Plan Review Details - Permit 07030064
Plan Review Stops For Permit 07030064
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-03-22 Cont ID  
Sent By adarroug Date 2007-03-22 Time 15:00 Rev Time 0.00
Received By adarroug Date 2007-03-22 Time 15:00 Sent To P
Notes
2007-03-22 15:00:28TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-03-14 Cont ID  
Sent By mperson Date 2007-03-14 Time 11:37 Rev Time 0.00
Received By mperson Date 2007-03-05 Time 15:51 Sent To  
Notes
2007-03-05 15:51:10TO "P" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-04-06 Cont ID  
Sent By mperson Date 2007-04-06 Time 10:01 Rev Time 0.33
Received By mperson Date 2007-04-06 Time 10:01 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-03-14 Cont ID  
Sent By mperson Date 2007-03-14 Time 09:50 Rev Time 0.55
Received By mperson Date 2007-03-14 Time 09:50 Sent To PC
Notes
2007-03-14 11:37:29DENIED
 REFERENCE: FBC-2004 PLUMBING.
  
 THE FOLLOWING CORRECTIONS/INFORMATION IS REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE BACKFOW PREVENTER BEING INDICATED ON THE PRINT
 AS A "DOUBLE CHECK BACKFLOW PREVENTER" IS WRONG FOR
 THIS APPLICATION. THIS LOCATION IS CONSIDERED"HIGH
 HAZARD" THEREFORE A "REDUCED PRESSURE PRINCIPLE
 BACKFLOW PREVENTER" MUST BE USED. PLEASE CORRECT AND
 INDICATE THIS ON THE RESUBMITTAL.
  
 2. IN THE LEGEND HIGH DENSITY POLYETHELENE (HEAT FUSED)
 PIPE IS INDICATED AS BEING USED PER ASTM F-714. THE
 REFERENCE STANDARD ASTM F-714 IS FOR SEWER PIPE, PER
 FBC-2004 PLUMBING TABLE 702.3. THE CORRECT REFERENCE
 STANDARD FOR POTABLE WATER FOR POLYETHELENE (PE)
 PLASTIC PIPE, PER FBC-2004 PLUMBING TABLE 605.3, IS
 ASTM D 2239, AND PER FBC-2004 PLUMBING SECTION 605.20.2
 HEAT FUSION JOINTS SHALL BE MADE IN ACCORDANCE WITH
 ASTM D 2657. NOTE: THERE IS NO INDICATION OF "HIGH
 DENSITY POLTETHELENE" BEING INDICATED IN THE FBC-2004
 PLUMBING ONLY POLYETHELENE (PE) PLASTIC PIPE, PLEASE
 DELETE "HIGH DENSITY" ON THE RESUBMITTAL OR PROVIDE
 INFORMATION THAT HIGH DENSITY CONFORMS TO THE ABOVE
 CODE COMPLIANT REFERENCE STANDARDS. PLEASE CORRECT AND
 INDICATE THIS ON THE RESUBMITTAL.
  
 3. IN THE HOSE BIBB DETAIL THERE IS AN ALRPRINE SADDLE
 WITH S.S. BOLTS TYP. BEING INDICATED FOR THE HOSE BIBB
 SUPPLY. PER FBC-2004 PLUMBING, SECTION 605.9(4)
 PROHIBITED JOINTS AND CONNECTIONS: SADDLE-TYPE FITTINGS
 SHALL BE PROHIBITED. POLYETHELENE (PE) FITTINGS SHALL
 CONFORM TO REFERENCE STANDARD ASTM D 2609 PER FBC-2004
 PLUMBING, TABLE 605.5. PLEASE CORRECT AND RESUBMIT.
  
 4. IN THE HOSE BIBB DETAIL THERE IS A "SDR 11 H.D.P.E.
 PIPE" BEING INDICATED. PLEASE PROVIDE INFORMATION THAT
 INDICATES THAT THIS PIPE IS COMPLIANT WITH REFERENCE
 STANDARD ASTM D 2239 OR DELETE ON RESUBMITTAL. PLEASE
 INDICATE POLYETHELENE (PE) PIPE THAT IS COMPLIANT WITH
 REFERENCE STANDARD ASTM D 2239 ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved