Plan Review Details - Permit 07030232
Plan Review Stops For Permit 07030232
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-05-10 Cont ID  
Sent By mawillia Date 2007-05-10 Time 12:03 Rev Time 0.00
Received By mawillia Date 2007-05-10 Time 11:56 Sent To M
Notes
2007-05-10 12:05:11*****APPROVED*****
  
  
 PLAN SHEET 1 OF 2 STAMPED, INITIALED, AND DEATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-03-12 Cont ID  
Sent By mawillia Date 2007-03-12 Time 16:54 Rev Time 0.00
Received By mawillia Date 2007-03-12 Time 16:46 Sent To  
Notes
2007-03-12 16:54:21*****UNSAT*****
  
  
 1.THESUITE NUMBER SHALL BE INCLUDED ALONG WITH THE
 COMPLETE ADDRESS CONTAINED IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.PLEASE BE ADVISED THAT THE
 UPDATED PLANS/SHOP DRAWINGS ARE TO BE PRESENTED WITH NO
 INK, PENCIL, OR ANY OTHER MARKING.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 56-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-01 Cont ID  
Sent By adarroug Date 2007-05-01 Time 15:18 Rev Time 0.00
Received By adarroug Date 2007-05-01 Time 15:18 Sent To FIRE
Notes
2007-05-01 15:18:33TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-12 Cont ID  
Sent By mawillia Date 2007-03-12 Time 16:46 Rev Time 0.00
Received By mawillia Date 2007-03-07 Time 15:21 Sent To  
Notes
2007-03-07 15:21:37TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-05-10 Cont ID  
Sent By tgordon Date 2007-05-10 Time 13:40 Rev Time 0.25
Received By tgordon Date 2007-05-10 Time 13:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-09 Cont ID  
Sent By tgordon Date 2007-03-09 Time 09:51 Rev Time 0.25
Received By tgordon Date 2007-03-09 Time 09:51 Sent To FIRE
Notes
2007-03-09 10:07:01*** DENIED ***
 1) INFORMATION MISSING FROM TITLE BLOCK. (AS PLANS ARE
 SEALED BY AN ENGINEER)
 SEE FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 2) PLEASE SHOW ON PLANS NOAIR INTAKE OPENINGS WILL BE
 WITH IN 10 FEET OF THE EXHAUST LOCATION, SEE 2004 FBC/M
 506.3.12.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.