 USED, THIS COULD CREATE SEPARATE CODE COMPLIANT
 COMMENTS.
 PLEASE SEE 240.21, 250.66, 450.3, 408.36 ETC.
 (TRANSFORMER T4 HAS BEEN NOTED ON OTHER PLANS AS THE
 OVER CURRENT PROTECTION ON THE LINE SIDE IS HIGH,
 450.3) THIS TRANSFORMER DOES NOT AFFECT THIS SPACE,
 HOWEVER AS THE TABLE FOR ALL PLANS SHOULD BE UPDATED,
 THIS SHOULD BE DONE AT THIS TIME. (MAX OPC 125%,
 70AMPS? DEPENDING ON TYPE OF UNIT)
  
 5) NOTE: PLEASE CLARIFY WHERE ON THE A-SHEETS IS THE
 INFORMATION FOR THE REQUIRED RATED WALLS FOR SERVER/IT
 ROOM.
 THIS IS INDICATING CHARACTERISTICS OF AN IT, HOWEVER
 WALL IS NOTED ON SHEET AS *032S* WHICH BY A14.10 DOES
 NOT CONTAIN ANY FIRE RATING?
 PLEASE SEE NFPA-75 CHAPTER 5. THIS INFORMATION IS BEING
 SENT TO THE BUILDING REVIEWER, FIRE MARSHAL AND
 MECHANICAL REVIEWER(S).
 ** PLEASE KNOW ANY INSTALLATIONS OF UPS SYSTEMS WILL
 NOT BE UNDER THIS PERMIT AS NO SYSTEMS ARE SHOWN ON
 PLANS.
  
 6) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WITH
 RESPECT TO THE ENERGY CODE FOR CONTROLS.
 PLEASE SEE SOME ITEMS ARE STILL NOT CLEAR FOR SYSTEM
 AND CONTROLS.
 PLEASE SEE SEPARATE SPACES, AND IN PARTICULAR ANY
 ADDITIONAL CONTROLS FOR DISPLAY OR ACCENT LIGHTING. FOR
 EXAMPLE: COFFEE ROOM *I* FIXTURE, BREAK ROOM *D*
 FIXTURES.
 PLEASE SEE 13-415.1.ABC.1.3.
 PLEASE BE SURE TO SEE 13-415.1.ABC.1.1 AS THE LIGHTING
 OVER RIDE CONTROLS ARE TO BE LOCATED SO THAT ALL OF THE
 LIGHTING WHICH IS BEING OVER RIDDEN CAN BE SEEM BY THE
 OCCUPANT. THERE IS AN EXCEPTION FOR INDICATOR
 LIGHTS/PILOT LIGHTS. PLEASE VERIFY ALL LOCATIONS ON
 PLANS AS NOTE #4 SEEMS TO BE FOR THE SLV DEVICE WHICH
 MENTIONS IT WILL OVER RIDE MULTIPLE LOCATIONS WHICH MAY
 NOT BE SEEN BY THE OCCUPANT.
  
 7) NOTE: ENERGY CALCULATIONS.
 AS NOTED BELOW IDR WILL REPRESENT THE INPUT DATA REPORT
 ON ALL NOTES:
 A) PLEASE SEE PREVIOUS NOTES WHICH REQUESTED FOR ALL
 INFORMATION ON THE INPUT DATA REPORT/ENERGY
 CALCULATIONS TO CORRELATE WITH *ALL* LIGHTING WHICH IS
 SHOWN ON PLANS.
  
 B) PLEASE SEE THERE ARE 91 +/- ROOMS/AREAS DESIGNATIONS
 ON PLANS, HOWEVER ONLY 65+/- ON THE IDR. IT SEEMS SOME
 OF THESE AREAS MAY BE FIGURED INTO ONE TYPE OF AREA,
 HOWEVER MANY OF THESE NUMBERS DO NOT MATCH FOR THE
 NUMBER OF FIXTURES, THE TYPES OF FIXTURES AND THE
 WATTAGE OF THE FIXTURES.
  
 C) PLEASE SEE AS THE ROOMS/AREA DESIGNATIONS ON THE IDR
 DO NOT CORRELATE WITH THE SAME DESIGNATIONS ON PLANS,
 SOME LOCATIONS CAN ONLY BE ASSUMED.
 PLEASE SEE ONE LOCATION WHICH IS NOT CLEAR IS OFFICE
 A.
  
 IF LOOKING AT THE PLANS AND TRYING TO MATCH UP THE
 NUMBERS OF FIXTURES AND WATTAGES WITH THE FIXTURE
 LEGEND IS THE WAY THIS IS TO BE FIGURED, THIS IS NOT
 CORRELATING.
 ** PLEASE SEE NW SECTION OF PLANS?
 EXAMPLE: THE OFFICE A IN THE NW SECTION OF IDR
 INDICATES 4-84WATT FIXTURES, YET THE OFFICE A IN THE NE
 SECTION OF IDR INDICATES ONLY 1-84 WATT FIXTURE. THIS
 ONE OFFICE A WITH ONLY ONE LIGHT FIXTURE COULD NOT BE
 FOUND ON THE NE SECTION OF THE FLOOR PLAN.
 THIS IS THE SAME FOR SEVERAL OTHER AREAS IN THE NW
 SECTION.
 ** PLEASE SEE NE SECTION OF FLOOR PLANS:
 EXAMPLE: BREAK ROOM WHICH INDICATES A FIXTURE *D* WHICH
 IS 50WATTS ON FIXTURE LEGEND AND NO 50WATT FIXTURE IS
 SHOWN ON THE IDR FOR THIS SAME ROOM.
 ** PLEASE SEE FILES ROOM IN THE IDR, WHICH C, A AND B
 FIXTURES, WATTAGE AND NUMBER OF FIXTURES ON IDR DOE NOT
 CORRELATE.
 ** PLEASE SEE SE SECTION OF PLANS:
 EXAMPLE: CONFERENCE ROOM 1202, 2-C, 5-M, 4-N AND 1-A,
 SEE IDR, SOME OF THESE ARE OK, HOWEVER SOME ARE MISSING
 AND/OR THE TOTAL OF FIXTURES AND WATTAGE ARE NOT THE
 SAME.
 ** PLEASE SEE SW SECTION OF PLANS:
 EXAMPLE: SMALL CONFERENCE? IF THIS IS THE SAME ROOM, IT
 IS UNCLEAR? PLEASE SEE ONLY TWO TYPES OF FIXTURES ARE
 LISTED IN THE IDR, YET PLANS SEEM TO SHOW FIXTURES C, A
 AND M?
  
 ** THESE ARE ONLY A FEW EXAMPLES OF SOME OF THE ROOMS
 WHICH FIXTURES ON PLANS DO NOT CORRELATE WITH THE IDR.
 THIS IS NOT ALL LOCATIONS. PLEASE BE SURE TO GO OVER
 ALL FIXTURES ON PLANS. PLEASE PLACE SOME SORT OF
 DESIGNATION ON THE IDR WHICH CORRESPONDS TO THE PLANS.
  
  
 D) PLEASE SEE THE FIXTURE LEGEND AND IDR CONTAINS
 FIXTURES WHICH DOE NOT MATCH.
 FOR EXAMPLE:
 ** PLEASE SEE THE FIXTURE LEGEND SHOWS 40W, 96W, 75W
 ETC FIXTURES AND IDR DOES NOT INDICATE THESE. PLEASE
 SEE BELOW FOR THE 96W FIXTURE.
 **PLEASE SEE THE IDR WHICH SEEMS TO INDICATE 300W
 FIXTURE(S) YET THE FIXTURE LEGEND DOES NOT.
 ** PLEASE SEE TYPE *S* FIXTURE WHICH IS SHOWN AS A 96W
 FIXTURE ON LEGEND HOWEVER THIS SEEMS TO BE SHOWN AS
 BOTH 84W AND 96W ON IDR. THIS IS SEEN IN TRAINING ROOM
 WHICH ON THE IDR SHOWS THESE AS TYPE *S* FIXTURE WHICH
 IS 96W ON THE IDR, YET THE SAME FIXTURE *S* IN THE
 OFFICES AND ALL OTHER AREAS ON PLANS ARE 84W?? PLEASE
 COORDINATE ALL OF THESE. IF THE FIXTURES ARE 84W,
 ADJUST LEGEND AND IDR, IF THE FIXTURES ARE 96W, PLEASE
 ADJUST FIXTURE LEGEND AND IDR.
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY
 ALSO AFFECT THE METHOD OR ENERGY CALCULATIONS. PLEASE
 SEE 13-415.1.A, 13-415.1.B, 13-415.1.C, 13-415.2
 PLEASE BE SURE ALL FIXTURE TYPES, WATTAGES, NUMBER OF
 FIXTURES, ROOMS AND AREAS ON PLANS COORDINATE WITH THE
 IDR AND FIXTURE LEGEND.
  
 8) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE NOTICE TO
 FS 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR
 CODE COMPLIANCE.
 PLEASE KNOW AS THE ENERGY CALCULATIONS COORDINATION
 COMMENT HAS BEEN REPEATED NOW FOR THE THIRD TIME.
 PLEASE KNOW DUE TO THIS COMMENT AND OTHER COMMENTS AS
 NOTED ABOVE ONE SET OF ELECTRICAL PLANS AND ENERGY
 CALCULATIONS ARE BEING RETAINED BY THIS OFFICE FOR PEER
 REVIEW AND WILL BE PLACED WITH PREVIOUS RETAINED
 PLANS.
 PLEASE KNOW THE FEE AS REQUIRED PER FLORIDA STATUTES
 THE FEE OF $18,600.00 HAS BEEN ASSESSED PENDING PEER
 REVIEW. THIS WOULD BE DUE BEFORE RESUBMISSION OF PLANS
 FOR THE 4TH REVIEW.
 IT IS STRONGLY SUGGESTED TO OVER ALL PLANS AND
 CALCULATIONS BEFORE RESUBMITTING PLANS FOR THE
 FOLLOWING REVIEW.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-27 Cont ID  
Sent By dpalmer Date 2007-06-27 Time 12:40 Rev Time 0.00
Received By dpalmer Date 2007-06-26 Time 18:54 Sent To  
Notes
2007-06-27 12:44:14 
 *** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE THERE ARE NOTES FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING.
 ** PLEASE ALSO SEE THERE SOME NEW COMMENTS BASED ON
 CHANGES AND REVISIONS TO PLANS WHICH WERE NOT SUBMITTED
 ON THE PREVIOUS REVIEW.
  
  
  
 1) NOTE: PLEASE SEE THE PLANS (ARCHITECTURAL) INDICATE
 THE BUILDING NOW AS A 16 STORY BUILDING HOWEVER THE
 ENERGY CALCULATIONS INDICATE 15 STORIES.
 PLEASE COORDINATE THESE.
 FBC 106.1.2, 13-415.1.AB.1.1
  
 2) NOTE: PLEASE SEE THE COMMENT RESPONSES WHICH STATE
 THE PREVIOUS REVIEW COMMENTS FROM EACH REVIEWER AND
 THEN THE RESPONSE FROM THE DESIGN TEAM. PLEASE SEE
 THERE ARE SEVERAL ELECTRICAL COMMENTS WHICH DO NOT
 DELINEATE THE NOTE WHICH WAS TYPED BY THIS REVIEWER. IF
 THE NOTES ARE TO BE QUOTED, PLEASE SEE THESE ARE NOT
 MATCHING. PLEASE SEE THERE ARE CODE SECTIONS WHICH WERE
 INDICATED ON RESPONSE SHEETS WHICH ARE NOT WHAT WAS
 TYPED IN THE REVIEW. PLEASE SEE COMMENT #13 FOR
 EXAMPLE.
 IF THE COMMENT RESPONSES ARE GOING TO INDICATE THE
 REVIEWER'S COMMENTS, PLEASE BE SURE TO STATE THE
 COMMENT(S) AS MADE.
 FBC 106.1.2
  
 3) NOTE: PLEAS SEE THE NEW FP SHEETS AS SUBMITTED ARE
 MISSING THE PRINTED NAME, PRINTED LICENSE NUMBER AND
 THE CERTIFICATE OF AUTHORIZATION NUMBER ON TITLE BLOCKS
 AS REQUIRED PER FLORIDA ADMINISTRATIVE CODE
 61G15-23.002 AND FLORIDA STATUTES 471.023.
 IF THE CONTRACTOR AS STATED IS OFFERING ENGINEERING
 SERVICES THEN THEY ARE REQUIRED TO BE LICENSED UNDER
 THE FLORIDA STATUTES.
 ** THIS COMMENT IS MADE AND REQUIRED WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADE(S).
  
 4) NOTE: PLEASE SEE NOT ALL TITLE BLOCKS ON SHEETS FOR
 THE ARCHITECTURAL FIRM CONTAIN THE PRINTED CERTIFICATE
 OF AUTHORIZATION NUMBER.
 PLEASE SEE PREVIOUS COMMENTS AS THIS IS REQUIRED ON ALL
 SHEETS WHICH CONTAIN THE TITLE BLOCK FOR SAID FIRM. FAC
 61G1-16.004, FS481.219
 ** THIS IS REQUIRED FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 ** PREVIOUS REVIEW NOTES*
 PLEASE SEE THE MISSING INFORMATION ON THE TITLE BLOCKS
 FOR THE ARCHITECTURAL FIRM AS REQUIRED UNDER THE FAC
 61G1-16.004 AND FS 481.219
 * THIS IS REQUIRED FOR ALL SHEETS INCLUDING TRADE
 SHEETS WHICH CONTAIN THE SAME TITLE BLOCKS.
  
  
 5) NOTE: PLEASE SEE THE MEP SHEETS. PLEASE SEE MANY OF
 THESE WERE NOT DATED WHEN SIGNED, AND SEALED. PLEASE
 SEE NUMEROUS SHEETS WHICH CONTAIN AS MANY AS THREE
 COMPLETELY DIFFERENT SIGNATURES FOR THE SAME ENGINEER
 OF RECORD.
 PLEASE KNOW PLANS ARE BEING RETAINED BY THIS OFFICE FOR
 POSSIBLE REVIEW FROM THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS AND LEGAL COUNSEL TO THE BOARD.
 PLEASE SUBMIT COMPLETED NOTARIZED LETTER FOR SIGNATURE
 VERIFICATION WHICH WILL BE REQUIRED TO BE SIGNED,
 DATED, SEALED AND NOTARIZED.
 PLEASE ALSO SUBMIT PHOTO-IDENTIFICATION WHICH CONTAINS
 THE SIGNATURE OF THE ENGINEER. PLEASE KNOW AT THIS TIME
 DUE TO THE MULTIPLE SIGNATURES, THIS OFFICE CAN VERIFY
 WHICH ONE IS CORRECT.
 PLEASE SEE THE FAC 61G15-23.002 AND FS 471.025 AS THE
 ENGINEER OF RECORD SHALL BE THE ONLY ONE TO SIGN
 PLANS.
  
 ** THIS IS REQUIRED FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADES.
  
 6) NOTE: PLEASE SEE THE ADDRESS AS LISTED ON TITLE
 BLOCKS FOR THE ENGINEERING FIRM AS SHOWN ON THE STATE
 WEBSITE.
 PLEASE SEE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION WEBSITE.
 ** AS THE MAIN OFFICE IS LISTED ON WEBSITE AND THIS IS
 A *SATELLITE OFFICE* PLEASE KNOW THAT THE PRIMARY
 ADDRESS WOULD STAY AND BE OK, HOWEVER NEED TO ADD TO
 PLANS.
 FAC 61G15-23.002
  
 7) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH STATED THE
 MINIMUM CODES TO BE STATED ON PLANS FOR ARCHITECTURAL
 AND ELECTRICAL SHEETS. PLEASE SEE RESPONSE FROM BOTH
 FIRMS STATE THIS WOULD BE DONE WHOEVER PLEASE SEE THE
 FOLLOWING WHICH WAS NOT CORRECTED.
 PLEASE SEE THE ARCHITECTURAL COVER SHEET WHICH STATES
 THE FOLLOWING:
 A) STATES: 2002 FLORIDA ELECTRICAL CODE NFPA-70. (THIS
 SHOULD BE THE NATIONAL ELECTRICAL CODE AND SHOULD BE
 THE 2005 EDITION AS PREVIOUSLY STATED.
 B) STATES: NATIONAL FIRE ALARM CODE AS 2005 NFPA-70.
 (THIS IS THE NEC AND SHOULD BE NATIONAL FIRE ALARM CODE
 NFPA-72 AND THE EDITION IS THE 2002.
 C) STATES: NATIONAL FIRE ALARM CODE AS THE 2003
 NFPA-101. (THIS IS NOTED IN *B* ABOVE. THE NFPA-101
 2003 WHICH IS THE LIFE SAFETY CODE IS STATED. PLEASE
 SEE THE ELECTRICAL SHEET E-0.1:
 A) STATES: THE 2002 NFPA-70 (NEC) ( THIS SHOULD BE THE
 2005 NFPA-70 AS PREVIOUSLY STATED IN PREVIOUS REVIEW
 NOTES.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE THAT ALL OF THE CODES WHICH PLANS ARE UNDER
 DESIGN AND RECORD SHALL BE STATED ON PLANS AS FOLLOWS.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 * PLEASE SEE THE ARCHITECTURAL SHEETS WHICH STATE SOME
 OF THE OLDER CODES.
 ** THESE ARE REQUIRED FOR THE REVIEWER AT A MINIMUM AND
 OTHER CODES WILL BE REQUIRED FOR OTHER TRADES.
  
 8) NOTE: PLEASE SEE THE ENERGY CALCULATIONS ARE STILL
 MISSING THE *OWNER AGENT* SIGNATURE. PLEASE ALSO SEE
 THESE WERE NOT DATED WHEN SIGNED, AND SEALED. PLEASE
 SEE COMMENTS WITH RESPECT TO THE ENGINEER'S SIGNATURE
 ALONG WITH COMMENTS WITH RESPECT TO THE ENERGY
 CALCULATIONS. PLEASE SEE FBC 13-103.1.1.1, FS471.025,
 FS 481.221
  
 9) NOTE:PLEASE SEE THE EMERGENCY LIGHTING IS BEING
 SHOWN COMING FROM A PANEL LOCATION WHICH IS NOT SHOWN
 AS ACCESSIBLE OR IN THE SAME ELECTRICAL ROOM AS OTHER
 ELECTRICAL EQUIPMENT FOR THE SAME TENANT. PLEASE SEE
 THE LOCATION OF THIS EQUIPMENT AND PANELS ARE NOT
 KNOWN. PLEASE SEE THE LIGHTING NOTES WHICH STATE THESE
 ARE BEING FED FROM THE11TH FLOOR AND YET THE RISER
 SHOWS THESE BEING FED FROM THE 10TH FLOOR? IN EITHER
 CASE IF THE DISCONNECTING MEANS/PANEL (EL212A)/OVER
 CURRENT PROTECTION ARE LOCATED ON THE 12TH FLOOR IN THE
 ELECTRICAL ROOM THIS WOULD BE ACCEPTABLE.
 240.24, 240.21, ETC.
 FBC ADMIN SECTION 104.6
  
 10) NOTE: PLEASE SEE THE BASE BUILDING PLANS INDICATE
 THE CIRCUIT AND LIGHTING FOR THE COMMON AREA AND
 CORRIDORS DIFFERENT THAN THE BUILD-OUT PLANS. PLEASE
 SEE THE BUILD OUT IS NOW INCLUDING THIS COMMON AREA AS
 PART OF THE TENANT BUILD-OUT?? PLEASE PROVIDE ALL
 INFORMATION ON THE CHANGES OF THESE PROPOSED DESIGNS.
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES. PLEASE
 BASE BUILDING PERMITTED PLANS WHICH INDICATE THE COMMON
 AREA IS BEING SHOWN AND DONE UNDER THE BASE BUILDING.
 PLEASE KNOW THAT ANY AND ALL CHANGES ON THE BUILD-OUT
 BEFORE CO OF THE BASE BUILDING WILL REQUIRE THE PLANS
 TO BE REVISED ALONG WITH ENERGY CALCULATIONS.
 FBC 106.1.2
  
 12) NOTE: PLEASE SEE THAT ALL OF THE CODES WHICH PLANS
 ARE UNDER DESIGN AND RECORD SHALL BE STATED ON PLANS AS
 FOLLOWS.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 * PLEASE SEE THE ARCHITECTURAL SHEETS WHICH STATE SOME
 OF THE OLDER CODES.
 ** THESE ARE REQUIRED FOR THE REVIEWER AT A MINIMUM AND
 OTHER CODES WILL BE REQUIRED FOR OTHER TRADES.
  
 13) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED DOSO NOT CORRELATE WITH THE PLANS AND THE
 FIXTURE LEGEND.
 PLEASE SE THE WATTAGE FOR THE SAME TYPE OF FIXTURES ARE
 BEING SHOWN AS TWO DIFFERENT LEVELS.
 PLEASE SEE THE NUMBER OF FIGURE FOR SPECIFIC ROOMS DO
 NOT ALL CORRELATE.
 PLEASE PROVIDE THE DESIGNATIONS ON THE ENERGY
 CALCULATIONS WHICH COORDINATES WITH PLANS OR THE
 DESIGNATIONS ON PLANS TO CORRELATE WITH THE ENERGY
 CALCULATIONS. PLEASE SEE THE DESIGNATIONS, AMOUNT OF
 ROOMS, AMOUNT OF LUMINARIES ETC FOR THE N.E> ZONE DOES
 NOT CORRELATE WITH PLANS. (OTHER AREAS ALSO). PLEASE
 PROVIDE MOTE INFORMATION FOR THESE INCLUDING NOTE BELOW
 WITH RESPECT TO EMERGENCY LIGHTING AND CIRCUITING.
 PLEASE BE SURE THE SQ FT LEVELS COORDINATE BASED ON
 AREA USED ON PLANS AND ENERGY CALCULATIONS.
 PLEASE SEE 13-415.2, 13-415.1.A
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 2004 FBC W/2006 REVISIONS FOR CHAPTER 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.PLEASE SEE
 SOME AREAS/LOCATIONS WHICH DO NOT SEEM TO INDICATE ANY
 LIGHTING CONTROLS. PLEASE SEE MAXIMUM LIGHTING CONTROL
 OF 25K SQ FT. PLEASE SEE ONLY ONE LIGHTING CONTROL
 PANEL IS BEING NOTED.
 PLEASE PROVIDE LOCATIONS AND MORE DETAIL OF THE OVER
 RIDES DEVICES AND HOW THEY ARE BEING PART OF THE
 *SYSTEM*.
 PLEASE PROVIDE ESTIMATED SCHEDULING.
 PLEASE SEE THE ENERGY CALCULATIONS INDICATE MANUAL
 CONTROLS FOR ALL LIGHTING CONTROL WHERE THIS SHOULD
 INDICATE THE ACTUAL DEVICES/SYSTEM ON PLANS. PLEASE SEE
 THAT THE LOCATIONS FOR ALL OVER RIDES DEVICES SHALL BE
 LOCATED SO THAT THE OCCUPANT CAN VISUALLY SEE THE
 LIGHTING WHICH IS BEING CONTROLLED. PLEASE PROVIDE MORE
 INFORMATION.
 PLEASE SEE 13-415.1.ABC.3 FOR TANDEM WIRING. PLEASE SEE
 13-415.1.AB.1; PLEASE SEE ENERGY CALCULATIONS FOR BUILD
 OUT OF SPACE WHICH DOES NOT CORRELATE WITH THE LIGHTING
 PLANS, FIXTURES, WATTAGES, NUMBER OF FIXTURES ETC.
 PLEASE SEE THERE ARE SEVERAL LIGHTING FIXTURES WHICH DO
 NOT CORRELATE WITH THE ELECTRICAL PLANS AND FIXTURE
 LEGEND.
  
 PLEASE SEE 13-415.2 AS LIGHTING POWER DENSITIES ARE NOT
 INDICATED FOR ALL AREAS. PLEASE BE SURE TO CORRELATE
 THIS WITH THE ENERGY CALCULATIONS WHICH ARE TO BE
 SUBMITTED.
 * PLEASE SEE ALL OF CHAPTER 13.
 PLEASE BE SURE ALL TO SEE 13-103.1.1.1
  
 14) NOTE: PLEASE SEE 700.12F OF THE 2005 NEC. PLEASE
 PROVIDE MORE INFORMATION ON HOW THIS PROPOSED DESIGN ON
 PLANS FOR SINGLE CIRCUIT OR SEPARATE SPACE AREAS MEETS
 THIS SECTION OF THE NEC.
  
  
 15) NOTE: PLEASE SEE ATTACHED SHEET WITH RESPECT TO FS
 553.80(2)(B). THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-27 07:06:00REVIEW IN PROGRESS
2007-06-26 18:55:01PLANS IN ELECTRIC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-19 Cont ID  
Sent By dpalmer Date 2007-03-19 Time 17:18 Rev Time 0.00
Received By dpalmer Date 2007-03-18 Time 16:43 Sent To  
Notes
2007-03-19 17:22:01** UNSAT **
  
 * PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 WILL BE FROM THE ADMINISTRATIVE SECTION OF THE CODE AS
 ADOPTED BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE SUBMIT PLANS INTO TWO COMPLETE SETS
 ATTACHED TOGETHER FOR REVIEW. PLEASE DO NOT SUBMIT
 LOOSE SHEETS NOT ATTACHED TO EACH OTHER AND NOT BOUND N
 ANY FASHION.
 FBC 106
  
 2) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS INDICATE
 THIS BUILDING AS A 20 STORY BUILDING WHERE AS THE BASE
 BUILDING PERMIT IS NOT FOR A 20-STORY BUILDING? PLEASE
 CORRELATE AND ADJUST PLANS.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE A PRINT OUT FROM THE STATE OF
 FLORIDA DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION WHICH INDICATES THE ARCHITECT'S LICENSE AS
 ON PLANS AS *DELINQUENT* AT THIS TIME. PLEASE KNOW THAT
 THIS IS PRINTED WITH DATES OF 3/19/07.
  
 4) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS DO NOT
 CONTAIN THE RAISED/EMBOSSED TYPE OF SEAL AS REQUIRED
 UNDER FAC 61G1-16.003
 PLEASE SEE THESE ARE ACTUALLY A *RUBBER STAMP* FOR THE
 RAISED SEAL.
 THIS IS NOT PERMITTED IN THE STATE OF FLORIDA. FS
 481.221
 * THIS IS REQUIRED FOR ALL SHEETS WHICH CONTAIN THE
 *RUBBER STAMP* WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADE(S).
  
 5) NOTE: PLEASE SEE THE MISSING INFORMATION ON THE
 TITLE BLOCKS FOR THE ARCHITECTURAL FIRM AS REQUIRED
 UNDER THE FAC 61G1-16.004 AND FS 481.219
 * THIS IS REQUIRED FOR ALL SHEETS INCLUDING TRADE
 SHEETS WHICH CONTAIN THE SAME TITLE BLOCKS.
  
 6) NOTE: PLEASE SEE THE ADDRESS OF THE PROJECT SHALL BE
 SPECIFIC ON THE TITLE BLOCKS AND COVER SHEET. THE
 STATEMENT WHICH INDICATES LOCATION IN THE *CITY OF WEST
 PALM BEACH* DOES NOT PROVIDE THE NEEDED INFORMATION.
 PLEASE SEE THE PROPOSED UNIT/SUITE NUMBER IS LISTED ON
 SHEETS.
 FAC 61G1-16
 FBC ADMIN SECTION 106.1.2
  
 7) NOTE: PLEASE SEE THE SEAL WHICH IS BEING USED BY THE
 PE FOR THE MEP PLANS IS NO LONGER VALID WITHIN THE
 STATE OF FLORIDA.
 PLEASE SEE RULE IN THE FLORIDA ADMINISTRATIVE CODE
 61G15-23.001 WHICH WAS CHANGED IN FEB OF 04 THAT ALL
 SEALS FOR ENGINEERS MUST HAVE THE WORDING IN SEALS
 CHANGED FROM * CERTIFICATE* TO THE WORDING OF
 *LICENSE*. AN EXTENSION WAS GRANTED TO THE DATE OF
 DECEMBER 31ST, 2005 HOWEVER AFTER SUCH DATE THE OLDER
 SEALS WITH THE PREVIOUS WORDING COULD NOT LONGER BE
 USED. PLEASE OBTAIN NEW SEAL AS REQUIRED.
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE(S).
  
 8) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 ARE NOT SIGNED, DATED AND SEALED AS REQUIRED. PLEASE
 SEE FBC 13-103.1.1.1
 PLEASE ALSO SEE SEVERAL CODE COMMENTS WHICH WILL
 REQUIRE THESE TO BE REVISED.
  
 9) NOTE: PLEASE SEE THAT ELECTRICAL ROOMS, MECHANICAL
 ROOMS, DATA/PHONE AND EMERGENCY ELECTRICAL ROOMS SHALL
 BE ACCESSIBLE WITHOUT ENTERING INTO THE TENANT SPACE.
 PLEASE EXTEND THE CORRIDORS ON FLOORS AND AREAS WHICH
 ARE FED FROM HOUSE POWER AND ANY ROOMS WHICH MAY FEED
 OTHER FLOORS. PLEASE SEE THE HALL WAYS ARE ALMOST DOWN
 TO THE ELECTRICAL ROOM ON ONE SIDE AND ONLY PART OF THE
 NORTH SIDE NEEDS TO BE CORRECTED. PLEASE KNOW THAT THE
 HOLD WHICH WAS PLACED ON THE PARCEL AS PART OF THE *
 PROVISO* ON THE ORIGINAL PLANS WILL REMAIN. PLEASE ALSO
 KNOW THAT ALL ORIGINAL PLANS FOR ISSUANCE OF PERMIT WAS
 ISSUED WITH THIS REDLINED ON PLANS AS CONDITIONS FOR
 ISSUANCE.
 240.24, 210.25, 90.4.
 FBC 104.6 ADMIN SECTION.
  
 10) NOTE: PLEASE SEE PLANS ON ARCHITECTURAL MENTIONS
 *MAG-LOCKS* OF SOME TYPE HOWEVER NO INFORMATION IS
 PROVIDED ON ELECTRICAL PLANS.
 PLEASE KNOW THAT ANY ACCESS CONTROL SYSTEMS SHALL MEET
 NFPA-101 7.1.9, 7.2.1.5.1 DOORS SHALL BE ARRANGED TO BE
 OPENED READILY FROM THE EGRESS SIDE WHENEVER THE
 BUILDING IS OCCUPIED.
 7.2.1.5.2 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR
 OPERATION FROM THE EGRESS SIDE.
  
 11) NOTE: PLEASE SEE PLANS MENTIONS A SERVER ROOM IS
 THIS AN IT ROOM? IF SO, PLEASE INCLUDE THE RATING OF
 THE WALL CONSTRUCTION AND PLEASE SEE 645.11 FOR MEANS
 OF DISCONNECT OF ELECTRICAL EQUIPMENT. PLEASE PROVIDE
 MORE INFORMATION ON THIS.
 FBC 106.1.2.
  
 12) NOTE: PLEASE SEE THAT ALL OF THE CODES WHICH PLANS
 ARE UNDER DESIGN AND RECORD SHALL BE STATED ON PLANS AS
 FOLLOWS.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
 * PLEASE SEE THE ARCHITECTURAL SHEETS WHICH STATE SOME
 OF THE OLDER CODES.
 ** THESE ARE REQUIRED FOR THE REVIEWER AT A MINIMUM AND
 OTHER CODES WILL BE REQUIRED FOR OTHER TRADES.
  
 13) NOTE: PLEASE SEE 2004 FBC W/2006 REVISIONS FOR
 CHAPTER 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.PLEASE SEE
 SOME AREAS/LOCATIONS WHICH DO NOT SEEM TO INDICATE ANY
 LIGHTING CONTROLS. PLEASE SE MAXIMUM LIGHTING CONTROL
 OF 25K SQ FT. PLEASE SEE ONLY ONE LIGHTING CONTROL
 PANEL IS BEING NOTED.
 PLEASE PROVIDE LOCATIONS AND MORE DETAIL OF THE OVER
 RIDES DEVICES AND HOW THEY ARE BEING PART OF THE
 *SYSTEM*.
 PLEASE PROVIDE ESTIMATED SCHEDULING.
 PLEASE SEE THE ENERGY CALCULATIONS INDICATES MANUAL
 CONTROLS FOR ALL LIGHTING CONTROL WHERE THIS SHOULD
 INDICATE THE ACTUAL DEVICES/SYSTEM ON PLANS. PLEASE SEE
 THATTHE LOCATIONS FOR ALL OVER RIDES DEVICES SHALL BE
 LOCATED SO THAT THE OCCUPANT CAN VISUALLY SEE THE
 LIGHTING WHICH IS BEING CONTROLLED. PLEASE PROVIDE MORE
 INFORMATION.
 PLEASE SEE 13-415.1.ABC.3 FOR TANDEM WIRING. PLEASE SEE
 13-415.1.AB.1; PLEASE SEE ENERGY CALCULATIONS FOR BUILD
 OUT OF SPACE WHICH DOES NOT CORRELATE WITH THE LIGHTING
 PLANS, FIXTURES, WATTAGES, NUMBER OF FIXTURES ETC.
 PLEASE SEE THERE ARE SEVERAL LIGHTING FIXTURES WHICH DO
 NOT CORRELATE WITH THE ELECTRICAL PLANS AND FIXTURE
 LEGEND.
  
 PLEASE SEE 13-415.2 AS LIGHTING POWER DENSITIES ARE NOT
 INDICATED FOR ALL AREAS. PLEASE BE SURE TO CORRELATE
 THIS WITH THE ENERGY CALCULATIONS WHICH ARE TO BE
 SUBMITTED.
 * PLEASE SEE ALL OF CHAPTER 13.
 PLEASE BE SURE ALL TO SEE 13-103.1.1.1
  
 14) NOTE: PLEASE PROVIDE ALL CIRCUITING ON PANEL
 SCHEDULES FOR ALL ROOMS AND AREAS WHICH THE CIRCUIT
 FEEDS. PLEASE SEE 408.4 AND COMMENTARY WHICH IS TAKEN
 FROM THE CODE.
 * CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* 408.4,
 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 15) NOTE: PLEASE SEE NOTE ON SHEET A05.12 WHICH
 MENTIONS TO SEE SHEET A05.00 FOR DETAILS OF SERVER/IT
 ROOM AND YET THERE IS NO SHEET 05.00 SUBMITTED.
  
 16) NOTE: PLEASE PROVIDE GROUNDING DETAIL FOR ALL
 TRANSFORMERS PER 250.20,250.30,250.66.
 PLEASE SHOW SIZE AND ATTACHMENT LOCATIONS.
  
 17) NOTE: PLEASE CLARIFY THE RISER AND THE BASE
 BUILDING PLANS INDICATE METERING DEVICES OFF OF THE
 BUS-DUCT RISER YET THE RISER SUBMITTED DOES NOT SHOW
 ANY OF THIS?
 IF THERE ARE METERING DEVICES AND THEY ARE AFTER THE
 FIRST MEANS OF DISCONNECT FOR THE BUILDING, PLEASE
 INDICATE A *FLOATING NEUTRAL* AT THAT METERING DEVICE.
 FBC 106.1.2
  
 18) NOTE: PLEASE CLARIFY DP1, AS THIS SEEMS TO INDICATE
 A MAIN , YET ALSO SHOWS THIS AS BEING A MAIN LUG ONLY
 PANEL?
 FBC 106.1.2
  
 19) NOTE: PLEASE SEE SCHEDULE FOR THE OVER CURRENT
 PROTECTION ON THE SECONDARY SIDE OF THE TRANSFORMER T7A
 INDICATES 500AMP, YET THE EQUIPMENT WHICH IS ON THE
 SECONDARY SIDE IS 400A RATED.
 PLEASE ALSO SEE THAT THE PANELS ON THE SECONDARY SIDE
 OF THE TRANSFORMER DO NOT INDICATE ANY MAIN BREAKERS IN
 EQUIPMENT.
 PLEASE SEE THAT A MAIN IS REQUIRED. 408.36, 240.21
  
 20) NOTE: PLEASE SEE THAT ALL LOADS WHICH ARE
 CONTINUOUS ARE TO BE SHOWN AT 125%. 215.3, 230.42 ETC.
  
 21) NOTE: PLEASE SEE THERE ARE TWO SECTIONS #3 FOR THE
 PANELS ON THE SECONDARY SIDE OF THE TRANSFORMER T7A.
 PLEASE CORRELATE.
 FBC 106.1.2
  
 22) NOTE: PLEASE SEE PANEL BOARD EL212A WHICH IS SHOWN
 CONTAINING A 15AMP MAIN CIRCUIT BREAKER WHICH IS OK,
 HOWEVER PLEASE SEE THAT THE PANEL IS ALSO BE SHOWN AS
 15AMP RATED.
 PLEASE ADJUST AND INDEED VERIFY THAT THIS PANEL
 CONTAINS A 15AMP RATED MAIN CIRCUIT BREAKER. IS THIS A
 BACK FED BREAKER? IF SO, PLEASE INDICATE THE REJECTION
 CLIP.
  
 23) NOTE: PLEASE INCLUDE ALL BRANCH CIRCUIT CONDUCTOR
 SIZES ON THE PANEL BOARD SCHEDULES.
 310.16, 240.4.
 FBC106.3.5.1.2, 106.1.2
  
 24) NOTE: PLEASE SEE THE EGRESS LIGHTING LEVELS WERE
 SUBMITTED UNDER NORMAL HOWEVER NO UNDER EMERGENCY COULD
 BE FOUND.
 PLEASE SUBMIT.
 NFPA-101 7.9
  
 25) NOTE: PLEASE SEE THE ENLARGED ELECTRICAL ROOM
 PLANS. PLEASE INCLUDE THE DESIGNATION OF THE 600AMP MCB
 AS SHOWN ON RISER ON LAYOUT.
 FBC106.1.2, 106.3.5.1.2
  
 26) NOTE: PLEASE SEE ANY COMMENTS FROM OTHER TRADES
 (FIRE) WHICH MAY AFFECT THE ELECTRICAL PLANS. PLEASE
 ALSO SEE THAT BASED ON THE ELECTRICAL COMMENTS THE
 POWER AND REFLECTED CEILING PLANS FOR THE ARCHITECTURAL
 SHEETS WILL NEED TO BE REVISED.
  
 27) NOTE: PLEASE VERIFY ALL NON-LINEAR LOADS ON THE
 NEUTRAL CONDUCTORS FOR BRANCH CIRCUITS. PLEASE PROVIDE
 INFORMATION WHETHER OR NOT EACH CIRCUIT WILL CONTAIN
 ITS OWN NEUTRAL OR IF THER WILL BE ANY MULTI-WIRE
 CIRCUITS WHICH SHARE A NEUTRAL? PLEAS EKNOW BASED ON
 SUBSTANTIAL INFORMATION FROM MANY COMPUTER MANUFACTURES
 THE HARMONIC LOADS CAN BE VERY HIGH ON SHARED NEUTRALS
 TO THE POIN OG FIRE ETC. THIS IS A FIRE AND LEFE SAFETY
 ISSUE. IT WAS NOTED THAT THE TRANSFORMERS TO PANELS
 CONTAIN 200% NEUTRALS AND TRANSFORMERS ARE K-RATED.
 QUESTION IS ON BRNACH CIRCUIT CONDUCTORS.
 PLEASE PROVIDE MORE INFORMATION.
 FBC 106.1.2
  
 ** PLEASE KNOW BASED ON THE PLANS SUBMITTED THERE IS
 SOME INFORMATION NOT YET SUBMITTED OR WILL BE REQUIRED
 TO BE CHANGED. PLEASE KNOW THERE MAY BE COMMENTS ON THE
 FOLLOWING REVIEW NOT YET MADE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-19 06:58:102007-03-18 06:58:10
 REVIEW IN PROGRESS
2007-03-18 17:01:422007-03-18 17:01:42
 NOTES TO FOLLOW ONCE REVIEW IS COMPLETE.
2007-03-18 16:43:40IN ELEC FOR REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-11-05 Cont ID  
Sent By mawillia Date 2007-11-05 Time 15:28 Rev Time 0.00
Received By mawillia Date 2007-11-05 Time 15:03 Sent To  
Notes
2007-11-05 15:28:41*****APPROVED*****
  
  
 PLAN SHEETSA00.10, E-1.1, FP1, FP2, AND FP3 WERE
 STAMPED, INTIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-09-20 Cont ID  
Sent By mawillia Date 2007-09-20 Time 10:46 Rev Time 0.00
Received By mawillia Date 2007-09-20 Time 10:26 Sent To  
Notes
2007-09-20 10:31:32*****UNSAT*****
  
 PREVIOUS FIRE PLAN REVIEW COMMENTS HAVE BEEN
 ADDRESSED;HOWEVER THE COMMENT BELOW ARE BASED UPON
 THE THE NEW FIRE PROTECTION SHEETS SUBMITTED.
  
 C.PLEASE SEE THE ELECTRICAL PLAN REVIEWER COMMENT #3
 IN REFERENCE TO TITLE BLOCK INFORMATION.
  
  
 PLEASE BE ADVISED THAT THE APPROPIATE PLAN SHEETS TO BE
 FIRE-STAMPED WHEN THE ABOVE COMMENT HAS BEEN SATISFIED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-08-09 Cont ID  
Sent By mawillia Date 2007-08-09 Time 13:57 Rev Time 0.00
Received By mawillia Date 2007-08-09 Time 12:14 Sent To  
Notes
2007-08-09 13:40:03*****DENIED*****
  
 PREVIOUS FIRE PLAN REVIEW COMMENTS HAVE BEEN
 ADDRESSED;HOWEVER THE COMMENTS BELOW ARE BASED UPON
 THE THE NEW FIRE PROTECTION SHEETS SUBMITTED.
  
  
 NEW COMMENTS
  
 A.ON DRAWING NUMBER A00-00 UNDER THE APPLICABLE CODES
 AND REFERENCES SECTION, THE 2002 EDITION OF NFPA 72 IS
 TO BE REFERENCED AS THE NATIONAL FIRE ALARM CODE.
  
 B.NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER
 SYSTEMS, 2002 EDITION -SHALL BE REFERENCED.
  
 C.PLEASE SEE THE ELECTRICAL PLAN REVIEWER COMMENT #3
 IN REFERENCE TO TITLE BLOCK INFORMATION.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-04-17 Cont ID  
Sent By mawillia Date 2007-04-17 Time 13:49 Rev Time 0.00
Received By mawillia Date 2007-04-17 Time 12:57 Sent To  
Notes
2007-04-17 13:14:16*****DENIED*****
  
  
 1.THE NUMERICAL ADDRESS OF WHERE THE SCOPE OF WORK
 WILL BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2.CLARIFY WHETHER THE SCOPE OF WORK IS FOR THE ENTIRE
 12TH FLOOR OR A PARTICULAR SUITE ON THAT FLOOR.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.PROVIDE A LAYOUT OF THE FIRE SPRINKLER SYSTEM FOR
 THIS SCOPE OF WORK.
  
  
 PLEASE BE ADVISED THAT POSITIVE RESPONSES TO OTHER PLAN
 REVIEW COMMENTS WILL FURTHER ASSIST IN THIS FIRE PLAN
 REVIEW
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-6722

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2008-06-17 Cont ID  
Sent By adarroug Date 2008-06-17 Time 16:43 Rev Time 0.00
Received By adarroug Date 2008-06-17 Time 16:43 Sent To E
Notes
2008-06-17 16:43:20TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2008-05-23 Cont ID  
Sent By adarroug Date 2008-05-23 Time 08:49 Rev Time 0.00
Received By adarroug Date 2008-05-23 Time 08:49 Sent To B
Notes
2008-05-23 08:49:45TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2008-05-22 Cont ID  
Sent By adarroug Date 2008-05-22 Time 10:59 Rev Time 0.00
Received By adarroug Date 2008-05-22 Time 10:59 Sent To E
Notes
2008-05-22 10:59:51TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2008-05-21 Cont ID  
Sent By adarroug Date 2008-05-21 Time 11:46 Rev Time 0.00
Received By adarroug Date 2008-05-21 Time 11:46 Sent To E
Notes
2008-05-21 11:46:28TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2008-05-21 Cont ID  
Sent By adarroug Date 2008-05-21 Time 10:31 Rev Time 0.00
Received By adarroug Date 2008-05-21 Time 10:30 Sent To FIRE
Notes
2008-05-21 10:31:22TO "F" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-05-02 Cont ID  
Sent By adarroug Date 2008-05-02 Time 10:15 Rev Time 0.00
Received By adarroug Date 2008-05-02 Time 10:15 Sent To B
Notes
2008-05-02 10:15:30TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-04-28 Cont ID  
Sent By adarroug Date 2008-04-28 Time 09:23 Rev Time 0.00
Received By adarroug Date 2008-04-28 Time 09:23 Sent To FIRE
Notes
2008-04-28 09:23:50TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-04-03 Cont ID  
Sent By adarroug Date 2008-04-03 Time 10:49 Rev Time 0.00
Received By adarroug Date 2008-04-03 Time 10:49 Sent To  
Notes
2008-04-03 10:50:33TO "COMM" BD#41--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-03-11 Cont ID  
Sent By adarroug Date 2008-03-11 Time 13:33 Rev Time 0.00
Received By adarroug Date 2008-03-11 Time 13:33 Sent To E
Notes
2008-03-11 13:34:04TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-02-19 Cont ID  
Sent By adarroug Date 2008-02-19 Time 10:00 Rev Time 0.00
Received By adarroug Date 2008-02-19 Time 10:00 Sent To M
Notes
2008-02-19 10:00:41TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-02-01 Cont ID  
Sent By adarroug Date 2008-02-01 Time 09:13 Rev Time 0.00
Received By adarroug Date 2008-02-01 Time 09:13 Sent To M
Notes
2008-02-01 09:14:33TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-01-23 Cont ID  
Sent By adarroug Date 2008-01-23 Time 12:41 Rev Time 0.00
Received By adarroug Date 2008-01-23 Time 12:41 Sent To M
Notes
2008-01-23 12:41:33TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-01-04 Cont ID  
Sent By adarroug Date 2008-01-04 Time 14:42 Rev Time 0.00
Received By adarroug Date 2008-01-04 Time 14:42 Sent To M
Notes
2008-01-04 14:42:49TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-11-28 Cont ID  
Sent By adarroug Date 2007-11-28 Time 10:21 Rev Time 0.00
Received By adarroug Date 2007-11-28 Time 10:21 Sent To  
Notes
2007-11-29 11:30:03TO "COMM" BD#18
2007-11-28 10:21:57WAITING FOR "COMM" BD--EXPEDITED--

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-11-09 Cont ID  
Sent By adarroug Date 2007-11-09 Time 16:59 Rev Time 0.00
Received By adarroug Date 2007-11-09 Time 16:59 Sent To E
Notes
2007-11-09 16:59:46TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-10-24 Cont ID  
Sent By adarroug Date 2007-10-24 Time 14:51 Rev Time 0.00
Received By adarroug Date 2007-10-24 Time 14:51 Sent To  
Notes
2007-11-05 14:52:12TO "COMM" BD#60

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-08-30 Cont ID  
Sent By adarroug Date 2007-08-30 Time 12:54 Rev Time 0.00
Received By adarroug Date 2007-08-30 Time 12:54 Sent To  
Notes
2007-09-14 11:49:57TO "COMM" BD#48--EXPEDITED PERMIT--
2007-08-30 12:55:01WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-06-12 Cont ID  
Sent By adarroug Date 2007-06-12 Time 14:04 Rev Time 0.00
Received By adarroug Date 2007-06-12 Time 14:04 Sent To  
Notes
2007-06-26 09:11:54TO "COMM" BD#50/PLANS ON RACK--2 ROLLS AND BINDERS
2007-06-12 14:04:19WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-17 Cont ID  
Sent By mawillia Date 2007-04-17 Time 12:57 Rev Time 0.00
Received By mawillia Date 2007-03-09 Time 14:29 Sent To  
Notes
2007-03-09 14:29:44TO "COMM" BD#60

Review Stop M MECHANICAL (A/C)
Rev No 11 Status P Date 2008-04-11 Cont ID  
Sent By rregueir Date 2008-04-11 Time 15:46 Rev Time 0.00
Received By rregueir Date 2008-04-11 Time 15:38 Sent To PC
Notes
2008-04-11 15:51:49REVISIONS H-0.1 AND H-1.1 REV 5 "AS-BUILT" 3/27/08

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2008-04-09 Cont ID  
Sent By rregueir Date 2008-04-09 Time 15:06 Rev Time 0.00
Received By rregueir Date 2008-04-09 Time 15:06 Sent To PC
Notes
2008-04-09 15:06:43PG H-1.1 "AS-BUILT" REVISION DATED 2/14/08

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2008-04-09 Cont ID  
Sent By rregueir Date 2008-04-09 Time 15:05 Rev Time 0.00
Received By rregueir Date 2008-04-09 Time 15:04 Sent To PC
Notes
2008-04-09 15:05:53PG H-1.1 "AS-BUILT" REVISION DATED 2/1/08

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2008-04-09 Cont ID  
Sent By rregueir Date 2008-04-09 Time 15:04 Rev Time 0.00
Received By rregueir Date 2008-02-25 Time 14:09 Sent To PC
Notes
2008-04-09 15:04:40PG H-1.1 "AS BUILT" REVISION DATED 1/22/08
2008-02-25 15:03:30REVISION REVIEW ON HOLD PENDING MEETING WITH JESSE
 CARTLIDGE. A CONSOLIDATION OF REVISIONS IS NEEDED PRIOR
 TO REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-01-23 Cont ID  
Sent By rregueir Date 2008-01-23 Time 09:47 Rev Time 0.00
Received By rregueir Date 2008-01-22 Time 11:34 Sent To PC
Notes
2008-01-23 09:47:35REV 7 INCORPORATING REV 4, 5 AND 6.
 REVIEW COMMENT FROM REV 4 DATED 11/30/07 HAVE BEEN
 ADDRESSED AS PART OF THIS REVISION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2007-11-30 Cont ID  
Sent By rregueir Date 2007-11-30 Time 15:08 Rev Time 0.00
Received By rregueir Date 2007-11-30 Time 15:03 Sent To E
Notes
2007-11-30 15:08:52THE FOLLOWING PAGES WERE DENIED WITH COMMENTS:
 H-1.1 REV.4
  
 COMMENT: PG A03.12 SHOWS THE WALLS WHICH FORM ROOM
 1296A ARE TYPE 132S. PG A14.10 SHOWS WALL TYPE TO BE
 1-HOUR RATED FROM FLOOR TO UNDERSIDE OF DECK. THEREFORE
 THE NEW SUPPLY, TRANDFER AND EXHAUST PENETRATIONS OF
 THESE WALLS SHALL HAVE OPENING PROTECTIVES IN
 ACCORDANCE WITH FBC, M 607.5. SHOW THESE PENETRATIONS
 TO BE PROTECTED IN ACCORDANCE WITH THIS SECTION AND
 RESUBMIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-11-30 Cont ID  
Sent By rregueir Date 2007-11-30 Time 15:03 Rev Time 0.00
Received By rregueir Date 2007-11-30 Time 13:46 Sent To E
Notes
2007-11-30 15:03:09THE FOLLOWING PAGES WERE PASSED:
 H-0.1 REV.4
 H-3.1 REV.2

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-11-03 Cont ID  
Sent By rregueir Date 2007-11-03 Time 17:01 Rev Time 0.00
Received By rregueir Date 2007-11-03 Time 16:39 Sent To  
Notes
2007-11-03 17:01:27***************PROVISO*****************
 PROVIDE THE PRINTED NAME OF THE ENGINEER OF RECORD,
 WHICH IS REQUIRED ON SIGNED AND SEALED PLANS IN
 ACCORDANCE WITH FAC 61G15-23.002.
  
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-09-17 Cont ID  
Sent By rregueir Date 2007-09-17 Time 17:05 Rev Time 0.00
Received By rregueir Date 2007-09-17 Time 16:29 Sent To  
Notes
2007-09-17 17:05:07REVIEW #:
 ACTION:
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 PREVIOUS REVIEW COMMENTS HAVE BEEN ADEQUATELY
 ADDRESSED.
  
 PLEASE ADDRESS THE FOLLOWIN NEW COMMENTS UPON
 RESUBMITTAL:
  
 1. IF THIS JOB IS TO UTILIZE A RESIDENT INSPECTOR, AS
 INDICATED BY THE LETTER FROM DAN PETROCCHI WHICH WAS
 INCLUDED WITH REVIEW COMMENT RESPONSES, A MINIMUM OF
 THREE COPIES OF ALL PLANS, SPECS, SUBMITTALS AND
 DOCUMENTATION SHALL BE PROVIDED IN ACCORDANCE WITH THE
 CITY OF WEST PALM BEACH RESIDENT AND SPECIAL INSPECTOR
 GUIDELINES AND POLICIES.
  
 2. SERVER ROOM 1222, PG H-1.1 SHOWS TWO DUCTS ENTERING
 ROOM WITH FIRE DAMPERS AS OPENING PROTECTIVES. PG
 A03.12 SHOWS THE WALLS TO TIS ROOM AS TYPE "032S" WHICH
 IS NOT A RATED WALL ASSEMBLY ACCORDING TO THE PARTITION
 TYPES SHOWN ON A14.10. FIRE DAMPERS CAN ONLY BE
 INSTALLED IN ACCORDANCE WITH THEIR LISTING AS REQUIRED
 BY FBC,M 607.2 IF THEY ARE INSTALLED WITHIN FIRE-RATED
 CONSTRUCTION. PLEASE COORDINATE ARCHITECTURAL PLANS AND
 MECHANICAL PLANS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-07-11 Cont ID  
Sent By rregueir Date 2007-07-11 Time 16:42 Rev Time 0.00
Received By rregueir Date 2007-07-11 Time 14:31 Sent To  
Notes
2007-07-11 16:41:58----------------DENIED------------------
  
 ALL TECHNICAL ASPECTS OF PREVIOUS REVIEW COMMENTS HAVE
 BEEN SATISFIED. HOWEVER, THE ENGINEER OF RECORD HAS NOT
 SIGNED, SEALED, DATED AND LEGIBLY PRINTED HIS/HER NAME
 ON EACH SHEET OF THE MECHANICAL PLANS AS REQUIRED BY
 FAC RULE 61G15-23.002. THE RELEVANT SECTION IS PROVIDED
 FOR YOU BELOW:
  
 "(2) EACH SHEET OF PLANS AND PRINTS WHICH MUST BE
 SEALED UNDER THE PROVISIONS OF CHAPTER 471, F.S., SHALL
 BE SEALED, SIGNED AND DATED BY THE PROFESSIONAL
 ENGINEER IN RESPONSIBLE CHARGE. ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON
 EACH SHEET. IF PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME AND LICENSE NUMBER, AS WELL AS, THE NAME,
 ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET. A TITLE BLOCK ON
 EACH SHEET CONTAINING THE PRINTED NAME, ADDRESS, AND
 LICENSE NUMBER OF THE ENGINEER OR IF APPLICABLE, THE
 NAME AND LICENSE NUMBER OF THE ENGINEER, AND THE NAME,
 ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT."
  
 PLEASE PROVIDE ALL THE REQUIREMENTS OF THE ABOVE
 SECTION ON EACH SHEET OF PLANS.
  
 ALSO, THE OWNER AGENT HAS NOT SIGNED IN THE PLACE
 INDICATED ON THE CODE COMPLIANCE CERTIFICATION PAGE OF
 THE ENERGY CALCULATIONS. PLEASE CORRECT AND RESUBMIT
 PER FBC 13-103.1.2.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-22 Cont ID  
Sent By rregueir Date 2007-03-22 Time 14:41 Rev Time 0.00
Received By rregueir Date 2007-03-20 Time 14:44 Sent To  
Notes
2007-03-22 14:41:38----------------DENIED------------------
  
 FBC 2004 W/2006 AMENDMENTS
 FBC,M 2004
 FBC CHAPTER 1 W/LOCALLY ADOPTED AMENDMENTS
  
 1. PG H-1.1: NOTE 2 STATES MAXIMUM LENGTH OF FLEX DUCT
 AT 7'. DETAIL 6 ON PG H-0.2 SHOWS THE MAX. LENGTH AT
 5'. DETAIL 4 ON PAGE H-0.2 SHOWS A MAX. LENGTH OF 3'.
 PLEASE CLARIFY. FBC 106.1.1.
  
 2. PG H-0.3: DETAIL 4, FIRE DAMPERS ARE TO BE INSTALLED
 IN ACCORDANCE WITH THEIR LISTING AND MANUFACTURER'S
 INSTALLATION INSTRUCTIONS PER FBC,M 607.2. THE
 INSTRUCTIONS ARE REQUIRED IN FIELD FOR INSPECTION.
  
 3. PG H-1.1 NOTE AT BOTTOM OF PAGE FOR PLENUMS, PLEASE
 REFERENCE FBC 2004 AND FBC,M 2004. CORRECT AND
 RESUBMIT.
  
 4. PG H-1.1 NOTE 3: REFERENCES HP-5-1. THIS UNIT IS NOT
 ON THE EQUIPMENT SCHEDULE AND DOES NOT APPEAR ON PLANS.
 PLEASE CLARIFY PER FBC 106.1.1.
  
 5. PG H-1.1 FPT-12-11 IS NOT SHOWN AS BEING CONNECTED
 TO ANY DUCT ON THE DISCHARGE SIDE. PLEASE CORRECT AND
 RESUBMIT.
  
 6. PG H1.1: ROOM 1206, FED BY FPT-12-3 IS MISSING THE
 DIFFUSER TYPE AND CFM TO BE SUPPLIED TO THIS SPACE.
 PLEASE CORRECT AND RESUBMIT.
  
 7. PG H-1.1 SHOWS FPT-12-5 PROVIDING 840 CFM OF SUPPLY
 AIR AT DIFFUSERS. EQUIPMENT SCHEDULE SHOWS FPT-12-5
 WITH A MAXIMUM OF 830 CFM. PLEASE CLARIFY PER FBC
 106.1.1.
  
 8. PG H-0.1 VAV TERMINAL SCHEDULE: THE MAXIMUM AND
 MINIMUM CFM APPEAR TO HAVE BEEN REVERSED. PLEASE
 CORRECT AND RESUBMIT.
  
 9. PG H-1.1 ROOM 1259 SHOWS ONE DIFFUSER BUT IS LABELED
 FOR TWO. IS THIS ROOM TO GET 140 OR 280 CFM?
  
 10. PG H-3.1 NOTE IV-A: PLEASE PROVIDE SUBMITTAL DATA
 SHOWING THE PLASTIC LABELS AS SPECIFIED MEET THE 25/50
 REQUIREMENTS OF FBC,M 602.2.1. IF NOT, PLEASE SUBMIT AN
 ALTERNATE METHOD OF LABELING THAT CONFORMS TO THE
 REQUIREMENTS OF THIS SECTION.
  
 11. PLEASE SUBMIT TWO COMPLETE SETS OF PLANS, EACH SET
 BOUND TOGETHER WITHOUT LOOSE SHEETS TO FACILITATE THE
 PROPER EXAMINATION OF DOCUMENTS AS REQUIRED UNDER FBC
 106.1.
  
 12. ENERGY CALCULATIONS ARE TO BE SIGNED AND SEALED BY
 A FLORIDA LICENSED ARCHITECT OR ENGINEER PER FBC
 13-103.1.1.1.
  
 13. PLEASE NOTE THAT THE ENGINEER'S SEAL ON THE MEP
 DRAWINGS IS OUT OF DATE AND NO LONGER VALID PER FAC 61G
 15-23.001
  
 PLEASE FEEL FREE TO CONTACY ME OF YOU HAVE ANY
 QUESTIONS.
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-11-06 Cont ID  
Sent By kstevens Date 2007-11-06 Time 12:06 Rev Time 0.00
Received By kstevens Date 2007-11-06 Time 12:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2007-09-19 Cont ID  
Sent By kstevens Date 2007-09-19 Time 09:55 Rev Time 0.00
Received By kstevens Date 2007-09-19 Time 09:55 Sent To  
Notes
2007-09-19 10:15:13DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WEST PALM BEACH MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW****
 ******FROM PREVIOUS REVIEWS******
  
 1. OK
 2. OK
 3. OK
  
 4. ALL ARCHITECTURAL SHEET SHALL BE SEALED BY AN
 IMPRESSION TYPE SEAL THAT SHALL IMPRESS ALL INFORMATION
 REQUIRED BY FAC 61G1-16.002 ON EACH SHEET. FAC
 61G1-16.001 AND FS 481.2055.
 ****RESPONSE NOTED, BUT PER FAC 61G1-16.003 &
 61G1-16.004(5) THE DATE THE SEAL & SIGNATURE ARE
 AFFIXED TO THE PLANS SHALL BE INDICATED BELOW THE
 SIGNATURE. FS 481.2055.
 ******RESPONSE NOTED, BUT NEW SHEETS WERE SUBMITTED AND
 NOW NOT ALL THE INFORMATION REQUIRED WHEN SEALING THE
 PLANS HAS BEEN IMPRESSED ON THE PLANS. SEE THE ORIGINAL
 PLANS SUBMITTED. WHEN SEALING THE PLANS, MAKE SURE ALL
 INFORMATION REQUIRED TO BE ON THE SEAL IS IMPRESSED ON
 TO THE PLANS.
  
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. SHT P1.1 SHOWS TWO ADDED DRINKING FOUNTAINS NOT
 SHOWN ON THE FLOOR PLAN, (A-03.12). PLEASE CORRELATE
 INFORMATION BETWEEN THE ARCHITECTURAL SHEETS AND THE
 PLUMBING SHEETS. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT ONLY ONE DRINKING FOUNTAIN IS
 SHOWN ON THE ARCHITECTURAL SHEETS.
 ******RESPONSE NOTED, BUT THE LOCATION OF THE DRINKING
 FOUNTAIN THAT HAS BEEN MOVED IS STILL NOT SHOWN ON THE
 ARCHITECTURAL SHEETS. PLEASE CORRELATE THE INFORMATION
 BETWEEN THE ARCHITECTURAL SHEETS AND THE PLUMBING
 SHEETS.
  
 OK
 11. OK
 12. OK
 **********NEW COMMENT**********
  
 1B. OK
  
 **********NEW COMMENT**********
  
 1C. THE SHELL BUILDING HAS NOT ACHIEVED A CERTIFICATE
 OF COMPLETION, THE PLANS SUBMITTED FOR THE TENANT
 BUILDOUT SHALL BE REVIEWED BY THE DESIGN TEAMS OF THE
 BASE BUILDING AND THE BASE BUILDING DESIGN
 PROFESSIONALS SHALL INDICATE APPROVAL OF THE TENANT
 BUILDOUT PLANS WITH A "SHOP PLANS" TYPE APPROVAL STAMP
 ON EACH SHEET OF THE BUILDOUT PLANS.
  
 2C. SINCE THIS IS A THRESHOLD INSPECTOR JOB, THREE SETS
 OF SIGNED, SEALED, DATED PLANS AND DOCUMENTS SHALL BE
 SUBMITTED FOR REVIEW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-07-14 Cont ID  
Sent By kstevens Date 2007-07-14 Time 11:15 Rev Time 0.00
Received By kstevens Date 2007-07-14 Time 09:43 Sent To  
Notes
2007-07-14 11:15:07DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WEST PALM BEACH MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW****
  
 1. OK
 2. OK
 3. OK
  
 4. ALL ARCHITECTURAL SHEET SHALL BE SEALED BY AN
 IMPRESSION TYPE SEAL THAT SHALL IMPRESS ALL INFORMATION
 REQUIRED BY FAC 61G1-16.002 ON EACH SHEET. FAC
 61G1-16.001 AND FS 481.2055.
 ****RESPONSE NOTED, BUT PER FAC 61G1-16.003 &
 61G1-16.004(5) THE DATE THE SEAL & SIGNATURE ARE
 AFFIXED TO THE PLANS SHALL BE INDICATED BELOW THE
 SIGNATURE. FS 481.2055.
  
 5. SHT A13.01 ALL 4 SINKS SHALL BE ACCESSIBLE. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 NOTE: CLEAR FLOOR SPACE SHALL BE FORWARD APPROACH AND
 EXTEND A MAXIMUM 19" UNDERNEATH THE SINK. CABINET DOORS
 ARE NOT APPROVED IN THE CLEAR FLOOR SPACE AND SHALL BE
 DELETED FROM THE DETAILS FOR EACH SINK. ****RESPONSE
 NOTED, BUT DETAIL #11 DOES NOT INDICATE THE WIDTH OF
 THE OPENING AND IT SCALES OUT LESS THAN THE REQUIRED
 30" WIDTH. SECTION 11-4.24.5. PLEASE CLARIFY.
  
 6. OK
 7. OK
  
 8. SHT H-0.3 DETAIL #3 A/C CONDENSATE TO THE FLOOR
 DRAIN IS NOT APPROVED TO THE SANITARY SEWER. MUNICIPAL
 CODE WWF, ART. III SEWERS AND SEWAGE DISPOSAL SECTION
 90-125(B)(5). CONDENSATE SHALL CONNECT TO A DEDICATED
 CONDENSATE LINE OR DISCHARGE SEPARATELY OUT OF THE
 BUILDING AND DRAIN INTO A CATCH BASIN, A STORM LINE OR
 A DRYWELL.
 ****RESPONSE NOTED, BUT THE CONDENSATE SHALL NOT
 CONNECT TO THE STORM. CONDENSATE SHALL CONNECT TO
 CONDENSATE AS INDICATED.
  
 9. SHT P1.1 SHOWS TWO ADDED DRINKING FOUNTAINS NOT
 SHOWN ON THE FLOOR PLAN, (A-03.12). PLEASE CORRELATE
 INFORMATION BETWEEN THE ARCHITECTURAL SHEETS AND THE
 PLUMBING SHEETS. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT ONLY ONE DRINKING FOUNTAIN IS
 SHOWN ON THE ARCHITECTURAL SHEETS.
  
 10. SUBMIT ISOMETRIC RISER DIAGRAMS FOR THE WATER, DWV,
 AND CONDENSATE. SHOW ALL PIPE SIZES, VALVES & WATER
 HAMMER ARRESTORS, (REQUIRED BY SECTION 604.9), ON THE
 WATER RISER DIATRAM. SHOW ALL PIPE SIZES TRAPS AND
 VENTS FOR THE DWV. SHOW THE PIPE SIZE AND THE
 TERMINATION POINT FOR THE CONDENSATE. INDICATE THE
 LOCATION OF THE POINT OF CONNECTION FOR THE WATER AND
 THE SANITARY. SECTION 106.3.5.1.3((3)(4)(6)(19)(13).
 ****RESPONSE NOTED, BUT NO WATER HAMMER ARRESTORS WERE
 SHOWN. (DISH WASHERS, ICE MAKER REQUIRE WHA'S).
  
 11. OK
 12. OK
  
 **********NEW COMMENT**********
  
 1B. THREE COPIES OF SHT P0.2 HAVE BEEN SUBMITTED WITH
 THE PLANS FOR THIS PERMIT APPLICATION. IT APPEARS TO
 HAVE A REVISION TO THE BASE BUILDING INDICATED ON THE
 SHEETS AS WELL AS THE GAS PLANS FOR THE GENERATORS. THE
 PLANS SHALL BE SUBMITTED UNDER THE CORRECT PERMIT
 APPLICATION NUMBER AND WITH THE PLANS FOR THOSE
 APPLICATION NUMBERS. THE BUILD-OUT FOR THE 12TH FLOOR
 IS NOT THE CORRECT NUMBER TO SUBMIT THESE PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-04-07 Cont ID  
Sent By kstevens Date 2007-04-07 Time 15:46 Rev Time 0.00
Received By kstevens Date 2007-04-07 Time 15:46 Sent To  
Notes
2007-04-07 16:28:06DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 WEST PALM BEACH MUNICIPAL CODE
  
 1. ALL ARCHITECTURAL SHEETS THE BUSINESS LICENSE FOR
 JOVA/DANIELS/BUSBY INC IS SHOWN AS DELINQUENT. ( SEE
 ATTACHED SHEET ).
  
 2. PLANS SHALL BE SUBMITTED IN TWO COMPLETE BOUND SETS.
 LOOSE SHEETS ARE NOT APPROVED. SECTION 106.1.
  
 3. A00-00 PROJECT INFORMATION INDICATES THIS TO BE A 20
 STORY BUILDING. BUILDING WAS PERMITTED AS A 16 STORY.
 PLEASE CORRELATE INFORMATION. SECTION 106.1.1.
  
 4. ALL ARCHITECTURAL SHEET SHALL BE SEALED BY AN
 IMPRESSION TYPE SEAL THAT SHALL IMPRESS ALL INFORMATION
 REQUIRED BY FAC 61G1-16.002 ON EACH SHEET. FAC
 61G1-16.001 AND FS 481.2055.
  
 5. SHT A13.01 ALL 4 SINKS SHALL BE ACCESSIBLE. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 EXPOSED PIPES & SURFACES
 E. 11-4.24.6 FAUCETS
 NOTE: CLEAR FLOOR SPACE SHALL BE FORWARD APPROACH AND
 EXTEND A MAXIMUM 19" UNDERNEATH THE SINK. CABINET DOORS
 ARE NOT APPROVED IN THE CLEAR FLOOR SPACE AND SHALL BE
 DELETED FROM THE DETAILS FOR EACH SINK.
  
 6. SHT P-0.1 FLOOR DRAINS ARE NOT AN APPROVED INDIRECT
 WASTE RECEPTOR FOR THE WATER HEATER, NOR THE ICE MAKER.
 DETAIL #2 SHALL SHOW A FLOOR SINK OR A HUB DRAIN FOR
 THE INDIRECT WASTE. SECTIONS 802.1.1, 803.2, 802.3 &
 802.3.2.
  
 7. SHT P-0.1 PLUMBING GENERAL NOTES #3 CODE ADOPTED IS
 FBC-2004 WITH AMENDMENTS. SHOWN IN NOTE #3 IS THE 2000
 IPC. PLEASE CHANGE REFERENCE AND DESIGN TO THE CORRECT
 CODE.
  
 8. SHT H-0.3 DETAIL #3 A/C CONDENSATE TO THE FLOOR
 DRAIN IS NOT APPROVED TO THE SANITARY SEWER. MUNICIPAL
 CODE WWF, ART. III SEWERS AND SEWAGE DISPOSAL SECTION
 90-125(B)(5). CONDENSATE SHALL CONNECT TO A DEDICATED
 CONDENSATE LINE OR DISCHARGE SEPARATELY OUT OF THE
 BUILDING AND DRAIN INTO A CATCH BASIN, A STORM LINE OR
 A DRYWELL.
  
 9. SHT P1.1 SHOWS TWO ADDED DRINKING FOUNTAINS NOT
 SHOWN ON THE FLOOR PLAN, (A-03.12). PLEASE CORRELATE
 INFORMATION BETWEEN THE ARCHITECTURAL SHEETS AND THE
 PLUMBING SHEETS. SECTION 106.1.1.
  
 10. SUBMIT ISOMETRIC RISER DIAGRAMS FOR THE WATER, DWV,
 AND CONDENSATE. SHOW ALL PIPE SIZES, VALVES & WATER
 HAMMER ARRESTORS, (REQUIRED BY SECTION 604.9), ON THE
 WATER RISER DIATRAM. SHOW ALL PIPE SIZES TRAPS AND
 VENTS FOR THE DWV. SHOW THE PIPE SIZE AND THE
 TERMINATION POINT FOR THE CONDENSATE. INDICATE THE
 LOCATION OF THE POINT OF CONNECTION FOR THE WATER AND
 THE SANITARY. SECTION 106.3.5.1.3((3)(4)(6)(19)(13).
  
 11. SUBMIT A DETAIL FOR THE ACCESSIBLE DRINKING
 FOUNTAIN. SHOW COMPLIANCE WITH SECTION 11-4.15 AND ALL
 SUBSECTIONS.
  
 12. AHA CONSULTING ENGINEERS SHALL INDICATE THE
 CERTIFICATE OF AUTHORIZATION NUMBER IN THE TITLE BLOCK.
 FAC 61G15-23.002(2) & FS 471.025. CA NUMBER 56959
 WRITTEN IN UNDER THE SEAL DOES NOT INDICATE AS A CA
 NUMBER FOR THE ENGINEERING FIRM. PLEASE CLARIFY.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-31 Cont ID  
Sent By pschmitz Date 2007-03-31 Time 12:42 Rev Time 0.00
Received By pschmitz Date 2007-03-31 Time 12:42 Sent To  
Notes
2007-03-31 13:32:36PAUL SCHMITZ
 [email protected] FBC 2004 PLUMBING
 CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
  
 DENIED
  
 1) SHT P-0.1WATER HEATER DETAIL (2)
 ICE MACHINE, I/W NOT APPROVED TO FLOOR DRAIN. 802.1.1
 FOOD HANDLING.
 EQUIPMENT AND FIXTURES UTILIZED FOR THE STORAGE,
 PREPARATION AND HANDLING OF FOOD SHALL DISCHARGE
 THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP.
  
 2)SHT H-0.3 DETAIL(3)A/C CONDENSATE TO FLOOR DRAIN
 NOT APPROVED TO SANITARY SEWER.
 WWF, ART.III SEWERS AND SEWAGE DISPOSAL, SEC. 90-125.
 (B) (5) A/C CONDENSATE TOTO SANITARY SEWER.
  
 3)SHT P-1.1 SHOWS TWOADDED DRINKING FOUNTAINS,
 PLEASE CORROLATE WITH, SHT A03.12, RM 1286B, DOES NOT
 SHOW A DRINKING FOUNTAIN.
  
 4) SHTA03.12 SHOWS FOUR BREAK ROOMS #
 1282,1284,1205,1256A. TO COMPLY WITH SEC 11-4.24
 11-4.24 SINKS.
 11-4.24.1 GENERAL.
 SINKS REQUIRED TO BE ACCESSIBLE BY SECTION 11-4.1 SHALL
 COMPLY WITH SECTION 11-4.24.
 11-4.24.2 HEIGHT.
 SINKS SHALL BE MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34 INCHES (865 MM) ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE.
 KNEE CLEARANCE THAT IS AT LEAST 27 INCHES (685 MM)
 HIGH, 30 INCHES (760 MM) WIDE, AND 19 INCHES (485 MM)
 DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.4 DEPTH.
 EACH SINK SHALL BE A MAXIMUM OF 6? INCHES (165 MM)
 DEEP.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK (SEE FIGURE 32).
 11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED UNDER SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT. THERE SHALL BE NO SHARP OR ABRASIVE
 SURFACES UNDER SINKS.
 11-4.24.7 FAUCETS.
 FAUCETS SHALL COMPLY WITH SECTION 11-4.27.4.
 LEVER-OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS ARE ACCEPTABLE
 DESIGNS.
 11-4.25 STORAGE.
 11-4.25.1 GENERAL.
 FIXED STORAGE FACILITIES SUCH AS CABINETS, SHELVES,
 CLOSETS, AND DRAWERS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION 11-4.25.
 11-4.25.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 THAT ALLOWS EITHER A FORWARD OR PARALLEL APPROACH BY A
 PERSON USING A WHEELCHAIR SHALL BE PROVIDED AT
 ACCESSIBLE STORAGE FACILITIES.
 11-4.25.3 HEIGHT.
 ACCESSIBLE STORAGE SPACES SHALL BE WITHIN AT LEAST ONE
 OF THE REACH RANGES SPECIFIED IN SECTION 11-4.2.5 AND
 11-4.2.6 (SEE FIGURE 5 AND FIGURE 6). CLOTHES RODS OR
 SHELVES SHALL BE A MAXIMUM OF 54 INCHES (1370 MM) ABOVE
 THE FINISH FLOOR FOR A SIDE APPROACH. WHERE THE
 DISTANCE FROM THE WHEELCHAIR TO THE CLOTHES ROD OR
 SHELF EXCEEDS 10 INCHES (255 MM) (AS IN CLOSETS WITHOUT
 ACCESSIBLE DOORS) THE HEIGHT AND DEPTH TO THE ROD OR
 SHELF SHALL COMPLY WITH FIGURE 38(A) AND FIGURE 38(B).
 11-4.25.4 HARDWARE.
 HARDWARE FOR ACCESSIBLE STORAGE FACILITIES SHALL COMPLY
 WITH SECTION 11-4.27.4. TOUCH LATCHES AND U-SHAPED
 PULLS ARE ACCEPTABLE.
  
 5) PLAN REVIEW IN PROGRESS,