| 2007-03-16 10:22:57 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS; FBC-2004 CHAPTER 1, THE |
| | CITY OF WEST PALM BEACH AMENDMENTS; |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| | REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL THE ZONING |
| | ISSUES HAVE BEEN RESOLVED. ON THE RESUBMITTED SURVEY |
| | PLEASE CLEARLY MARK THE PROPOSED LOCATION OF THE |
| | GENERATOR. INDICATION OF ALL DIMENSIONS FROM PROPERTY |
| | LINES AND DISTANCES FROM ADJACENT DWELLING STRUCTURES. |
| | INDICATION THAT THE GENERATOR EXHAUST IS NOT INSTALLED |
| | ANY CLOSER THAN TEN FEET FROM ANY OPENING INTO THE |
| | DWELLING STRUCTURE. THIS INCLUDES DOORS, WINDOWS AND |
| | ATTIC VENTILATION OPENINGS. |
| | |
| | 2. PLEASE SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY |
| | SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. CLEARLY INDICATE ON THE RESUBMITTAL THE |
| | EXISTING GAS PIPE AND NEW GAS PIPE. |
| | |
| | 3. PLEASE SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED ON THE RESUBMITTED |
| | ISOMETRIC. |
| | NOTE: THE PIPING TO THE GENERATOR NEEDS TO BE INCREASED |
| | TO 1-1/4" PE DUE TO THE BTU LOAD OF 560,000 TO THE |
| | GENERATOR. PLEASE REFERENCE THE SUBMITTED |
| | MANUFACTURER'S SPECIFICATIONS INDICATING THE BTU LOAD |
| | TO THE GENERATOR. |
| | |
| | 4. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL) ON |
| | THE RESUBMITTED ISOMETRIC. |
| | |
| | 5. PLEASE INDICATE THE BTU LOAD OF EACH APPLIANCE AND |
| | THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33) ON THE RESUBMITTED ISOMETRIC. |
| | NOTE: PLEASE INDICATE THE BTU LOAD TO THE GENERATOR ON |
| | THE RESUBMITTED ISOMETRIC. |
| | |
| | 6. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | 7. PLEASE INDICATE THE DELIVERY PRESSURE (PSI) PER |
| | FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI ON THE RESUBMITTED |
| | ISOMETRIC. |
| | NOTE: ON THE SUBMITTED DRAWING THE GAS PRESSURE WAS |
| | INDICATED AS 0.5 PSI. PLEASE NOTE THE RED LINE |
| | CORRECTIONS TO THE PE PIPING TO THE GENERATOR. PLEASE |
| | REFERENCE THE ATTACHED SIZING TABLES TO THE GAS |
| | COMMENTS INDICATING THE NEED TO INCREASE THE GAS PIPE |
| | TO THE GENERATOR. |
| | |
| | 8. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |