Plan Review Details - Permit 07030261
Plan Review Stops For Permit 07030261
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-12-29 Cont ID  
Sent By mjacobs Date 2007-12-29 Time 07:08 Rev Time 0.00
Received By mjacobs Date 2007-12-29 Time 06:43 Sent To PC
Notes
2007-12-29 06:44:19PROCESS PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-12-24 Cont ID  
Sent By mjacobs Date 2007-12-24 Time 06:45 Rev Time 0.00
Received By mjacobs Date 2007-12-24 Time 06:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-06-16 Cont ID  
Sent By mjacobs Date 2007-06-16 Time 16:08 Rev Time 0.00
Received By mjacobs Date 2007-06-16 Time 14:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-19 Cont ID  
Sent By mjacobs Date 2007-03-15 Time 09:35 Rev Time 0.00
Received By mjacobs Date 2007-03-15 Time 07:48 Sent To  
Notes
2007-03-15 16:01:13BUILDING PLAN REVIEW
 PERMIT:07030261
 ADD: 5913 S.DIXIE HWY
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
 THIS INFORMATION IS REQUIRED TO DETERM THE WIDTH OF THE
 STAIRS. FBC 1005.1 THE TOTAL WIDTH OF MEANS OF EGRESS
 IN INCHES SHALL NOT BE LESS THAN THE TOTAL OCCUPANT
 LOAD SEVED BY THE MEANS OF EGRESS MULTIPLIED BY THE
 FACTORS IN TABLE 1005.1.
 FBC. 1004.1 IN DETERMINING MEANS OF EGRESS
 REQUIREMENTS,THE MUMBER OF OCCUPANTS FOR WHOM NEANS OF
 EGRESS FACILITIES SHALL BE PROVIDED SHALL BE
 ESTABLISHED BY THE LARGEST NUMBER COMPUTED IN
 ACCORDANCE WITH SECTIONS 1004.1 THROUGH 1004.1.3
  
 4)PROVIDE AN EXISTING AND PROPOSED FLOOR PLAN. SHOW
 THE MEANS OF EGRESS FOR THE SECOND FLOOR ON THE
 EXISTING FLOOR PLAN AND SHOW THE NEW SET OF STAIRS ON
 THE PROPOSED FLOOR PLAN.
  
 5)FBC.1007.1STAIRS REQUIRED TO BE ACCESSIBLE SHALL
 COMPLY WITH SECTIONS FBC 11-4.9
  
 6)FBC. 11-4.9.4STAIRWAYS SHALL HAVE HANDRAILS AT
 BOTH SIDES OF ALL STAIRS, HANDRAILS SHALL COMPLY WITH
 SEC. 11-4.26 AND FIG, 19A AND 19B. THEY SHALL EXTEND AT
 LEAST 12 INCHES BEYOND THE TOP RISER AND 12 INCHES PLUS
 THE WIDTH OF ONE TREAD BEYOND THE BOTTOM RISER.
  
 7)FBC. 11-4.13.6MINIMUM MANEUVERING CLEARANCE AT
 DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE
 AS SHOWN IN FIG. 25THE FLOOR OR GROUND AREA WITHIN
 THE REQUIRED CLARANCES SHALL BE LEVEL AND CLEAR.
  
 8)THE H/C BATH SHALL BE IN COMPLIANCE WITH FBC
 11-4.17.SHOW THE CLEAR FLOOR SPACE FOR THE TOILET
 STALL. SEE FIG 30A / 30E AND FIG 28 CH.11 FOR MORE
 INFORMATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-12-10 Cont ID  
Sent By dpalmer Date 2007-12-10 Time 08:51 Rev Time 0.00
Received By dpalmer Date 2007-12-10 Time 08:51 Sent To  
Notes
2007-12-10 08:53:11** NOTE ADDED,
  
 NO 2ND SET OF BUILDING SHEETS WERE SUBMITTED BACK ONLY
 ONE SET FO A-SHEETS WITH THE TWO SETS OF ELECTRICAL.
 SHEETS WERE NOT ATTACHED INTO TWO SETS WHICH WAS DONE
 BY THIS REVIEWER WITH THE SHEETS SUBMITTED.
2007-12-10 08:51:46**** PROVISO/ REVISION NEEDED ****
  
 1) NOTE: PLEASE SEE THE NOTE AS TYPEWRITTEN ON SHEET E1
 OF 2 WITH RESPECT TO MINIMUM LEVELS OF LIGHTING UNDER
 EMERGENCY CONDITIONS IS NOT STATED CORRECTLY AS PER
 CODE SECTION GIVEN.
 PLEASE SEE 7.8.1.3 WHICH REQUIRES 10FT CANDLES MINIMUM
 UNDER NORMAL LIGHTING CONDITIONS AND 7.9.2.2 WHICH
 PERMITS THE LEVELS TO GO DOWN TO 1FT CANDLE UNDER
 EMERGENCY CONDITIONS.
 THESE CODES ARE UNDER THE ADOPTED LIFE SAFETY CODE 101,
 2003.
 THE NOTE AS TYPED IS OF ANOTHER CODE SECTION WITH
 RESPECT TO THE POSSIBLE BURNING OUT OF THE EMERGENCY
 LIGHT FIXTURE(S).
  
  
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-18 Cont ID  
Sent By dpalmer Date 2007-06-18 Time 15:05 Rev Time 0.00
Received By dpalmer Date 2007-06-18 Time 14:43 Sent To  
Notes
2007-06-18 15:08:33 
  
 *** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE SOME COMMENTS FROM THE PREVIOUS ARE STILL
 IN NEED OF ADDRESSING.
 ** PLEASE KNOW AS NOT ALL INFORMATION NEEDED WAS
 SUBMITTED FOR A CODE COMPLIANT REVIEW THERE MAY BE NEW
 COMMENTS ON RE-SUBMITTAL OF PLANS.
  
 1) NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS REVIEW. A
 NOTE IS NOW PLACED ON PLANS WHICH STATES TWO WAYS OF
 CIRCUITING EMERGENCY LIGHTS WHICH IS NOT PERMITTED.
 PLEASE SEE 700.12F AS THE EM LTS MUST BE CIRCUITED TO
 THE LOCAL LIGHTING BRANCH CIRCUIT IN THAT AREA.
 PLEASE ALSO SEE MISSING LIGHTING PHOTO-METRICS UNDER
 NORMAL AND UNDER EMERGENCY AS PREVIOUSLY REQUESTED.
 PLEASE SEE 7.8.1.3, 7.9.2.2 2003 LS 101.
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-18 Cont ID  
Sent By dpalmer Date 2007-03-18 Time 08:20 Rev Time 0.00
Received By dpalmer Date 2007-03-18 Time 08:04 Sent To  
Notes
2007-03-18 08:20:29** UNSAT **
  
 1) NOTE: PLEASE PROVIDE ALL MINIMUM LIGHTING LEVELS
 UNDER NORMAL AND EMERGENCY CONDITIONS PER LS 101
 7.8.1.3, 7.9.2.2.
 PLEASE INDICATE AND SHOW HOW LIGHTING WILL BE
 CONTROLLED AND WHERE LIGHTING WILL BE CIRCUITED. PLEASE
 SEE 700.12E FOR CIRCUITING OF ANY EM/EXT LTS. FBC
 106.1.2, 106.3.5.1.2
  
 2) NOTE: PLEASE BE SURE THE FOLLOWING CODES WHICH THIS
 PROJECT IS UNDER SHALL BE STATED ON THE PLANS. PLEASE
 KNOW THERE MAY BE OTHER CODES WHICH MAY BE MENTIONED BY
 OTHER TRADES.
 FBC 2004 W/2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72 (WHERE/IF APPLICABLE)
 2003 NFPA-101
 FBC ADMIN SECTION 106.1.2, 110.1.2
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS/LAYOUT.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status N Date 2007-12-28 Cont ID  
Sent By mawillia Date 2007-12-28 Time 10:40 Rev Time 0.00
Received By mawillia Date 2007-12-28 Time 10:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-12-28 Cont ID  
Sent By mawillia Date 2007-12-28 Time 10:52 Rev Time 0.00
Received By mawillia Date 2007-12-28 Time 10:40 Sent To B1
Notes
2007-12-28 10:49:52*****APPROVED*****
  
  
 PLAN SHEETS 2 (OF 4) AND E1 (OF 2) WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-06-21 Cont ID  
Sent By mawillia Date 2007-06-21 Time 12:54 Rev Time 0.00
Received By mawillia Date 2007-06-21 Time 12:38 Sent To  
Notes
2007-06-21 12:49:51*****PROVISO*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED, HOWEVER THE APPROPIATE PLAN SHEET(S) TO
 BE FIRE-STAMPED WHEN THE ELECTRIC REVIEW HAS BEEN
 SATISFIED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-30 Cont ID  
Sent By mawillia Date 2007-03-30 Time 15:53 Rev Time 0.00
Received By mawillia Date 2007-03-30 Time 14:24 Sent To  
Notes
2007-03-30 15:28:48*****DENIED*****
  
  
 1. THE INDEX OF DRAWINGS ON SHEET 1 INDICATES THAT
 THERE ARE FOUR PLAN SHEETS;ONLY THREE OF THE FOUR
 PLAN SHEETS WERE SUBMITTED (WHERE IS SHEET #3?).
  
 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 3.NFPA 101 - 2003 EDITION SHALL BE REFERENCED.
  
 4.PLEASE SEE THAT OTHER PLAN REVIEW COMMENTS HAVE
 BEEN ADDRESSED WHICH MAY ASSIST IN FURTHER FIRE PLAN
 REVIEW.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW EACH ITEM WAS ADDRESSED,
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-12-07 Cont ID  
Sent By adarroug Date 2007-12-07 Time 08:47 Rev Time 0.00
Received By adarroug Date 2007-12-07 Time 08:47 Sent To  
Notes
2007-12-07 08:50:16TO "COMM" BD#26

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-29 Cont ID  
Sent By adarroug Date 2007-05-29 Time 11:01 Rev Time 0.00
Received By adarroug Date 2007-05-29 Time 11:01 Sent To  
Notes
2007-06-14 14:18:20TO "COMM' BD#28
2007-05-29 11:01:42WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-30 Cont ID  
Sent By mawillia Date 2007-03-30 Time 15:52 Rev Time 0.00
Received By mawillia Date 2007-03-08 Time 11:34 Sent To  
Notes
2007-03-08 11:35:54TO"BOB"#4