Plan Review Details - Permit 07030135
Plan Review Stops For Permit 07030135
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-08-18 Cont ID  
Sent By mjacobs Date 2007-08-18 Time 10:39 Rev Time 0.00
Received By mjacobs Date 2007-08-18 Time 07:17 Sent To PC
Notes
2007-08-18 07:38:35BUILDING PLAN REVIEW
 PERMIT: 07030135
 ADD: 716 NATHAN HALE RD
 CONT: GUERRERO ALFREDO (OWNER)
 TEL: (561)588-9658
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)108.3*THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS
 ICC (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS.
  
 3)OK
  
 4)OK
  
 NEW******
 A)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 B) SHEET #11 THE CODE REFERENCE SECTION 1606 WIND LOAD
 SCHEDULE AND DESIGN CRITERIA 1606.2 IS FROM THE 2001
 FBC. ALL PLANS SUBMITTED AFTER OCTOBER, 1, 2004 SHALL
 BE DESIGNED TO THE 2004 FLORIDA BUILDING CODE. SEE 2004
 FBC SECT.1609 FOR MORE INFORMATION.
  
 C)TWO SETS OF PRODUCT OF PRODUCT APPROVAL SHALL BE
 SUBMITTED TO THE CITY. WHEN THE PERMIT IS ISSUED, ONE
 SET WILL BE RETAIN AND OTHER WILL BE RETURN TO THE
 COUSTOMER. ONLY ONE SET IS IN THE PACKAGE.
  
 D) ADDITIONAL FEES ARE DUE $268.77
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-14 Cont ID  
Sent By mperson Date 2007-04-14 Time 14:31 Rev Time 0.00
Received By mjacobs Date 2007-04-13 Time 17:07 Sent To PC
Notes
2007-04-13 19:03:35BUILDING PLAN REVIEW
 PERMIT: 07030135
 ADD: 716 NATHAN HALE RD
 CONT: GUERRERO ALFREDO (OWNER)
 TEL: (561)588-9658
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)108.3*THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS
 ICC (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS.
  
 3)106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. THE PRODUCT APPROVALS SHALL
 APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 4)SHEET #5 INDICATE A DETAIL #1 ON SHEET #5, HOWEVER
 THERE IS NO DETAIL ON THAT PAGE. THE DETAIL REFERENCES
 SHALL REFERENCE THE CORRECT PAGES. CLARIFY. SHEET #6
 HAS THE SAME PROBLEM. DETAIL 1 OF 5 ON SHEET #6 ATTHE
 CORNERS CANNOT HAVE THE SAME TYPE OF CONNECTION AS THE
 POSTS IN THE MIDDLE OF THE PROJECT. SEE THE USP CATALOG
 ANDCLARIFY THE DETAILS. THESE DETAILS SHALL BE
 CLEAR.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-03-12 Cont ID  
Sent By btrobaug Date 2007-03-12 Time 15:04 Rev Time 0.33
Received By btrobaug Date 2007-03-12 Time 14:57 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-08-16 Cont ID  
Sent By adarroug Date 2007-08-16 Time 09:49 Rev Time 0.00
Received By adarroug Date 2007-08-16 Time 09:49 Sent To B
Notes
2007-08-16 09:49:26TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-16 Cont ID  
Sent By jroach Date 2007-08-15 Time 17:51 Rev Time 0.00
Received By adarroug Date 2007-07-16 Time 14:49 Sent To P
Notes
2007-07-16 14:50:51TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-09 Cont ID  
Sent By adarroug Date 2007-03-09 Time 10:55 Rev Time 0.00
Received By adarroug Date 2007-03-09 Time 10:55 Sent To E
Notes
2007-03-09 10:55:53TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2007-03-06 Time 14:04 Sent To  
Notes
2007-03-06 14:06:01TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-03-14 Cont ID  
Sent By tgordon Date 2007-03-14 Time 08:53 Rev Time 0.20
Received By tgordon Date 2007-03-14 Time 08:53 Sent To P
Notes
2007-03-14 08:57:01*** PROVISO ***
 1) MECHANICAL PERMIT WILL BE NEED FOR BATHROOM EXHAUST
 FAN.
  
 2)NO MECHANICAL PLANS SUBMITTED, AND NO MECHANICAL
 PERMIT NUMBER APPLIED FOR AT THIS TIME.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-07-31 Cont ID  
Sent By mperson Date 2007-07-31 Time 13:05 Rev Time 0.33
Received By mperson Date 2007-07-31 Time 13:05 Sent To Z
Notes
2007-07-31 13:30:44****************PROVISO****************
 PER FBC-2004 PLUMBING SECTIONS 424.3 AND P2708.3 SHOWER
 VALVES: SHOWER AND TUB/SHOWER COMBINATIONS SHALL BE
 EQUIPPED WITH CONTROL VALVES OF THE PRESSURE BALANCE,
 THE THERMOSTATIC MIXING OR THE COMBINATION PRESSURE
 BALANCE/THERMOSTATIC MIXING VALVE TYPES WITH HIGH LIMIT
 STOPS IN ACCORDANCE WITH ASSE 1016. THE HIGH LIMIT
 STOPS SHALL BE SET TO LIMIT WATER TEMPERATURE TO A
 MAXIMUM 120 DEGREES FAHRENHEIT.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-16 Cont ID  
Sent By mperson Date 2007-03-16 Time 14:31 Rev Time 0.45
Received By mperson Date 2007-03-16 Time 14:31 Sent To B
Notes
2007-03-16 15:08:22DENIED
 REFERENCE: FBC-2004 PLUMBING;FBC-2004 CHAPTER 1, THE
 CITY OF WEST PALM BEACH AMENDMENTS;
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 13, SANITARY ISOMETRIC RISER DIAGRAM.PER
 FBC-2004 CHAPTER 1, SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 A} SANITARY ISOMETRIC RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN OF SHEET 2 AND IS NOT CODE COMPLIANT.
  
 B} FIXTURES ARE IDENTIFIED WRONG, SHEET 2 FIXTURES ARE
 A LAVATORY, WATER CLOSET, AND A SHOWER. SHEET 13
 SANITARY RISER DIAGRAM INDICATES A SINK, WATER CLOSET
 AND A TUB. PLEASE CORRECT AND RESUBMIT.
  
 C} SANITARY RISER DIAGRAM ON SHEET 13 IS INDICATING A
 DOUBLE SANITARY TEE PER FBC-2004 PLUMBING SECTION 706.3
 IS ILLEGAL ON A HORIZONTAL INSTALLATION. PLEASE CORRECT
 AND RESUBMIT.
  
 D} 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A TWO-WAY
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER. PLEASE ADD TO
 THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL. PLEASE REFERENCE THE ATTACHED SANITARY
 ISOMETRIC RISER DIAGRAM TO THE PLUMBING COMMENTS THAT
 REFLECTS THE FLOOR PLAN AND IS CODE COMPLIANT.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  

Review Stop Z ZONING
Rev No 2 Status F Date 2007-08-15 Cont ID  
Sent By jroach Date 2007-08-15 Time 17:50 Rev Time 0.00
Received By jroach Date 2007-08-15 Time 17:50 Sent To I
Notes
2007-08-15 17:51:33***FAILED***
  
 1) CURRENT SURVEY SHALL BE PROVIDED.SURVEY SHALL BE
 UPDATED TO SHOW THE PROPOSED ADDITION AS WELL AS THE
 SETBACKS FROM ALL OF THE PROPERTY LINES TO THE PROPOSED
 ADDITION.
  
 2) THE PROPOSED ADDITION SHALL BE NO CLOSER THAN 6 FEET
 TO THE ACCESSORY STRUCTURE (I.E. SHED).IF THIS
 STRUCTURE IS NO LONGER ON THE PROPERTY, THE CURRENT
 SURVEY SHOULD REFLECT THIS.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-08 Cont ID  
Sent By jroach Date 2007-03-08 Time 11:30 Rev Time 0.00
Received By jroach Date 2007-03-08 Time 11:30 Sent To I
Notes
2007-03-08 13:06:53***FAILED***
  
 1) CURRENT SURVEY SHALL BE PROVIDED.SURVEY SHALL BE
 UPDATED TO SHOW THE PROPOSED ADDITION AS WELL AS THE
 SETBACKS FROM ALL OF THE PROPERTY LINES TO THE PROPOSED
 ADDITION.
  
 2) THE PROPOSED ADDITION SHALL BE NO CLOSER THAN 6 FEET
 TO THE ACCESSORY STRUCTURE (I.E. SHED).
  
 3) THE SIDE SETBACKS SHALL BE A MINIMUM OF 15 FEET
 TOTAL.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.
  