Plan Review Details - Permit 07030272
Plan Review Stops For Permit 07030272
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-04-13 Cont ID  
Sent By mjacobs Date 2007-04-13 Time 08:43 Rev Time 0.00
Received By mjacobs Date 2007-04-13 Time 07:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-15 Cont ID  
Sent By mjacobs Date 2007-03-15 Time 07:44 Rev Time 0.00
Received By mjacobs Date 2007-03-15 Time 06:29 Sent To  
Notes
2007-03-15 07:43:00 
  
 BUILDING PLAN REVIEW
 PERMIT:07030272
 ADD:1611 WORTHINGTON ROAD
 CONT: RANCO CONST CORP.
 TEL: (954)920-3350
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 3)61G15-23.002(2)EACH SHEET OF PLANS AND PRINTS
 WHICH MUST BE SEALED UNDER THE PROVISIONS OF CHAPTER
 471, F.S., SHALL BE SEALED, SIGNED AND DATED BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. ENGINEERS
 SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS, AND LICENSE
 NUMBER ON EACH SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION
 NUMBER OF THE ENGINEERING BUSINESS ON EACH SHEET.
  
 4)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-04-10 Cont ID  
Sent By dpalmer Date 2007-04-10 Time 12:49 Rev Time 0.00
Received By dpalmer Date 2007-04-10 Time 12:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-09 Cont ID  
Sent By dpalmer Date 2007-03-09 Time 07:03 Rev Time 0.00
Received By dpalmer Date 2007-03-08 Time 16:55 Sent To  
Notes
2007-03-09 07:03:59** UNSAT **
  
 1) NOTE: PLEASE SEE THAT ONLY ONE SET OF PLANS
 SUBMITTED IS SIGNED, DATED AND SEALED BY THE ENGINEER.
 THE OTHER SHEET DOES CONTAIN A RAISED SEAL BUT THAT IS
 IT. FS 471.025, FAC 61G15-23.002
 PLEASE ALSO SEE THAT ALL OF THE SHEETS BY THE ARCHITECT
 ARE NOT DATED WHEN SIGNED AND SEALED AS REQUIRED.
 FS 481.221
  
 PLEASE KNOW THE ABOVE IS REQUIRED WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADES
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-04-13 Cont ID  
Sent By mwennerg Date 2007-04-13 Time 10:08 Rev Time 0.00
Received By mwennerg Date 2007-04-13 Time 10:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-20 Cont ID  
Sent By mawillia Date 2007-03-20 Time 13:31 Rev Time 0.00
Received By mawillia Date 2007-03-20 Time 12:54 Sent To  
Notes
2007-03-20 13:30:58*****UUNSAT*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.PLEASE INDICATE IF THE BUILDING OR POTIONS OF THE
 BUILDING WILL BE OCCUPIED DURING THE SCOPE OF WORK.IF
 SO, THIS WILL BE PERMITTED ONLY WHERE REQUIRED MEANS OF
 EGRESS AND REQUIRED FIRE PROTECTION FEATURES ARE
 INPLACE AND MAINTAINED.
  
 4.BE SPECIFIC IN INDICATING THE WALL AND CEILING
 CLASSIFICATION FOR THE SCOPE OF WORK BEING PROPOSED.
 PLEASE BE ADVISED THAT CLASS A OR CLASS BARE REQUIRED
 IN EXITS AND EXIT ACCESS CORRIDORS, AND CLASS A, CLASS
 B, OR CLASS C IN ALL OTHER AREAS.
  
 5.WILL THE SCOPE OF WORK CAUSE THE LOCATION OF FIRE
 SPRINKLER HEADS/DEVICES (IF SO EQUIPPED) TO BE
 MODIFIED?IF SO, SEPARATE PERMIT AND SHOP DRAWINGS
 WILL BE REQUIRED FOR THE FIRE SPRINKLER REMODEL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A REQPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-10 Cont ID  
Sent By adarroug Date 2007-04-10 Time 09:21 Rev Time 0.00
Received By adarroug Date 2007-04-10 Time 09:21 Sent To  
Notes
2007-04-10 09:21:55TO "BOB"#3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-20 Cont ID  
Sent By mawillia Date 2007-03-20 Time 12:55 Rev Time 0.00
Received By mawillia Date 2007-03-08 Time 13:39 Sent To  
Notes
2007-03-08 13:43:13TO "BOB"#8

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-04-10 Cont ID  
Sent By tgordon Date 2007-04-10 Time 14:09 Rev Time 0.30
Received By tgordon Date 2007-04-10 Time 14:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-13 Cont ID  
Sent By tgordon Date 2007-03-13 Time 14:15 Rev Time 0.30
Received By tgordon Date 2007-03-13 Time 14:15 Sent To  
Notes
2007-03-13 14:21:30*** DENIED ***
 1) INFORMATION MISSING FROM TITLE BLOCK ON PAGE M-1.
 SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.