Plan Review Details - Permit 07030028
Plan Review Stops For Permit 07030028
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2007-05-02 Cont ID  
Sent By rmcdouga Date 2007-05-02 Time 16:03 Rev Time 0.00
Received By rmcdouga Date 2007-05-02 Time 16:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-04-05 Cont ID  
Sent By mperson Date 2007-04-25 Time 16:17 Rev Time 0.00
Received By rmcdouga Date 2007-04-05 Time 07:48 Sent To  
Notes
2007-04-05 08:22:45DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE NAME OF THE PERSON RESPONSIBLE FOR THE PLANS
 SHOULD BE ON EACH SHEET OF THE DRAWINGS.
  
 3) THE ADDRESS AND IDENTIFICATION OF THE PROJECT SHOULD
 APPEAR ON EACH SHEET.
  
 4) ADDRESS COMMENTS OF OTHER REVIEWERS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2007-04-20 Cont ID  
Sent By btrobaug Date 2007-04-20 Time 13:33 Rev Time 0.33
Received By btrobaug Date 2007-04-20 Time 13:22 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-09 Cont ID  
Sent By btrobaug Date 2007-03-09 Time 07:46 Rev Time 0.33
Received By btrobaug Date 2007-03-09 Time 07:41 Sent To M
Notes
2007-03-09 07:46:50 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC
  
 .BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2007-05-02 Cont ID  
Sent By pschmitz Date 2007-05-02 Time 10:22 Rev Time 0.00
Received By pschmitz Date 2007-05-02 Time 10:22 Sent To B
Notes
2007-05-02 10:24:53GAS PERMIT RE-OPENED PER MR DALENBERG
 GAS PIPING TO BE COMPLETED BY PREMIER PLUMBING, OWNER
 VITAS VIKTANAS 832-0010

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2007-04-26 Cont ID  
Sent By mperson Date 2007-04-25 Time 15:53 Rev Time 0.00
Received By mperson Date 2007-04-25 Time 15:53 Sent To  
Notes
2007-04-25 16:22:09ROUTED TO P. SCHMITZ FOR RESEARCH FOR VARIFICATION OF
 GAS PERMIT APPLICATION BEING VOIDED.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-03-13 Cont ID  
Sent By mperson Date 2007-03-13 Time 11:37 Rev Time 0.33
Received By mperson Date 2007-03-13 Time 11:37 Sent To B
Notes
2007-03-13 11:58:44DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THIS INCLUDES THE EXISTING GAS SYSTEM. PLEASE
 DISTINGUISH THE EXISTING FROM THE PROPOSED ON THE
 RESUBMITTAL. PLEASE REFERENCE THE ATTACHED PERMIT
 INFORMATION TO THE DENIED GAS COMMENTS INDICATING SAID
 RESIDENCE HAS GAS.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 3. INDICATE THE TYPE OF GAS, (LP OR NATURAL) BEING
 USED.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: THIS INCLUDES THE EXISTING GAS SYSTEM.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: PLEASE SUBMIT MANUFACTURER SPECIFICATION/CUT
 SHEETS OF FIREPLACE VERIFYING BTU,S AND THAT FIREPLACE
 SHOWS A LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY (NRTL). IF GAS SYSTEM IS A 2 PSI SYSTEM
 PLEASE SUBMIT MANUFACTURER SPECIFICATION/CUT SHEETS OF
 THE MP REGULATOR AND THAT THE REGULATOR SHOWS A LISTING
 FROM A NATIONALLY RECOGNIZED TESTING LABORATORY
 (NRTL).
  
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 12. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2007-04-20 Cont ID  
Sent By adarroug Date 2007-04-20 Time 11:00 Rev Time 0.00
Received By adarroug Date 2007-04-20 Time 10:59 Sent To E
Notes
2007-04-20 11:00:28TO "BTROBAUGH" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-05 Cont ID  
Sent By rmcdouga Date 2007-04-05 Time 08:23 Rev Time 0.00
Received By rmcdouga Date 2007-03-03 Time 17:30 Sent To  
Notes
2007-03-03 17:34:15TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2007-04-20 Cont ID  
Sent By tgordon Date 2007-04-20 Time 14:52 Rev Time 0.25
Received By tgordon Date 2007-04-20 Time 14:52 Sent To G
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-04-20 Cont ID  
Sent By tgordon Date 2007-03-09 Time 16:41 Rev Time 0.25
Received By tgordon Date 2007-03-09 Time 16:41 Sent To P
Notes
***NONE***