| 2007-03-06 19:11:41 | *** UNSAT *** |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN |
| | SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH WILL |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS.(ALREADY ON MAIN |
| | ARCHITECTURAL SHEETS) |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | 2002 NFPA-110 |
| | |
| | PLEASE SEE PLANS CALL FOR THE 1996 NFPA IN SOME NOTES? |
| | |
| | 2) NOTE: PLEASE SEE THE INFORMATION ON TITLE BLOCKS FOR |
| | THE FIRM LIST A LOCAL/PLANTATION ADDRESS HOWEVER THE |
| | STATE OF FLORIDA HAS A HUNT VALLEY, MARYLAND ADDRESS. |
| | PLEASE CORRELATE. |
| | |
| | 3) NOTE: PLEASE CLARIFY THE ENGINEER OF RECORD WHICH |
| | HAS SIGNED AND SEALED PLANS AND STRUCTURAL PLANS WHICH |
| | TITLE BLOCK CALLS FOR THIS ENGINEER AS STATED AS A |
| | *CIVIL ENGINEER*? PLEASE EXPLAIN SCOPE OF WORK BEING |
| | SIGNED AND SEALED FOR THE STATED CIVIL ENGINEER. FS |
| | 471.025 |
| | |
| | 4) NOTE: PLEASE CLARIFY WHAT APPEARS TO BE A MISSING |
| | TITLE BLOCK FOR THE ELECTRICAL ENGINEER OF RECORD, MR. |
| | VARGAS. PLEASE SEE STATE DOES NOT LIST MR. VARGAS FROM |
| | EITHER AREA AS LISTED ON THE TITLE BLOCKS FOR KCI OR |
| | STATE WEBSITE. PLEASE SEE STATE LISTS FROM A THIRD |
| | LOCAL? |
| | PLEASE SEE FAC 61G15-23.002 |
| | ** NOTES 2,3 AND 4 ARE REQUIRED TO BE CLARIFIED FOR ALL |
| | SHEETS AND FOR ALL TRADES WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER TRADES. |
| | |
| | 5) NOTE: PLEASE KNOW AT THIS TIME THE SCOPE OF WORK AS |
| | APPLIED FOR IS IN QUESTION AS IT DOES NOT CORRELATE |
| | WITH PLANS SUBMITTED. PLEASE SEE SCOPE ON APPLICATION |
| | HAS THE GENERATOR CROSSED OUT YET PLANS INDICATE THIS |
| | INCLUDE IN SCOPE. PLEASE SEE COMMENTS WITH RESPECT TO |
| | THE PLANS AND COORDINATION OF GENERATORS. |
| | PLEASE KNOW THAT IT IS THE UNDERSTANDING THAT CELL |
| | EQUIPMENT IS PART OF A LEGALLY REQUIRED BACK UP SYSTEM |
| | UNDER THE STATE OF FLORIDA STATUTES. PLEASE PROVIDED |
| | INFORMATION IF THIS IS NOT INDEED THE CASE FOR 911 |
| | REQUIREMENTS ETC. |
| | PLEASE SEE SOME OF THESE COMMENTS WILL HAVE TO DO WITH |
| | THE TYPE OF GENERATOR PROVIDED. |
| | FBC ADMIN SECTION 106.1.2, 106.3.5.1.2 |
| | |
| | 6) NOTE: AS NOTED IN NOTE #5 ABOVE, AS A LEGALLY |
| | REQUIRED SYSTEM, ON-SITE FUEL WOULD BE REQUIRED. PLEASE |
| | KNOW THAT THE PLANS SHOW THE GENERATOR AS NATURAL GAS |
| | AND DIESEL AT THIS TIME. PLEASE KNOW THAT IN EITHER |
| | CASE ON-SITE FUEL SHALL BE LOCATED AS CLOSE TO THE |
| | GROUND AS PERMITTED BY CODE AND THE FIRE MARSHAL'S |
| | OFFICE. |
| | PLEASE KNOW AT THIS TIME, ANY ONSITE FUEL FOR PROPANE |
| | WOULD NOT PERMIT ANY TANK ON THE ROOF STRUCTURE. PLEASE |
| | SEE PLANS DO NOT INDICATE HOW THE POWER FOR THE |
| | GENERATOR FEEDERS, POWER SHUT DOWN OF GENERATOR, FUEL |
| | SUPPLY TO UNIT WILL BE OBTAINED AT THE GROUND LEVEL FOR |
| | FIRE DEPARTMENT OR ANY OTHER PERSONS WITH THE NEED TO |
| | SHUT OFF POWER/FUEL TO THE BUILDING ETC. |
| | 230.70, 230.72, 445, |
| | NFPA-72, NFPA-110 CHAPTER 6 AND 7. |
| | PLEASE KNOW, GAS FUEL LINE SHALL NOT BE GALVANIZED |
| | 7.9.3.1. |
| | PLEASE ALSO SEE 701.11(B)(3) FOR DUEL FUEL SUPPLIES |
| | REQUIRED. |
| | PLEASE SEE COMMENTS FROM FIRE REVIEW. |
| | PLEASE KNOW AS THE PLANS DO NOT CORRELATE AND |
| | INFORMATION ON TYPE OF SYSTEM ETC IS NOT ACCURATE THERE |
| | MAY BE REVIEW COMMENTS WHEN PLANS ARE RESUBMITTED. |
| | THERE ARE CURRENTLY MANY CODE ISSUES WHICH CAN NOT BE |
| | REVIEWED AT THIS TIME. |
| | |
| | 7) NOTE: PLEASE SUBMIT AND INDICATE ALL AIC RATINGS FOR |
| | ALL EQUIPMENT. |
| | 110.9. NEC |
| | NFPA-110 6.5.3 |
| | |
| | 8) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE GENERATOR, FUEL TANKS, ATS EQUIPMENT. |
| | 110.3, 90.7. |
| | |
| | 9) NOTE: PLEASE KNOW AS THE SCOPE OF WORK FOR PROJECT |
| | AS APPLIED AND AS SHOWN ON PLANS CAN NOT BE CONFIRMED |
| | OR VERIFIED AT THIS TIME, THE VALUE BASED ON ALL LABOR |
| | AND MATERIALS CAN NOT BE EVALUATED AS REQUIRED PER FBC |
| | 108.3 ADMIN SECTION. |
| | |
| | 10) NOTE: PLEASE SEE THE RISER IS MISSING THE |
| | *EQUIPMENT GROUNDING CONDUCTOR* TO THE METER AND |
| | DISCONNECT. RISER MENTIONS THE CONDUCTORS FROM FPL, |
| | HOWEVER THIS IS NOT POSSIBLE AS THIS IS BEING FED FROM |
| | THE 8TH FLOOR ELECTRICAL ROOM WHICH WOULD BE AFTER THE |
| | FIRST MEANS OF DISCONNECT FOR THE BUILDING. PLEASE SEE |
| | 250.6 AND 250.24 AS AN *EQUIPMENT GROUNDING CONDUCTOR* |
| | IS REQUIRED. THE METER IN FACT WOULD CONTAIN A NOTE FOR |
| | REQUIRED *FLOATING NEUTRAL KIT*. |
| | PLEASE ADJUST AND SEE 250.122 FOR SIZING. |
| | |
| | 11) NOTE: PLEASE PROVIDE LOAD CALCULATIONS ON THE |
| | EQUIPMENT WHICH THE NEW LOADS ARE BEING CONNECTED TO. |
| | PLEASE CORRELATE THE LOAD CALCULATIONS FOR THE |
| | GENERATOR AS SHOWN ON PLANS AT THIS TIME. SHOWS 24KW |
| | AND SHOWS 39.9 KVA. |
| | PLEASE SEE PLANS ALSO CALL FOR A 100KW UNIT AND CALL |
| | FOR A 24KW UNIT? |
| | PLEASE SHOW ALL CONTINUOUS LOADS (3 OR MORE HOURS) AT |
| | 125%. |
| | 220, 230.42, 215.3 ETC |
| | PLEASE SUBMIT PER |
| | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION FOR ADDITIONAL |
| | INFORMATION. |
| | |
| | 12) NOTE: PLEASE SEE THE SEALS ON MANY SHEETS FOR MR. |
| | PRUETTE ARE NOT CLEAR AND VISIBLE WITH ALL INFORMATION |
| | AS REQUIRED PER FAC 61G15-23.001. |
| | PLEASE SEE SOME ARE OK, HOWEVER NOT ALL. |
| | PLEASE BE SURE PLANS ARE SEALED SO THAT THE INFORMATION |
| | IS CLEAR/RAISED. |
| | |
| | 13) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE |
| | ROUTING OF THE ELECTRICAL CONDUITS. PLEASE KNOW THAT |
| | ANY ROUTING OF ELECTRICAL CONDUITS AND PIPING MAY NOT |
| | BE PLACED IN STAIRWAYS, OR ELEVATOR EQUIPMENT ROOMS. |
| | PLEASE SEE COMMENTS FROM OTHER TRADES FOR THE FBC AND |
| | SEE THE STATE ELEVATOR CODE. |
| | |
| | 14) NOTE: PLEASE KNOW A FIRE REVIEW WAS ADDED. FEES |
| | WILL BE OWED. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-03-06 14:34:57 | IN ELEC FOR REVIEW |