Plan Review Details - Permit 07030026
Plan Review Stops For Permit 07030026
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-03-30 Cont ID  
Sent By jwitmer Date 2007-03-30 Time 11:15 Rev Time 1.22
Received By jwitmer Date 2007-03-30 Time 11:15 Sent To  
Notes
2007-03-30 12:27:33BUILDING PLAN REVIEW
 PERMIT: 07030026
 ADD: 1501 S FLAGLER DR
 CONT: SBA NETWORK SERVICES
 TEL: (352)629-1774
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) SHEET A-1 WIND LOAD INFORMATION IS MISSING THE
 IMPORTANCE FACTOR, NOTE NEXTEL CELL PHONES ARE USED IN
 THE HURRICANE ASSESMENT AND PART OF CITY'S
 EMERGENCY PREPAREDNESS AND COMMUNICATION SYSTEM
 CATEGORYIV = IMPORTANCE FACTOR 1.15
  
 4)IS THE 13'-3"X16'-2" CABINET A STATE MANUFACTURED
 BUILDING?PLEASE PROVIDE DETAILS ON THIS STRUCTURE.
 SHEET N-1 GENERAL NOTE 12 INDICATES THIS IS A
 PREMANUFACTURED BUILDING PROVIDE STATE APPROVED PLANS.
  
 5) PLANS INDICATE ROOFING WORK AND FLASHING, NOTE THERE
 IS NO ROOFING CONTRACTOR SIGNED ON AT THIS TIME.
  
 6)SHEET E-2 INDICATES THE ELECTRICAL RUNS FROM THE
 8TH FLOOR ELECTRIC ROOM, HOW OR WHERE WILL THESE RUNS
 CONTINUE TO THE ROOF ? NOTE NOT TO USE THE STAIR TOWERS
 FOR ACCESS.
 1019.1.2 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 AND ELECTRICAL RACEWAY SERVING THE EXIT ENCLOSURE AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING 16 SQUARE
 INCHES (0.010 M 2 ). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 712 . THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 NOTE THE INFORMATION FOR THE GENERATOR WAS STRUCK!
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-03-06 Cont ID  
Sent By dpalmer Date 2007-03-06 Time 19:11 Rev Time 0.00
Received By dpalmer Date 2007-03-06 Time 14:34 Sent To  
Notes
2007-03-06 19:11:41*** UNSAT ***
  
  
 1) NOTE: PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN
 SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH WILL
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.(ALREADY ON MAIN
 ARCHITECTURAL SHEETS)
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2002 NFPA-110
  
 PLEASE SEE PLANS CALL FOR THE 1996 NFPA IN SOME NOTES?
  
 2) NOTE: PLEASE SEE THE INFORMATION ON TITLE BLOCKS FOR
 THE FIRM LIST A LOCAL/PLANTATION ADDRESS HOWEVER THE
 STATE OF FLORIDA HAS A HUNT VALLEY, MARYLAND ADDRESS.
 PLEASE CORRELATE.
  
 3) NOTE: PLEASE CLARIFY THE ENGINEER OF RECORD WHICH
 HAS SIGNED AND SEALED PLANS AND STRUCTURAL PLANS WHICH
 TITLE BLOCK CALLS FOR THIS ENGINEER AS STATED AS A
 *CIVIL ENGINEER*? PLEASE EXPLAIN SCOPE OF WORK BEING
 SIGNED AND SEALED FOR THE STATED CIVIL ENGINEER. FS
 471.025
  
 4) NOTE: PLEASE CLARIFY WHAT APPEARS TO BE A MISSING
 TITLE BLOCK FOR THE ELECTRICAL ENGINEER OF RECORD, MR.
 VARGAS. PLEASE SEE STATE DOES NOT LIST MR. VARGAS FROM
 EITHER AREA AS LISTED ON THE TITLE BLOCKS FOR KCI OR
 STATE WEBSITE. PLEASE SEE STATE LISTS FROM A THIRD
 LOCAL?
 PLEASE SEE FAC 61G15-23.002
 ** NOTES 2,3 AND 4 ARE REQUIRED TO BE CLARIFIED FOR ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER TRADES.
  
 5) NOTE: PLEASE KNOW AT THIS TIME THE SCOPE OF WORK AS
 APPLIED FOR IS IN QUESTION AS IT DOES NOT CORRELATE
 WITH PLANS SUBMITTED. PLEASE SEE SCOPE ON APPLICATION
 HAS THE GENERATOR CROSSED OUT YET PLANS INDICATE THIS
 INCLUDE IN SCOPE. PLEASE SEE COMMENTS WITH RESPECT TO
 THE PLANS AND COORDINATION OF GENERATORS.
 PLEASE KNOW THAT IT IS THE UNDERSTANDING THAT CELL
 EQUIPMENT IS PART OF A LEGALLY REQUIRED BACK UP SYSTEM
 UNDER THE STATE OF FLORIDA STATUTES. PLEASE PROVIDED
 INFORMATION IF THIS IS NOT INDEED THE CASE FOR 911
 REQUIREMENTS ETC.
 PLEASE SEE SOME OF THESE COMMENTS WILL HAVE TO DO WITH
 THE TYPE OF GENERATOR PROVIDED.
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2
  
 6) NOTE: AS NOTED IN NOTE #5 ABOVE, AS A LEGALLY
 REQUIRED SYSTEM, ON-SITE FUEL WOULD BE REQUIRED. PLEASE
 KNOW THAT THE PLANS SHOW THE GENERATOR AS NATURAL GAS
 AND DIESEL AT THIS TIME. PLEASE KNOW THAT IN EITHER
 CASE ON-SITE FUEL SHALL BE LOCATED AS CLOSE TO THE
 GROUND AS PERMITTED BY CODE AND THE FIRE MARSHAL'S
 OFFICE.
 PLEASE KNOW AT THIS TIME, ANY ONSITE FUEL FOR PROPANE
 WOULD NOT PERMIT ANY TANK ON THE ROOF STRUCTURE. PLEASE
 SEE PLANS DO NOT INDICATE HOW THE POWER FOR THE
 GENERATOR FEEDERS, POWER SHUT DOWN OF GENERATOR, FUEL
 SUPPLY TO UNIT WILL BE OBTAINED AT THE GROUND LEVEL FOR
 FIRE DEPARTMENT OR ANY OTHER PERSONS WITH THE NEED TO
 SHUT OFF POWER/FUEL TO THE BUILDING ETC.
 230.70, 230.72, 445,
 NFPA-72, NFPA-110 CHAPTER 6 AND 7.
 PLEASE KNOW, GAS FUEL LINE SHALL NOT BE GALVANIZED
 7.9.3.1.
 PLEASE ALSO SEE 701.11(B)(3) FOR DUEL FUEL SUPPLIES
 REQUIRED.
 PLEASE SEE COMMENTS FROM FIRE REVIEW.
 PLEASE KNOW AS THE PLANS DO NOT CORRELATE AND
 INFORMATION ON TYPE OF SYSTEM ETC IS NOT ACCURATE THERE
 MAY BE REVIEW COMMENTS WHEN PLANS ARE RESUBMITTED.
 THERE ARE CURRENTLY MANY CODE ISSUES WHICH CAN NOT BE
 REVIEWED AT THIS TIME.
  
 7) NOTE: PLEASE SUBMIT AND INDICATE ALL AIC RATINGS FOR
 ALL EQUIPMENT.
 110.9. NEC
 NFPA-110 6.5.3
  
 8) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT
 SHEETS FOR THE GENERATOR, FUEL TANKS, ATS EQUIPMENT.
 110.3, 90.7.
  
 9) NOTE: PLEASE KNOW AS THE SCOPE OF WORK FOR PROJECT
 AS APPLIED AND AS SHOWN ON PLANS CAN NOT BE CONFIRMED
 OR VERIFIED AT THIS TIME, THE VALUE BASED ON ALL LABOR
 AND MATERIALS CAN NOT BE EVALUATED AS REQUIRED PER FBC
 108.3 ADMIN SECTION.
  
 10) NOTE: PLEASE SEE THE RISER IS MISSING THE
 *EQUIPMENT GROUNDING CONDUCTOR* TO THE METER AND
 DISCONNECT. RISER MENTIONS THE CONDUCTORS FROM FPL,
 HOWEVER THIS IS NOT POSSIBLE AS THIS IS BEING FED FROM
 THE 8TH FLOOR ELECTRICAL ROOM WHICH WOULD BE AFTER THE
 FIRST MEANS OF DISCONNECT FOR THE BUILDING. PLEASE SEE
 250.6 AND 250.24 AS AN *EQUIPMENT GROUNDING CONDUCTOR*
 IS REQUIRED. THE METER IN FACT WOULD CONTAIN A NOTE FOR
 REQUIRED *FLOATING NEUTRAL KIT*.
 PLEASE ADJUST AND SEE 250.122 FOR SIZING.
  
 11) NOTE: PLEASE PROVIDE LOAD CALCULATIONS ON THE
 EQUIPMENT WHICH THE NEW LOADS ARE BEING CONNECTED TO.
 PLEASE CORRELATE THE LOAD CALCULATIONS FOR THE
 GENERATOR AS SHOWN ON PLANS AT THIS TIME. SHOWS 24KW
 AND SHOWS 39.9 KVA.
 PLEASE SEE PLANS ALSO CALL FOR A 100KW UNIT AND CALL
 FOR A 24KW UNIT?
 PLEASE SHOW ALL CONTINUOUS LOADS (3 OR MORE HOURS) AT
 125%.
 220, 230.42, 215.3 ETC
 PLEASE SUBMIT PER
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION FOR ADDITIONAL
 INFORMATION.
  
 12) NOTE: PLEASE SEE THE SEALS ON MANY SHEETS FOR MR.
 PRUETTE ARE NOT CLEAR AND VISIBLE WITH ALL INFORMATION
 AS REQUIRED PER FAC 61G15-23.001.
 PLEASE SEE SOME ARE OK, HOWEVER NOT ALL.
 PLEASE BE SURE PLANS ARE SEALED SO THAT THE INFORMATION
 IS CLEAR/RAISED.
  
 13) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE
 ROUTING OF THE ELECTRICAL CONDUITS. PLEASE KNOW THAT
 ANY ROUTING OF ELECTRICAL CONDUITS AND PIPING MAY NOT
 BE PLACED IN STAIRWAYS, OR ELEVATOR EQUIPMENT ROOMS.
 PLEASE SEE COMMENTS FROM OTHER TRADES FOR THE FBC AND
 SEE THE STATE ELEVATOR CODE.
  
 14) NOTE: PLEASE KNOW A FIRE REVIEW WAS ADDED. FEES
 WILL BE OWED.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-03-06 14:34:57IN ELEC FOR REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-04-02 Cont ID  
Sent By mawillia Date 2007-04-02 Time 17:51 Rev Time 0.00
Received By mawillia Date 2007-04-02 Time 16:56 Sent To  
Notes
2007-04-02 17:48:08*****DENIED*****
  
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT
 ENCLOSURE ASSEMBLY SHALL BE LIMITED AS PER SECTION
 7.1.3.2.1 (6) OF NFPA 101.
  
 3.PLEASE CLARIFY THE EXISTING AND/OR THE PROPOSED
 INSTALLATION OF A NATURAL GAS GENERATOR.
  
 4.FURTHER FIRE PLAN REVIEW SHALL BE CONDUCTED ONCE
 ADDITIONAL INFORMATION IS ASCERTAINED FROM BUILIDING
 AND ELECTRICAL COMMENTS.
  
  
 TO EXPEIDTE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-03-17 Cont ID  
Sent By pschmitz Date 2007-03-17 Time 13:17 Rev Time 0.00
Received By pschmitz Date 2007-03-17 Time 13:17 Sent To  
Notes
2007-03-17 13:21:37PAUL SCHMITZ
 [email protected] FBC 2004 PLUMBING
 CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
  
 DENIED
  
 PLEASE SEE ELECTRIC PLAN REVIEW NOTES REGARDING THE
 EMERGENCY GENERATOR TYPES OF FUEL.
  
  
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-04-02 Cont ID  
Sent By mawillia Date 2007-04-02 Time 17:49 Rev Time 0.00
Received By mawillia Date 2007-03-05 Time 09:15 Sent To  
Notes
2007-03-05 09:15:43TO "COMM" BD#5

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-03-20 Cont ID  
Sent By rregueir Date 2007-03-20 Time 13:59 Rev Time 0.00
Received By rregueir Date 2007-03-20 Time 13:52 Sent To  
Notes
2007-03-20 13:59:27NO MECHANICAL. GENERATOR REMOVED FROM THIS APPLICATION.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-03-16 Cont ID  
Sent By bpowell Date 2007-03-16 Time 11:11 Rev Time 0.00
Received By bpowell Date 2007-03-16 Time 11:11 Sent To  
Notes
2007-03-16 11:23:12DETAILS FOR THE GENERATOR NEED TO BE PROVIDED AS WELL
 AS A SCREENING ENCLOSURE FOR THE GENERATOR IF
 REQUIRED.
  
 PLEASE PROVIDE INFORMATION ABOUT THE RUBIX, WHICH IS
 SHOWN.
  
 FLESH MOUNTED PANELS ARE PREFERRED AS OPPOSED TO THE
 ROUND PANELS.
  
 BOBBY POWELL, JR. , PLANNER, (561) 822-1435