Plan Review Details - Permit 07030094
Plan Review Stops For Permit 07030094
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-10-28 Cont ID  
Sent By lmartine Date 2007-10-28 Time 12:39 Rev Time 0.00
Received By lmartine Date 2007-10-28 Time 12:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-08-15 Cont ID  
Sent By jwitmer Date 2007-08-15 Time 16:17 Rev Time 1.33
Received By jwitmer Date 2007-08-15 Time 16:17 Sent To PC
Notes
2007-08-15 16:19:21BUILDING PLAN REVIEW
 PERMIT: 07030094
 ADD: 851 VILLAGE BLVD# 502
 CONT: "PLAN REVIEW"
 TEL: (859)223-1000
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2-5C) COMPLIED.
  
 5D) 5D)THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER
 6, TABLE 503 & 601 . THIS WOULD BE FOR THE BUILDING,
 NOT THE TENANT SPACE. NOTE ALSO THERE MAY 4 HR FIRE
 WALLS THAT BREAKS THE BUILDING TRUELY INTO SEPERATE
 BUILDINGS. THE COVER SHEET INDICATES THAT THE TENANT
 SPACE IS 2500 SQ FT. THE ISSUE IS NOT PROVIDING THE
 BUILDING TYPE FOR THE "BUILDING" NOT THE TENANT SPACE.
 SECTION 504.2 DOES PROVIDE FOR UNLIMITED AREA FOR
 SPRINKLED BUILDINGS OCCUPANCY TYPE B,F,M OR S AND GROUP
 A-4 FOR ONE STORY BUILDINGS.
 PLEASE PROVIDE THE SQUARE FOOTAGE OF THE BUILDING AND
 ANY AREA INCREASES TAKEN.
  
 6-9) COMPLIED.
  
 10)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY
 OF THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE INFORMATION.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-06-19 Cont ID  
Sent By jwitmer Date 2007-06-19 Time 08:07 Rev Time 1.11
Received By jwitmer Date 2007-06-19 Time 08:07 Sent To  
Notes
2007-06-19 08:30:13BUILDING PLAN REVIEW
 PERMIT: 07030094
 ADD: 851 VILLAGE BLVD# 502
 CONT: "PLAN REVIEW"
 TEL: (859)223-1000
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLEASE EXCUSE MY SHORTING THE VERBAGE WHEN IT
 SHOULN'T HAVE BEEN, THECOVER SHEET CODE SUMMARY
 PLEASE REFER TO THE "2004 FBC, WITH 2006 REVISIONS.
 PLANS SUBMITTED AFTER DEC. 8 2006 WILL BE REVIEWED
 UNDER THENEW 2006 EDITION OF FBC.
  
 4) PLEASE EXCUSE MY SHORTING THE VERBAGE WHEN IT
 SHOULN'T HAVE BEEN, THECOVER SHEET CODE SUMMARY LIST
 THE 2006 ACCESSIBILITY CODE, THE SUMMARY SHOULD READ
 THE2004 FBC WITH 2006 REVISIONS TO CHAPTER 11 .
  
 5A-C) COMPLIED.
  
 5D)THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 503 & 601 . THIS WOULD BE FOR THE BUILDING, NOT
 THE TENANT SPACE. NOTE ALSO THERE MAY 4 HR FIRE WALLS
 THAT BREAKS THE BUILDING TRUELY INTO SEPERATE
 BUILDINGS.
  
 5F-G) COMPLIED.
  
 6) COMPLIED.
  
 7) COMPLIED.
  
 8) COMPLIED, THE SCOPE OF WORK DOES NOT INCLUDE THE
 REPLACEMENT OF EXTERIOR DOORS.
  
 9) COMPLIED.
  
 10) THIS MAY BE A CHANGE OF OCCUPANCY, PLANS ARE TO BE
 SUBMITTED TO THE PALM BEACH COUNTY IMPACT FEE OFFICE
 FOR ASSESSMENT BEFORE THIS PERMIT MAY BE ISSUED.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-02 Cont ID  
Sent By jwitmer Date 2007-04-02 Time 11:49 Rev Time 1.33
Received By jwitmer Date 2007-04-02 Time 11:49 Sent To  
Notes
2007-04-02 14:04:22BUILDING PLAN REVIEW
 PERMIT: 07030094
 ADD: 851 VILLAGE BLVD# 502
 CONT: "PLAN REVIEW"
 TEL: (859)223-1000
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID.
 NOTE: 713.13(6)THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION
 SITE BEFORE THE FIRST INSPECTION.
  
 3) COVER SHEET CODE SUMMARY PLEASE REFER TO THE
 2006FBC,
 PLANS SUBMITTED AFTER DEC. 8 2006 WILL BE REVIEWED
 UNDER THE
 NEW 2006 EDITION OF FBC.
  
 4) COVER SHEET CODE SUMMARY LIST THE 2001 ACCESSIBILITY
 CODE, 2006 FBC CHAPTER 11 IS THE
 DOJ APPROVED ACCESSIBILITY CODE.
  
 5) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WILL BEISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) WAS THIS A RESTARAUNT OR CAFETERIA USE BEFORE? D)
 THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601 & TABLE 503.
 NOTE!!! THIS IS FOR THE BUILDING NOT TENANT SPACE!E)
 THE OCCUPANT LOAD, SEE 1004.
 F) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 6)FOOD SEERVICE LINE, SHEET A2 DETAIL 04 INDICATES
 THE FOOD SEERVICE LINE AT A HIGH GREATER THAN 36" FROM
 FINISH FLOOR.
 11-5.5 FOOD SERVICE LINES.
 FOOD SERVICE LINES SHALL HAVE A MINIMUM CLEAR WIDTH OF
 36 INCHES (915 MM), WITH A PREFERRED CLEAR WIDTH OF 42
 INCHES (1065 MM) TO ALLOW PASSAGE AROUND A PERSON USING
 A WHEELCHAIR. TRAY SLIDES SHALL BE MOUNTED NO HIGHER
 THAN 34 INCHES (865 MM) ABOVE THE FLOOR (SEE FIGURE
 11-53 ). IF SELF-SERVICE SHELVES ARE PROVIDED, AT LEAST
 50 PERCENT OF EACH TYPE MUST BE WITHIN REACH RANGES
 SPECIFIED IN SECTIONS 11-4.2.5 AND 11-4.2.6 .
  
 7) 11-5.1 PROVIDE AT LEAST 5% ACCESSIBLE SETING.
 11-4.33.3 ALSO PROVIDE COMPANION SEATING 11-4.33.3.
  
 8)SHEET A-4.0 ENTRY DOOR DETAIL # 1 INDICATES THAT
 DOORS ARE TO BE REUSED WHERE POSSIBLE. STATE EITHER TO
 REMAIN OR BE REPLACED. IF REPLACED:
 FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 GLAZED FRONT ENTRY DOORS
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 9)CARDINAL POINT IS MISSING THEIR CERTIFICATE OF
 AUTHORIZATION NUMBER;
 481.219 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 10) DEPENDING ON THE ANSWER TO QUESTION # 3C:BEFORE A
 PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
 ,

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-02-11 Cont ID  
Sent By dpalmer Date 2008-02-09 Time 08:28 Rev Time 0.00
Received By dpalmer Date 2008-02-09 Time 08:27 Sent To  
Notes
2008-02-11 08:29:04** DENIED REVISION **
 1) NOTE:PLEASE SEE THE REVISIONS IN TITLE BLOCKS DO
 NOT CORRELATE WITH PLANS. ELECTRICAL PLANS SEEM TO
 INDICATE NOT ONLY A CLOUD FOR A REVISION FOUR WHICH IS
 NOT ON TITLE BLOCKS AS MENTION BUT ALSO SEEMS TO CLOUD
 OTHER ITEMS SUCH AS LIGHTING WHICH SEEMS TO INDICATE A
 REVISION.
 PLEASE KNOW IF THE LIGHTING FIXTURES, NUMBER OF
 FIXTURES ETC HAVE BEEN CHANGED PLEASE SUBMIT REVISED
 LIGHTING PERFORMANCE CALCULATIONS AS REQUIRED PER
 13-415.2
 PLEASE REVISE SHEETS TO REFLECT CHANGES AND
 COORDINATION WITH TITLE BLOCKS.
 FBC 106.1.2, 106.5 FOR COORDINATION AND ADDITIONAL
 INFORMATION.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-10-18 Cont ID  
Sent By dpalmer Date 2007-10-18 Time 14:19 Rev Time 0.00
Received By dpalmer Date 2007-10-18 Time 14:19 Sent To  
Notes
2007-10-18 14:22:26REDLINED ENERGY CALCULATIONS AS METHOD OF CONTROL SHOWN
 FOR DINING ROOM IS SHWON AS *MANUAL ON/OFF* WHEN AN
 AUTOMATED SYSTEM IS SHOWN.
 THESE CAN BE REVISED AT LATER DATE AND BEFORE FINAL.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-08-12 Cont ID  
Sent By dpalmer Date 2007-08-12 Time 12:18 Rev Time 0.00
Received By dpalmer Date 2007-08-12 Time 11:00 Sent To  
Notes
2007-08-12 12:20:35 
 ** DENIED 3RD TIME **
  
 2ND REVIEW UNDER PERMIT APPLICATION.
  
 ** PLEASE SEE THAT SOME NOTES FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE THE LETTERS NOW SUBMITTED FOR
 SIGNATURE VERIFICATION NOT DATED AND SEALED WHEN
 SIGNED. IF THIS WAS THE ONLY ITEM, THESE COULD BE
 MAILED IN TO THIS OFFICE HOWEVER AS THE PLANS HAVE
 OTHER COMMENTS PLEASE SUBMIT.
 FS 481.221, 471.025
  
 2) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC
 CHAPTER 13 IS STILL IN NEED OF ADDRESSING.
 PLEASE SEE THE LIGHTING REFLECT CEILING PLAN ON SHEET
 A1.4 DOES NOT COORDINATE WITH THE ELECTRICAL LIGHTING
 PLANS?
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED WERE ONCE
 AGAIN NOT SEALED BY THE DESIGN PROFESSIONAL AS STATED
 ON THE TWO PREVIOUS REVIEWS. THIS WAS SPECIFICALLY
 MENTIONED ON THE TWO PREVIOUS REVIEWS AS THIS IS
 REQUIRED PER THE FLORIDA BUILDING CODE AND FLORIDA
 STATUTES. THESE WERE SIGNED BUT WERE NOT SEALED AND
 DATED.
 PLEASE ALSO SEE THE *OWNER AGENT* IS ALSO NOT SIGNED ON
 SHEETS.
 PLEASE SEE THE PREVIOUS NOTE WHICH REQUIRES THE
 DESIGNER(S) OF RECORD RESPONSIBLE FOR SCOPE OF WORK TO
 *SIGN, DATE AND SEAL* SAID DOCUMENTS. THIS IS NOT ONLY
 REQUIRED PER FS 471.025, 481.221, FAC 61G15-23, 61G1-16
 BUT ALSO FBC 13-103.1.1.1.
  
 PLEASE SEE THE FIXTURES AND WATTAGES AS SHOWN ON ENERGY
 CALCULATIONS DO NOT CORRELATE WITH THE SUBMITTED PLANS
 AND FIXTURE LEGEND(S).
 PLEASE SEE THE TWO PREVIOUS REVIEWS WHICH WERE MARKED
 WITH AN ASTERISK ** FOR 13-415.2.ABC.1.2 SPECIFICALLY
 FOR TRACK LIGHTING, HOWEVER THE WATTAGE ON THE ENERGY
 CALCULATIONS NEED TO BE ADJUSTED.
 PLEASE SEE THAT THE WATTAGE USED MUST BE THE WATTAGE OF
 THE TRACK LIGHTING HEADS WITH A *MINIMUM* OF 30VA PER
 FT. THIS MEANS WHICH EVER FIGURE IS HIGHER BASED ON THE
 MINIMUM OF THE TWO.
 EXAMPLE:
 IF THE TOTAL NUMBER OF TRACK FIXTURES WERE 100 AND EACH
 WAS 75WATTS EACH THIS WOULD BE 7500VA.
 IF THE TOTAL LENGTH OF THE TRACK WAS 300FT AND THE
 MINIMUM PER FOOT OF TRACK AS STATED FROM THE FBC WAS
 30VA PER FT, THEN THE TOTAL OF 9000VA WOULD BE
 REQUIRED.
 ** PLEASE SEE THE TOTAL LENGTH OFTRACK PER LINEAR
 FEET ON PLANS WITH THE 30VA MINIMUM PER FOOT EXCEEDS
 THE TOTAL WATTAGE OF THE TRACK HEADS BEING USED IN THE
 CALCULATIONS.(PLEASE ADJUST).
  
 3) NOTE: PLEASE SEE THE TWO PREVIOUS REVIEWS STATED
 THAT *NO**EQUIPMENT GROUNDING CONDUCTOR* IS PERMITTED
 BEFORE THE FIRST MEANS OF DISCONNECT YET THE RISER
 STILL INDICATES THIS CONDUCTOR ON THE LINE SIDE OF THE
 SERVICE MAIN.
 PLEASE SEE 250.6 AND 250.24B. PLEASE KNOW IF THIS
 CONDUCTOR IS INSTALLED ON THE LINE SIDE OF THE MAIN AND
 THE MAIN THE GROUNDED CONDUCTOR IS BONDED AS REQUIRED
 PER 250.24B, THEN THIS WOULD CREATE A PARALLEL PATH
 WITH THE NEUTRAL(GROUNDED) CONDUCTOR AND THEREFORE
 CREATING *OBJECTIONABLE CURRENTS* AS STATED IN 250.6 OF
 THE NEC.
 PLEASE REMOVE.
  
 4) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS AND REPEAT CODE
 COMPLIANT COMMENTS. AS THE PLANS WERE SUBMITTED FOR
 ONLY *PLAN REVIEW* THE FIRST TIME, THIS IS NOT ASSESSED
 AT THIS TIME. PLEASE KNOW IF THE PLANS ARE RESUBMITTED
 WITH OUT THE ABOVE NOTES #2 AND #3 BEING ADDRESSED THIS
 OFFICE WILL BE REQUIRED PER THE ABOVE FLORIDA STATUTES
 TO ASSESS THE FOUR TIMES PLAN REVIEW FEE FOR THE
 PORTION OF THE PERMIT FEE ATTRIBUTED TO PLAN REVIEW.
 THIS ISTO THE DESIGN PROFESSIONAL.
 THIS FEE WOULD NOT BE THE RESPONSIBILITY OF THE OWNER
 OR CONTRACTOR.
 THIS IS ONLY A NOTICE AT THIS TIME.
 PLEASE ALSO KNOW ONE SET OF ELECTRICAL PLANS AND ENERGY
 CALCULATIONS ARE BEING RETAINED BY THIS OFFICE AT THIS
 TIME.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-06-05 Cont ID  
Sent By dpalmer Date 2007-06-05 Time 18:49 Rev Time 0.00
Received By dpalmer Date 2007-06-05 Time 16:39 Sent To  
Notes
2007-06-05 18:57:10** UNSAT **
  
 *** PLEASE KNOW THAT AS SOME ITEMS ARE NOT SHOWN FOR
 CODE COMPLIANCE AT THIS TIME OR MISSING FOR REVIEW,
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW NOT
 YET ABLE TO BE MADE.
  
 ** PLEASE ALSO SEE THERE ARE SEVERAL ITEMS FROM
 PREVIOUS REVIEW WHICH ARE IN NEED OF ADDRESSING AND NEW
 COMMENTS BASED ON REVISED SHEETS OR SUBMITTED DOCUMENTS
 WHICH WERE NOT THE SAME AS PREVIUS SUBMITTED PLANS.
  
 ** PLANS HAVE NOW BEEN SUBMITTED FOR PERMIT.
  
 1) NOTE:PLEASE SEE THE CODES AS STATED ON THE COVER
 SHEETS INDICATE 2004 FBC WITH 2006 WPB AND PB
 AMENDMENTS WHICH SHOULD INDICATE THE *2006 REVISIONS*.
 THESE 2006 REVISIONS ARE REVISIONS ADOPTED BY THE STATE
 FOR THE FLORIDA BUILDING CODE AS OF DECEMBER 8TH, 2006.
 PLEASE SEE WPB AND PB IS TWO SEPARATE MUNICIPALITIES.
 PLEASE SEE THE ADA IS REFERENCING A 2006 FBC ? SHOULD
 NOT THIS ALSO READ THE2004 FBC W/ 2006 REVISIONS.
 PLEASE SEE OTHER POSSIBLE COMMENTS FROM OTHER TRADES.
  
  
 2) NOTE: PLEASE SEE THE LETTER INDICATING THE USE OF
 MULTIPLE SIGNATURES AS THE LEGAL SIGNATURE OF THE
 SINGLE ARCHITECT OF RECORD FOR FILE IS NOT ACCEPTABLE.
 THIS MAY ONLY BE THE LEGAL SIGNATURE OF THE DESIGNER.
 PLEASE SEE THE COMMENT WITH RESPECT TO THE ENERGY
 CALCULATIONS AS THESE ARE SIGNED AND SEALED HOWEVER ARE
 NOT SIGNED WITH EITHER OF THE SIGNATURES ON LETTER AND
 IN FACT THIS *SIGNATURE* IS COMPLETELY DIFFERENT.
 PLEASE SEE THE FLORIDA STATUTES WHICH REQUIRES THE
 ORIGINAL SIGNATURE, DATE AND SEAL ON DOCUMENTS. THIS
 WAS NOT DONE AND DOCUMENTS WILL BE RETAINED BY THIS
 OFFICE.
  
 3) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 AS REQUIRED UNDER FLORIDA ADMINISTRATIVE CODE
 61G1523.002 FOR THE ENGINEER OF RECORD. PLEASE SEE THE
 MISSING PRINTED NAME AND PRINTED LICENSE NUMBER.
  
 4) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC
 CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1,
 .1.2 AND .1.3.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED DO NOT
 CONTAIN THE MOST RECENT ADOPTED VERSION PER THE FBC.
 PLEASE SEE THE PREVIOUS NOTE WHICH REQUIRES THE
 DESIGNER(S) OF RECORD RESPONSIBLE FOR SCOPE OF WORK TO
 *SIGN, DATE AND SEAL* SAID DOCUMENTS. THIS IS NOT ONLY
 REQUIRED PER FS 471.025, 481.221, FAC 61G15-23, 61G1-16
 BUT ALSO FBC 13-103.1.1.1.
 PLEASE SEE THE FIXTURES AND WATTAGES AS SHOWN ON ENERGY
 CALCULATIONS DO NOT CORRELATE WITH THE SUBMITTED PLANS
 AND FIXTURE LEGEND(S).
 PLEASE SEE THE TWO FIXTURE LEGENDS AS SUBMITTED ON THE
 ARCHITECTURAL AND ELECTRICAL PLANS DO NOT CORRELATE.
 PLEASE SEE THE LIGHTING CONTROL METHODS ON THE ENERGY
 CALCULATIONS DOES NOT CORRELATE WITH PLANS AS THESE ARE
 INDICATING *MANUAL ON/OFF8 WHICH IS NOT POSSIBLE WHEN
 THE PLANS INDICATE *AUTOMATED* MEANS. PLEASE ADJUST AND
 COORDINATE.
 PLEASE SUBMIT THE TIME SCHEDULING.
 PLEASE INDICATE THE REQUIRED OVER RIDE DEVICES AND
 LOCATION PER CODE.
 PLEASE INDICATE AND SHOW LOCATIONS OF DEVICES FOR
 SEPARATE SPACES.
 PLEASE INDICATE ALL OVER RIDE TIMES FOR DEVICES CHOSEN
 IN THE DESIGN. THE TIMES FOR OVER RIDES CAN NOT BE
 REVIEWED UNTIL A DEVICE IS SHOWN. PLEASE INDICATE
 OCCUPANCY TYPE DEVICES OR TIMER OVER RIDES. PLEASE
 INDICATE THE TIMES AS CODE PERMITS 4HRS MAXIMUM ON
 TIMER/MANUAL OVER RIDES AND 30 MINS FOR OS TYPE
 DEVICES.
 PLEASE SEE THE TYPE OF FIXTURES ON PLANS NEED TO
 COORDINATE WITH THE ENERGY CALCULATIONS.
 PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING MINIMUM
 TO BE FIGURED.
 PLEASE SEE 13-415.1.AB.1.1, 13-415.2
 *** PLEASE BE SURE TO SEE 13-415.2.ABC.1.2**
  
 5) NOTE: PLEASE SEE AS MENTIONED ON THE PREVIOUS
 REVIEW, THE APPLIED VALUE MUST INCLUDE ALL LABOR,
 MATERIALS AND EQUIPMENT PERMANENTLY INSTALLED EVEN IF
 ANY OF THE ABOVE IS OWNER SUPPLIED. THE VALUE FOR SCOPE
 OF WORK IS LOW.
 PLEASE SEE FBC 108.
  
 6) NOTE: PLEASE KNOW THAT ANY PHONE/CATV LOW VOLTAGE
 WILL BE UNDER SEPARATE PERMIT. THESE PLANS MAY BE
 REFERENCED FOR A TURN AROUND PERMIT. THE FEES FOR THE
 LV PERMIT ARE SEPARATE.
  
 7) NOTE: PLEASE SEE RISER STILL SHOWS AN *EQUIPMENT
 GROUNDING CONDUCTOR* BEING INSTALLED BEFORE THE FIRST
 MEANS OF DISCONNECT WHICH WILL CAUSE OBJECTIONABLE
 CURRENTS. PLEASE SEE 250.6 AND 250.24B. PLEASE REMOVE.
  
 8) NOTE: PLEASE SEE THE CIRCUITING FOR THE SHOW WINDOW
 RECEPTACLES AS THE CIRCUITS TO PANEL INDICATE 14 AND
 16, YET THE PLANS INDICATE CIRCUITS 16 AT BOTH
 LOCATIONS.
 PLEASE COORDINATE.
 FBC 106.1.2
  
 9) NOTE: PLEASE PROVIDE THE LOAD ANALYSIS/LOAD SUMMARY
 OF THE LOADS SHOWN FOR THE SERVICE FOR SPACE #502.
 PLEASE SEE THE LOADS FOR TRACK LIGHTING, NORMAL
 LIGHTING AND OTHER LIGHTING DO NOT ADD UP TO THE
 FIGURES ACCORDING TO THE NEC FOR MINIMUM LOADS TO BE
 FIGURED.
 PLEASE SEE THE CODE SECTIONS GIVEN ON PREVIOUS REVIEW
 AND SHOW A BREAKDOWN ON HOW LOADS WERE DERIVED. THIS
 REVIEWER WENT THROUGH THE CALCULATIONS TWICE AND CAME
 UP WITH FIGURES WHICH ARE LARGER THAN SHOWN. PLEASE
 INCLUDE THE KW RATINGS FOR A/C. PLEASE ALSO SEE 424.3B
 AS THE OCP FOR EACH OF THESE UNITS WHICH CONTAIN HEAT
 WILL REQUIRE THE SIZING AT 125% FOR MINIMUM OCP. PLEASE
 SEE THE LOAD FOR THE UNOCCUPIED SPACE MUST BE FIGURED
 INTO THE SPACE. THIS IS A MINIMUM LOAD FOR SERVICE. IT
 HAS NO RELEVANCE THAT THE SPACE IS NOT OCCUPIED, AS IT
 MAY BE BY NOW, NEXT WEEK OR ANYTIME THERE AFTER. IF THE
 SPACE IS FED FROM THE SAME SERVICE THEN THE SERVICE
 MUST INCLUDE THE MINIMUM LOADS PER CODE. PLEASE
 ADJUST.
 PLEASE SEE 220.12, 220.14, 220.42, 220.44, 220.43
 B.ETC.
 215.5, FBC 106.3.5.1.2, 106.1.2
  
 10) NOTE: PLEASE PROVIDE AIC RATING FOR NEW MAIN.
 110.9. THIS IS THE SAME NOTE. THE RATINGS ARE SHOWN FOR
 PANELS, BUT NOT FOR MAINS. (PLEASE VERIFY THE 65K
 RATING SHOWN FOR THE EXISTING AND NEW PANELS AND BRANCH
 BREAKERS. AS THERE IS A RATING ABOVE THE 29K OF COMMON
 SIZE WHICH HAS A SUBSTANTIALLY LESS EXPENSE) (THIS IS
 ONLY NOTED AS THE HIGHER RATING MAY BE INSTALLED AND
 DOES NOT VIOLATE THE CODE IN ANY WAY). PLEASE KNOW IF
 THE PLANS CALL FOR THIS RATING, THEN THIS WILL BE
 REQUIRED.)
 FBC 106.3.5.1.2
  
 11) NOTE: PLEASE SEE 210.8B2 AS ALL RECEPTACLES IN
 KITCHENS AND AREAS OF THE LIKE ALONG WITH FOOD PREP
 SHALL BE GFI/ GFI PROTECTED.
 NO CHANGES COULD BE LOCATED ON PLANS FOR THIS.
  
 12) NOTE:PLEASE LABEL ALL MAINS FOR SERVICE. ( 1OF 5,
 3 OF 5 ETC).
 FBC 106.1.2 , NEC 230.2E
 PLEASE INDICATE THE LOCATION OF THE NEW PROPOSED MAIN.
 THIS IS REQUIRED TO BE GROUPED PER 230.72
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-11 Cont ID  
Sent By dpalmer Date 2007-03-11 Time 12:52 Rev Time 0.00
Received By dpalmer Date 2007-03-11 Time 11:52 Sent To  
Notes
2007-03-11 12:55:27** UNSAT**
  
 ** PLEASE KNOW THAT PLANS HAVE ONLY BEEN SUBMITTED FOR
 A *PLAN REVIEW* ONLY AND HAVE NOT BEEN SUBMITTED FOR
 PERMIT.
 PLEASE KNOW THAT EVEN IF AND WHEN PLANS ARE CODE
 COMPLIANT, PLANS WILL STILL REMAIN IN A *FAILED* STATUS
 UNTIL PERMIT APPLICATION, FEES ETC HAVE BEEN DONE.
  
 ** PLEASE KNOW AS THERE ARE MANY ITEMS NOT YET
 SUBMITTED FOR REVIEW, NEW COMMENTS MAY BE POSSIBLE ON
 THE FOLLOW UP REVIEW AS REVIEW OF MANY OF THESE ITEMS
 CAN NOT BE DONE AT THIS TIME.
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM. THIS WOULD INCLUDE A-SHEETS AS
 WELL AS E-SHEETS.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 AS REQUIRED UNDER FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 AND FLORIDA STATUTES 481.219
 PLEASE SEE MISSING PRINTED NAME AND MISSING FIRM
 LICENSE NUMBER ALSO KNOWN AS THE CERTIFICATE OF
 AUTHORIZATION.
 THIS OFFICE IS AWARE THAT APPLICATION HAS BEEN MADE TO
 THE STATE HOWEVER MAY NOT POSSESS THE TITLE BLOCK AS
 SHOWN UNTIL SUCH TIME A CA # FOR THE FIRM HAS BEEN
 ISSUED.
 *PLEASE ALSO SEE THE STATE ALSO HAS THE ADDRESS LISTED
 IN CINCINNATI, OHIO.
  
 3) NOTE: PLEASE SEE PLANS APPEAR TO BE SIGNED WITH WHAT
 APPEARS TO BE INITIALS? IF THIS IS INDEED THE LEGAL
 SIGNATURE, PLEASE SUBMIT A LETTER FOR SIGNATURE
 VERIFICATION. THE LETTER WILL NEED TO BE SIGNED, DATED
 AND SEALED ALONG WITH BEING NOTARIZED.PLEASE KNOW
 THAT THIS LETTER MUST BE ORIGINAL.
 PLEASE KNOW THIS WILL BE PLACED IN OUR SIGNATURE FILE
 FOR FUTURE REFERENCE.
  
 4) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC
 CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1,
 .1.2 AND .1.3.
 PLEASE SEE BY DEFINITION THIS SPACE IS IN A BUILDING
 GREATER THAN 5K SQ FT.
 PLEASE SHOW COMPLIANCE WITH THIS AND IF THERE ARE ANY
 QUESTIONS, PLEASE CALL TO GO OVER THIS.
 PLEASE SUBMIT LIGHTING POWER DENSITIES PER THE 2004 FBC
 W/ 2006 REVISION. PLEASE SEE 13-415.1.AB.1.1, 13-415.2
 FOR LIGHTING PERFORMANCE CALCULATIONS ALONG WITH ENERGY
 CALCULATIONS. PLEASE SEE THE CALCULATIONS SUBMITTED ARE
 NOT COMPLIANT AT THIS TIME ABSE DON THE INFORMATION
 SHOWN.
 PLEASE SEE THAT THE FIXTURE SCHEDULE SHALL BE SPECIFIC
 FOR FIXTURES TO BE INSTALLED AND COORDINATION WITH THE
 LPD/CALCULATIONSWHICH IS TO BE REVIEWED FOR
 COMPLIANCE.
 *** PLEASE BE SURE TO SEE 13-415.2.ABC.1.2** PLEASE BE
 SURE TO HAVE THE DESIGNER OF RECORD FOR THE ENERGY
 CALCULATIONS SIGN, DATE AND SEAL THESE AS REQUIRED PER
 13-103.1.1.1 THESE ARE NOT SEALED WIHT RAISED SEAL AAS
 REQUIRED PER SECTION AS STATED.
  
 **PLEASE SEE NOTES ON PLANS MENTIONS SOME OF THESE
 AREAS AS EXISTING FOR NO WORK, YET PLANS INDICATE WORK
 BEING DONE IN THESE AREAS.
  
 5) NOTE: PLEASE SEE THE VALUE WHEN APPLYING FOR PERMIT
 SHALL INCLUDE ALL LABOR AND MATERIALS EVEN IF
 MATERIALS/EQUIPMENT IS OWNER SUPPLIED.
 FBC ADMIN SECTION 108.3
  
 6) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS. ANY DEVICE SHALL BE SHOWN ON BASE
 PLANS EVEN THOUGH THE SCOPE OF WORK FOR ANY FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS WILL BE DONE UNDER
 SEPARATE PERMIT.
 **DEVICES ARE BEING SHOWN ON PLANS/LEGEND.
  
 7) NOTE: PLEASE SEE RISER SHOWS AN *EQUIPMENT GROUNDING
 CONDUCTOR* BEING INSTALLED WHICH WILL CAUSE
 OBJECTIONABLE CURRENTS. PLEASE SEE 250.6 AND 250.24B.
  
 8) NOTE: PLEASE VERIFY THE SERVICE ENTRANCE CONDUCTORS
 AND PLACE THE INFORMATION ON RISER. PLEASE SEE THAT THE
 RISER MAKES NOTE TO VERIFY, YET THIS INFORMATION SHALL
 BE KNOWN AND STATED ON PLANS AT THIS TIME.
 PLEASE ALSO SUBMIT COMPLETE LOAD CALCULATIONS ON THE
 EXISTING SERVICE AS SHOWN WITH NEW LOAD ADDED TO
 SERVICE.
 PLEASE SEENEC 2005 220.
 NEED TO VERIFY 310.16, 240.4 ETC.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION.
  
 9) NOTE: PLEASE SEE THE LOAD ANALYSIS WHICH STATES THE
 2002 NEC FOR CALCULATIONS.
 PLEASE KNOW WE ARE UNDER THE 2005.
 PLEASE ALSO CLARIFY ON THE LOAD CALCULATIONS FOR SPACE
 HOW THE FOLLOWING LOADS WERE DERIVED.
 LIGHTING?
 TRACK LIGHTS?
 RECEPTACLES?
 PLEASE SEE 220.12, 220.14, 220.42, 220.44, 220.43 B.
  
 10) NOTE: PLEASE PROVIDE AIC RATING FOR NEW MAIN.
 110.9.
 FBC 106.3.5.1.2
  
 11) NOTE: PLEASE SEE 210.8B2 AS ALL RECEPTACLES IN
 KITCHENS AND AREAS OF THE LIKE ALONG WITH FOOD PREP
 SHALL BE GFI/ GFI PROTECTED.
  
 12) NOTE: PLEASE PLACE THE SIZING OF THE BRANCH CIRCUIT
 CONDUCTORS ON PANEL SCHEDULES. PLEASE SEE 310.16,
 240.4
 FBC 106.3.5.1.2, 106.1.2
  
 13) NOTE: PLEASE LABEL ALL MAINS FOR SERVICE. ( 1OF 5,
 3 OF 5 ETC).
 PLEASE PLACE NOTE ON PLANS WHICH WILL REQUIRE THE
 REMOVAL OF THE EXISTING METER AND MAIN FOR THE SPACE
 SERVICE WHICH IS BEING REPLACED.
 THE OLD METER AND MAIN WILL BE REQUIRED BY THIS AHJ TO
 BE REMOVED COMPLETELY.
 FBC 106.1.2 ADDITIONAL INFORMATION.
 104.6
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-08-14 Cont ID  
Sent By mawillia Date 2007-08-14 Time 12:50 Rev Time 0.00
Received By mawillia Date 2007-08-14 Time 10:49 Sent To  
Notes
2007-08-14 10:53:02*****APPROVED*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEETS A1.1 AND A1.4 WERE
 STAMPED, INITIALED, AND DATED.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-07-05 Cont ID  
Sent By mwennerg Date 2007-07-05 Time 15:03 Rev Time 0.00
Received By mwennerg Date 2007-07-05 Time 15:03 Sent To  
Notes
2007-07-05 15:38:29***DENIED***
  
 FROM PREVIOUS FIRE REVIEW
  
 1) OK
  
 2) OK
  
 3) OK
  
 4) OK
  
 5) OK PLEASE ADD NOTE TO PLANS FOR CLARIFICATION AS
 THIS IS A LOCAL REQUIREMENT. PLEASE CLARIFY IF THERE IS
 AN EXISTING FULL FIRE ALARM SYSTEM. IT IS NOTED THAT
 THERE IS AN AUTOMATIC FIRE SPRINKLER SYSTEM THAT AT A
 MINIMUM SHALL BE MONITORED.
  
 6) OK NOTE 29 DOES NOT MENTION NFPA 96 WHICH IS
 REFERENCED ON M3.0. PLEASE ADD TO RESPONSE OR PLANS IN
 COMPLIANCE WITH UL 300 FOR WET CHEMICAL SYSTEMS.
  
 7) OK
  
 NEW COMMENT
  
 1) PLEASE SEE NFPA 101, SEC. 12.2.2.2.3 FOR ASSEMBLY
 OCCUPANCIES REQUIRES PANIC OR FIRE EXIT HARDWARE ON
 DOORS IN MEANS OF EGRESS WHERE OCCUPANT LOAD IS 100 OR
 GREATER. NO MENTION IN DOOR SCHEDULE. IF ALREADY
 PROVIDED AS EXISTING CONDITION, PLEASE ADVISE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-04-12 Cont ID  
Sent By mawillia Date 2007-04-12 Time 11:55 Rev Time 0.00
Received By mawillia Date 2007-04-12 Time 10:41 Sent To  
Notes
2007-04-12 11:54:16*****DENIED*****
  
  
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.IT IS NOT INDICATED WHETHER THE TENANT SPACE HAS A
 FIRE SPRINKLER AND/OR A FIRE ALARM SYSTEM.IF SO, ANY
 MODIFICATIONS TO THESE SYSTEMS AS A RESULT OF THE SCOPE
 OF WORK, WILL REQUIRE SEPARATE PLANS AND PERMIT FOR THE
 REMODEL.
  
 4. THEINTERIOR WALL AND CEILING FINISH CLASSIFICATION
 SHALL BE CLASS A, CLASS B, OR CLASS C IN ASSEMBLY AREAS
 HAVING AN OCCUPANT LOAD OF 300 OR FEWER.PLEASE
 SPECIFY.
  
 5.AS PER WEST PALM BEACH FIRE PREVENTION, DUCT SMOKE
 DETECTOR SHALL INITIATE A GENERAL ALARM.
  
 6.COMMERCIAL COOKING EQUIPMENT SHALL BE IN ACCORDANCE
 WITH NFPA 96 (2001 EDIITION);SEPARATE PLANS AND PEMI
 WILL BE REQUIRED FOR THE HOOD INSTALLATION AND THE HOOD
 SUPPRESSION SYSTEM.
  
 7.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE
 REQUIREMENT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (IN THE PLANS) EACH COMMENT
 WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2007-10-31 Cont ID  
Sent By kstevens Date 2007-10-24 Time 17:19 Rev Time 0.00
Received By kstevens Date 2007-10-24 Time 18:13 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-08-16 Cont ID  
Sent By kstevens Date 2007-08-16 Time 06:50 Rev Time 0.00
Received By kstevens Date 2007-08-15 Time 06:50 Sent To  
Notes
2007-08-16 07:15:45SEE PLUMBING REVIEW COMMENTS

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-08-16 Cont ID  
Sent By kstevens Date 2007-06-15 Time 06:49 Rev Time 0.00
Received By kstevens Date 2007-06-15 Time 06:49 Sent To  
Notes
2007-08-16 07:15:36SEE PLUMBING REVIEW COMMENTS

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-08-16 Cont ID  
Sent By kstevens Date 2007-03-21 Time 06:48 Rev Time 0.00
Received By kstevens Date 2007-03-20 Time 06:48 Sent To  
Notes
2007-08-16 07:15:25SEE PLUMBING REVIEW COMMENTS

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-02-08 Cont ID  
Sent By adarroug Date 2008-02-08 Time 16:37 Rev Time 0.00
Received By adarroug Date 2008-02-08 Time 16:37 Sent To  
Notes
2008-02-08 16:37:48TO "COMM" BD#64

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-10-05 Cont ID  
Sent By adarroug Date 2007-10-05 Time 11:48 Rev Time 0.00
Received By adarroug Date 2007-10-05 Time 11:47 Sent To  
Notes
2007-10-05 11:48:38WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-07-26 Cont ID  
Sent By adarroug Date 2007-07-26 Time 13:52 Rev Time 0.00
Received By adarroug Date 2007-07-26 Time 13:52 Sent To  
Notes
2007-08-07 18:38:37TO COMM BOARD #37
2007-07-26 13:53:20WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-05-10 Cont ID  
Sent By adarroug Date 2007-05-10 Time 16:43 Rev Time 0.00
Received By adarroug Date 2007-05-10 Time 16:43 Sent To  
Notes
2007-05-24 16:36:59TO "COMM" BD#31/PLANS ON RACK--2 ROLLS
2007-05-10 16:43:50WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-12 Cont ID  
Sent By mawillia Date 2007-04-12 Time 10:43 Rev Time 0.00
Received By mawillia Date 2007-03-07 Time 09:11 Sent To  
Notes
2007-03-08 14:17:08TO "COMM" BD#37
2007-03-07 09:11:59WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-02-26 Cont ID  
Sent By rregueir Date 2008-02-26 Time 13:40 Rev Time 0.00
Received By rregueir Date 2008-02-26 Time 11:26 Sent To  
Notes
2008-02-26 13:40:05SUBMITTED LETTER FROM ENGINEER, SUBSTITUTING DETAIL FOR
 GOOSENECK VENT WITH GREENHECK MUSHROOM CAP WITH
 BACKDRAFT DAMPER FOR BAROMETRIC RELIEF. NO DATA FOR
 WIND LOADS WERE SUBMITTED. SUCH INFORMATION SHALL BE
 PROVIDED PRIOR TO FINAL INSPECTION.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-10-19 Cont ID  
Sent By rregueir Date 2007-10-19 Time 16:17 Rev Time 0.00
Received By rregueir Date 2007-10-19 Time 16:17 Sent To  
Notes
2007-10-19 16:17:30REVIEW #:
 ACTION:
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 CONDITIONS OF ALL PROVISOS HAVE BEEN SATISFIED PRIOR TO
 PERMIT ISSUANCE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-08-10 Cont ID  
Sent By rregueir Date 2007-08-10 Time 13:22 Rev Time 0.00
Received By rregueir Date 2007-08-10 Time 11:13 Sent To  
Notes
2007-08-10 13:21:48***********PROVISO************
 1) REVISE ENERGY CALCULATIONS TO SHOW CORRECT ROOF
 ASSEMBLY AND R-VALUE PRIOR TO INSPECTION.
 2) PROVIDE AUXILIARY DRAIN PROTECTION (INTERNAL FLOAT
 SWITCH, NOT SECONDARY DRAIN ON ROOF) ON RTU'S.
 3) RTU'S TO BE FASTENED PER SUBMITTED STRUCTURAL
 CALCULATIONS, NOT DETAIL ON PLAN.
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-06-07 Cont ID  
Sent By rregueir Date 2007-06-07 Time 08:38 Rev Time 0.00
Received By rregueir Date 2007-06-06 Time 11:44 Sent To  
Notes
2007-06-07 08:38:28---------------DENIED-----------------
  
 FBC 2004 CODE FAMILY W/ 2006 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLWOING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS FOR CONTINUITY. ADDITIONAL
 COMMENTS ARE AT THE NED OF THIS REVIEW.
  
 1. PLEASE REMOVE REFERENCE TO CODES WHICH ARE NOT
 ADOPTED BY THE STATE OF FLORIDA SUCH AS THE IMC ANS
 STANDARD CODES.
  
 2. PRE-ENGINEERED A/C STANDS ARE STRUCTURAL ELEMNTS AS
 DEFINED BY FAC 9B-72. PRODUCT APPROVAL IS REQUIRED.
 PLEASE SEE WWW.FLORIDABUILDING.ORG FOR MORE INFORMATION
 ON THE FLORIDA PRODUCT APPROVAL SYSTEM. ALSO, ASCE 7-98
 IS NO LONGER THE REFERENCE STANDARD UNDER THE 2004 FBC.
 DESIGN LOADS ARE TO COMPLY WITH ASCE 7-02.
  
 3. OK
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN
 HOOD, HOOD SUPPRESSION, WALK-IN COOLER/FREEZERS.
  
 4. DRAWINGS STILL DO NOT SHOW COMPLIANCE WITH FBC,M
 307.2.3 FOR AUXILIARY DRAIN PROTECTION.
  
 5. OK
  
 6.OK
  
 NEW COMMENTS
  
 A. ENERGY CALCULATIONS SHOULD BE ON FORM 400B-04R
 GENERATED BY FLA/COM-2004 V2.5.
  
 B. PLANS WHICH ARE SIGNED AND SEALED BY AN ENGINEER OF
 RECORD SHALL COMPLY WITH FAC 61G1523.002.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
  
 RONALS J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-03-28 Cont ID  
Sent By rregueir Date 2007-03-28 Time 14:53 Rev Time 0.00
Received By rregueir Date 2007-03-27 Time 19:23 Sent To  
Notes
2007-03-28 14:53:15------------------DENIED-------------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS
  
 1. HVAC GENERAL NOTE 3 AND KEY NOTE 3, PLEASE REFERENCE
 FBC,M 2004.
  
 2. ROOF MOUNTED EQUIPMENT SHALL BE SECURED TO STRUCTURE
 TO MEET 140 MPH WIND LOADS PER FBC,M 301.13 AND FBC
 CH.16. PROVIDE WIND LOAD CALCULATIONS AND STRUCTURAL
 DETAIL DRAWINGS FOR BUILDING PLAN REVIEW.
  
 3. EF SCHEDULE ON M1.0 SHOWS EF 1A,1B FOR THE GREASE
 HOOD. M3.0 SHOWS ONLY ONE FAN. PLEASE CLARIFY PER FBC
 106.1.1.
  
 4. PLEASE SHOW MEANS OF CONDENSATE DISPOSAL WHICH IS IN
 COMPLIANCE WITH FBC,M 307, INCLUDING AUXILIARY OR
 SECONDARY DRAIN PROTECTION PER FBC,M 307.2.3. ALSO SHOW
 COMPLIANCE WITH FBC 1506.3.
  
 5. PG M1.0 SHOWS VOLUME DAMPERS IN GREASE EXHAUST
 DUCTS. IS THIS INTENDED OR A MISTAKE? IF IT IS
 INTENDED, PLEASE PROVIDE SUBMITTAL DATA WITH
 INSTALLATION DETAIL FOR A PRODUCT LISTED AND LABELED
 FOR THIS USE.
  
 6. HVAC GENERAL NOTE 24: OUTER JACKET AND INSULATION ON
 FLEX DUCT CONNECTIONS SHOULD NOT BE COMPRESSED WITH A
 CLAMP PER FBC,M 603.5.6.3. ALSO, FLEXIBLE DUCT SUPPORTS
 SHALL BE MINIMUM 1 1/2" WIDE PER FBC,M 603.5.6.6(6).
  
 IF YOU HAVE ANY QUESTIONS PLEASE FEEL FREE TO CONTACT:
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 5 Status F Date 2008-02-29 Cont ID  
Sent By kstevens Date 2008-02-29 Time 08:53 Rev Time 0.00
Received By kstevens Date 2008-02-29 Time 08:44 Sent To  
Notes
2008-02-29 08:52:26REVISION DENIED
 REFERENCE: FBC-2004 CHAPTER 1
  
 1. SHT P3.0 SHOWS NO NEW REVISION NUMBER ON THE SHEET.
 THE REVISION #2 IN THE REVISION INDEX IS DATED 6-20-07
 AND THAT REVISION IS SHOWN ON THE FIXTURE SCHEDULE.
 REVISION NUMBER 3 WAS NEVER SHOWN ON THE PLANS AND HAS
 NOT BEEN APPROVED. THE NEW REVISION SUBMITTED ALSO HAS
 A REVISION NUMBER 2 INDICATED. EACH REVISION SHALL HAVE
 A NEW NUMBER ASSOCIATED WITH IT FOR TRACKING PURPOSES.
 SECTION 1061.3 THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-10-31 Cont ID  
Sent By kstevens Date 2007-10-31 Time 11:56 Rev Time 0.00
Received By kstevens Date 2007-10-24 Time 18:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-08-16 Cont ID  
Sent By kstevens Date 2007-08-16 Time 06:46 Rev Time 0.00
Received By kstevens Date 2007-08-15 Time 18:56 Sent To  
Notes
2007-08-16 07:14:34DENIED
 REFERENCE: FBC-2004
 FBC-2004 CHAPTER 1
 FBC-2004 BUILDING
 WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ******FROM PREVIOUS REVIEW:
 ****FROM PREVIOUS REVIEWS:
  
  
 1. OK
  
 2. THE SIGNATURE OF THE ARCHITECT IS REQUIRED WHEN
 SEALING EACH SHEET. IT APPEARS THAT INITIALS HAVE BEEN
 USED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 ARCHITECT, PLEASE PROVIDE A SIGNED, SEALED, AND
 NOTORIZED LETTER FOR OUR FILES. FAC 61G1-16.003,
 61G1-16.004((5) & FS 481.2055.
 ******RESPONSE NOTED, BUT MULTIPLE LEGAL SIGNATURES ARE
 NOT APPROVED. ONLY THE RECOGNIZED LEGAL SIGNATURE OF
 THE ARCHITECT OF RECORD WILL BE ACCEPTED. ****RESPONSE
 NOTED, BUT LETTER NOT SEALED/DATED.
  
 3. OK - REVIEWER ATTACHED SHEETS.
  
 4. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE UTILITY
 DEPT. ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY
 COMPO, (561) 822-2272, OR BY FAX (561) 822-2287, OR
 E-MAIL [email protected]. SECTION III OF THE MUNICIPAL
 CODE.
 ******RESPONSE NOTED, BUT NO ATTACHED LETTER SHOWING
 APROVAL FOUND IN RESUBMITTAL OF PLANS. ****RESPONSE
 NOTED, BUT STILL NO REFERENCE TO CONTACTING
 ENVIRONMENTAL COMPLIANCE FOR SIZING OF GREASE
 INTERCEPTOR.
  
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION:
  
 A. OK
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ******RESPONSE NOTED, BUT MANUF. SHEETS FOR ITEM #41
 INDICATES 50,000 BTU'S AND THE RISER DIAGRAM INDICATES
 100,000 BTU'S. ALSO SUBMIT THE UL LISTING FOR THIS
 PRODUCT.--ITEM 38 MANUF. SPECIFICATION SHEETS ARE
 NOT LEGIBLE AND DO NOT INDICATE BTU OR CFH INPUT
 RATING.--ITEM 47 (7), NOT SUBMITTED. (NUMBER 47 NOT
 IN LEGEND). PLEASE SUBMIT MANUF SPECIFICATION SHEETS
 FOR THE TANKLESS WATER HEATERS.--TWO COPIES OF THE
 GAS MANUF SPECIFICATION SHEETS REQUIRED FOR REVIEW.
 ONLY ONE SUBMITTED. SECTION 106.1.
 ****RESPONSE NOTED, BUT ITEMS #41 & #38 ARE INDICATED
 AS "KEY NOTES" BUT ARE SHOWN ON THE GAS RISER DIAGRAM.
 THIS CAUSED CONFUSION ON MY PART BECAUSE THE NUMBERS
 ARE INDICATED ON THE RISER DIAGRAM. BOTH NUMBERS ARE
 INDICATED IN THE KEY NOTES ALSO. BE THAT AS IT MAY, THE
 COMMENTS STILL STAND. KEY NOTE 41, ITEM STILL INDICATES
 50,000BTU ON THE MANUF. SPECIFICATION SHEETS, BUT IS
 INDICATED AS 100,000BTU ON THE RISER DIAGRAM. ALSO KEY
 NOTE 38, ITEM 18 DOES NOT SHOW BTU"S ON THE MANUF.
 SHEET. THIS WAS WRITTEN ON THE SHEETS AND BTU'S CAN NOT
 BE VERIFIED.ITEM 47 LISTING CAN NOT BE VERIFIED ON A
 QUESTION AND ANSWER SHEET. PLEASE SEE CSA PRODUCT
 LISTING SEARCH SHEET ATTACHED TO COMMENTS. FILL OUT
 REQUIRED SECTIONS OR SUBMIT LISTING INFORMATION FROM
 CSA TO VERIFY LISTING.
  
 10. OK
  
 **********NEW COMMENT**********
  
 1B. ALL ELEC., MECH., & PLUMBING SHEETS. ENGINEERS
 SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS, AND LICENSE
 NUMBER ON EACH SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION
 NUMBER ON THE ENGINEERING BUSINESS ON EACH SHEET. FAC
 61G15-23.002(2) & FS 471.025
 ****RESPONSE NOTED, BUT THE ADDRESS FOR THE ENGINEER IS
 NOT BEEN INCLUDED AS INDICATED. (SEE ATTACHED SHEET
 FROM FLORIDA STATE DBPR WEBSITE LISTING ENGINEER'S
 ADDRESS).
  
 **********NEW COMMENT**********
  
 1C. SHT P5.0 INDICATE THE PIPE SIZE FOR ALL STUB OUTS
 FOR EACH GAS APPLIANCE. PIPE SIZE SHALL BE FULL SIZE
 THRU THE SHUT OFF VALVE TO EACH APPLIANCE.
 (SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2007-06-15 Cont ID  
Sent By kstevens Date 2007-06-15 Time 14:22 Rev Time 0.00
Received By kstevens Date 2007-06-15 Time 14:22 Sent To  
Notes
2007-06-15 16:55:13DENIED
 REFERENCE: FBC-2004
 FBC-2004 CHAPTER 1
 FBC-2004 BUILDING
 WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. THE SIGNATURE OF THE ARCHITECT IS REQUIRED WHEN
 SEALING EACH SHEET. IT APPEARS THAT INITIALS HAVE BEEN
 USED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 ARCHITECT, PLEASE PROVIDE A SIGNED, SEALED, AND
 NOTORIZED LETTER FOR OUR FILES. FAC 61G1-16.003,
 61G1-16.004((5) & FS 481.2055.
 ******RESPONSE NOTED, BUT MULTIPLE LEGAL SIGNATURES ARE
 NOT APPROVED. ONLY THE RECOGNIZED LEGAL SIGNATURE OF
 THE ARCHITECT OF RECORD WILL BE ACCEPTED.
  
 3. ROUTE PLANS TO THE STATE OF FLORIDA, DEPT OF
 BUSINESS REGULATION, HOTEL AND RESTAURANT DIVISION FOR
 PLAN REVIEW PRIOR TO RESUBMITTING FOR REVIEW. A MINIMUM
 OF TWO REVIEWED AND STAMPED PLANS WITH THE "TWO PAGE
 WORKSHEETS" ATTACHED TO THE STAMPED SHEET ARE REQUIRED
 FOR REVIEW AT THE CITY WPB. SECTION 102.2.1.
 ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED
 COMPLETLY. ONLY ONE SET OF PLANS IS STAMPED, AND THE
 TWO PAGE "WORKSHEETS" ARE NOT ATTACHED TO THE STAMPED
 SHEET.
  
 4. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE UTILITY
 DEPT. ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY
 COMPO, (561) 822-2272, OR BY FAX (561) 822-2287, OR
 E-MAIL [email protected]. SECTION III OF THE MUNICIPAL
 CODE.
 ******RESPONSE NOTED, BUT NO ATTACHED LETTER SHOWING
 APROVAL FOUND IN RESUBMITTAL OF PLANS.
  
 5. OK
 6. OK
 7. OK
 8. OK
  
 9. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION:
  
 A. OK
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ******RESPONSE NOTED, BUT MANUF. SHEETS FOR ITEM #41
 INDICATES 50,000 BTU'S AND THE RISER DIAGRAM INDICATES
 100,000 BTU'S. ALSO SUBMIT THE UL LISTING FOR THIS
 PRODUCT.--ITEM 38 MANUF. SPECIFICATION SHEETS ARE
 NOT LEGIBLE AND DO NOT INDICATE BTU OR CFH INPUT
 RATING.--ITEM 47 (7), NOT SUBMITTED. (NUMBER 47 NOT
 IN LEGEND). PLEASE SUBMIT MANUF SPECIFICATION SHEETS
 FOR THE TANKLESS WATER HEATERS.--TWO COPIES OF THE
 GAS MANUF SPECIFICATION SHEETS REQUIRED FOR REVIEW.
 ONLY ONE SUBMITTED. SECTION 106.1.
  
 10. OK
  
 **********NEW COMMENT**********
  
 1B. ALL ELEC., MECH., & PLUMBING SHEETS. ENGINEERS
 SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS, AND LICENSE
 NUMBER ON EACH SHEET. IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL
 AS, THE NAME, ADDRESS, AND CERTIFICATE OF AUTHORIZATION
 NUMBER ON THE ENGINEERING BUSINESS ON EACH SHEET. FAC
 61G15-23.002(2) & FS 471.025
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-29 Cont ID  
Sent By kstevens Date 2007-03-21 Time 06:55 Rev Time 0.00
Received By kstevens Date 2007-03-20 Time 06:47 Sent To  
Notes
2007-03-21 07:41:57DENIED
 REFERENCE: FBC-2004
 FBC-2004 CHAPTER 1
 FBC-2004 BUILDING
 WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS, THE PRINTED NAME OF THE ARCHITECT AND
 THE BUSINESS LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), ARE REQUIRED IN THE TITLE BLOCK. FAC
 61G1-16.004(2)(6) & FS 481.219, 481.2055.
  
 2. THE SIGNATURE OF THE ARCHITECT IS REQUIRED WHEN
 SEALING EACH SHEET. IT APPEARS THAT INITIALS HAVE BEEN
 USED. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE
 ARCHITECT, PLEASE PROVIDE A SIGNED, SEALED, AND
 NOTORIZED LETTER FOR OUR FILES. FAC 61G1-16.003,
 61G1-16.004((5) & FS 481.2055.
  
 3. ROUTE PLANS TO THE STATE OF FLORIDA, DEPT OF
 BUSINESS REGULATION, HOTEL AND RESTURANT DIVISION FOR
 PLAN REVIEW PRIOR TO RESUBMITTING FOR REVIEW. A MINIMUM
 OF TWO REVIEWED AND STAMPED PLANS WITH THE "TWO PAGE
 WORKSHEETS" ATTACHED TO THE STAMPED SHEET ARE REQUIRED
 FOR REVIEW AT THE CITY WPB. SECTION 102.2.1.
  
 4. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE UTILITY
 DEPT. ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY
 COMPO, (561) 822-2272, OR BY FAX (561) 822-2287, OR
 E-MAIL [email protected]. SECTION III OF THE MUNICIPAL
 CODE.
  
 5. SHT A2.1 ELEVATIONS A2.1-03, A2.1-05, A2.1-06, &
 A2.1-08. WALLS WITHIN 2' OF A W/C OR URINAL SHALL HAVE
 A "SMOOTH, HARD, NONABSORBENT SURFACE" TO A HEIGHT OF
 4' ABOVE THE FLOOR. ELEVATIONS INDICATE THE REQUIRED
 SURFACE ONLY UP TO 45.5". SECTION 1210.2. PLEASE
 CORRECT ELEVATIONS.
  
 6. SHT P2.0 PLUMBING PLAN KEY NOTES #21, DOUBLE CHECK
 VALVE ASSEMBLY IS NOT APPROVED. PLEASE DELETE FROM
 FLOOR PLAN AND KEY NOTES. TABLE 608.1. THE RPZV
 BACKFLOW IS REQUIRED AND WILL BE SUFFICIENT.--THE
 RPZV BACKFLOW WILL BE REQUIRED TO BE INSTALLED A
 MAXIMUM OF 4' ABOVE THE FINISHED FLOOR FOR SERVICING
 AND CERTIFICATION. AN INDIRECT WASTE RECEPTOR SHALL BE
 PROVIDED FOR THE DRAINAGE OFF THE BACKFLOW. SECTION
 802.1.3.
  
 7. SHT P5.0 WATER RISER DIAGRAM & PLUMBING PLAN KEY
 NOTES #21 THE DOUBLE CHECK VAVLE ASSEMBLY IS NOT
 APPROVED. PLEASE DELETE FROM THE RISER AND THE KEY
 NOTES. TABLE 608.1.
  
 8. SHT P1.0 KITCHEN EQUIPMENT SCHEDULE INDICATES A
 FILTERED WATER SYSTEM. THE FILTER SHALL BE NSF-42
 APPROVED. PLEASE SUBMIT THE MANUF. SPECIFICATION SHEETS
 SHOWING APPROVAL. SECTIONS 106.1.1 & 611.1.
  
 9. A SEPARATE GAS PERMIT IS REQUIRED. SUBMIT THE
 FOLLOWING INFORMATION:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - SHOW ALL LENGTHS.
  
 B. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 10. SHT P5.0 GAS NOTES INDICATE THE GAS DATA WAS BASED
 ON THE INTERNATIONAL FUEL GAS CODE. THE ADOPTED CODE IS
 FBC-2004 FUEL GAS CODE. PLEASE CHANGED REFERENCE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved