Plan Review Details - Permit 07030159
Plan Review Stops For Permit 07030159
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-04-27 Cont ID  
Sent By jwitmer Date 2007-04-27 Time 07:59 Rev Time 1.22
Received By jwitmer Date 2007-04-27 Time 07:59 Sent To FIRE
Notes
2007-04-27 08:03:57 
 *** ISSUED PERMIT***
 -PLAN REVIEW HISTORY-
  
 PERMIT# 07030159
 ADDRESS: 1401 BRANYWINE
 CONT: PURDY CONSTRUCTION
 TELL # (561) 718-8080
  
 THE ATTACHED COMMENTS ARE PART OF THE
 PERMIT AND PLAN REVIEW PACKAGE AND ARE
 NOT TO BE REMOVED FROM THE ISSUED SET
 OF PLANS.106.1.1 ADMINISTRATIVE CODE/ 06.
  
 BUILDING PROVISO:
  
 ROOFING PRODUCT APPROVALS WERE NOT HIGHLIGHTED AS TO
 WHICH
 SUBSYSTEM TO BE USED. NO ROOFER ON AS SUB PERMIT WILL
 REQUIRE A
 SEPERATE PERMIT, PRODUCT APPROVALS AND ASSOCIATED
 FEES.
  
 NOTE; WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-03 Cont ID  
Sent By jwitmer Date 2007-04-03 Time 15:45 Rev Time 1.22
Received By jwitmer Date 2007-04-03 Time 15:45 Sent To  
Notes
2007-04-03 16:51:33BUILDING PLAN REVIEW
 PERMIT: 07030159
 ADD: 1401 BRANDYWINE ROAD
 CONT: PURDY CONSTRUCTION
 TEL: (561)
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)S-1 FOUNDATION F-2REQUIRES A MINIMUM SAFE BEARING
 VALUE, AND SOILS REPORT,
 FBC 1802.2.1 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE A LOAD-BEARING
 VALUE SUPERIOR TO THAT SPECIFIED IN THIS CODE IS
 CLAIMED, THE BUILDING OFFICIAL SHALL
 REQUIRE THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6
 .
  
 4) S-1 WIND PRESSURE REFRENCES 2004 FBC , CORRECT ASCE
 7-02 AS THE REFRENCE.
  
 5)106.1.2* ADDITIONAL INFORMATION,
 A-0 DETAIL# 8 INDICATES UPRIGHT STEEL BUT THERE IS NO
 SIZE NOR SPACING OF THE STEEL.
  
 6) SHEET A-0 DETAIL # 2 ROOF FRAMING DETAIL INDICATES A
 SKYLIGHT BUT THE RAFTERS( TRIMMER) ARE NOT DOUBLED NOR
 IS THE UPLIFT INCREASED.
 2308.10.4.3 FRAMING AROUND OPENINGS.
 TRIMMER AND HEADER RAFTERS SHALL BE DOUBLED, OR OF
 LUMBER OF EQUIVALENT CROSS SECTION, WHERE THE SPAN OF
 THE HEADER EXCEEDS 4 FEET (1219 MM). THE ENDS OF HEADER
 RAFTERS MORE THAN 6 FEET (1829 MM) LONG SHALL BE
 SUPPORTED BY FRAMING ANCHORS OR RAFTER HANGERS UNLESS
 BEARING ON A BEAM, PARTITION OR WALL.
  
 7) SHEET A-0 DETAIL# 2 DOESN'T INDICATE TYPE OF
 FASTENER / BUCKET FOR THE HEDERS OF THE SKYLIGHT.
  
 8) A-0 DOESN'T INDICATE ANY SOILS TERMITE TREATMENT,
 1816.1.
  
  
 9) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
  
 10)FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) CURRIES EXTERIOR DOOR - THE FLORIDA COVERSHEET
 INDICATES THESE DOORS TO BE
 HOLLOW METAL DOORS. THE CORRESPONDING NOA WAS NOT
 PRINTED. NOTE THE ELEVATIONS
 INDICATE A LOUVERED DOOR NOT A HOLLOW METAL DOOR.
 B) SKYLIGHT -OK
 C) GAF MODIFIED BITUMEN ROOF SYSTEMS- MISSING THE
 CORRESPONDING MIAMI-DADE NOA.
 ) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 _X__ CONTRACTOR DID NOT PROVIDE THE MEAN
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 _X__ CONTRACTOR FAILED TO SUBMIT MIAMI-DADE NOA.
  
 _X__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE
 USED.
  
 _X__ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE _2&3__ .
  
 *****EITHER OF THE FOLLOWING WILL BE IN EACH
 SUBSYSTEM:****
  
 ___ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 10D) LOUVER / EXHAUST FAN NO REPORT SUBMITTED
  
 11) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 12)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-04-21 Cont ID  
Sent By dpalmer Date 2007-04-21 Time 14:39 Rev Time 0.00
Received By dpalmer Date 2007-04-21 Time 14:04 Sent To  
Notes
2007-04-21 14:40:26** NOTES REDLINED/ PROVISO **
  
 1) NOTE: PLEASE SEE PLANS HAVE BEEN REDLINED AS NO
 INFORMATION WAS PROVIDED ON RISER OR IS PROVIDED IN
 MANUFACTURES SPECS/CUT SHEETS ATTACHED FOR HOW THE SD
 SYSTEM WILL BE DETERMINED.
 250.20,250.30,250.50,250.66
  
 2) NOTE: PLEASE ALSO SPECIFICATIONDO NOTE THAT A
 SECONDARY MAIN IS REQUIRED , BUT ONLY ONE OF THE TWO
 PICTURES IN SPECS INDICATE THIS.THE SPECS/OR PLANS DO
 NOT INDICATE. THE NOTES ONLY MENTION ONE IS TO BE
 INSTALLED PER NEC. HOWEVER SIZE OF OCP AND CONDUCTOR
 SIZES ARE TO BE VERIFIED IN FIELD. ANY CHANGES IN
 EQUIPMENT OR CODE COMPLIANCE MUST BE SUBMITTED.
  
 ** PLEASE SUBMIT THIS INFORMATION BEFORE FINAL TO CLEAR
 UP INFORMATION FOR ELECTRICAL AS NOTED.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-09 Cont ID  
Sent By dpalmer Date 2007-03-09 Time 07:40 Rev Time 0.00
Received By dpalmer Date 2007-03-09 Time 07:08 Sent To  
Notes
2007-03-10 16:42:59** UNSAT **
  
 ** REVIEW BASED ON 2ND ELECTRICAL RISER ATTACHED ON
 PLANS WITH PRODUCT APPROVALS WHICH WAS NOT REVIEWED
 WITH THE ARCHITECTURAL PLANS.
 PLEASE BE SURE TO HAVE ALL ELECTRICAL AS REFERENCE ON
 THE ARCHITECTURAL SHEETS REMOVED. DO NOT CROSS OUT,
 THIS MUST BE REMOVED.
 PLANS ARE COMING BACK FOR CORRECTIONS.
 ** PLEASE SEE SOME COMMENTS ON THE NOTES FROM 3/9 ARE
 STILL VALID WITH RESPECT TO LOCATIONS OF ALL EQUIPMENT
 TO BE SHOWN ON PLANS ETC.
  
 1) NOTE: PLANS MISSING TITLE BLOCK INFORMATION AS
 REQUIRED PER FLORIDA ADMINISTRATIVE CODE 61G15-23.002,
 AND FLORIDA STATUTES 471.023.
 PLEASE SEE THAT PLANS ARE NOT SIGNED, DATED OR SEALED
 BY THE ENGINEER. FS 471.025, FAC 61G15-23.001
 PLEASE SEE THAT THE LICENSE NUMBER OF ENGINEER IS NOT
 VISIBLE. VERIFICATION CAN NOT BE DONE.
 PLEASE COMPLETE ALL INFORMATION AS REQUIRED.
  
 2) NOTE: PLEASE SEE MISSING COLD WATER AS PART OF THE
 GROUNDING ELECTRODE SYSTEM. 250.50
  
 3) NOTE: PLEASE SEE THAT NOT ENOUGH INFORMATION IS
 SUBMITTED FOR THE TRANSFORMER WHICH IS BEING NOTED AS
 PART OF THE LISTED PUMP CONTROL BOARD. PLEASE KNOW AS
 THIS IS SHOWING A TRANSFORMER FOR 120/240V USE, WHERE
 IS THE GROUNDING FOR THE SEPARATELY DERIVED SYSTEM PER
 250.20, 250.30, AND 250.66?
 PLEASE SEE NOT NEUTRAL IS BEING BROUGHT TO THE
 EQUIPMENT AND IS NOT REQUIRED AS PLANS SEEM TO SHOW
 ONLY MOTOR LOADS, ALTHOUGH THE SD SYSTEM WILL REQUIRE
 NEUTRAL.
 PLEASE SUBMIT THIS INFORMATION ALONG WITH THE EQUIPMENT
 SPECS/DOCUMENTS FOR REVIEW. 110.3, 90.7
 * PLEASE KNOW AT THIS TIME TAP CONDUCTORS AND HOW THIS
 TRANSFORMER IS BEING FED AND THE OVER-CURRENT
 PROTECTION IS NOT SHOWN AND REVIEW OF THESE ITEMS ALONG
 WITH TERMINATION OF THE TAPS IN OCP WHICH LIMITS THE
 LOAD ON THE CONDUCTORS NOT SHOWN CAN NOT BE VERIFIED.
 240.21. 408.36?
  
 ***********
  
  
  
2007-03-09 07:45:56** UNSAT **
  
 1) NOTE: PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN
 SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH WILL
 AFFECT DESIGNS FOR ALL TRADES.
  
 2) NOTE: PLEASE SEE FS 471.003(2)H(2A) WHERE AS THE
 277/480V SERVICE MUST BE DESIGNED AND SIGNED AND SEALED
 BY A PE.
  
 3) NOTE: PLEASE SEE THE SITE PLAN SHEETS WHICH CONTAIN
 TITLE BLOCKS FROM THE ARCHITECT SHALL BE SIGNED, DATED
 AND SEALED PER FS 481.221
  
 ** PLEASE SEE SOME OF THE FOLLOWING NOTES ARE BASED ON
 THE ELECTRICAL PLANS SUBMITTED EVEN THOUGH THESE WILL
 BE REQUIRED TO BE RE-DONE BY AN ENGINEER.
  
 4) NOTE: PLEASE SEE THE GROUNDING ELECTRODE CONDUCTOR
 IS NOT LARGE ENOUGH PER 250.66.
  
 5) NOTE: PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS AND
 FEEDERS ARE NOT LARGE ENOUGH PER 310.16. (MAY NOT USE
 310.15B6 FOR COMMERCIAL)
  
 6) NOTE: PLEASE SEE 250.6 AND 250.24B FOR OBJECTIONABLE
 CURRENTS ON NEUTRAL AS SHOWN.
  
 7) NOTE: PLEASE SUBMIT ALL EQUIPMENT ON THE NEW PANEL
 AND LOADS. PUMPS , CONTINUOUS LOADS, SIZES ETC NEED TO
 BE VERIFIED WHICH CAN NOT BED DONE AT THIS TIME. 220,
 310.16, 430, 240 ETC
 FBC 106.1.2 ADMIN SECTION.
  
 8) NOTE: PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS
 FOR THE NEW PUMP CONTROL PANEL. 110.3, 90.7.
 FBC 106.1.2
  
 9) NOTE: PLEASE INDICATE THE LOCATION OF PANEL ON
 PLANS.
 110.26 NEEDS TO BE VERIFIED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2007-04-21 Cont ID  
Sent By dpalmer Date 2007-04-21 Time 14:04 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-04-10 Cont ID  
Sent By mawillia Date 2007-04-10 Time 18:34 Rev Time 0.00
Received By mawillia Date 2007-04-10 Time 18:20 Sent To  
Notes
2007-04-10 18:33:34*****PROVISO******
  
  
  
 THE CONSTRUCTION OPERATION AND/OR THE LOCATION OF THE
 PROPOSED STRUCTURE SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE TO THE PROPERTY OR VICINITY THEREOF
 (INCLUDING STREETS, ROADWAYS, OR FIRE LANES).

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-05 Cont ID  
Sent By adarroug Date 2007-07-05 Time 14:33 Rev Time 0.00
Received By adarroug Date 2007-07-05 Time 14:33 Sent To B
Notes
2007-07-05 14:33:57TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-02 Cont ID  
Sent By adarroug Date 2007-05-02 Time 09:13 Rev Time 0.00
Received By adarroug Date 2007-05-02 Time 09:13 Sent To Z
Notes
2007-05-02 09:14:03TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-19 Cont ID  
Sent By adarroug Date 2007-04-19 Time 10:27 Rev Time 0.00
Received By adarroug Date 2007-04-19 Time 10:27 Sent To  
Notes
2007-04-19 10:27:39TO "COMM" BD#1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-04-13 Time   Rev Time 0.00
Received By adarroug Date 2007-03-06 Time 16:35 Sent To  
Notes
2007-03-08 14:13:36TO "COMM" BD#42
2007-03-06 16:35:54WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-04-21 Cont ID  
Sent By dpalmer Date 2007-04-21 Time 14:03 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2007-03-22 Cont ID  
Sent By kstevens Date 2007-03-22 Time 10:13 Rev Time 0.00
Received By kstevens Date 2007-03-22 Time 10:13 Sent To  
Notes
2007-03-22 10:22:50PER CONTRACTOR - ONLY THE SHELL BLDG THIS PERMIT.
 SEPARATE IRRIGATION PLANS & PERMIT AT A LATER DATE

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-21 Cont ID  
Sent By kstevens Date 2007-03-21 Time 14:05 Rev Time 0.00
Received By kstevens Date 2007-03-21 Time 12:33 Sent To  
Notes
2007-03-21 14:41:57DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA STATUTES
  
 1. AN IRRIGATION CONTRACTOR IS REQUIRED FOR THE
 IRRIGATION WORK. (CONNECTING THE PUMP TO THE EXISTING
 IRRIGATION PIPE).
  
 2. SEE ELECTRICAL COMMENT NUMBER 2 WITH RESPECT TO FS
 471.003(2)(H)(2A).
  
 3. SUBMIT MANUF. SPECIFICATION SHEETS FOR THE
 IRRIGATION PUMP. MUST SHOW LISTING. SECTION 303.4.
  
 4. SUBMIT PIPING INFORMATION FOR THE CONNECTION TO THE
 PUMP. IS THIS A NEW SYSTEM OR ALTERED SYSTEM?SHOW THE
 LOCATION OF THE CONTROLLER AND THE RAIN SENSOR.
 INDICATE EXISTING PIPING AND NEW PIPING ON THE PLANS.
 PLEASE INDICATE THE PREVIOUS SOURCE OF WATER FOR THIS
 IRRIGATION SYSTEM. IF THE SOURCE WAS CITY WATER,
 (POTABLE), THEN THE SOURCE OF WATER SHALL BE CAPPED OFF
 BY A PLUMBING CONTRACTOR. SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2007-05-02 Cont ID  
Sent By eschneid Date 2007-05-02 Time 16:19 Rev Time 0.00
Received By eschneid Date 2007-05-02 Time 16:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-04-26 Cont ID  
Sent By eschneid Date 2007-04-26 Time 18:10 Rev Time 0.00
Received By eschneid Date 2007-04-26 Time 18:10 Sent To  
Notes
2007-04-26 18:11:55FAILED
  
 1)INCLUDE THE APPROVAL LETTER FROM THE NORTHERN PALM
 BEACH IMPROVEMENT DISTRICT.
  
 3) AT LEAST 30% OF THE LINEAR FEET AROUND THE PUMP
 HOUSE SHALL BE LANDSCAPED WITH TREES, SHRUBS OR
 HEDGES.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-04-13 Cont ID  
Sent By eschneid Date 2007-04-13 Time 08:24 Rev Time 0.00
Received By eschneid Date 2007-04-13 Time 08:24 Sent To  
Notes
2007-04-13 08:30:53FAILED
  
 1) THE PLACEMENT OF A NEW STRUCTURE ON THIS SITE
 REQUIRES THE APPROVAL OF A MINOR PD AMENDMENT.WHILE A
 MINOR AMENDMENT HAS BEEN SUBMITTED, IT IS CURRENTY
 INSUFFICIENT DUE TO THE EASEMENT ISSUES OUTLINED
 BELOW.
  
 2) THE PROPOSED PUMP HOUSE IS LOCATED IN A DRAINAGE
 EASEMENT.EITHER PROVIDE EVIDENCE THAT THE EASEMENT
 HAS BEEN ABANDONED, OR MOVE THE PUMP HOUSE OUT OF THE
 EASEMENT.
  
 3) AT LEAST 30% OF THE LINEAR FEET AROUND THE PUMP
 HOUSE SHALL BE LANDSCAPED WITH TREES, SHRUBS OR
 HEDGES.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.