| Plan Review Stops For Permit 07030135 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-08-18 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-08-18 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-08-18 |
Time |
07:17 |
Sent To |
PC |
|
| Notes |
| 2007-08-18 07:38:35 | BUILDING PLAN REVIEW | | | PERMIT: 07030135 | | | ADD: 716 NATHAN HALE RD | | | CONT: GUERRERO ALFREDO (OWNER) | | | TEL: (561)588-9658 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 2ND | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)108.3*THE CLAIMED VALUATION ON THE PERMIT | | | APPLICATION IS LOW. FOR PERMITTING PURPOSES, VALUATION | | | OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT | | | COST EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS | | | ICC (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS. | | | | | | 3)OK | | | | | | 4)OK | | | | | | NEW****** | | | A)BEFORE A PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | B) SHEET #11 THE CODE REFERENCE SECTION 1606 WIND LOAD | | | SCHEDULE AND DESIGN CRITERIA 1606.2 IS FROM THE 2001 | | | FBC. ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL | | | BE DESIGNED TO THE 2004 FLORIDA BUILDING CODE. SEE 2004 | | | FBC SECT.1609 FOR MORE INFORMATION. | | | | | | C)TWO SETS OF PRODUCT OF PRODUCT APPROVAL SHALL BE | | | SUBMITTED TO THE CITY. WHEN THE PERMIT IS ISSUED, ONE | | | SET WILL BE RETAIN AND OTHER WILL BE RETURN TO THE | | | COUSTOMER. ONLY ONE SET IS IN THE PACKAGE. | | | | | | D) ADDITIONAL FEES ARE DUE $268.77 | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-04-14 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-04-14 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-04-13 |
Time |
17:07 |
Sent To |
PC |
|
| Notes |
| 2007-04-13 19:03:35 | BUILDING PLAN REVIEW | | | PERMIT: 07030135 | | | ADD: 716 NATHAN HALE RD | | | CONT: GUERRERO ALFREDO (OWNER) | | | TEL: (561)588-9658 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2)108.3*THE CLAIMED VALUATION ON THE PERMIT | | | APPLICATION IS LOW. FOR PERMITTING PURPOSES, VALUATION | | | OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT | | | COST EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS | | | ICC (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS. | | | | | | 3)106.3.3* PRODUCT APPROVALS- 2004 | | | THOSE PRODUCTS THAT ARE RGULATED BY DCA | | | RULE 9B-72 SHALL BE REVIEWED AND | | | APPROVED IN WRITTING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. THE PRODUCT APPROVALS SHALL | | | APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 4)SHEET #5 INDICATE A DETAIL #1 ON SHEET #5, HOWEVER | | | THERE IS NO DETAIL ON THAT PAGE. THE DETAIL REFERENCES | | | SHALL REFERENCE THE CORRECT PAGES. CLARIFY. SHEET #6 | | | HAS THE SAME PROBLEM. DETAIL 1 OF 5 ON SHEET #6 ATTHE | | | CORNERS CANNOT HAVE THE SAME TYPE OF CONNECTION AS THE | | | POSTS IN THE MIDDLE OF THE PROJECT. SEE THE USP CATALOG | | | ANDCLARIFY THE DETAILS. THESE DETAILS SHALL BE | | | CLEAR. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2007-03-12 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-03-12 |
Time |
15:04 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2007-03-12 |
Time |
14:57 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-08-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-08-16 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-08-16 |
Time |
09:49 |
Sent To |
B |
|
| Notes |
| 2007-08-16 09:49:26 | TO "MJACOBS" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-07-16 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2007-08-15 |
Time |
17:51 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-16 |
Time |
14:49 |
Sent To |
P |
|
| Notes |
| 2007-07-16 14:50:51 | TO "P" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-03-09 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-03-09 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-09 |
Time |
10:55 |
Sent To |
E |
|
| Notes |
| 2007-03-09 10:55:53 | TO "E" BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-03-06 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2007-03-06 14:06:01 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2007-03-14 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-03-14 |
Time |
08:53 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-03-14 |
Time |
08:53 |
Sent To |
P |
|
| Notes |
| 2007-03-14 08:57:01 | *** PROVISO *** | | | 1) MECHANICAL PERMIT WILL BE NEED FOR BATHROOM EXHAUST | | | FAN. | | | | | | 2)NO MECHANICAL PLANS SUBMITTED, AND NO MECHANICAL | | | PERMIT NUMBER APPLIED FOR AT THIS TIME. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2007-07-31 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-07-31 |
Time |
13:05 |
Rev Time |
0.33 |
| Received By |
mperson |
Date |
2007-07-31 |
Time |
13:05 |
Sent To |
Z |
|
| Notes |
| 2007-07-31 13:30:44 | ****************PROVISO**************** | | | PER FBC-2004 PLUMBING SECTIONS 424.3 AND P2708.3 SHOWER | | | VALVES: SHOWER AND TUB/SHOWER COMBINATIONS SHALL BE | | | EQUIPPED WITH CONTROL VALVES OF THE PRESSURE BALANCE, | | | THE THERMOSTATIC MIXING OR THE COMBINATION PRESSURE | | | BALANCE/THERMOSTATIC MIXING VALVE TYPES WITH HIGH LIMIT | | | STOPS IN ACCORDANCE WITH ASSE 1016. THE HIGH LIMIT | | | STOPS SHALL BE SET TO LIMIT WATER TEMPERATURE TO A | | | MAXIMUM 120 DEGREES FAHRENHEIT. | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL= [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-03-16 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-03-16 |
Time |
14:31 |
Rev Time |
0.45 |
| Received By |
mperson |
Date |
2007-03-16 |
Time |
14:31 |
Sent To |
B |
|
| Notes |
| 2007-03-16 15:08:22 | DENIED | | | REFERENCE: FBC-2004 PLUMBING;FBC-2004 CHAPTER 1, THE | | | CITY OF WEST PALM BEACH AMENDMENTS; | | | | | | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING | | | PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. SHEET 13, SANITARY ISOMETRIC RISER DIAGRAM.PER | | | FBC-2004 CHAPTER 1, SECTION 106.1.1 INFORMATION ON | | | CONSTRUCTION | | | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL | | | BE OF SUFFICIENT CLARITY TO INDICATE THE | | | LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE | | | AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, | | | AS DETERMINED BY THE | | | BUILDING OFFICIAL. | | | | | | A} SANITARY ISOMETRIC RISER DIAGRAM DOES NOT REFLECT | | | THE FLOOR PLAN OF SHEET 2 AND IS NOT CODE COMPLIANT. | | | | | | B} FIXTURES ARE IDENTIFIED WRONG, SHEET 2 FIXTURES ARE | | | A LAVATORY, WATER CLOSET, AND A SHOWER. SHEET 13 | | | SANITARY RISER DIAGRAM INDICATES A SINK, WATER CLOSET | | | AND A TUB. PLEASE CORRECT AND RESUBMIT. | | | | | | C} SANITARY RISER DIAGRAM ON SHEET 13 IS INDICATING A | | | DOUBLE SANITARY TEE PER FBC-2004 PLUMBING SECTION 706.3 | | | IS ILLEGAL ON A HORIZONTAL INSTALLATION. PLEASE CORRECT | | | AND RESUBMIT. | | | | | | D} 708.3.5 BUILDING DRAIN AND BUILDING | | | SEWER JUNCTION. THERE SHALL BE A TWO-WAY | | | CLEANOUT NEAR THE JUNCTION OF THE | | | BUILDING DRAIN AND THE BUILDING SEWER. PLEASE ADD TO | | | THE RESUBMITTAL. | | | | | | ********IMPORTANT INFORMATION******** | | | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, | | | PLEASE REPLACE ONLY SHEETS | | | WHICH HAVE CHANGED, PLEASE INCLUDE A | | | TRANSMITTAL LETTER INDICATING HOW EACH | | | ITEM WAS ADDRESSED AND PROVIDE ONE COPY | | | OF ALL OLD/VOIDED SHEETS FOR REFERENCE | | | ONLY. | | | NOTE: ONLY ONE CORRECTED DRAWING | | | IN RED INK FOR REFERENCE FOR | | | RESUBMITTAL. PLEASE REFERENCE THE ATTACHED SANITARY | | | ISOMETRIC RISER DIAGRAM TO THE PLUMBING COMMENTS THAT | | | REFLECTS THE FLOOR PLAN AND IS CODE COMPLIANT. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2007-08-15 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2007-08-15 |
Time |
17:50 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2007-08-15 |
Time |
17:50 |
Sent To |
I |
|
| Notes |
| 2007-08-15 17:51:33 | ***FAILED*** | | | | | | 1) CURRENT SURVEY SHALL BE PROVIDED.SURVEY SHALL BE | | | UPDATED TO SHOW THE PROPOSED ADDITION AS WELL AS THE | | | SETBACKS FROM ALL OF THE PROPERTY LINES TO THE PROPOSED | | | ADDITION. | | | | | | 2) THE PROPOSED ADDITION SHALL BE NO CLOSER THAN 6 FEET | | | TO THE ACCESSORY STRUCTURE (I.E. SHED).IF THIS | | | STRUCTURE IS NO LONGER ON THE PROPERTY, THE CURRENT | | | SURVEY SHOULD REFLECT THIS. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | | AT (561) 822-1435. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-03-08 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2007-03-08 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2007-03-08 |
Time |
11:30 |
Sent To |
I |
|
| Notes |
| 2007-03-08 13:06:53 | ***FAILED*** | | | | | | 1) CURRENT SURVEY SHALL BE PROVIDED.SURVEY SHALL BE | | | UPDATED TO SHOW THE PROPOSED ADDITION AS WELL AS THE | | | SETBACKS FROM ALL OF THE PROPERTY LINES TO THE PROPOSED | | | ADDITION. | | | | | | 2) THE PROPOSED ADDITION SHALL BE NO CLOSER THAN 6 FEET | | | TO THE ACCESSORY STRUCTURE (I.E. SHED). | | | | | | 3) THE SIDE SETBACKS SHALL BE A MINIMUM OF 15 FEET | | | TOTAL. | | | | | | QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER, | | | AT (561) 822-1435. | | | |
|
|