| 2007-03-05 13:30:39 | BUILDING REVIEW CHECKLIST: |
| | 1- FLAT ROOF PRODUCT APPROVAL SUBMITTED IS FOR LIGHT |
| | WEIGHT CONCRETE DECK.PROVIDE PRODUCT APPROVAL FOR |
| | WOOD DECK APPLICATION.LIGHT WEIGHT CONCRETE DECKS ARE |
| | USUALLY FOUND IN COMMERCIAL BUILDINGS NOT IN SINGLE |
| | FAMILY RESIDENCES. |
| | |
| | 2- ON FLAT ROOF PRODUCT APPROVAL CLEARLY IDENTIFY |
| | SPECIFIC APPROVED ASSEMBLY THAT IS GOING TO BE |
| | INSTALLED AS REQUIRED BY CITY POLICY FOR ROOFING |
| | PERMITS. SEE ATTACHED COPY. |
| | |
| | 3- ON SELECTED APPROVED ASSEMBLY CLEARLY IDENTIFY BASE |
| | SHEET FASTENING OPTION. SEE CITY ROOFING PERMITS |
| | POLICY. |
| | |
| | 4- IF SELECTED APPROVED ASSEMBLY IS LIMITED BY GENERAL |
| | LIMITATION #7, THEN PROVIDE RAS 117 CALCULATIONS FOR |
| | NAIL ENHANCING AT PERIMETER AND CORNER AREAS. NEED TO |
| | MEET THE DESIGN PRESSURES OF TABLE R301.2(2) OF 2004 |
| | FLORIDA RESIDENTIAL CODE. SEE GENERAL LIMITATION #7 ON |
| | LAST PAGE OF NOA. IF GENERAL LIMITATION #7 REQUIRES |
| | CALCULATIONS TO BE DONE BY ARCHITECT OR ENGINEER, THEN |
| | PROVIDE SIGNED AND SEALED CALCULATIONS. |
| | |
| | 5- IF SELECTED APPROVED ASSEMBLY IS LIMITED BY GENERAL |
| | LIMITATION #9, THEN ASSEMBLY MAY NOT BE INSTALLED IN |
| | THIS AREA BECAUSE THE ASSEMBLY MUST MEET THE DESIGN |
| | PRESSURES OF TABLE R301.2(2)2004 FLORIDA RESIDENTIAL |
| | CODE AND NAIL ENHANCING IS NOT ALLOWED. SEE GENERAL |
| | LIMITATION #9 ON LAST PAGE OF NOA. |
| | |
| | 6- SPECIFY HOW MUCH AREA IS FLAT ROOF AND HOW MUCH AREA |
| | ARE SHINGLES TO DETERMINE BUILDING PERMIT VALUATION AS |
| | REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (56`1)805-6712 |