 |
Plan Review Details - Permit 07030094
| Plan Review Stops For Permit 07030094 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-10-28 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2007-10-28 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2007-10-28 |
Time |
12:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-08-15 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-08-15 |
Time |
16:17 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2007-08-15 |
Time |
16:17 |
Sent To |
PC |
|
| Notes |
| 2007-08-15 16:19:21 | BUILDING PLAN REVIEW | | | PERMIT: 07030094 | | | ADD: 851 VILLAGE BLVD# 502 | | | CONT: "PLAN REVIEW" | | | TEL: (859)223-1000 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 3RDREVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2-5C) COMPLIED. | | | | | | 5D) 5D)THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER | | | 6, TABLE 503 & 601 . THIS WOULD BE FOR THE BUILDING, | | | NOT THE TENANT SPACE. NOTE ALSO THERE MAY 4 HR FIRE | | | WALLS THAT BREAKS THE BUILDING TRUELY INTO SEPERATE | | | BUILDINGS. THE COVER SHEET INDICATES THAT THE TENANT | | | SPACE IS 2500 SQ FT. THE ISSUE IS NOT PROVIDING THE | | | BUILDING TYPE FOR THE "BUILDING" NOT THE TENANT SPACE. | | | SECTION 504.2 DOES PROVIDE FOR UNLIMITED AREA FOR | | | SPRINKLED BUILDINGS OCCUPANCY TYPE B,F,M OR S AND GROUP | | | A-4 FOR ONE STORY BUILDINGS. | | | PLEASE PROVIDE THE SQUARE FOOTAGE OF THE BUILDING AND | | | ANY AREA INCREASES TAKEN. | | | | | | 6-9) COMPLIED. | | | | | | 10)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, | | | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE | | | ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY | | | OF THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE INFORMATION. | | | | | | BUILDING PLAN REVIEW II | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-06-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-06-19 |
Time |
08:07 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2007-06-19 |
Time |
08:07 |
Sent To |
|
|
| Notes |
| 2007-06-19 08:30:13 | BUILDING PLAN REVIEW | | | PERMIT: 07030094 | | | ADD: 851 VILLAGE BLVD# 502 | | | CONT: "PLAN REVIEW" | | | TEL: (859)223-1000 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID.NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) PLEASE EXCUSE MY SHORTING THE VERBAGE WHEN IT | | | SHOULN'T HAVE BEEN, THECOVER SHEET CODE SUMMARY | | | PLEASE REFER TO THE "2004 FBC, WITH 2006 REVISIONS. | | | PLANS SUBMITTED AFTER DEC. 8 2006 WILL BE REVIEWED | | | UNDER THENEW 2006 EDITION OF FBC. | | | | | | 4) PLEASE EXCUSE MY SHORTING THE VERBAGE WHEN IT | | | SHOULN'T HAVE BEEN, THECOVER SHEET CODE SUMMARY LIST | | | THE 2006 ACCESSIBILITY CODE, THE SUMMARY SHOULD READ | | | THE2004 FBC WITH 2006 REVISIONS TO CHAPTER 11 . | | | | | | 5A-C) COMPLIED. | | | | | | 5D)THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6, | | | TABLE 503 & 601 . THIS WOULD BE FOR THE BUILDING, NOT | | | THE TENANT SPACE. NOTE ALSO THERE MAY 4 HR FIRE WALLS | | | THAT BREAKS THE BUILDING TRUELY INTO SEPERATE | | | BUILDINGS. | | | | | | 5F-G) COMPLIED. | | | | | | 6) COMPLIED. | | | | | | 7) COMPLIED. | | | | | | 8) COMPLIED, THE SCOPE OF WORK DOES NOT INCLUDE THE | | | REPLACEMENT OF EXTERIOR DOORS. | | | | | | 9) COMPLIED. | | | | | | 10) THIS MAY BE A CHANGE OF OCCUPANCY, PLANS ARE TO BE | | | SUBMITTED TO THE PALM BEACH COUNTY IMPACT FEE OFFICE | | | FOR ASSESSMENT BEFORE THIS PERMIT MAY BE ISSUED. | | | | | | BUILDING PLAN REVIEW II | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-04-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-04-02 |
Time |
11:49 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2007-04-02 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2007-04-02 14:04:22 | BUILDING PLAN REVIEW | | | PERMIT: 07030094 | | | ADD: 851 VILLAGE BLVD# 502 | | | CONT: "PLAN REVIEW" | | | TEL: (859)223-1000 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2006 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | 2) FL S S 713.13 | | | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF | | | THE COURT. | | | NOTE: 713.13(2) | | | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS | | | NOT ACTUALLY | | | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, | | | SUCH NOTICE IS NULL & VOID. | | | NOTE: 713.13(6)THE POSTING OF THE NOTICE OF | | | COMMENCEMENT AT THE CONSTRUCTION | | | SITE BEFORE THE FIRST INSPECTION. | | | | | | 3) COVER SHEET CODE SUMMARY PLEASE REFER TO THE | | | 2006FBC, | | | PLANS SUBMITTED AFTER DEC. 8 2006 WILL BE REVIEWED | | | UNDER THE | | | NEW 2006 EDITION OF FBC. | | | | | | 4) COVER SHEET CODE SUMMARY LIST THE 2001 ACCESSIBILITY | | | CODE, 2006 FBC CHAPTER 11 IS THE | | | DOJ APPROVED ACCESSIBILITY CODE. | | | | | | 5) 110.2* W. P. B. ADMINISTRATIVE | | | CODE, INFORMATION THAT IS REQUIRED FOR | | | RECORD KEEPING & FOR CERTIFICATE OF | | | OCCUPANCY: | | | A) THE EDITION OFTHE CODE UNDER WHICH | | | THE PERMIT WILL BEISSUED. | | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | | WITH THE PROVISIONS OF CHAPTER 3. | | | C) WAS THIS A RESTARAUNT OR CAFETERIA USE BEFORE? D) | | | THE TYPE OF CONSTRUCTION AS DEFINED | | | IN CHAPTER 6, TABLE 601 & TABLE 503. | | | NOTE!!! THIS IS FOR THE BUILDING NOT TENANT SPACE!E) | | | THE OCCUPANT LOAD, SEE 1004. | | | F) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | | IS REQUIRED. | | | G) ANY SPECIAL STIPULATIONS & CONDITIONS | | | OF THE BUILDING PERMIT. | | | | | | 6)FOOD SEERVICE LINE, SHEET A2 DETAIL 04 INDICATES | | | THE FOOD SEERVICE LINE AT A HIGH GREATER THAN 36" FROM | | | FINISH FLOOR. | | | 11-5.5 FOOD SERVICE LINES. | | | FOOD SERVICE LINES SHALL HAVE A MINIMUM CLEAR WIDTH OF | | | 36 INCHES (915 MM), WITH A PREFERRED CLEAR WIDTH OF 42 | | | INCHES (1065 MM) TO ALLOW PASSAGE AROUND A PERSON USING | | | A WHEELCHAIR. TRAY SLIDES SHALL BE MOUNTED NO HIGHER | | | THAN 34 INCHES (865 MM) ABOVE THE FLOOR (SEE FIGURE | | | 11-53 ). IF SELF-SERVICE SHELVES ARE PROVIDED, AT LEAST | | | 50 PERCENT OF EACH TYPE MUST BE WITHIN REACH RANGES | | | SPECIFIED IN SECTIONS 11-4.2.5 AND 11-4.2.6 . | | | | | | 7) 11-5.1 PROVIDE AT LEAST 5% ACCESSIBLE SETING. | | | 11-4.33.3 ALSO PROVIDE COMPANION SEATING 11-4.33.3. | | | | | | 8)SHEET A-4.0 ENTRY DOOR DETAIL # 1 INDICATES THAT | | | DOORS ARE TO BE REUSED WHERE POSSIBLE. STATE EITHER TO | | | REMAIN OR BE REPLACED. IF REPLACED: | | | FL BLD CODE 1609.1.4: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | GLAZED FRONT ENTRY DOORS | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | WPB ADMIN CODE 106.3* PRODUCT | | | APPROVALS. THOSE PRODUCT WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL. | | | | | | 9)CARDINAL POINT IS MISSING THEIR CERTIFICATE OF | | | AUTHORIZATION NUMBER; | | | 481.219 F.S.CERTIFICATE OF | | | AUTHORIZATION.THE TITLE BLOCK FOR ANY | | | SHEET BEARING THE NAME OF AN ARCHITECT | | | PRACTICING UNDER A FICTITIOUS NAME, A | | | CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL | | | SERVICES, SHALL INCLUDE | | | THE CERTIFICATE OF AUTHORIZATION | | | NUMBER.ADD THE NUMBER TO EACH SHEET. | | | THIS MAY BE ADDED BY HAND. | | | | | | 10) DEPENDING ON THE ANSWER TO QUESTION # 3C:BEFORE A | | | PERMIT TO CONSTRUCT, MAY | | | BE ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER C. B. O. | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | | | | | | | | | | , |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2008-02-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-02-09 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-02-09 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2008-02-11 08:29:04 | ** DENIED REVISION ** | | | 1) NOTE:PLEASE SEE THE REVISIONS IN TITLE BLOCKS DO | | | NOT CORRELATE WITH PLANS. ELECTRICAL PLANS SEEM TO | | | INDICATE NOT ONLY A CLOUD FOR A REVISION FOUR WHICH IS | | | NOT ON TITLE BLOCKS AS MENTION BUT ALSO SEEMS TO CLOUD | | | OTHER ITEMS SUCH AS LIGHTING WHICH SEEMS TO INDICATE A | | | REVISION. | | | PLEASE KNOW IF THE LIGHTING FIXTURES, NUMBER OF | | | FIXTURES ETC HAVE BEEN CHANGED PLEASE SUBMIT REVISED | | | LIGHTING PERFORMANCE CALCULATIONS AS REQUIRED PER | | | 13-415.2 | | | PLEASE REVISE SHEETS TO REFLECT CHANGES AND | | | COORDINATION WITH TITLE BLOCKS. | | | FBC 106.1.2, 106.5 FOR COORDINATION AND ADDITIONAL | | | INFORMATION. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2007-10-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-10-18 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-10-18 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2007-10-18 14:22:26 | REDLINED ENERGY CALCULATIONS AS METHOD OF CONTROL SHOWN | | | FOR DINING ROOM IS SHWON AS *MANUAL ON/OFF* WHEN AN | | | AUTOMATED SYSTEM IS SHOWN. | | | THESE CAN BE REVISED AT LATER DATE AND BEFORE FINAL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2007-08-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-08-12 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-08-12 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2007-08-12 12:20:35 | | | | ** DENIED 3RD TIME ** | | | | | | 2ND REVIEW UNDER PERMIT APPLICATION. | | | | | | ** PLEASE SEE THAT SOME NOTES FROM PREVIOUS REVIEW ARE | | | STILL IN NEED OF ADDRESSING. | | | | | | 1) NOTE: PLEASE SEE THE LETTERS NOW SUBMITTED FOR | | | SIGNATURE VERIFICATION NOT DATED AND SEALED WHEN | | | SIGNED. IF THIS WAS THE ONLY ITEM, THESE COULD BE | | | MAILED IN TO THIS OFFICE HOWEVER AS THE PLANS HAVE | | | OTHER COMMENTS PLEASE SUBMIT. | | | FS 481.221, 471.025 | | | | | | 2) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC | | | CHAPTER 13 IS STILL IN NEED OF ADDRESSING. | | | PLEASE SEE THE LIGHTING REFLECT CEILING PLAN ON SHEET | | | A1.4 DOES NOT COORDINATE WITH THE ELECTRICAL LIGHTING | | | PLANS? | | | PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED WERE ONCE | | | AGAIN NOT SEALED BY THE DESIGN PROFESSIONAL AS STATED | | | ON THE TWO PREVIOUS REVIEWS. THIS WAS SPECIFICALLY | | | MENTIONED ON THE TWO PREVIOUS REVIEWS AS THIS IS | | | REQUIRED PER THE FLORIDA BUILDING CODE AND FLORIDA | | | STATUTES. THESE WERE SIGNED BUT WERE NOT SEALED AND | | | DATED. | | | PLEASE ALSO SEE THE *OWNER AGENT* IS ALSO NOT SIGNED ON | | | SHEETS. | | | PLEASE SEE THE PREVIOUS NOTE WHICH REQUIRES THE | | | DESIGNER(S) OF RECORD RESPONSIBLE FOR SCOPE OF WORK TO | | | *SIGN, DATE AND SEAL* SAID DOCUMENTS. THIS IS NOT ONLY | | | REQUIRED PER FS 471.025, 481.221, FAC 61G15-23, 61G1-16 | | | BUT ALSO FBC 13-103.1.1.1. | | | | | | PLEASE SEE THE FIXTURES AND WATTAGES AS SHOWN ON ENERGY | | | CALCULATIONS DO NOT CORRELATE WITH THE SUBMITTED PLANS | | | AND FIXTURE LEGEND(S). | | | PLEASE SEE THE TWO PREVIOUS REVIEWS WHICH WERE MARKED | | | WITH AN ASTERISK ** FOR 13-415.2.ABC.1.2 SPECIFICALLY | | | FOR TRACK LIGHTING, HOWEVER THE WATTAGE ON THE ENERGY | | | CALCULATIONS NEED TO BE ADJUSTED. | | | PLEASE SEE THAT THE WATTAGE USED MUST BE THE WATTAGE OF | | | THE TRACK LIGHTING HEADS WITH A *MINIMUM* OF 30VA PER | | | FT. THIS MEANS WHICH EVER FIGURE IS HIGHER BASED ON THE | | | MINIMUM OF THE TWO. | | | EXAMPLE: | | | IF THE TOTAL NUMBER OF TRACK FIXTURES WERE 100 AND EACH | | | WAS 75WATTS EACH THIS WOULD BE 7500VA. | | | IF THE TOTAL LENGTH OF THE TRACK WAS 300FT AND THE | | | MINIMUM PER FOOT OF TRACK AS STATED FROM THE FBC WAS | | | 30VA PER FT, THEN THE TOTAL OF 9000VA WOULD BE | | | REQUIRED. | | | ** PLEASE SEE THE TOTAL LENGTH OFTRACK PER LINEAR | | | FEET ON PLANS WITH THE 30VA MINIMUM PER FOOT EXCEEDS | | | THE TOTAL WATTAGE OF THE TRACK HEADS BEING USED IN THE | | | CALCULATIONS.(PLEASE ADJUST). | | | | | | 3) NOTE: PLEASE SEE THE TWO PREVIOUS REVIEWS STATED | | | THAT *NO**EQUIPMENT GROUNDING CONDUCTOR* IS PERMITTED | | | BEFORE THE FIRST MEANS OF DISCONNECT YET THE RISER | | | STILL INDICATES THIS CONDUCTOR ON THE LINE SIDE OF THE | | | SERVICE MAIN. | | | PLEASE SEE 250.6 AND 250.24B. PLEASE KNOW IF THIS | | | CONDUCTOR IS INSTALLED ON THE LINE SIDE OF THE MAIN AND | | | THE MAIN THE GROUNDED CONDUCTOR IS BONDED AS REQUIRED | | | PER 250.24B, THEN THIS WOULD CREATE A PARALLEL PATH | | | WITH THE NEUTRAL(GROUNDED) CONDUCTOR AND THEREFORE | | | CREATING *OBJECTIONABLE CURRENTS* AS STATED IN 250.6 OF | | | THE NEC. | | | PLEASE REMOVE. | | | | | | 4) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH | | | RESPECT TO DESIGN PROFESSIONALS AND REPEAT CODE | | | COMPLIANT COMMENTS. AS THE PLANS WERE SUBMITTED FOR | | | ONLY *PLAN REVIEW* THE FIRST TIME, THIS IS NOT ASSESSED | | | AT THIS TIME. PLEASE KNOW IF THE PLANS ARE RESUBMITTED | | | WITH OUT THE ABOVE NOTES #2 AND #3 BEING ADDRESSED THIS | | | OFFICE WILL BE REQUIRED PER THE ABOVE FLORIDA STATUTES | | | TO ASSESS THE FOUR TIMES PLAN REVIEW FEE FOR THE | | | PORTION OF THE PERMIT FEE ATTRIBUTED TO PLAN REVIEW. | | | THIS ISTO THE DESIGN PROFESSIONAL. | | | THIS FEE WOULD NOT BE THE RESPONSIBILITY OF THE OWNER | | | OR CONTRACTOR. | | | THIS IS ONLY A NOTICE AT THIS TIME. | | | PLEASE ALSO KNOW ONE SET OF ELECTRICAL PLANS AND ENERGY | | | CALCULATIONS ARE BEING RETAINED BY THIS OFFICE AT THIS | | | TIME. | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2007-06-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-06-05 |
Time |
18:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-06-05 |
Time |
16:39 |
Sent To |
|
|
| Notes |
| 2007-06-05 18:57:10 | ** UNSAT ** | | | | | | *** PLEASE KNOW THAT AS SOME ITEMS ARE NOT SHOWN FOR | | | CODE COMPLIANCE AT THIS TIME OR MISSING FOR REVIEW, | | | THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW NOT | | | YET ABLE TO BE MADE. | | | | | | ** PLEASE ALSO SEE THERE ARE SEVERAL ITEMS FROM | | | PREVIOUS REVIEW WHICH ARE IN NEED OF ADDRESSING AND NEW | | | COMMENTS BASED ON REVISED SHEETS OR SUBMITTED DOCUMENTS | | | WHICH WERE NOT THE SAME AS PREVIUS SUBMITTED PLANS. | | | | | | ** PLANS HAVE NOW BEEN SUBMITTED FOR PERMIT. | | | | | | 1) NOTE:PLEASE SEE THE CODES AS STATED ON THE COVER | | | SHEETS INDICATE 2004 FBC WITH 2006 WPB AND PB | | | AMENDMENTS WHICH SHOULD INDICATE THE *2006 REVISIONS*. | | | THESE 2006 REVISIONS ARE REVISIONS ADOPTED BY THE STATE | | | FOR THE FLORIDA BUILDING CODE AS OF DECEMBER 8TH, 2006. | | | PLEASE SEE WPB AND PB IS TWO SEPARATE MUNICIPALITIES. | | | PLEASE SEE THE ADA IS REFERENCING A 2006 FBC ? SHOULD | | | NOT THIS ALSO READ THE2004 FBC W/ 2006 REVISIONS. | | | PLEASE SEE OTHER POSSIBLE COMMENTS FROM OTHER TRADES. | | | | | | | | | 2) NOTE: PLEASE SEE THE LETTER INDICATING THE USE OF | | | MULTIPLE SIGNATURES AS THE LEGAL SIGNATURE OF THE | | | SINGLE ARCHITECT OF RECORD FOR FILE IS NOT ACCEPTABLE. | | | THIS MAY ONLY BE THE LEGAL SIGNATURE OF THE DESIGNER. | | | PLEASE SEE THE COMMENT WITH RESPECT TO THE ENERGY | | | CALCULATIONS AS THESE ARE SIGNED AND SEALED HOWEVER ARE | | | NOT SIGNED WITH EITHER OF THE SIGNATURES ON LETTER AND | | | IN FACT THIS *SIGNATURE* IS COMPLETELY DIFFERENT. | | | PLEASE SEE THE FLORIDA STATUTES WHICH REQUIRES THE | | | ORIGINAL SIGNATURE, DATE AND SEAL ON DOCUMENTS. THIS | | | WAS NOT DONE AND DOCUMENTS WILL BE RETAINED BY THIS | | | OFFICE. | | | | | | 3) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS | | | AS REQUIRED UNDER FLORIDA ADMINISTRATIVE CODE | | | 61G1523.002 FOR THE ENGINEER OF RECORD. PLEASE SEE THE | | | MISSING PRINTED NAME AND PRINTED LICENSE NUMBER. | | | | | | 4) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC | | | CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1, | | | .1.2 AND .1.3. | | | PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO NOT | | | CONTAIN THE MOST RECENT ADOPTED VERSION PER THE FBC. | | | PLEASE SEE THE PREVIOUS NOTE WHICH REQUIRES THE | | | DESIGNER(S) OF RECORD RESPONSIBLE FOR SCOPE OF WORK TO | | | *SIGN, DATE AND SEAL* SAID DOCUMENTS. THIS IS NOT ONLY | | | REQUIRED PER FS 471.025, 481.221, FAC 61G15-23, 61G1-16 | | | BUT ALSO FBC 13-103.1.1.1. | | | PLEASE SEE THE FIXTURES AND WATTAGES AS SHOWN ON ENERGY | | | CALCULATIONS DO NOT CORRELATE WITH THE SUBMITTED PLANS | | | AND FIXTURE LEGEND(S). | | | PLEASE SEE THE TWO FIXTURE LEGENDS AS SUBMITTED ON THE | | | ARCHITECTURAL AND ELECTRICAL PLANS DO NOT CORRELATE. | | | PLEASE SEE THE LIGHTING CONTROL METHODS ON THE ENERGY | | | CALCULATIONS DOES NOT CORRELATE WITH PLANS AS THESE ARE | | | INDICATING *MANUAL ON/OFF8 WHICH IS NOT POSSIBLE WHEN | | | THE PLANS INDICATE *AUTOMATED* MEANS. PLEASE ADJUST AND | | | COORDINATE. | | | PLEASE SUBMIT THE TIME SCHEDULING. | | | PLEASE INDICATE THE REQUIRED OVER RIDE DEVICES AND | | | LOCATION PER CODE. | | | PLEASE INDICATE AND SHOW LOCATIONS OF DEVICES FOR | | | SEPARATE SPACES. | | | PLEASE INDICATE ALL OVER RIDE TIMES FOR DEVICES CHOSEN | | | IN THE DESIGN. THE TIMES FOR OVER RIDES CAN NOT BE | | | REVIEWED UNTIL A DEVICE IS SHOWN. PLEASE INDICATE | | | OCCUPANCY TYPE DEVICES OR TIMER OVER RIDES. PLEASE | | | INDICATE THE TIMES AS CODE PERMITS 4HRS MAXIMUM ON | | | TIMER/MANUAL OVER RIDES AND 30 MINS FOR OS TYPE | | | DEVICES. | | | PLEASE SEE THE TYPE OF FIXTURES ON PLANS NEED TO | | | COORDINATE WITH THE ENERGY CALCULATIONS. | | | PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING MINIMUM | | | TO BE FIGURED. | | | PLEASE SEE 13-415.1.AB.1.1, 13-415.2 | | | *** PLEASE BE SURE TO SEE 13-415.2.ABC.1.2** | | | | | | 5) NOTE: PLEASE SEE AS MENTIONED ON THE PREVIOUS | | | REVIEW, THE APPLIED VALUE MUST INCLUDE ALL LABOR, | | | MATERIALS AND EQUIPMENT PERMANENTLY INSTALLED EVEN IF | | | ANY OF THE ABOVE IS OWNER SUPPLIED. THE VALUE FOR SCOPE | | | OF WORK IS LOW. | | | PLEASE SEE FBC 108. | | | | | | 6) NOTE: PLEASE KNOW THAT ANY PHONE/CATV LOW VOLTAGE | | | WILL BE UNDER SEPARATE PERMIT. THESE PLANS MAY BE | | | REFERENCED FOR A TURN AROUND PERMIT. THE FEES FOR THE | | | LV PERMIT ARE SEPARATE. | | | | | | 7) NOTE: PLEASE SEE RISER STILL SHOWS AN *EQUIPMENT | | | GROUNDING CONDUCTOR* BEING INSTALLED BEFORE THE FIRST | | | MEANS OF DISCONNECT WHICH WILL CAUSE OBJECTIONABLE | | | CURRENTS. PLEASE SEE 250.6 AND 250.24B. PLEASE REMOVE. | | | | | | 8) NOTE: PLEASE SEE THE CIRCUITING FOR THE SHOW WINDOW | | | RECEPTACLES AS THE CIRCUITS TO PANEL INDICATE 14 AND | | | 16, YET THE PLANS INDICATE CIRCUITS 16 AT BOTH | | | LOCATIONS. | | | PLEASE COORDINATE. | | | FBC 106.1.2 | | | | | | 9) NOTE: PLEASE PROVIDE THE LOAD ANALYSIS/LOAD SUMMARY | | | OF THE LOADS SHOWN FOR THE SERVICE FOR SPACE #502. | | | PLEASE SEE THE LOADS FOR TRACK LIGHTING, NORMAL | | | LIGHTING AND OTHER LIGHTING DO NOT ADD UP TO THE | | | FIGURES ACCORDING TO THE NEC FOR MINIMUM LOADS TO BE | | | FIGURED. | | | PLEASE SEE THE CODE SECTIONS GIVEN ON PREVIOUS REVIEW | | | AND SHOW A BREAKDOWN ON HOW LOADS WERE DERIVED. THIS | | | REVIEWER WENT THROUGH THE CALCULATIONS TWICE AND CAME | | | UP WITH FIGURES WHICH ARE LARGER THAN SHOWN. PLEASE | | | INCLUDE THE KW RATINGS FOR A/C. PLEASE ALSO SEE 424.3B | | | AS THE OCP FOR EACH OF THESE UNITS WHICH CONTAIN HEAT | | | WILL REQUIRE THE SIZING AT 125% FOR MINIMUM OCP. PLEASE | | | SEE THE LOAD FOR THE UNOCCUPIED SPACE MUST BE FIGURED | | | INTO THE SPACE. THIS IS A MINIMUM LOAD FOR SERVICE. IT | | | HAS NO RELEVANCE THAT THE SPACE IS NOT OCCUPIED, AS IT | | | MAY BE BY NOW, NEXT WEEK OR ANYTIME THERE AFTER. IF THE | | | SPACE IS FED FROM THE SAME SERVICE THEN THE SERVICE | | | MUST INCLUDE THE MINIMUM LOADS PER CODE. PLEASE | | | ADJUST. | | | PLEASE SEE 220.12, 220.14, 220.42, 220.44, 220.43 | | | B.ETC. | | | 215.5, FBC 106.3.5.1.2, 106.1.2 | | | | | | 10) NOTE: PLEASE PROVIDE AIC RATING FOR NEW MAIN. | | | 110.9. THIS IS THE SAME NOTE. THE RATINGS ARE SHOWN FOR | | | PANELS, BUT NOT FOR MAINS. (PLEASE VERIFY THE 65K | | | RATING SHOWN FOR THE EXISTING AND NEW PANELS AND BRANCH | | | BREAKERS. AS THERE IS A RATING ABOVE THE 29K OF COMMON | | | SIZE WHICH HAS A SUBSTANTIALLY LESS EXPENSE) (THIS IS | | | ONLY NOTED AS THE HIGHER RATING MAY BE INSTALLED AND | | | DOES NOT VIOLATE THE CODE IN ANY WAY). PLEASE KNOW IF | | | THE PLANS CALL FOR THIS RATING, THEN THIS WILL BE | | | REQUIRED.) | | | FBC 106.3.5.1.2 | | | | | | 11) NOTE: PLEASE SEE 210.8B2 AS ALL RECEPTACLES IN | | | KITCHENS AND AREAS OF THE LIKE ALONG WITH FOOD PREP | | | SHALL BE GFI/ GFI PROTECTED. | | | NO CHANGES COULD BE LOCATED ON PLANS FOR THIS. | | | | | | 12) NOTE:PLEASE LABEL ALL MAINS FOR SERVICE. ( 1OF 5, | | | 3 OF 5 ETC). | | | FBC 106.1.2 , NEC 230.2E | | | PLEASE INDICATE THE LOCATION OF THE NEW PROPOSED MAIN. | | | THIS IS REQUIRED TO BE GROUPED PER 230.72 | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-03-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-03-11 |
Time |
12:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-03-11 |
Time |
11:52 |
Sent To |
|
|
| Notes |
| 2007-03-11 12:55:27 | ** UNSAT** | | | | | | ** PLEASE KNOW THAT PLANS HAVE ONLY BEEN SUBMITTED FOR | | | A *PLAN REVIEW* ONLY AND HAVE NOT BEEN SUBMITTED FOR | | | PERMIT. | | | PLEASE KNOW THAT EVEN IF AND WHEN PLANS ARE CODE | | | COMPLIANT, PLANS WILL STILL REMAIN IN A *FAILED* STATUS | | | UNTIL PERMIT APPLICATION, FEES ETC HAVE BEEN DONE. | | | | | | ** PLEASE KNOW AS THERE ARE MANY ITEMS NOT YET | | | SUBMITTED FOR REVIEW, NEW COMMENTS MAY BE POSSIBLE ON | | | THE FOLLOW UP REVIEW AS REVIEW OF MANY OF THESE ITEMS | | | CAN NOT BE DONE AT THIS TIME. | | | | | | | | | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH | | | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS | | | UNDER THE NEW CODES ADOPTED BY THE STATE. | | | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO | | | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. | | | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY | | | AFFECT DESIGNS FOR ALL TRADES. | | | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS | | | REVIEWER AT A MINIMUM. THIS WOULD INCLUDE A-SHEETS AS | | | WELL AS E-SHEETS. | | | 2004 FBC W/ 2006 REVISIONS. | | | 2005 NFPA-70 | | | 2002 NFPA-72 | | | 2003 NFPA-101 | | | | | | 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS | | | AS REQUIRED UNDER FLORIDA ADMINISTRATIVE CODE | | | 61G1-16.004 AND FLORIDA STATUTES 481.219 | | | PLEASE SEE MISSING PRINTED NAME AND MISSING FIRM | | | LICENSE NUMBER ALSO KNOWN AS THE CERTIFICATE OF | | | AUTHORIZATION. | | | THIS OFFICE IS AWARE THAT APPLICATION HAS BEEN MADE TO | | | THE STATE HOWEVER MAY NOT POSSESS THE TITLE BLOCK AS | | | SHOWN UNTIL SUCH TIME A CA # FOR THE FIRM HAS BEEN | | | ISSUED. | | | *PLEASE ALSO SEE THE STATE ALSO HAS THE ADDRESS LISTED | | | IN CINCINNATI, OHIO. | | | | | | 3) NOTE: PLEASE SEE PLANS APPEAR TO BE SIGNED WITH WHAT | | | APPEARS TO BE INITIALS? IF THIS IS INDEED THE LEGAL | | | SIGNATURE, PLEASE SUBMIT A LETTER FOR SIGNATURE | | | VERIFICATION. THE LETTER WILL NEED TO BE SIGNED, DATED | | | AND SEALED ALONG WITH BEING NOTARIZED.PLEASE KNOW | | | THAT THIS LETTER MUST BE ORIGINAL. | | | PLEASE KNOW THIS WILL BE PLACED IN OUR SIGNATURE FILE | | | FOR FUTURE REFERENCE. | | | | | | 4) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC | | | CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1, | | | .1.2 AND .1.3. | | | PLEASE SEE BY DEFINITION THIS SPACE IS IN A BUILDING | | | GREATER THAN 5K SQ FT. | | | PLEASE SHOW COMPLIANCE WITH THIS AND IF THERE ARE ANY | | | QUESTIONS, PLEASE CALL TO GO OVER THIS. | | | PLEASE SUBMIT LIGHTING POWER DENSITIES PER THE 2004 FBC | | | W/ 2006 REVISION. PLEASE SEE 13-415.1.AB.1.1, 13-415.2 | | | FOR LIGHTING PERFORMANCE CALCULATIONS ALONG WITH ENERGY | | | CALCULATIONS. PLEASE SEE THE CALCULATIONS SUBMITTED ARE | | | NOT COMPLIANT AT THIS TIME ABSE DON THE INFORMATION | | | SHOWN. | | | PLEASE SEE THAT THE FIXTURE SCHEDULE SHALL BE SPECIFIC | | | FOR FIXTURES TO BE INSTALLED AND COORDINATION WITH THE | | | LPD/CALCULATIONSWHICH IS TO BE REVIEWED FOR | | | COMPLIANCE. | | | *** PLEASE BE SURE TO SEE 13-415.2.ABC.1.2** PLEASE BE | | | SURE TO HAVE THE DESIGNER OF RECORD FOR THE ENERGY | | | CALCULATIONS SIGN, DATE AND SEAL THESE AS REQUIRED PER | | | 13-103.1.1.1 THESE ARE NOT SEALED WIHT RAISED SEAL AAS | | | REQUIRED PER SECTION AS STATED. | | | | | | **PLEASE SEE NOTES ON PLANS MENTIONS SOME OF THESE | | | AREAS AS EXISTING FOR NO WORK, YET PLANS INDICATE WORK | | | BEING DONE IN THESE AREAS. | | | | | | 5) NOTE: PLEASE SEE THE VALUE WHEN APPLYING FOR PERMIT | | | SHALL INCLUDE ALL LABOR AND MATERIALS EVEN IF | | | MATERIALS/EQUIPMENT IS OWNER SUPPLIED. | | | FBC ADMIN SECTION 108.3 | | | | | | 6) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) | | | AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR | | | ADA REQUIRED AREAS. ANY DEVICE SHALL BE SHOWN ON BASE | | | PLANS EVEN THOUGH THE SCOPE OF WORK FOR ANY FIRE | | | SPRINKLER AND FIRE ALARM SYSTEMS WILL BE DONE UNDER | | | SEPARATE PERMIT. | | | **DEVICES ARE BEING SHOWN ON PLANS/LEGEND. | | | | | | 7) NOTE: PLEASE SEE RISER SHOWS AN *EQUIPMENT GROUNDING | | | CONDUCTOR* BEING INSTALLED WHICH WILL CAUSE | | | OBJECTIONABLE CURRENTS. PLEASE SEE 250.6 AND 250.24B. | | | | | | 8) NOTE: PLEASE VERIFY THE SERVICE ENTRANCE CONDUCTORS | | | AND PLACE THE INFORMATION ON RISER. PLEASE SEE THAT THE | | | RISER MAKES NOTE TO VERIFY, YET THIS INFORMATION SHALL | | | BE KNOWN AND STATED ON PLANS AT THIS TIME. | | | PLEASE ALSO SUBMIT COMPLETE LOAD CALCULATIONS ON THE | | | EXISTING SERVICE AS SHOWN WITH NEW LOAD ADDED TO | | | SERVICE. | | | PLEASE SEENEC 2005 220. | | | NEED TO VERIFY 310.16, 240.4 ETC. | | | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION. | | | | | | 9) NOTE: PLEASE SEE THE LOAD ANALYSIS WHICH STATES THE | | | 2002 NEC FOR CALCULATIONS. | | | PLEASE KNOW WE ARE UNDER THE 2005. | | | PLEASE ALSO CLARIFY ON THE LOAD CALCULATIONS FOR SPACE | | | HOW THE FOLLOWING LOADS WERE DERIVED. | | | LIGHTING? | | | TRACK LIGHTS? | | | RECEPTACLES? | | | PLEASE SEE 220.12, 220.14, 220.42, 220.44, 220.43 B. | | | | | | 10) NOTE: PLEASE PROVIDE AIC RATING FOR NEW MAIN. | | | 110.9. | | | FBC 106.3.5.1.2 | | | | | | 11) NOTE: PLEASE SEE 210.8B2 AS ALL RECEPTACLES IN | | | KITCHENS AND AREAS OF THE LIKE ALONG WITH FOOD PREP | | | SHALL BE GFI/ GFI PROTECTED. | | | | | | 12) NOTE: PLEASE PLACE THE SIZING OF THE BRANCH CIRCUIT | | | CONDUCTORS ON PANEL SCHEDULES. PLEASE SEE 310.16, | | | 240.4 | | | FBC 106.3.5.1.2, 106.1.2 | | | | | | 13) NOTE: PLEASE LABEL ALL MAINS FOR SERVICE. ( 1OF 5, | | | 3 OF 5 ETC). | | | PLEASE PLACE NOTE ON PLANS WHICH WILL REQUIRE THE | | | REMOVAL OF THE EXISTING METER AND MAIN FOR THE SPACE | | | SERVICE WHICH IS BEING REPLACED. | | | THE OLD METER AND MAIN WILL BE REQUIRED BY THIS AHJ TO | | | BE REMOVED COMPLETELY. | | | FBC 106.1.2 ADDITIONAL INFORMATION. | | | 104.6 | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2007-08-14 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-08-14 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-08-14 |
Time |
10:49 |
Sent To |
|
|
| Notes |
| 2007-08-14 10:53:02 | *****APPROVED***** | | | | | | ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | | BEEN ADDRESSED;PLAN SHEETS A1.1 AND A1.4 WERE | | | STAMPED, INITIALED, AND DATED. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2007-07-05 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-07-05 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-07-05 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2007-07-05 15:38:29 | ***DENIED*** | | | | | | FROM PREVIOUS FIRE REVIEW | | | | | | 1) OK | | | | | | 2) OK | | | | | | 3) OK | | | | | | 4) OK | | | | | | 5) OK PLEASE ADD NOTE TO PLANS FOR CLARIFICATION AS | | | THIS IS A LOCAL REQUIREMENT. PLEASE CLARIFY IF THERE IS | | | AN EXISTING FULL FIRE ALARM SYSTEM. IT IS NOTED THAT | | | THERE IS AN AUTOMATIC FIRE SPRINKLER SYSTEM THAT AT A | | | MINIMUM SHALL BE MONITORED. | | | | | | 6) OK NOTE 29 DOES NOT MENTION NFPA 96 WHICH IS | | | REFERENCED ON M3.0. PLEASE ADD TO RESPONSE OR PLANS IN | | | COMPLIANCE WITH UL 300 FOR WET CHEMICAL SYSTEMS. | | | | | | 7) OK | | | | | | NEW COMMENT | | | | | | 1) PLEASE SEE NFPA 101, SEC. 12.2.2.2.3 FOR ASSEMBLY | | | OCCUPANCIES REQUIRES PANIC OR FIRE EXIT HARDWARE ON | | | DOORS IN MEANS OF EGRESS WHERE OCCUPANT LOAD IS 100 OR | | | GREATER. NO MENTION IN DOOR SCHEDULE. IF ALREADY | | | PROVIDED AS EXISTING CONDITION, PLEASE ADVISE. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-04-12 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-04-12 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-04-12 |
Time |
10:41 |
Sent To |
|
|
| Notes |
| 2007-04-12 11:54:16 | *****DENIED***** | | | | | | | | | | | | 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.IT IS NOT INDICATED WHETHER THE TENANT SPACE HAS A | | | FIRE SPRINKLER AND/OR A FIRE ALARM SYSTEM.IF SO, ANY | | | MODIFICATIONS TO THESE SYSTEMS AS A RESULT OF THE SCOPE | | | OF WORK, WILL REQUIRE SEPARATE PLANS AND PERMIT FOR THE | | | REMODEL. | | | | | | 4. THEINTERIOR WALL AND CEILING FINISH CLASSIFICATION | | | SHALL BE CLASS A, CLASS B, OR CLASS C IN ASSEMBLY AREAS | | | HAVING AN OCCUPANT LOAD OF 300 OR FEWER.PLEASE | | | SPECIFY. | | | | | | 5.AS PER WEST PALM BEACH FIRE PREVENTION, DUCT SMOKE | | | DETECTOR SHALL INITIATE A GENERAL ALARM. | | | | | | 6.COMMERCIAL COOKING EQUIPMENT SHALL BE IN ACCORDANCE | | | WITH NFPA 96 (2001 EDIITION);SEPARATE PLANS AND PEMI | | | WILL BE REQUIRED FOR THE HOOD INSTALLATION AND THE HOOD | | | SUPPRESSION SYSTEM. | | | | | | 7.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE | | | EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE | | | REQUIREMENT. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE (IN THE PLANS) EACH COMMENT | | | WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2007-10-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-10-24 |
Time |
17:19 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-10-24 |
Time |
18:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2007-08-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-08-16 |
Time |
06:50 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-08-15 |
Time |
06:50 |
Sent To |
|
|
| Notes |
| 2007-08-16 07:15:45 | SEE PLUMBING REVIEW COMMENTS |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2007-08-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-06-15 |
Time |
06:49 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-06-15 |
Time |
06:49 |
Sent To |
|
|
| Notes |
| 2007-08-16 07:15:36 | SEE PLUMBING REVIEW COMMENTS |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2007-08-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-03-21 |
Time |
06:48 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-03-20 |
Time |
06:48 |
Sent To |
|
|
| Notes |
| 2007-08-16 07:15:25 | SEE PLUMBING REVIEW COMMENTS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-02-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-08 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-08 |
Time |
16:37 |
Sent To |
|
|
| Notes |
| 2008-02-08 16:37:48 | TO "COMM" BD#64 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2007-10-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-10-05 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-10-05 |
Time |
11:47 |
Sent To |
|
|
| Notes |
| 2007-10-05 11:48:38 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2007-07-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-07-26 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-07-26 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2007-08-07 18:38:37 | TO COMM BOARD #37 | | 2007-07-26 13:53:20 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2007-05-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-05-10 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-05-10 |
Time |
16:43 |
Sent To |
|
|
| Notes |
| 2007-05-24 16:36:59 | TO "COMM" BD#31/PLANS ON RACK--2 ROLLS | | 2007-05-10 16:43:50 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-04-12 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-04-12 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-03-07 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2007-03-08 14:17:08 | TO "COMM" BD#37 | | 2007-03-07 09:11:59 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2008-02-26 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-02-26 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-02-26 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2008-02-26 13:40:05 | SUBMITTED LETTER FROM ENGINEER, SUBSTITUTING DETAIL FOR | | | GOOSENECK VENT WITH GREENHECK MUSHROOM CAP WITH | | | BACKDRAFT DAMPER FOR BAROMETRIC RELIEF. NO DATA FOR | | | WIND LOADS WERE SUBMITTED. SUCH INFORMATION SHALL BE | | | PROVIDED PRIOR TO FINAL INSPECTION. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2007-10-19 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-10-19 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-10-19 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2007-10-19 16:17:30 | REVIEW #: | | | ACTION: | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | CONDITIONS OF ALL PROVISOS HAVE BEEN SATISFIED PRIOR TO | | | PERMIT ISSUANCE. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2007-08-10 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-08-10 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-08-10 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2007-08-10 13:21:48 | ***********PROVISO************ | | | 1) REVISE ENERGY CALCULATIONS TO SHOW CORRECT ROOF | | | ASSEMBLY AND R-VALUE PRIOR TO INSPECTION. | | | 2) PROVIDE AUXILIARY DRAIN PROTECTION (INTERNAL FLOAT | | | SWITCH, NOT SECONDARY DRAIN ON ROOF) ON RTU'S. | | | 3) RTU'S TO BE FASTENED PER SUBMITTED STRUCTURAL | | | CALCULATIONS, NOT DETAIL ON PLAN. | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2007-06-07 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-06-07 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-06-06 |
Time |
11:44 |
Sent To |
|
|
| Notes |
| 2007-06-07 08:38:28 | ---------------DENIED----------------- | | | | | | FBC 2004 CODE FAMILY W/ 2006 REVISIONS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLWOING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS FOR CONTINUITY. ADDITIONAL | | | COMMENTS ARE AT THE NED OF THIS REVIEW. | | | | | | 1. PLEASE REMOVE REFERENCE TO CODES WHICH ARE NOT | | | ADOPTED BY THE STATE OF FLORIDA SUCH AS THE IMC ANS | | | STANDARD CODES. | | | | | | 2. PRE-ENGINEERED A/C STANDS ARE STRUCTURAL ELEMNTS AS | | | DEFINED BY FAC 9B-72. PRODUCT APPROVAL IS REQUIRED. | | | PLEASE SEE WWW.FLORIDABUILDING.ORG FOR MORE INFORMATION | | | ON THE FLORIDA PRODUCT APPROVAL SYSTEM. ALSO, ASCE 7-98 | | | IS NO LONGER THE REFERENCE STANDARD UNDER THE 2004 FBC. | | | DESIGN LOADS ARE TO COMPLY WITH ASCE 7-02. | | | | | | 3. OK | | | NOTE: SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN | | | HOOD, HOOD SUPPRESSION, WALK-IN COOLER/FREEZERS. | | | | | | 4. DRAWINGS STILL DO NOT SHOW COMPLIANCE WITH FBC,M | | | 307.2.3 FOR AUXILIARY DRAIN PROTECTION. | | | | | | 5. OK | | | | | | 6.OK | | | | | | NEW COMMENTS | | | | | | A. ENERGY CALCULATIONS SHOULD BE ON FORM 400B-04R | | | GENERATED BY FLA/COM-2004 V2.5. | | | | | | B. PLANS WHICH ARE SIGNED AND SEALED BY AN ENGINEER OF | | | RECORD SHALL COMPLY WITH FAC 61G1523.002. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | | | | RONALS J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-03-28 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-03-28 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-03-27 |
Time |
19:23 |
Sent To |
|
|
| Notes |
| 2007-03-28 14:53:15 | ------------------DENIED------------------- | | | | | | FBC 2004 CODE FAMILY W/2006 REVISIONS | | | | | | 1. HVAC GENERAL NOTE 3 AND KEY NOTE 3, PLEASE REFERENCE | | | FBC,M 2004. | | | | | | 2. ROOF MOUNTED EQUIPMENT SHALL BE SECURED TO STRUCTURE | | | TO MEET 140 MPH WIND LOADS PER FBC,M 301.13 AND FBC | | | CH.16. PROVIDE WIND LOAD CALCULATIONS AND STRUCTURAL | | | DETAIL DRAWINGS FOR BUILDING PLAN REVIEW. | | | | | | 3. EF SCHEDULE ON M1.0 SHOWS EF 1A,1B FOR THE GREASE | | | HOOD. M3.0 SHOWS ONLY ONE FAN. PLEASE CLARIFY PER FBC | | | 106.1.1. | | | | | | 4. PLEASE SHOW MEANS OF CONDENSATE DISPOSAL WHICH IS IN | | | COMPLIANCE WITH FBC,M 307, INCLUDING AUXILIARY OR | | | SECONDARY DRAIN PROTECTION PER FBC,M 307.2.3. ALSO SHOW | | | COMPLIANCE WITH FBC 1506.3. | | | | | | 5. PG M1.0 SHOWS VOLUME DAMPERS IN GREASE EXHAUST | | | DUCTS. IS THIS INTENDED OR A MISTAKE? IF IT IS | | | INTENDED, PLEASE PROVIDE SUBMITTAL DATA WITH | | | INSTALLATION DETAIL FOR A PRODUCT LISTED AND LABELED | | | FOR THIS USE. | | | | | | 6. HVAC GENERAL NOTE 24: OUTER JACKET AND INSULATION ON | | | FLEX DUCT CONNECTIONS SHOULD NOT BE COMPRESSED WITH A | | | CLAMP PER FBC,M 603.5.6.3. ALSO, FLEXIBLE DUCT SUPPORTS | | | SHALL BE MINIMUM 1 1/2" WIDE PER FBC,M 603.5.6.6(6). | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE FEEL FREE TO CONTACT: | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
F |
Date |
2008-02-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-02-29 |
Time |
08:53 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-02-29 |
Time |
08:44 |
Sent To |
|
|
| Notes |
| 2008-02-29 08:52:26 | REVISION DENIED | | | REFERENCE: FBC-2004 CHAPTER 1 | | | | | | 1. SHT P3.0 SHOWS NO NEW REVISION NUMBER ON THE SHEET. | | | THE REVISION #2 IN THE REVISION INDEX IS DATED 6-20-07 | | | AND THAT REVISION IS SHOWN ON THE FIXTURE SCHEDULE. | | | REVISION NUMBER 3 WAS NEVER SHOWN ON THE PLANS AND HAS | | | NOT BEEN APPROVED. THE NEW REVISION SUBMITTED ALSO HAS | | | A REVISION NUMBER 2 INDICATED. EACH REVISION SHALL HAVE | | | A NEW NUMBER ASSOCIATED WITH IT FOR TRACKING PURPOSES. | | | SECTION 1061.3 THE BUILDING OFFICIAL MAY ESTABLISH | | | THROUGH DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND | | | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS | | | RECORD RETENTION PROGRAM. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2007-10-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-10-31 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-10-24 |
Time |
18:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2007-08-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-08-16 |
Time |
06:46 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-08-15 |
Time |
18:56 |
Sent To |
|
|
| Notes |
| 2007-08-16 07:14:34 | DENIED | | | REFERENCE: FBC-2004 | | | FBC-2004 CHAPTER 1 | | | FBC-2004 BUILDING | | | WPB MUNICIPAL CODE | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ******FROM PREVIOUS REVIEW: | | | ****FROM PREVIOUS REVIEWS: | | | | | | | | | 1. OK | | | | | | 2. THE SIGNATURE OF THE ARCHITECT IS REQUIRED WHEN | | | SEALING EACH SHEET. IT APPEARS THAT INITIALS HAVE BEEN | | | USED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE | | | ARCHITECT, PLEASE PROVIDE A SIGNED, SEALED, AND | | | NOTORIZED LETTER FOR OUR FILES. FAC 61G1-16.003, | | | 61G1-16.004((5) & FS 481.2055. | | | ******RESPONSE NOTED, BUT MULTIPLE LEGAL SIGNATURES ARE | | | NOT APPROVED. ONLY THE RECOGNIZED LEGAL SIGNATURE OF | | | THE ARCHITECT OF RECORD WILL BE ACCEPTED. ****RESPONSE | | | NOTED, BUT LETTER NOT SEALED/DATED. | | | | | | 3. OK - REVIEWER ATTACHED SHEETS. | | | | | | 4. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE UTILITY | | | DEPT. ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY | | | COMPO, (561) 822-2272, OR BY FAX (561) 822-2287, OR | | | E-MAIL [email protected]. SECTION III OF THE MUNICIPAL | | | CODE. | | | ******RESPONSE NOTED, BUT NO ATTACHED LETTER SHOWING | | | APROVAL FOUND IN RESUBMITTAL OF PLANS. ****RESPONSE | | | NOTED, BUT STILL NO REFERENCE TO CONTACTING | | | ENVIRONMENTAL COMPLIANCE FOR SIZING OF GREASE | | | INTERCEPTOR. | | | | | | 5. OK | | | 6. OK | | | 7. OK | | | 8. OK | | | | | | 9. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE | | | FOLLOWING INFORMATION: | | | | | | A. OK | | | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ******RESPONSE NOTED, BUT MANUF. SHEETS FOR ITEM #41 | | | INDICATES 50,000 BTU'S AND THE RISER DIAGRAM INDICATES | | | 100,000 BTU'S. ALSO SUBMIT THE UL LISTING FOR THIS | | | PRODUCT.--ITEM 38 MANUF. SPECIFICATION SHEETS ARE | | | NOT LEGIBLE AND DO NOT INDICATE BTU OR CFH INPUT | | | RATING.--ITEM 47 (7), NOT SUBMITTED. (NUMBER 47 NOT | | | IN LEGEND). PLEASE SUBMIT MANUF SPECIFICATION SHEETS | | | FOR THE TANKLESS WATER HEATERS.--TWO COPIES OF THE | | | GAS MANUF SPECIFICATION SHEETS REQUIRED FOR REVIEW. | | | ONLY ONE SUBMITTED. SECTION 106.1. | | | ****RESPONSE NOTED, BUT ITEMS #41 & #38 ARE INDICATED | | | AS "KEY NOTES" BUT ARE SHOWN ON THE GAS RISER DIAGRAM. | | | THIS CAUSED CONFUSION ON MY PART BECAUSE THE NUMBERS | | | ARE INDICATED ON THE RISER DIAGRAM. BOTH NUMBERS ARE | | | INDICATED IN THE KEY NOTES ALSO. BE THAT AS IT MAY, THE | | | COMMENTS STILL STAND. KEY NOTE 41, ITEM STILL INDICATES | | | 50,000BTU ON THE MANUF. SPECIFICATION SHEETS, BUT IS | | | INDICATED AS 100,000BTU ON THE RISER DIAGRAM. ALSO KEY | | | NOTE 38, ITEM 18 DOES NOT SHOW BTU"S ON THE MANUF. | | | SHEET. THIS WAS WRITTEN ON THE SHEETS AND BTU'S CAN NOT | | | BE VERIFIED.ITEM 47 LISTING CAN NOT BE VERIFIED ON A | | | QUESTION AND ANSWER SHEET. PLEASE SEE CSA PRODUCT | | | LISTING SEARCH SHEET ATTACHED TO COMMENTS. FILL OUT | | | REQUIRED SECTIONS OR SUBMIT LISTING INFORMATION FROM | | | CSA TO VERIFY LISTING. | | | | | | 10. OK | | | | | | **********NEW COMMENT********** | | | | | | 1B. ALL ELEC., MECH., & PLUMBING SHEETS. ENGINEERS | | | SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS, AND LICENSE | | | NUMBER ON EACH SHEET. IF PRACTICING THROUGH A DULY | | | AUTHORIZED ENGINEERING BUSINESS, ENGINEERS SHALL | | | LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL | | | AS, THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION | | | NUMBER ON THE ENGINEERING BUSINESS ON EACH SHEET. FAC | | | 61G15-23.002(2) & FS 471.025 | | | ****RESPONSE NOTED, BUT THE ADDRESS FOR THE ENGINEER IS | | | NOT BEEN INCLUDED AS INDICATED. (SEE ATTACHED SHEET | | | FROM FLORIDA STATE DBPR WEBSITE LISTING ENGINEER'S | | | ADDRESS). | | | | | | **********NEW COMMENT********** | | | | | | 1C. SHT P5.0 INDICATE THE PIPE SIZE FOR ALL STUB OUTS | | | FOR EACH GAS APPLIANCE. PIPE SIZE SHALL BE FULL SIZE | | | THRU THE SHUT OFF VALVE TO EACH APPLIANCE. | | | (SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE). | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2007-06-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-06-15 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-06-15 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2007-06-15 16:55:13 | DENIED | | | REFERENCE: FBC-2004 | | | FBC-2004 CHAPTER 1 | | | FBC-2004 BUILDING | | | WPB MUNICIPAL CODE | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. OK | | | | | | 2. THE SIGNATURE OF THE ARCHITECT IS REQUIRED WHEN | | | SEALING EACH SHEET. IT APPEARS THAT INITIALS HAVE BEEN | | | USED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE | | | ARCHITECT, PLEASE PROVIDE A SIGNED, SEALED, AND | | | NOTORIZED LETTER FOR OUR FILES. FAC 61G1-16.003, | | | 61G1-16.004((5) & FS 481.2055. | | | ******RESPONSE NOTED, BUT MULTIPLE LEGAL SIGNATURES ARE | | | NOT APPROVED. ONLY THE RECOGNIZED LEGAL SIGNATURE OF | | | THE ARCHITECT OF RECORD WILL BE ACCEPTED. | | | | | | 3. ROUTE PLANS TO THE STATE OF FLORIDA, DEPT OF | | | BUSINESS REGULATION, HOTEL AND RESTAURANT DIVISION FOR | | | PLAN REVIEW PRIOR TO RESUBMITTING FOR REVIEW. A MINIMUM | | | OF TWO REVIEWED AND STAMPED PLANS WITH THE "TWO PAGE | | | WORKSHEETS" ATTACHED TO THE STAMPED SHEET ARE REQUIRED | | | FOR REVIEW AT THE CITY WPB. SECTION 102.2.1. | | | ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED | | | COMPLETLY. ONLY ONE SET OF PLANS IS STAMPED, AND THE | | | TWO PAGE "WORKSHEETS" ARE NOT ATTACHED TO THE STAMPED | | | SHEET. | | | | | | 4. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE UTILITY | | | DEPT. ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY | | | COMPO, (561) 822-2272, OR BY FAX (561) 822-2287, OR | | | E-MAIL [email protected]. SECTION III OF THE MUNICIPAL | | | CODE. | | | ******RESPONSE NOTED, BUT NO ATTACHED LETTER SHOWING | | | APROVAL FOUND IN RESUBMITTAL OF PLANS. | | | | | | 5. OK | | | 6. OK | | | 7. OK | | | 8. OK | | | | | | 9. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE | | | FOLLOWING INFORMATION: | | | | | | A. OK | | | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ******RESPONSE NOTED, BUT MANUF. SHEETS FOR ITEM #41 | | | INDICATES 50,000 BTU'S AND THE RISER DIAGRAM INDICATES | | | 100,000 BTU'S. ALSO SUBMIT THE UL LISTING FOR THIS | | | PRODUCT.--ITEM 38 MANUF. SPECIFICATION SHEETS ARE | | | NOT LEGIBLE AND DO NOT INDICATE BTU OR CFH INPUT | | | RATING.--ITEM 47 (7), NOT SUBMITTED. (NUMBER 47 NOT | | | IN LEGEND). PLEASE SUBMIT MANUF SPECIFICATION SHEETS | | | FOR THE TANKLESS WATER HEATERS.--TWO COPIES OF THE | | | GAS MANUF SPECIFICATION SHEETS REQUIRED FOR REVIEW. | | | ONLY ONE SUBMITTED. SECTION 106.1. | | | | | | 10. OK | | | | | | **********NEW COMMENT********** | | | | | | 1B. ALL ELEC., MECH., & PLUMBING SHEETS. ENGINEERS | | | SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS, AND LICENSE | | | NUMBER ON EACH SHEET. IF PRACTICING THROUGH A DULY | | | AUTHORIZED ENGINEERING BUSINESS, ENGINEERS SHALL | | | LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL | | | AS, THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION | | | NUMBER ON THE ENGINEERING BUSINESS ON EACH SHEET. FAC | | | 61G15-23.002(2) & FS 471.025 | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-02-29 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-03-21 |
Time |
06:55 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-03-20 |
Time |
06:47 |
Sent To |
|
|
| Notes |
| 2007-03-21 07:41:57 | DENIED | | | REFERENCE: FBC-2004 | | | FBC-2004 CHAPTER 1 | | | FBC-2004 BUILDING | | | WPB MUNICIPAL CODE | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. ALL SHEETS, THE PRINTED NAME OF THE ARCHITECT AND | | | THE BUSINESS LICENSE NUMBER, (CERTIFICATE OF | | | AUTHORIZATION), ARE REQUIRED IN THE TITLE BLOCK. FAC | | | 61G1-16.004(2)(6) & FS 481.219, 481.2055. | | | | | | 2. THE SIGNATURE OF THE ARCHITECT IS REQUIRED WHEN | | | SEALING EACH SHEET. IT APPEARS THAT INITIALS HAVE BEEN | | | USED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE | | | ARCHITECT, PLEASE PROVIDE A SIGNED, SEALED, AND | | | NOTORIZED LETTER FOR OUR FILES. FAC 61G1-16.003, | | | 61G1-16.004((5) & FS 481.2055. | | | | | | 3. ROUTE PLANS TO THE STATE OF FLORIDA, DEPT OF | | | BUSINESS REGULATION, HOTEL AND RESTURANT DIVISION FOR | | | PLAN REVIEW PRIOR TO RESUBMITTING FOR REVIEW. A MINIMUM | | | OF TWO REVIEWED AND STAMPED PLANS WITH THE "TWO PAGE | | | WORKSHEETS" ATTACHED TO THE STAMPED SHEET ARE REQUIRED | | | FOR REVIEW AT THE CITY WPB. SECTION 102.2.1. | | | | | | 4. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE UTILITY | | | DEPT. ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY | | | COMPO, (561) 822-2272, OR BY FAX (561) 822-2287, OR | | | E-MAIL [email protected]. SECTION III OF THE MUNICIPAL | | | CODE. | | | | | | 5. SHT A2.1 ELEVATIONS A2.1-03, A2.1-05, A2.1-06, & | | | A2.1-08. WALLS WITHIN 2' OF A W/C OR URINAL SHALL HAVE | | | A "SMOOTH, HARD, NONABSORBENT SURFACE" TO A HEIGHT OF | | | 4' ABOVE THE FLOOR. ELEVATIONS INDICATE THE REQUIRED | | | SURFACE ONLY UP TO 45.5". SECTION 1210.2. PLEASE | | | CORRECT ELEVATIONS. | | | | | | 6. SHT P2.0 PLUMBING PLAN KEY NOTES #21, DOUBLE CHECK | | | VALVE ASSEMBLY IS NOT APPROVED. PLEASE DELETE FROM | | | FLOOR PLAN AND KEY NOTES. TABLE 608.1. THE RPZV | | | BACKFLOW IS REQUIRED AND WILL BE SUFFICIENT.--THE | | | RPZV BACKFLOW WILL BE REQUIRED TO BE INSTALLED A | | | MAXIMUM OF 4' ABOVE THE FINISHED FLOOR FOR SERVICING | | | AND CERTIFICATION. AN INDIRECT WASTE RECEPTOR SHALL BE | | | PROVIDED FOR THE DRAINAGE OFF THE BACKFLOW. SECTION | | | 802.1.3. | | | | | | 7. SHT P5.0 WATER RISER DIAGRAM & PLUMBING PLAN KEY | | | NOTES #21 THE DOUBLE CHECK VAVLE ASSEMBLY IS NOT | | | APPROVED. PLEASE DELETE FROM THE RISER AND THE KEY | | | NOTES. TABLE 608.1. | | | | | | 8. SHT P1.0 KITCHEN EQUIPMENT SCHEDULE INDICATES A | | | FILTERED WATER SYSTEM. THE FILTER SHALL BE NSF-42 | | | APPROVED. PLEASE SUBMIT THE MANUF. SPECIFICATION SHEETS | | | SHOWING APPROVAL. SECTIONS 106.1.1 & 611.1. | | | | | | 9. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE | | | FOLLOWING INFORMATION: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE. - SHOW ALL LENGTHS. | | | | | | B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | 10. SHT P5.0 GAS NOTES INDICATE THE GAS DATA WAS BASED | | | ON THE INTERNATIONAL FUEL GAS CODE. THE ADOPTED CODE IS | | | FBC-2004 FUEL GAS CODE. PLEASE CHANGED REFERENCE. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |