Plan Review Details - Permit 07030154
Plan Review Stops For Permit 07030154
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-11-13 Cont ID  
Sent By jgomez Date 2007-11-13 Time 16:38 Rev Time 0.00
Received By jgomez Date 2007-11-13 Time 16:38 Sent To PC
Notes
2007-11-13 16:54:53STORM SHUTTERS PRODUCT APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-05-25 Cont ID  
Sent By jgomez Date 2007-05-25 Time 13:54 Rev Time 0.00
Received By jgomez Date 2007-05-25 Time 13:54 Sent To PC
Notes
2007-05-25 13:56:46BUILDING REVIEW APPROVED WITH PROVISO:
 1- SUBMITTAL MISSING THE STORM SHUTTERS SUBMITTED THE
 FIRST TIME. PROVIDE 2 COPIES OF PRODUCT APPROVALS AND
 MAKE SURE ENGINEER OF RECORD REVIEWS AND APPROVES IT IN
 WRITING AS REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO
 FBC 2004.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-13 Cont ID  
Sent By jgomez Date 2007-04-13 Time 19:07 Rev Time 0.00
Received By jgomez Date 2007-04-13 Time 19:07 Sent To PC
Notes
2007-04-13 19:07:51BUILDING REVIEW CHECKLIST:
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTE.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.
 (561)233-5115) TO PAY IMPACT FEES. BRING BACK STAMPED
 PLANS AND COPY OF PAID RECEIPT.
  
 3- VALUE DECLARED ON THE PERMIT APPLICATION WAS TOO
 LOW. IT WAS UPDATED TO $222,730. THEREFORE, OWES
 $1261.49 FOR UPDATED VALUE AND RADON FEES. SEC. 108.3
 CITY AMENDMENTS TO FBC 2004.
  
 4- NEED TO SPECIFY TWO LAYERS OF UNDERLAYMENT FOR ROOF
 PITCH OF 3.36:12 AS REQUIRED BY SEC. R905.3.3.1 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 5- SPECIFY TILE FASTENING AS REQUIRED BY SEC. 106.1.1.2
 CITY AMENDMENTS TO FBC 2004.
 ***NOTE: MAKE SURE PROPOSED FASTENING MEETS THE
 CALCULATED UPLIFT LOADS.
  
 6- SHEET 5 OF 7: UPDATE ALLSTANDARDS REFERENCED IN
 THE GENERAL NOTES.SEE CHAPTER 43 OF 2004 FLORIDA
 RESIDENTIAL CODE FOR CORRECT STANDARD AND YEAR TO BE
 USED AND REVISE ALL NOTES AS REQUIRED.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9B-72
 FOR:
 A) PRECAST LINTELS.
 B) ALL TRUSSCONNECTORS SPECIFIED ON PLANS AND
 DETAILS.
  
 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 9- REVISE ROOF SHEATHING TYPE OF FASTENER.SEE SEC.
 R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE AND REVISE
 AS REQUIRED.
  
 10- SOIL TEST REPORT:
 A) REPORT SUBMITTED IS FOR ONE STORY ADDITION. PLANS
 SHOW TWO STORY ADDITION. REVISE AS REQUIRED.
 B) REPORT NEEDS TO HAVE THE ENGINEERING FIRM
 CERTIFICATE OF AUTHORIZATION NUMBER IN ALL SHEETS AS
 REQUIRED BY SEC. 61G15-23.002 OF FLORIDA ADMINISTRATIVE
 CODE.
  
 11- STORM SHUTTERS: PROVIDE KEY PLAN AND COMPLETE
 INSTALLATION SCHEDULE. SEE ATTACHED COPY OF
 INSTALLATION SCHEDULE AND COMPLETE ALL INFORMATION.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 12- OWNER/AGENT TO SIGN AND DATE THE ENERGY
 CALCULATIONS AT THE BOTTOM OF FORM.
  
 13- ROOF SHEATHING SPECS ON SHEET 5 OF 7 DON'TMATCH
 SPECS SHOWN ON TYPICAL WALL SECTIONS.REVISE
 THICKNESS OF PLYWOOD AND MAKE SURE REVISED INFORMATION
 IS ADDRESSING ITEM #9 ABOVE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-12-31 Cont ID  
Sent By btrobaug Date 2007-12-31 Time 11:08 Rev Time 0.00
Received By btrobaug Date 2007-12-31 Time 10:05 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-09-25 Cont ID  
Sent By btrobaug Date 2007-09-25 Time 16:07 Rev Time 0.00
Received By btrobaug Date 2007-09-25 Time 15:55 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-05-10 Cont ID  
Sent By btrobaug Date 2007-05-10 Time 11:41 Rev Time 0.33
Received By btrobaug Date 2007-05-10 Time 11:23 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-19 Cont ID  
Sent By btrobaug Date 2007-03-19 Time 11:28 Rev Time 0.00
Received By btrobaug Date 2007-03-19 Time 07:27 Sent To M
Notes
2007-03-20 09:05:07 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} THE EQUIPMENT GROUND BETWEEN THE METER AND
 DISCONNECT ON THE RISER DIAGRAM CREATES A PARALLEL PATH
 TO GROUND WITH THE NEUTRAL AND MUST BE REMOVED. AN
 ISOLATED NEUTRAL AND EQUIPMENT GROUND ARE TO BE RAN
 FROM THE FIRST MEANS OF DISCONNECT. 250.6.
  
 3} NOTE #1 REFERS TO "IAW" PLEASE NOTE THAT THE STATE
 OF FLORIDA HAS ADOPTED NFPA 70 OR THE NEC. IF
 REFERENCING ANOTHER CODE TO USE FOR WIRING COMPLIANCE,
 INDICATE WHERE IT IS REFERENCED AS REPLACING THE
 BUILDING CODE REFERENCES.
  
 4} NOTE #6: SEE THE DEFINITION OF "SMOKE DETECTORS"
 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS,
 TO AVOID CONFUSION IN THE FIELD.
  
 5} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY. THE CONTRACTOR OF RECORD MAY BE THE
 DESIGN PROFESSIONAL IF EXEMPTIONS UNDER THOSE STATUTES
 ARE APPLICABLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-12-21 Cont ID  
Sent By spalmer Date 2007-12-21 Time 16:18 Rev Time 0.00
Received By spalmer Date 2007-12-21 Time 16:18 Sent To E
Notes
2007-12-21 16:19:33TO BILL TROBAUGH

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-11-09 Cont ID  
Sent By adarroug Date 2007-11-09 Time 12:59 Rev Time 0.00
Received By adarroug Date 2007-11-09 Time 12:59 Sent To B
Notes
2007-11-09 12:59:37TO "JGOMEZ" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-09-18 Cont ID  
Sent By adarroug Date 2007-09-18 Time 10:04 Rev Time 0.00
Received By adarroug Date 2007-09-18 Time 10:04 Sent To E
Notes
2007-09-18 10:04:44TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-09-07 Cont ID  
Sent By adarroug Date 2007-09-07 Time 16:58 Rev Time 0.00
Received By adarroug Date 2007-09-07 Time 16:58 Sent To M
Notes
2007-09-07 16:59:02TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-08-30 Cont ID  
Sent By adarroug Date 2007-08-30 Time 16:14 Rev Time 0.00
Received By adarroug Date 2007-08-30 Time 16:14 Sent To M
Notes
2007-08-30 16:14:42TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-10 Cont ID  
Sent By adarroug Date 2007-05-10 Time 08:16 Rev Time 0.00
Received By adarroug Date 2007-05-10 Time 08:16 Sent To E
Notes
2007-05-10 08:16:46TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-05-07 Cont ID  
Sent By adarroug Date 2007-05-07 Time 14:18 Rev Time 0.00
Received By adarroug Date 2007-05-07 Time 14:18 Sent To Z
Notes
2007-05-07 14:18:23TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-13 Cont ID  
Sent By adarroug Date 2007-03-13 Time 09:59 Rev Time 0.00
Received By adarroug Date 2007-03-13 Time 09:59 Sent To E
Notes
2007-03-13 09:59:29TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-13 Cont ID  
Sent By jroach Date 2007-04-13 Time 19:07 Rev Time 0.00
Received By jgomez Date 2007-03-07 Time 09:03 Sent To  
Notes
2007-03-07 09:03:47TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-09-12 Cont ID  
Sent By tgordon Date 2007-09-12 Time 16:02 Rev Time 0.25
Received By tgordon Date 2007-09-12 Time 16:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-09-04 Cont ID  
Sent By tgordon Date 2007-09-04 Time 11:27 Rev Time 0.30
Received By tgordon Date 2007-09-04 Time 11:27 Sent To  
Notes
2007-09-04 11:46:27PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 MECHANICAL REVISION
 *** DENIED ***
 1) DUCT LAY-OUT AND OTHER INFORMATION ON MECHANICAL
 PLAN IS FADED AND DIFFICULT TO SEE, AND COPY FOR
 FILING. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY. PER 2004 FBC 106.1.1.
  
 2) PLEASE SIZE ALL RETURN AIR GRILLS, SEE YELLOW HIGH
 LIGHTS ON PLAN.
  
 3) PLEASE SIZE THE SUPPLY AIR DUCT FROM AHU #1 TO THE
 HALF BATHROOM.
  
 4) PLEASE SHOW THE CFM'S AT THE SUPPLY AIR GRILL OVER
 THE STAIR-WAY.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2007-05-15 Cont ID  
Sent By tgordon Date 2007-05-15 Time 09:47 Rev Time 0.30
Received By tgordon Date 2007-05-15 Time 09:47 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-19 Cont ID  
Sent By tgordon Date 2007-03-19 Time 14:08 Rev Time 0.40
Received By tgordon Date 2007-03-19 Time 14:08 Sent To E
Notes
2007-03-19 14:25:26*** DENIED ***
 1) IF SORIN POPESCU ARCHITECTURAL SERVICES IS AN
 ARCHITECTURAL FIRM THEN THEY MUST SIGN AND SEAL THE
 MECHANICAL PLANS AS THEIR INFORMATION IS IN THE TITLE
 BLOCK, SEE FAC 61G1-16.003.
  
 2)MECHANICAL PLANS HAVE TO MUCH FLOOR PLAN DETAIL ON
 THEM AND ARE DIFFICULT TO READ. CONSTRUCTION DOCUMENTS
 SHALL BE OF SUFFICIENT CLARITY. PER 2004 FBC 106.1.1.
  
 3) COOLING LOAD CALCULATIONS FOR FIRST FLOOR ARE
 INCLUDING THE EXISTING LIVING AREA FOR A/C #1, BUT THE
 MECHANICAL PLANS ARE NOT, PLEASE CORRECT LOAD CAL'S OR
 MECHANICAL PLANS.
  
 4) MECHANICAL PLANS EQUIPMENT LISTING ONLY SHOWS ONE
 A/C SYSTEM, PLEASE CORRECT.
  
 5) PLEASE SHOW SENSIBLE BTU'S, MODEL NUMBERS, AND OTHER
 PERTINENT INFORMATION ON MECHANICAL PLANS.
  
 6)ENERGY CALCULATIONS NEED TO BE SIGNED BY
 OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-05-14 Cont ID  
Sent By mperson Date 2007-05-14 Time 14:22 Rev Time 0.45
Received By mperson Date 2007-05-14 Time 14:22 Sent To M
Notes
2007-05-14 14:50:30 
 ****************PROVISO****************
 FBC-2004 PLUMBING
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 (B) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK.
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 NOTE: CLEANOUT FOR WASHING MACHINE TO BE THREE INCH
 (3").
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: CLEANOUT FOR WASHING MACHINE TO BE FOUR FEET
 ABOVE FINNISH FLOOR (4' A.F.F.)
  
 (E) 802.1.6 DOMESTIC DISHWASHING MACHINES SHALL
 DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK
 INTO A STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH
 SECTION 802.2 OR DISCHARGE INTO A WYE-BRANCH FITTING ON
 THE TAILPIECE OF THE KITCHEN SINK OR THE DISHWASHER
 CONNECTION OF A FOOD WASTE GRINDER.
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-28 Cont ID  
Sent By mperson Date 2007-03-28 Time 13:54 Rev Time 0.55
Received By mperson Date 2007-03-28 Time 13:54 Sent To B
Notes
2007-03-28 14:32:48DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION IS REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 7 SANITARY ISOMETRIC RISER DIAGRAM AND FIRST
 AND SECOND FLOOR PLAN:
 IF SORIN POPESCU ARCHITECTURAL SERVICES IS AN
 ARCHITECTURAL FIRM THE FOLLOWING IS REQUIRED.
 FAC-61G1-16.004 TITLE BLOCK:
 A TITLE BLOCK MUST APPEAR ON ALL
 ARCHITECTURAL OR INTERIOR DESIGN
 DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK
 MUST, AT A MINIMUM, CONTAIN THE
 FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE
 NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED
 SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT.
  
 2. SHEET 7 SANITARY ISOMETRIC RISER DIAGRAM:
 THE FOLLOWING IS REQUIRED FOR THE WASHING MACHINE.
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER. PLEASE CORRECT THE PIPE SIZING ON THE
 RESUBMITTAL.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE THE STANDPIPE ON THE
 RESUBMITTAL.
  
 3. SHEET 7 SANITARY ISOMETRIC RISER DIAGRAM:
 PER FBC-2004, PLUMBING, SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 NOTE: THE 3" SANIARY STACK FOR THE SECOND FLOOR
 BATHROOM MUST CONNECT DOWNSTREAM OF THE FIRST FLOOR
 BATHROOM. PLEASE CORRECT ON THE RESUBMITTAL.
  
 4. SHEET 7 SANITARY ISOMETRIC RISER DIAGRAM: THE FIRST
 AND SECOND FLOOR TUBS REQUIRE VENTS PER FBC-2004
 PLUMBING, SECTION
 901.2.1 VENTING REQUIRED: EVERY TRAP AND
 TRAPPED FIXTURE SHALL BE VENTED IN
 ACCORDANCE WITH ONE OF THE VENTING
 METHODS SPECIFIED IN THIS CHAPTER.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop Z ZONING
Rev No 2 Status P Date 2007-05-08 Cont ID  
Sent By choops Date 2007-05-08 Time 11:27 Rev Time 0.00
Received By choops Date 2007-05-08 Time 11:27 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-12 Cont ID  
Sent By jroach Date 2007-03-12 Time 18:57 Rev Time 0.00
Received By jroach Date 2007-03-12 Time 18:57 Sent To I
Notes
2007-03-12 18:59:14***FAILED***
  
 1) PLEASE INDICATE ON THE SURVEY THE NEW LOCATION OF
 THE A/C EQUIPMENT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,