Plan Review Details - Permit 07030267
Plan Review Stops For Permit 07030267
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2007-05-08 Cont ID  
Sent By shill Date 2007-05-08 Time 15:50 Rev Time 0.00
Received By shill Date 2007-05-08 Time 15:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-05-08 Cont ID  
Sent By shill Date 2007-05-08 Time 15:27 Rev Time 0.00
Received By shill Date 2007-05-08 Time 15:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-04-21 Cont ID  
Sent By shill Date 2007-04-21 Time 15:19 Rev Time 0.00
Received By shill Date 2007-04-21 Time 15:19 Sent To  
Notes
2007-04-21 15:20:08****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)CONTRACTOR SPECIFIES 6INCH SPACING ON THE
 INSTALLATION SCHEDULE, BUT HAS CIRCLED 3INCH.3INCH
 REQUIRED FOR THE SHUTTER WHICH WAS CIRCLED ON THE
 PRODUCT APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-04-16 Cont ID  
Sent By shill Date 2007-04-16 Time 12:33 Rev Time 0.00
Received By shill Date 2007-04-16 Time 12:33 Sent To  
Notes
2007-04-16 12:34:06****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)PROVIDE THE BUILDING HEIGHT.THE PLAN STATES
 >60FEET.THIS DOES NOT PROVIDE ENOUGH INFORMATION TO
 DETERMINE CODE COMPLIANCE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-04-03 Cont ID  
Sent By shill Date 2007-04-03 Time 10:21 Rev Time 0.00
Received By shill Date 2007-04-03 Time 10:21 Sent To  
Notes
2007-04-03 10:22:07****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY
 OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 ____1.A NOTICE OF COMMENCEMENT MUST BE FILED WITH
 THE CLERK OF COURTS BEFORE A PERMIT CAN BE ISSUED,
 FS713.13.
  
 _XX_2.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A
 DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ENGINEER
 AND SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED SEALED
 ORIGINALS FAC61G15-23.002. YOU ARE DESIGNING TO A
 PRESSURE OF APPROX -47 PSF ON A HIGH RISE.THE
 ENGINEERING IN THE PACKAGE IS A PHOTOCOPY.
  
 ____3.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_4.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.
  
 ____5.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 ____6.ON THE PRODUCT APPROVAL, MARK WHICH DETAILS
 APPLY TO THIS JOB.PLEASE USE INK RATHER THAN A
 HIGHLIGHTER.
  
 ____7.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC
 R310.
  
 ____8.PROVIDE A FLOOR PLAN SHOWING WHERE THE
 SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH
 CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 4
 ABOVE.
  
 ____9.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2),
 FBC R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE
 C HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC
 R301.2.1.4.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-24 Cont ID  
Sent By shill Date 2007-03-24 Time 12:22 Rev Time 0.00
Received By shill Date 2007-03-24 Time 12:22 Sent To  
Notes
2007-03-24 12:23:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)YOU HAVE SPECIFIED -126 AS THE DESIGN PRESSURE,
 BUT HAVE SPECIFIED ANCHOR SPACING FOR -47.2.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-05-04 Cont ID  
Sent By adarroug Date 2007-05-04 Time 14:57 Rev Time 0.00
Received By adarroug Date 2007-05-04 Time 14:57 Sent To B
Notes
2007-05-04 14:57:36TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-18 Cont ID  
Sent By adarroug Date 2007-04-18 Time 14:30 Rev Time 0.00
Received By adarroug Date 2007-04-18 Time 14:30 Sent To B
Notes
2007-04-18 14:31:09TO "SHILL"DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-09 Cont ID  
Sent By adarroug Date 2007-04-09 Time 16:24 Rev Time 0.00
Received By adarroug Date 2007-04-09 Time 16:24 Sent To B
Notes
2007-04-09 16:24:51TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-02 Cont ID  
Sent By spalmer Date 2007-04-02 Time 14:12 Rev Time 0.00
Received By spalmer Date 2007-04-02 Time 14:12 Sent To B
Notes
2007-04-02 14:12:37TO SAMANTHA HILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-24 Cont ID  
Sent By shill Date 2007-03-24 Time 12:23 Rev Time 0.00
Received By shill Date 2007-03-08 Time 16:23 Sent To  
Notes
2007-03-08 16:24:02TO "MISC" BOX#1